NOX E Datasheets

Embed Size (px)

Citation preview

  • 7/28/2019 NOX E Datasheets

    1/12

    NOX EMAdata sheets

    Content may change without prior notice.

    edited byNOX Systems AGAlvierweg 179490 VaduzPrincipality of Liechtenstein

    Tel +423 370 25 25Fax +423 370 25 26

    [email protected]

    EN 50130-4

    NOX data sheets, December 03, p 1 of 12

    mailto:[email protected]:[email protected]
  • 7/28/2019 NOX E Datasheets

    2/12

    central unit data sheet

    NOX central

    a) NOXCPU

    NOXCPU main board with bus input from

    power supply, MMC card slot, Ethernet RJ-

    45 socket and three NOX bus outputs to

    connect all other NOX Systems devices.

    NOX data sheets, December 03, p 2 of 12

    MMC slot

    backupbattery

    power in / bus 3

    Etherne

    bus 3

    bus 2

    bus 1

    NOXPSU power supply

    NOXCPU

    NOXMIO

    2x 17 Ah accumulators

  • 7/28/2019 NOX E Datasheets

    3/12

    technical data:

    min. nom. max.

    supply voltage (VBUS) VDC 14.25 15.0 15.75

    power consumption at 15 VDC mA ? ?

    operating temperature range C 0 25 40

    air humidity at +40C (non

    condensing)

    % rel. h 93

    dimensions (L x B x H): mm 640 x 404 x 105

    fuses (F1 to F4) 1A slow-blow order no.: 154.001T

    maximum bus output current (bus 1to 3)

    A 2.5

    terminal assignment:

    plugs description

    terminal P1 MMC connector

    terminal P2 RJ45 Ethernet connection

    BAT1 Lithium battery CR2032S1 CPU reset button

    terminal P7 + - A B

    pin 15 5% VDC GND Bus A Bus B

    description input from PSU device

    terminal P3 + - A B

    pin 15 5% VDC GND Bus A Bus B

    description supply voltage (VBUS) bus connection

    terminal P4 + - A Bpin 15 5% VDC GND Bus A Bus B

    description supply voltage (VBUS) bus connection

    terminal P6 + - A B

    pin 15 5% VDCC

    GND Bus A Bus B

    description supply voltage (VBUS) bus connection

    terminal P5 1 2 3

    pin GND TX RX

    description send receive

    NOX data sheets, December 03, p 3 of 12

    P5 for specialpurpose only!

  • 7/28/2019 NOX E Datasheets

    4/12

    CPA data sheet

    NOXCPA

    The NOXCPA is the operating panel for the NOX alarmsystem with 128 x 64 pixels LCD graphic display, white

    back light, integrated alarm buzzer, a numeric key padwith clear C and enter E keys and two scroll keyswith variable function.

    technical data:

    Min. Nom. Max.

    supply voltage (VBUS) VDC 9.0 15.0 15.5

    power consumption at 15 VDC mA 15 50

    operating temperature range C 0 25 40

    air humidity at +40C (non

    condensing)

    % rel. h 93

    dimensions (L x B x H): mmon wall 175 x 110 x 24

    in wall 212 x 148 x 23

    protection class IP30

    terminal assignment:

    terminal P2 + - A B

    pin 9-15.5 VDC GND Bus A Bus B

    description supply voltage (VBUS) bus connection

    NOX data sheets, December 03, p 4 of 12

  • 7/28/2019 NOX E Datasheets

    5/12

    MIO data sheet

    NOXMIO

    NOXMIO is an input and output modulewith eight relay outputs plus four

    resistance monitored inputs with driver forconnected flash lights or sirens. Althoughflexible in the programming, the outputsare often used to interface to alarmtransmission devices.

    technical data:

    min. nom. max.

    supply voltage (VBUS) VDC 9.0 15.0 15.5power consumption 15 VDC mA 15 83

    operating temperature C 0 25 40

    air humidity at +40C (noncondensing)

    % rel. h 93

    input impedance range 1-4 k 3.5 12 50

    electrical data relay 1-4 each contact max. 30VDC/1A

    fuses (F1 to F4) 500mA slow-bloworder no.: 154.500T

    dimensions (L x B): mm 47.5 x 65

    terminal assignment:

    terminal P2 + - A Bpin 9-15.5 VDC GND Bus A Bus B

    description supply voltage (VBUS) bus connection

    terminal P3 1 2 3 4 5 6

    pin VBUS Input 1 O.C. (1) VBUS Input 2 O.C. (1)

    description input 1 input 2

    7 8 9 10 11 12

    pin VBUS Input 3 O.C. (1) VBUS Input 4 O.C. (1)

    description input 3 input 4

    terminal P4 1 2 3 4 5 6

    pin NO (2) COM (3) NC (4) NO (2) COM (3) NC (4)

    description relay 1 relay 2

    7 8 9 10 11 12

    pin NO (2) COM (3) NC (4) NO (2) COM (3) NC (4)

    description relay 3 relay 4

    terminal P5 1 2 3 4 5 6

    pin NO (2) COM (3) NC (4) NO (2) COM (3) NC (4)

    description relay 5 relay 6

    7 8 9 10 11 12

    pin NO (2) COM (3) NC (4) NO (2) COM (3) NC (4)

    description relay 7 relay 8

    O.C.: open collector, NO: normally open, COM: common, 4 NC: normally closed

    NOX data sheets, December 03, p 5 of 12

  • 7/28/2019 NOX E Datasheets

    6/12

    IN4 data sheet

    NOXIN4

    NOXIN4 is a universal input module connectable to the NOXalarm bus with four resistance monitored inputs.

    technical data:

    min. nom. max.

    supply voltage (VBUS) VDC 9.0 15.0 15.5power consumption 15 VDC mA 12 16

    operating temperature C 0 25 40

    air humidity at +40C (noncondensing)

    % rel. h 93

    input impedance range 1-4 k 3.5 12 50

    dimensions (L x B x H): mm 85 x 66 x 27

    protection class IP30

    terminal assignment:

    terminal P2 + - A B

    pin 9-15.5 VDC GND Bus A Bus Bdescription supply voltage (VBUS) bus connection

    terminal P3 1 2 3 4 5 6

    pin VBUS Input 1 GND VBUS Input 2 GND

    description input 1 input 2

    7 8 9 10 11 12

    pin VBUS Input 3 GND VBUS Input 4 GND

    description input 3 input 4

    NOX data sheets, December 03, p 6 of 12

  • 7/28/2019 NOX E Datasheets

    7/12

    RE4 data sheet

    b) NOXRE4

    The NOXRE4 offers four programmable relay outputs totransmit alarms or the status of detector groups to supervising

    systems.

    technical data:

    Min. Nom. Max.supply voltage (VBUS) VDC 9.0 15.0 15.5

    power consumption at 15 VDC mA 12 30

    operating temperature range C 0 25 40

    air humidity at +40C (noncondensing)

    % rel. h 93

    electrical data relay 1-4 each contact max. 30 VDC/1A

    dimensions (L x B x H): mm 85 x 66 x 27

    protection class IP30

    terminal assignment:

    terminal P2 + - A Bpin 9-15.5 VDC GND Bus A Bus B

    description supply voltage (VBUS) bus connection

    terminal P3 1 2 3 4 5 6

    pin NO (1) COM (2) NC (3) NO (1) COM (2) NC (3)

    description relay 1 relay 2

    7 8 9 10 11 12

    pin NO (1) COM (2) NC (3) NO (1) COM (2) NC (3)

    description relay 3 relay 4

    1 NO: normally open, 2 COM: common, 3 NC: normally closed

    NOX data sheets, December 03, p 7 of 12

  • 7/28/2019 NOX E Datasheets

    8/12

    CRD data sheet

    NOXCRD with Wiegand 26 Bit interface

    The NOXCRD is a universal input/output module connected tothe NOX alarm bus with one resistance monitored input, one

    relay output and a card reader port with Wiegand 26 Bitinterface.

    technical data:

    min. nom. max.

    supply voltage (VBUS) VDC 9.0 15.0 15.5power consumption at 15 VDC mA 12 18

    operating temperature range C 0 25 40

    air humidity at +40C % rel. h 93

    input impedance range (noncondensing)

    k 3.5 12 50

    electrical data relay max. 30VDC/1A

    dimensions (L x B x H): mm 85 x 66 x 27

    protection class IP30

    terminal assignment:

    terminal P2 + - A Bpin 9-15.5 VDC GND Bus A Bus B

    description supply voltage (VBUS) bus connection

    terminal P3 1 2 3 4 5 6

    pin VBUS Input GND 5 VDC GND LED 1

    description input card reader

    7 8 9 10 11 12

    pin LED 2 Data 0 Data 1 NO (1) COM (2) NC (3)

    description card reader relay

    1 NO: normally open, 2 COM: common, 3 NC: normally closed

    NOX data sheets, December 03, p 8 of 12

  • 7/28/2019 NOX E Datasheets

    9/12

    RPT data sheet

    NOXRPT

    The NOXRPT is a universal module configurable as repeater(RS485) or as serial gateway (RS232) to connect a personal

    computer to the NOX alarm bus.

    technical data:

    min. nom. max.

    supply voltage (VBUS) VDC 9.0 15.0 15.5power consumption at 15 VDC mA 13 14

    operating temperature range C 0 25 40

    air humidity at +40C (noncondensing)

    % rel. h 93

    dimensions (L x B x H) mm 85 x 66 x 27

    protection class IP30

    terminal assignment:

    terminal P1 1 2 3 4

    pin 5 VDC GND RX TX

    description reserve serial interface (RS232)

    terminal P2 + - A B

    pin 9-15.5 VDC GND Bus 1 A Bus 1 B

    description supply voltage 1 (VBUS1) bus 1 - input

    terminal P3 + - A B

    pin 9-15.5 VDC GND Bus 2 A Bus 2 B

    description supply voltage 2 (VBUS2) bus 2 - output

    jumper assignment:

    JP1 1-2 2-3 JP2 ON OFF

    function repeater serialinterface

    function VBUS1=VBUS2

    VBUS2external

    output Bus 2output

    RS232

    NOX data sheets, December 03, p 9 of 12

  • 7/28/2019 NOX E Datasheets

    10/12

    THS data sheet

    NOXTHS

    The NOXTHS module connects an internal or externalcombined sensor for temperature and humidity to the NOxbus.

    The module contains a freely programmable relay outputon the board.

    This device is not approved by the SVV.

    technical data:

    min. nom. max.

    supply voltage (VBUS) VDC 9.0 15.0 15.5

    power consumption at 15 VDC mA 12 14

    operating temperature range C 0 25 40

    air humidity at +40C % rel. h 93

    electrical data relay max. 30VDC / 1A

    dimensions (L x B x H) mm 85 x 66 x 27

    protection class IP30

    terminal assignment:

    terminal P2 + - A B

    pin 9 - 15.5VDC GND Bus A Bus B

    description supply voltage (VBUS) bus connection

    terminal P3 1 2 3 4 5 6

    pinX X X Sensor

    5VGND Data1

    description X= not used Sensor

    7 8 9 10 11 12

    pin Data2 X X NO (1) COM (2) NC (3)

    description Sensor X= do not use relay

    1 NO: normally open, 2 COM: common, 3 NC: normally closed

    NOX data sheets, December 03, p 10 of 12

  • 7/28/2019 NOX E Datasheets

    11/12

    technical data sensor (SHT71)

    Tested for temperature range from:-25 to +75 C for the externalsensor

    Tested for temperature range from:0 to +40 C for the internal sensor

    Tested for humidity range from: 0to 100% RHfor both, the internal and theexternal sensor

    NOX data sheets, December 03, p 11 of 12

  • 7/28/2019 NOX E Datasheets

    12/12

    M31 data sheet

    NOXM31

    NOXM31 is a compact module with one output and threeinputs for integration into the housing of a detector.

    technical data:

    min. nom. max.

    supply voltage (VBUS) VDC 9.0 15.0 15.5

    power consumption 15 VDC mA 12 16

    operating temperature C 0 25 40

    air humidity at +40C (non

    condensing)

    % rel. h 93

    electrical data open collector output max. 15 VDC/ 50 mA (to GND)

    dimensions (L x B x H): mm 16 x 23 x 10

    terminal assignment:

    terminal P? A B

    pin Bus A Bus B

    description bus connection

    wire red black yellow green 1

    pin + - OUT IN 1

    description supply voltage output inputwire green 2 green 3

    pin IN 2 IN 3

    description input

    All three input are equipped with a 10k pull up resistor. The inputs are triggered bytying them down to GND.

    attention: It is not allowed to lengthen the pre-connected wires!

    NOX data sheets, December 03, p 12 of 12