PROJECT: PRIVATE VILLA G+1 DETAILS OF CONNECTED LOAD / MAX DEMAND & kWH METERING  AREA: DUBAI LAND PLANNED COMPLETION DATE: OCT-2013 PLOT: RC-089 CONSULTANT: AL WAHA ENGINEERING CONSULTANT LOCATION: BOUNDRY WALL PVC/*/ XLPE ECC SIZE  ________ 2/4 X 2/3/4 C 1c SWA/PVC C mm^2 mm^2 mm^2 INCOMING 4P  200Amps 35 26.41 26.51 29.65 82.57 1 OUTGOING DB-G TP 80 25 XLPE/SWA/PVC 4CX25 1CX16 9.00 8.60 10.10 27.70 DB-F TP 60 25 XLPE/SWA/PVC 4CX16 1CX10 4.60 5.50 4.80 14.90 DB-AC TP 100 25 XLPE/SWA/PVC 4CX35 1CX16 12.81 12.81 14.35 39.97 0.90 CONTRACTOR: FAX: REMARKS  PROPOSED TYPE & NOS. OF kWHr METER  1-PH (1)  3-PH (3) LV / HV CT(4)  3-PH (2) 74.31 82.57 BY DEWA TOTAL 1 26.91 ( 1 Phase ) ( 3 Phase ) TELEPHONE: TYPE OF METER ( RATING OF INCOMER ): 200 A (1) Up to 60 A (2) Up to 100 A (3) 125 - 160 A (4) LV CT …/…300A / HV CT ……………./……. .A Y-PH kW CABLE SIZE Length of Cable ( Mtrs.)  CONNECTED LOAD - kW B-PH kW TOTAL kW R-PH kW 26.41  ( SHEET 1 OF 1 ) MDB-: BY DEWA CIRCUIT / FEEDER / DB No.  RATING (AMPS) FAULT DUTY KA F/S ISO SP / TP  ACB/ MCCB CLIENT: MR.MOHAMED ROSHANALI MERALI DEWJI. MAX. DEMAND = TOTAL CONNECTED LOAD = 29.25 82.57 TOTAL BUILD-UP AREA = TOTAL CONNECTED LOAD PER PHASE: MDB CONNECTED TO: DEWA LV DB / TRANSFORMER SMDB CONNECTED TO : DEMAND FACTOR =

MDB-RC-089

Embed Size (px)

DESCRIPTION

s

Citation preview

MDBPROJECT: PRIVATE VILLA G+1DETAILS OF CONNECTED LOAD / MAX DEMAND & kWH METERINGAREA:DUBAI LANDPLANNED COMPLETION DATE: OCT-2013CLIENT: MR.MOHAMED ROSHANALI MERALI DEWJI.PLOT:RC-089MDB-: BY DEWA( SHEET 1 OF 1 )CONSULTANT:AL WAHA ENGINEERING CONSULTANTLOCATION:BOUNDRY WALLCIRCUIT / FEEDER / DB No.SP / TPRATING (AMPS)FAULT DUTY KAPVC/*/ XLPECABLE SIZELength of Cable ( Mtrs.)ECC SIZECONNECTED LOAD - kWPROPOSED TYPE & NOS. OF kWHr METERREMARKSF/S ISOACB/ MCCB________2/4 X2/3/4 C1cR-PH kWY-PH kWB-PH kWTOTAL kW1-PH (1)3-PH (2)3-PH (3)LV / HV CT(4)SWA/PVC1C mm^2mm^2mm^2INCOMING4P200Amps35BY DEWA26.4126.5129.6582.571OUTGOINGDB-GTP8025XLPE/SWA/PVC4CX251CX169.008.6010.1027.70DB-FTP6025XLPE/SWA/PVC4CX161CX104.605.504.8014.90DB-ACTP10025XLPE/SWA/PVC4CX351CX1612.8112.8114.3539.97MDB CONNECTED TO: DEWA LV DB / TRANSFORMERTOTAL CONNECTED LOAD PER PHASE:26.4126.9129.2582.571TOTALSMDB CONNECTED TO :DEMAND FACTOR =0.90MAX. DEMAND =74.31TOTAL CONNECTED LOAD =82.57TOTAL BUILD-UP AREA =CONTRACTOR:TELEPHONE:FAX:TYPE OF METER ( RATING OF INCOMER ): 200 A(1) Up to 60 A (2) Up to 100 A (3) 125 - 160 A (4) LV CT /300A / HV CT ./..A( 1 Phase )( 3 Phase )