Postes

Embed Size (px)

DESCRIPTION

postes

Citation preview

  • Esquema para calculo de viento para postes telescopicos

    Tipo de Exposicion: c Factor = 7 Zg(m)= 270Grupo Segn el Uso: b Factor de importancia eolica: 1Velocidad del viento (Region): 90 Km/h

    Tipo de Poste Z(m) Kz qz(kg/m2) A(m2) F=qz*A(kg) Brazo (m) M=F*Brazo(Kg-m)1 20mts 8.20 0.95 37.35 1.80 67.23 4.10 275.62

    4.50 0.80 31.46 0.80 25.17 10.45 263.034.50 0.80 31.46 0.63 19.82 14.95 296.34

    V= 112.22 M1= 834.992 18mts 7.50 0.93 36.41 1.64 59.71 3.75 223.90

    4.00 0.77 30.42 0.71 21.60 9.50 205.204.00 0.77 30.42 0.56 17.04 13.50 229.99

    V= 98.34 M2= 659.093 15mts 6.30 0.88 34.64 1.38 47.80 3.15 150.57

    3.25 0.73 28.67 0.58 16.63 7.93 131.783.25 0.73 28.67 0.45 12.90 11.18 144.17

    V= 77.33 M3= 426.534 11,28mts 4.24 0.79 30.93 0.59 18.25 2.12 38.69

    2.67 0.69 27.10 0.31 8.40 5.58 46.842.67 0.69 27.10 0.24 6.50 8.25 53.63

    V= 33.16 M4= 139.17

    h1= 3mh2 2.7h3 2.4h4 1.9

    Sheet1