KONEL ADS V1.0AUTOMATIC DOOR SYSTEMS
USER MANUAL
www.konelsan.com.tr
ASANSÖR SİSTEMLERİ
Manufacturer: KONEL Araştırma Geliştirme Bilişim Otomasyon Elektronik ve Danışmanlık Hizm.San.Tic.Ltd.Şti
Head Quarter:Selçuk Üniversitesi Teknoloji Gel. BölTeknokent Safir Panorama Blok No:67 A2/307Selçuklu KONYA - TURKEY
Factory:Fevzi Çakmak Mh. Modesa San Sit.10746.Sk No:20 Karatay KONYA - TURKEY
Tel: + 90 332 262 02 22
2015
v1.0
Konel Electronic ADS v1.0
www.konelsan.com.tr
Document Date
Software Version
Konel Electronic ADS v1.0
Technical SpesificationInput Voltage
20V AC - 35V DC Voltage
Motor Information
24V DC Brushed Motor with Gear4 Ch mosfet driver2 Ch Encoder min 100 pulse
Inputs
Door OpenDoor CloseNudgeAt floor
Outputs
Door fully openedDoor fully closedDoor squeezed
Dimensions
116 x 160 x 50 mm (W x L x H)
Language Choosing
TürkçeEnglish
4 Ch mosfet driver with H bridge
Motor protection with soft start
Top level protected material is used for protect
board from undesired energy of motor
Smooth motion control with double channel
encoder. Digital signal processor ensure that
accuracy and precision with hardware encoder
reading.
Ability of fast moving with departure and drop
ramp. Same squeeze control at every door because
of differantial current control.
Squeeze control with current and encoder
parameters.
If squeeze is made by mechanical, door running
slowly for closing.
If squeeze is continued, back open algorith will be
run.
If squeeze is sensed, door is opened. Then door will
be closed by slow pass from squeeze area.
Access menu with admin or limited entrance.
General Spesificationswww.konelsan.com.tr
10
ADS v1.0
User Interface
2 Line LCD Screen
Up Button
Menu Entrance with 3 secMenu Shift Right
Down Button
Recognition with 3 secMenu Shift Left
KONEL ADS v1.0
P:15cm V:5cm/s
DOOR OPENING
DC BUS VOLTAGE
28.5 Volt
MANUAL MOVING
OPEN:X CLOSE:
NDG: FSL:
The first opening screen. If close command is sensed
door runs to closing. If close command is not sensed,
door runs to opening.
P : Position, V :velocity
Door status is showing on second line of LCD
On this screen, If Menu Right button is pressed along to
3 sec, Parameter Menu will be shown.
If Menu Left button pressed along to 3 sec, Recognition
mode is running.
Input voltage is shown.
Motor is controlled by buttons on board
If menu left button is pressed, door will be opened.
If menu right button is pressed, door will be closed.
Input status is shown on that screen. If input is sensed
you can see X. And You can see input status with
indicator leds on board.
www.konelsan.com.tr
11
RECOGNITION
P:10 cm
Door is fully opened by recognition speed, then it starts
for closing and position is shown on screen. If position of
door is wrong, you need to change motor parameters.
Konel Electronic
ADS v1.0
Menus
LISAN/LANGUAGE
ENGLISH
SPEED ADJUST.
PERSONEL
Speed adjust screen. In this screen you can chose
speed as factory slow, normal and fast.
Menu language screen. Up and Down button is
using for changing.
OPEN SPEED
50 cm/s
Door open side fast speed parameter.
Software uses motor parameters for calculation
of velocity.
OP. SLOW SPEED8 cm/s
Door open side slow speed parameter
OPEN RAMP LENGTH
20 cm
Door open side ramp length for soft starter.
If ramp parameter is so small, door may be
shaked.
OPEN SLOW ZONE
4 cm
When door is next to open slow length at door
open side, motor speed will be slow down.
CLOSE SPEED
50 cm/s
Door close side fast speed parameter.
Software uses motor parameters for calculation
of velocity.
CLOSE SLOW SPEED
8 cm/s
When door is next to close slow length at door
open side, motor speed will be slow down.
CL. RAMP LENGTH
20 cm
Door close side ramp length for soft speed down
If ramp parameter is so small, door may be
shaked.
www.konelsan.com.tr
12Konel Electronic
ADS v1.0
Menus
3 cm
SKATE ZONE
3 cm
Skate zone length. If parameter is wrong, door
will not run regular at skate zone.
When door is next to close slow length at door
close side, motor speed will be slow down.
SKATE OP. SPEED
10 cm/s
Open speed parameter on skate zone
SKATE CL. SPEED8 cm/s
Close speed parameter on skate zone
OP. HOLD FORCE
40
Force parameter when door is fully opened.
Force is increased when parameter value is
inreased.
CL. HOLD FORCE
20
Force parameter when door is fully closed. Force
is increased when parameter value is inreased.
LEARNING SPEED
10 cm/s
Speed parameter when recognition length of
door size. Motor encoder and current calculation
is using that parameter.
OBSTRUCTION PRS
40
Door obstruction sense parameter.
if value increases, pressure force will be increase
when system sensed obstacle.
SPRING FORCE
20
Spring force will be added to open side
obstruction pressure.
CLOSE SLOW ZONE
AD
MIN
AD
MIN
AD
MIN
AD
MIN
www.konelsan.com.tr
14Konel Electronic
ADS v1.0
Menus
OP/CL SIGNAL
DEMO MODE
CLOSE
Close: No demo mode
Open Slow,Normal, Fast: Demo mode - open
and close waiting time
Op/Cl Signal: Open signal is needed to open door. Close
signal is needed to close door. Close Signals: Close signal
will close door, if no close signal, door will be opened.
ENCODER PULSE100
Enkoder pulse parameter. This parameter is
effect to velocity. If door length and speed is
wrong on learning mode, you must to checked.
SP. CONTROL KP100
PID P control parameter. If value increases,
shaking will increase. Speed jumps is seen.
SP. CONTROL KI
6
PID I control parameter. If value increase, motor
speed reaction will be delayed.
GEAR RATIO 1
3000
Motor gear ratio 1: This parameter is effect to
velocity calculation. Standart is 15:1 or 3000:200
GEAR RATIO 2
200
Motor gear ratio 2: This parameter is effect to
velocity calculation. Standart is 15:1 or 3000:200
RESET COUNTER
0
If value is set to 1, op/cl counter will be reset.
LIMIT CONTACTS
OPEN CONTACT
Fully opened and fully closed relay has Normaly
open contacts.
SIGNAL TYPE
AD
MIN
AD
MIN
AD
MIN
AD
MIN
AD
MIN
AD
MIN
AD
MIN
AD
MIN
AD
MIN
www.konelsan.com.tr
15Konel Electronic
ADS v1.0
Menus
OPEN CONTACT
OP/CL SIGNALS
OPEN CONTACT
OPEN CONTACT: If OPEN/CLOSE input is set to 1,
command will be run.
CLOSE CONTACT: If OPEN/CLOSE input is set to 1,
command will be run.
Obstruction contact has normaly opened
contact.
DOOR TYPE
FULL AUTO
FULL AUTO: skate zone and speed parameter values is
included
TELESCOPIC: Skate zone and peed parameters is not
included
MOTOR SIDERIGHT
If motor cable is wrong, you can change
movement side from this parameter.
ENCODER SIDE
RIGHT
If motor is running truely, but position is not
change, may be encoder side is wrong. You can
change it from this parameter.
QUIT MENUIf Up button is pressed, save and quit menu. If
menu is admin type, you will be admin again
when you enter menu again.
ADMIN QUITIf Up button is pressed, save and quit admin
menu. If you enter again, that time menu is
limited.
OBSTRUCTION CONT
1. Menu right button is pressed by 3 sec for entering the parameter menu.
2. Menu right and left button is used to scroll through parameters.
3. Press up button to increase parameter value, and press down button to decrease parameter value.
4. Cut off input voltage from board for entering admin menu. And turn on board while up and down
button is pressed.
AD
MIN
AD
MIN
AD
MIN
AD
MIN
www.konelsan.com.tr
16Konel Electronic
ADS v1.0
Terminal Names
KONEL ADS V 1.0
MOTOR
CONNECTION
ENCODER INPUTS+5V
GNDB
A
RELAY OUTPUT
OBSTRUCTION
CLOSE
OPEN
20V AC INPUT
ACCUMULATOR+-
COMOPENCLOSE
OPEN/CLOSE
INPUTS+24VGNDNDGKATTA
SPECIFIC INPUTS
MOUNTING HOLES
+15V
+5V Door Open Door CloseObstruction
UP
DOWN
LEFT RIGHT
Wiring Diagram
KONEL ADS V 1.0+5V
GNDB
A+-
COMOPENCLOSE
+24VGNDNDGKATTA
+15V
+5V
1000
100
1000 and 100 can be canged
MEncoder
4
220 AC 20 AC
www.konelsan.com.tr
17
MOUNTING HOLES
MOUNTING HOLES MOUNTING HOLES
Door Open Door Close
Obstruction
UP
DOWN
LEFT RIGHT
OBSTRUCTION
CLOSE
OPEN
Konel Electronic
ADS v1.0
Warnings1. 18V to 22V AC input is suitable for running system. Other wise system does not run at full performance.
2. Motor must be 24V brushed DC with gear and encoder. Motor power can be 200W at maximum.
Please call company for over.
3. Motor gear ratio and encoder parameters must be true. If door length and velocity is wrong, you must change
parameter values on menu.
4. Pressure force should not increase excessive. Our company can not be held responsible. Because it could
cause serious injury
5. Input signals should not over 28V DC.
1. Obstruction protocol: When door sensed obstacle at traditional methot, door velocity wants to increase
motor voltage according to PI algorithm. If obstruction force is big, door does not sense obstacle. It means
obstacle is exposed to maximum force. At the Konel control board, door speed is decreased to minimum when
door sensed obstacle. If door movement is continued, motor is running at slowly until close the door. If door
movement is not continued, motor is stopped and door is opened back and board gives alarm.
2. Obstruction point is get memory. When position is at that point, motor speed is slow down while passing that
point. Then If door position is passed that point, door will run normally speed and stop the alarm.
3. Strain and abrasion can be prevented by skate closing algorithm while running at skate zone. Skate open and
close speed parameters are important factor in this specification.
4. Motor will continue to run while position information is zero but door is not at zero position. In that time
motor speed is door open speed. In real zero zone, system looks motor current and encoder information and
then motor stops and system takes reference of zero point. So settings do not shift.
5. Motor and encoder sides are wrong, you can change sides on software.
6. In encoder fault, door runs at slow speed and gives alarm while running. If encoder fault is fixed, door is
running normal mode.
7. In classic control board, If board energy is turn off and door is opened by manual, motor runs as generator. So
motor gives energy to board. this energy can damage materials. In Konel Door Board, We prevent this fault.
Special Algorithms belongs to Konel Door Control Board
www.konelsan.com.tr
18Konel Electronic
ADS v1.0
TroubleshootingTurn on and motor doesnt move. All leds are
inactive.
1. Check the fuses.
2. Some leds are active, Motor driver must be damaged.
Turn on, leds and lcd are active but motor doesnt
move.
1. Check the motor and encoder cables.
2. Check the Motor speed parameters.
3. Check the KP and KI parameters.
Door is running uncontgrolled. Door is hitting
hard.
1. Check the encoder and be sure running correctly
2. check the motor and encoder cable directions.
3. Check the KP and KI parameters.
Door is opening slowly at some floor. Out door mechanism may force the motor. Obstruction protocole
is running. For this fault, you need to increase obstruction
parameter. If this fault is given at every floor, you need to learning
mode. And increase parameters to %20.
Buzzer is alarmed while closing and door is
opened back
Check the skate zone and speed.
Increase skate speeds.
May increase the obstruction parameter.
Buzzer sound of what it said. If sound is discrete, it is obstruction. And door will be opened.
If sound is discrete and frequently, system gives encoder
fault. and door will run slowly.
In that time, you need to learning mode and check the
obstruction parameters.
www.konelsan.com.tr
19
Door is running but position is not change on lcd. Check the connection of encoder and motors.
Check the motor side and encoder side on admin menu.
Konel Electronic