IZBOR ELEMENATA PRIMARNE OPREME. “PROJEKTIRANJE ELEKTRIČNIH POSTROJENJA”. ELEKTRIČNA POSTROJENJA. UNUTARNJA IZVEDBA. VANJSKA IZVEDBA. OTVORENA POSTROJENJA ZATVORENA POSTROJENJA PLINOM IZOLIRANA POSTROJENJA. OTVORENA POSTROJENJA ZATVORENA POSTROJENJA. - PowerPoint PPT Presentation
Citation preview
IZBOR ELEMENATA PRIMARNE OPREME
“PROJEKTIRANJE ELEKTRIČNIH POSTROJENJA”
ELEKTRIČNA POSTROJENJAUNUTARNJA IZVEDBA VANJSKA IZVEDBA
-OTVORENA POSTROJENJA
-ZATVORENA POSTROJENJA
-PLINOM IZOLIRANA POSTROJENJA
-OTVORENA POSTROJENJA
-ZATVORENA POSTROJENJA
PRIMARNA OPREMA ELEKTRIČNOG POSTROJENJA
I. NAPREZANJA PRIMARNE OPREME ELEKTRIČNOG
POSTROJENJA (HRN-HD 637)
1. NAPONSKA NAPREZANJA
2. STRUJNA NAPREZANJA
3. MEHANIČKA NAPREZANJA (POTRESI I SL.)
4. KLIMATSKI UTJECAJ
5. UTJECAJ OKOLIŠA KOJI SE OČEKUJE NA LOKACIJI POSTROJENJA
ELEKTRIČNI ZAHTJEVI
1. NAČINI POSTUPANJA S NEUTRALNOM TOČKOM
2. RAZREDBA NAPONA
3. STRUJA U NORMALNOM POGONU
4. STRUJA KRATKOG SPOJA
5. NAZIVNA FREKVENCIJA
6. KORONA
PRORAČUN STRUJA KS-a(HRN HD 533)
VRSTE KRATKIH SPOJEVA:
1. TROPOLNI KS
2. DVOPOLNI KS
3. ZEMLJOSPOJ
4. DVOPOLNI KS S ISTODOBNIM SPOJEM SA ZEMLJOM
5. DVOSTRUKI ZEMLJOSPOJ
JEDNOPOLNI KS
ZdVd
ZiVi
Z0V0
K
P
K
P
K
P
IdId
Id0
0
0
T
S
R
I
I
V
DVOPOLNI KS
0
0
TS
R
TS
II
I
VVZd
Vd
ZiVi
K
P
K
P
Id
Id
DVOPOLNI KS S ISTOVREMENIM SPOJEM SA ZEMLJOM
0
0
0
R
T
S
I
V
V
ZdVd
ZiVi
Z0V0
K
P
K
P
K
P
Id
-I0
-Ii
TROPOLNI KS
0
TSR
TSR
III
VVV
Zd
K
P
Id
Vd=0
Zi
K
P
Ii=0
Vi=0
Z0
K
P
I0=0
V0=0
PRORAČUN STRUJA KS-a (2)
U struji kratkog spoja razlikujemo tri struje
presudne za dimenzioniranje i odabir
elemenata rasklopnog postrojenja:
• UDARNA STRUJA KS-a,
• PREKIDNA STRUJA KS-a i
• STRUJA MJERODAVNA ZA UGRIJAVANJE
ODREĐIVANJE NAJVEĆE STRUJE ZA RAZLIČITE VRSTE KS-a
ODREĐIVANJE UDARNE STRUJE KRATKOG SPOJA
''''
''2
dk
ku
Z
VI
IkI
0''
''
''
3
2
ZZZ
VI
IkI
idk
ku
JEDNOPOLNI KSTROPOLNI KS
Ik'' – efektivna vrijednost struje neposredno nakon nastanka kratkog spoja,Zd''– zbroj subtranzijentne (početne) reaktancije generatora i impedancije u direktnom sustavu od generatora do mjesta kratkog spoja,V – efektivna vrijednost faznog napona mreže, k – faktor u ovisnosti o omjeru R/X zadane mreže.
k
1,0
1,1
1,2
1,3
1,4
1,5
1,6
1,7
1,8
1,9
2,0
0,5 1,0 1,50 R/X
ODREĐIVANJE PREKIDNE STRUJE KRATKOG SPOJA
22''akpr III
-EFEKTIVNA VRIJEDNOST STRUJE KOJA PROTIČE KROZ PREKIDAČ U TRENUTKU ODVAJANJA KONTAKATA
-Ia VRIJEDNOST ISTOSMJERNE KOMPONENTE U TRENUTKU ODVAJANJA KONTAKATA
ODREĐIVANJE STRUJE MJERODAVNE ZA UGRIJAVANJE
mnII dt ''
MEHANIČKI ZAHTJEVI
1. NORMALNO OPTEREĆENJE2. OPTEREĆENJE USLIJED ZATEZANJA3. OPTEREĆENJE USLIJED IZVOĐENJA4. OPTEREĆENJE USLIJED LEDA5. OPTEREĆENJE USLIJED VJETRA6. SILE USLIJED SKLAPANJA7. SILE USLIJED KRATKOG SPOJA8. OTPUŠTANJE VODIČA9. VIBRACIJE10. DIMENZIONIRANJE NOSIVIH
KONSTRUKCIJA
KLIMATSKI UVJETI IUVJETI OKOLIŠA
1. TEMPERATURA
2. NADMORSKA VISINA I TLAK
3. VLAŽNOST
4. OBORINE
5. ONEČIŠĆENJE
6. SUNČEVO ZRAČENJE
POSEBNI ZAHTJEVI
1. POSTROJENJA NA VELIKIM NADMORSKIM VISINAMA
2. UČINCI MALIH ŽIVOTINJA I MIKROORGANIZAMA
3. RAZINA BUKE
4. UČINCI POTRESA
II. IZOLACIJA
• KOORDINACIJU IZOLACIJE USKLADITI S EN 60071-1 I EN 60071-2
• EN 60071-1 DEFINIRA VRIJEDNOSTI NAJVIŠEG NAPONA OPREME Um
• EN 60071-2 DEFINIRA ODGOVARAJUĆE MINIMALNE RAZMAKE
NAJMANJI IZOLACIJSKI RAZMACI U ZRAKU ZA AKTIVNE DIJELOVE (1)
NAJMANJI IZOLACIJSKI RAZMACI U ZRAKU ZA AKTIVNE DIJELOVE (2)
NAJMANJI IZOLACIJSKI RAZMACI U ZRAKU ZA AKTIVNE DIJELOVE (3)
III. OPREMA
1. SABIRNICE
2. PREKIDAČI
3. OSIGURAČI
4. RASTAVLJAČI
5. MJERNI TRANSFORMATORI
6. ODVODNICI PRENAPONA
7. IZOLATORI
1. SABIRNICE
DIMENZIONIRANJE:• OBZIROM NA MAKSIMALNU STRUJU U
NORMALNOM POGONU• OBZIROM NA DOZVOLJENO POVIŠENJE
TEMPERATURE ZA VRIJEME KRATKOG SPOJA
• OBZIROM NA MEHANIČKA NAPREZANJA ZA VRIJEME KRATKOG SPOJA
MAKSIMALNA STRUJA U NORMALNOM POGONU
• LOCIRATI NAJVIŠE OPTEREĆENI DIO SABIRNICA U NORMALNOM POGONU, ALI I U SLUČAJU n-1
• VODITI RAČUNA O PROPISIMA KOJI ODREĐUJU MINIMALNE PRESJEKE ODNOSNO PROMJERE CIJEVNIH SABIRNICA
• PROVJERITI TRAJNU STRUJU ODABRANIH SABIRNICA TE IZVRŠITI KOREKCIJE U OVISNOSTI O DOZVOLJENOJ NADTEMPERATURI
KONTROLA PRESJEKA OBZIROM NA UGRIJAVANJE ZA VRIJEME KS-a
• RAČUNSKIM PUTEM ODREDITI PRESJEK SABIRNICA TE GA USPOREDITI S PRESJEKOM ODABRANOG TIPA SABIRNICE
2.
135
1655.7 mmtIq pog
tCu
2.
115
1650.12 mmtIq
pogtAl
ZA ALUMINIJ
ZA BAKAR
KONTROLA PRESJEKA SABIRNICA OBZIROM NA MEHANIČKA
NAPREZANJA ZA VRIJEME KS-a• ODREDITI RAZMAK SABIRNICA POJEDINIH FAZA
TEMELJEM PROPISA, A U OVISNOSTI O NAPONSKOJ RAZINI
• ODREDITI RAZMAK POTPORNIH IZOLATORA• IZRAČUNATI MAKSIMALNI MOMENT SAVIJANJA
U UPORIŠTIMA• ODREDITI LINIJSKI OTPORNI MOMENT• ODREDITI MAKSIMALNO NAPREZANJE I
USPOREDITI GA S DVOSTRUKOM VRIJEDNOSTI GRANICE TEČENJA ODABRANOG MATERIJALA SABIRNICA
2. PREKIDAČI
DIMENZIONIRANJE:
• OBZIROM NA NAZIVNI NAPON
• OBZIROM NA MAKSIMALNU STRUJU U NORMALNOM POGONU
• OBZIROM NA VRIJEDNOST PREKIDNE STRUJE Ipr
• KONTROLA OBZIROM NA UDARNU STRUJU KS-a
VRSTE PREKIDAČA
• ULJNI
• MALOULJNI
• HIDROMATSKI
• PNEUMATSKI (KOMPRIMIRANI ZRAK, SF6)
• VAKUUMSKI PREKIDAČI
• ZRAČNI PREKIDAČI
3. OSIGURAČI• ZAŠTITA OD KS-a I PREOPTEREĆENJA• UPORABA VN OSIGURAČA DO 35 kV• UGRADNJA NA MJESTU SMANJENJA PRESJEKA I
POČETKU ŠTIĆENOG VODIČA• SELEKTIVNOST - OMJER NAZIVNIH STRUJA
SUSJEDNIH OSIGURAČA >= 1,6• IZBOR - PREMA NAZIVNOM NAPONU I STRUJI
4. RASTAVLJAČI
VIDLJIVO ODVAJANJE DIJELOVA POD NAPONOM OD OSTALIH DIJELOVA KOJI NISU POD NAPONOM
DIMENZIONIRANJE OBZIROM NA:• NAZIVNI NAPON RASTAVLJAČA• MAKSIMALNU STRUJU U
NORMALNOM POGONU• KONTROLA OBZIROM NA UDARNU
STRUJU KS-a I STRUJU MJERODAVNU ZA UGRIJAVANJE
5.MJERNI TRANSFORMATORI
5.1 STRUJNI MJERNI TRANSFORMATORI
• PRIKLJUČAK ZAŠTITNIH I MJERNIH UREĐAJA NA SEKUNDARNE STEZALJKE
• IZBOR PRIMARNE STRUJE PREMA MAKSIMALNOJ STRUJI U NORMALNOM POGONU
• SEKUNDARNA STRUJA 5A ILI 1A• BROJ PRIKLJUČENIH INSTRUMENATA
ODREĐUJE SNAGU STRUJNOG TRANSFORMATORA
• KLASA STRUJNOG TRANSFORMATORA
5.2 NAPONSKI MJERNI TRANSFORMATORI
• IZVEDBA KAO U TRANSFOMRATORA SNAGE
• INDUKTIVNI ILI KAPACITIVNI TRANSFORMATORI
• PRIMARNI NAPON ODGOVARA LINIJSKOM ILI FAZNOM NAPONU POSTROJENJA
• SEKUNDARNI NAPON IZNOSI 100V ILI 100/√3V
• SNAGU DEFINIRAJU PRIKLJUČENI INSTRUMENTI NA SEKUNDARU
6. ODVODNICI PRENAPONA• NAZIVNI NAPON ODVODNIKA VEĆI OD
NAJVEĆEG POVREMENOG POVIŠENJA POGONSKOG NAPONA UP0
UP0=cu*cf*Um/√3 cu=1,07 cf=1,3 izravno uzemljena mreža cf=1,74 izolirana ili “gašena” mreža
Um-najveća vrijednost linijskog pogonskog napona• PRORADNI NAPON - DJELOVANJE
ODVODNIKA• PREOSTALI NAPON - MANJI OD NAPONSKE
RAZINE IZOLACIJE ŠTIĆENOG UREĐAJA (POSTROJENJA)
• VENTILNI ODVODNICI, CIJEVNI ODVODNICI, BROJAČI PRORADE ODVODNIKA
7. IZOLATORI
7.1 POTPORNI IZOLATORIODABIR SE VRŠI PREMA:• NAZIVNOM NAPONU I VELIČINI SILE KOJA SE
PRENOSI NA IZOLATOR• TIPOVI: PORCULAN, UMJETNA SMOLA
7.2 PROVODNI IZOLATORIODABIR SE VRŠI PREMA:• NAZIVNOM NAPONU• MAKSIMALNOJ STRUJI U NORMALNOM POGONU• MEHANIČKIM NAPREZANJIMA ZA VRIJEME KS-a• UGRIJAVANJU ZA VRIJEME KS-a