    S W I T C H G E A R

    S A F E & S U R E

    Motor ProtectionRelay

    MPR300

  • 8/12/2019 MPR300

    2/4

    M P R 3 0 0

    ApplicationsMPR 300 Motor protection relay is suitablefor back panel surface mounting or DIN railmounting. It offers multiple protections to 3phase induction motors. The R-Y-B phasewires of the motor passes through the relay(no need for external Cts).The measurements are carried out throughintegral CTs and electronics built inside therelay. One set of trip contacts (1 N/O + 1N/C) is available for trip functions along withindividual LED indications. The relay is

    ideally suitable for protection of motorscoupled to pumps, compressors, fans,ventilators, cranes, elevators, escalators,saw mills, paper mills, motorized valves,conveyor belts etc. where frequent over loads, rotor stalling, faulty bearings, and dryrunning conditions are expected.

    PROTECTIONS

    a) Thermal over load protection :b) Negative sequence protectionc) Earth Fault protection

    d) Locked rotor protectione) Under current protection

    Each of the above faults are indicated by aLED on the front panel. On occurrence of fault, the relay provides two contacts 1 N/Oand 1 N/C. These contacts are manual resetand can be used to open a contactor. TheLED fault indication is manual reset onclearance of the fault, the LED has to bereset by the front panel Reset PB.

    TECHNOLOGYMPR 300 uses state of the art digitaltechnology to measure the three phaseand residual currents in the motor feeder.The current signals are sensed throughinbuilt CTs and evaluated bymicrocontroller using advanced digitalsampling techniques. Special algorithmsare used for deriving the thermal statusand other parameters required for variousprotections. The hardware design provideshigh degree of accuracy and reliability.The relay comes in 6 different models tocover full range of motor rated currentsstarting from 1A to 88A. In addition tooffering important protections, the relay ismost user friendly, simple to withstandhigh level of EMI/EMC interferences whichare increasingly present in the present dayindustrial environment.

    Compact Microcontroller based

    design 6 models to cover motor

    rated currents upto 88A 5 protections 3 integral Cts DIP switch selection for

    Thermal Characteristics Trip indication Test funct ion

  • 8/12/2019 MPR300

    3/4

    TECHNICAL SPECIFICATIONS

    Input Connection R-Y-B wires of motor passes through relayBasic Protections Thermal Over load, Negative Sequence (Phase Unbalance)

    Locked Rotor, Earth Fault and Under Current

    Thermal Over Load Protecti on

    1. Current setting 1 to 88A in 6 different models as follow s :1 to 2.75A 2 to 5.50A 4 to 11A8 to 22A 16 to 44A 32 to 88A

    2. Trip Time Characteristics Class 10A, 10, 20 and 30 as per LEC 947-4-1Field selectable through front DIP switches.

    3. Pre alarmAt 1.05 lm by flashing LED (lm = Motor rated current)4. Thermal MemoryProvided.

    Earth Fault Protecti on1. Current setting 10 to 50% of Im field selectable by front panel pot.2. Trip time delay 200 msec factory set3. Disable feature Available from front panel pot.

    Phase Unbalance Protecti on1. Unbalance current 50% of Im factory set2. Trip time delay 3 sec factory set

    Locked Rotor Protection1. Locked rotor current3 Im factory set2. Trip time delay 1sec factory set3. Disable featureAvailable from front panel DIP switch

    Under Current Protection1. Under current threshold50% of Im factory set2. Trip time delay3 sec factory set3. Disable featureAvailable from front panel DIP switch

    Operation al IndicatorsLED indications for Power OnLED indications for trip on each of the 5 faultsLED starts flashing when fault is detected. Becomes steady onWhen the relay trips after the preset time delay.LEDs are manual reset.

    Contacts 1 N/O + 1 N/C manual resetRated Voltage 250 V AC / 30 V DCRated Current 5ARated breaking capacity 2000 VA / 240 W (resistive)

    Auxi li ary Power Supply 240 V AC +/- 20%

    Operating Temperature 0 to 60 degrees C Accurac y As per IEC 947-4-1Reset Current 95% to 90% of ImReset Time Less than 160 millisec for O/L, N/S, U/C and L/R faults

    Less than 80 milisec for Earth faultReference Standards IEC 60255, IEC 61000 and IEC 60068

    TRIPCLASS Tripping Time at multiple of Ie

    10A102030

    120%> 2 hours> 2 hours> 2 hours> 2 hours

    150%2min4min6min12min

    720%2-10 sec.4-10 sec.6-20 sec.9-30 sec.

  • 8/12/2019 MPR300

    4/4

    Wiring Diagram for MPR300

    LARSEN & TOUBRO LIMITEDPowai Works, Saki Vihar Road, P.O. Box 8901Mumbai 400 072