Qureshi 2014

Embed Size (px)

Citation preview

  • 8/10/2019 Qureshi 2014

    1/9

    Heat exchanger inventory cost optimization for power cycles with one

    feedwater heater

    Bilal Ahmed Qureshi, Mohamed A. Antar, Syed M. Zubair

    Mechanical Engineering Department, KFUPM Box # 1474, King Fahd University of Petroleum & Minerals, Dhahran 31261, Saudi Arabia

    a r t i c l e i n f o

    Article history:

    Received 6 March 2014Accepted 7 May 2014

    Keywords:

    Inventory

    Heat exchanger

    Thermoeconomic

    Optimization

    Feedwater heater

    a b s t r a c t

    Cost optimization of heat exchanger inventory in power cycles with one open feedwater heater is under-

    taken. In this regard, thermoeconomic analysis for an endoreversible power cycle with an open feedwater

    heater is shown. The scenarios of constant heat rejection and addition rates, power as well as rate of heat

    transfer in the open feedwater heater are studied. All cost functions displayed minima with respect to the

    high-side absolute temperature ratio (h1). In this case, the effect of the Carnot temperature ratio (U1),

    absolute temperature ratio (n) and the phase-change absolute temperature ratio for the feedwater heater

    (U2) are qualitatively the same. Furthermore, the constant heat addition scenario resulted in the lowest

    value of the cost function. For variation of all cost functions, the smaller the value of the phase-change

    absolute temperature ratio for the feedwater heater (U2), lower the cost at the minima. As feedwater

    heater to hot end unit cost ratio decreases, the minimum total conductance required increases.

    2014 Elsevier Ltd. All rights reserved.

    1. Introduction

    Using feedwater heaters, also called regenerators, to enhance

    efficiency of steam power plants is a standard practice in industry

    and, therefore, thermoeconomic analysis of such systems is

    important. Feedwater heaters can either be open or closed type.

    When the heat is transferred from the steam (bled from the tur-

    bine) to the feedwater by mixing, it is considered an open type.

    The advantages offered include a higher efficiency of the power

    plant due to a rise in the average temperature of heat addition.

    Next, it helps to prevent boiler corrosion by providing an easy

    way to remove air that leaks into the condenser. Also, it lowers

    the volume flow in the final turbine stages. For further details,

    the work of Babcock & Wilcox [1] may be consulted along with

    textbooks on Thermodynamics such as Cengel and Boles [2].

    Authors such as Bejan[3,4]addressed the issue of heat exchan-ger inventory allocation for different situations such as maximizing

    the efficiency. The Carnot model developed by Bejan[4]was used

    by Antar and Zubair[5]to study cost optimization of power plant

    heat exchanger inventory for a specified power output. The total

    inventory reached a minimum when the unit cost ratio attained

    unity. Sahin and Kodal [6] carried out thermoeconomic optimiza-

    tion of endoreversible heat engines using a new thermoeconomic

    optimization criterion i.e. power output per unit total cost.

    Analytical equations for optimum working fluid temperatures,

    specific power output, thermal efficiency and distribution of heat

    exchanger areas were determined. The effect of relative fuel cost

    was also discussed. This new criteria was later used by the authors

    for irreversible heat engines[7]as well. Using profit maximization

    as the objective function, exergoeconomic performance optimiza-

    tion of a finite-time irreversible Carnot engine was investigated

    by Chen et al.[8]. The authors derived relevant formulae concern-

    ing profit and efficiency for this purpose.

    Bandyopadhyay et al. [9] studied combined cycle power plant

    cost optimization using irreversible Carnot-like heat engines. It

    was found that the yearly plant cost rose along with a decline in

    power output as the number of stages was increased. For off-

    design conditions in combined cycle gas turbine power plants,

    Rovira et al.[10]performed thermoeconomic optimization in heat

    recovery steam generators. Based on design conditions, negligibledifference was found in the optimization results when compared

    to those obtained from usual thermoeconomic models except for

    the fact that, with the new model, a minor decrease was seen in

    the amortization cost and design efficiency. For combined cycle

    power plants, genetic algorithms have also been used for the pur-

    pose of thermoeconomic optimization [1113]. Using the Second

    Law of Thermodynamics, Silveira and Tuna[14]presented a ther-

    moeconomic functional analysis method. Four cogeneration sys-

    tems were analyzed and the system consisting of a gas turbine

    with heat recovery steam generator only was found to have the

    lowest exergetic production cost. Al-Sulaiman et al. [15,16]

    http://dx.doi.org/10.1016/j.enconman.2014.05.028

    0196-8904/2014 Elsevier Ltd. All rights reserved.

    Corresponding author. Tel.: +966 3 860 3135.

    E-mail address:[email protected](S.M. Zubair).

    Energy Conversion and Management 86 (2014) 379387

    Contents lists available at ScienceDirect

    Energy Conversion and Management

    j o u r n a l h o m e p a g e : w w w . e l s e v i e r . c o m / l o c a t e / e n c o n m a n

    http://dx.doi.org/10.1016/j.enconman.2014.05.028mailto:[email protected]://dx.doi.org/10.1016/j.enconman.2014.05.028http://www.sciencedirect.com/science/journal/01968904http://www.elsevier.com/locate/enconmanhttp://www.elsevier.com/locate/enconmanhttp://www.sciencedirect.com/science/journal/01968904http://dx.doi.org/10.1016/j.enconman.2014.05.028mailto:[email protected]://dx.doi.org/10.1016/j.enconman.2014.05.028http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://crossmark.crossref.org/dialog/?doi=10.1016/j.enconman.2014.05.028&domain=pdfhttp://-/?-
  • 8/10/2019 Qureshi 2014

    2/9

    performed thermoeconomic optimization of three trigeneration

    systems using organic Rankine cycles. Formulations were pre-

    sented and the systems examined which revealed that, from the

    three systems, the solar trigeneration system offered the best ther-

    moeconomic performance. Abusoglu and Kanoglu [17] reviewed

    exergoeconomic optimization and analysis for combined heat

    and power systems. A comparison of the advantages and disadvan-

    tages regarding important thermoeconomic methodologies found

    in the literature were made.

    Xiong et al.[18]performed thermoeconomic optimization of a

    600 MWe pulverized-coal-fired power plant using oxy-combus-

    tion. A 10% increase in unit thermoeconomic product costs was

    seen due to the extra power utilization for the oxy-combustion

    system and another 10% due to its other related costs such as oper-

    ation and maintenance, investment as well as interest. Bassily[19]

    performed cost optimization of commercial combined cycle power

    plants with triple-pressure reheating. It was determined that, for a

    400 MW power plant, an annual saving of about $29.2 million

    could be obtained by optimizing the net revenue.

    Rosen and Dincer [20] thermoeconomically examined an electri-

    calgeneratingstationfueled by coal basedon capital cost only. They

    emphasized that the reason for this is that the capital cost is often

    the most significant cost component and costs other than that are

    often proportional to it. Thus, qualitative agreement is expected.

    Forthe designand analysis of energysystems, Silveiraet al.[21] pre-

    sented a thermoeconomic optimization methodology using the

    exergetic production cost as the objective function. Depending on

    the energy system analyzed, the various costs included operationalandcapital cost fora given amount andtype of exergy. Seyyedi et al.

    [22] provided a new approach for optimization of thermal power

    plants based on the exergoeconomic analysis and structural optimi-

    zation method. Important advantages of this new method are its

    applicability to large complex thermal systems and rapid conver-

    gence. Considering various objective functions based on finite-time

    thermodynamics and thermoeconomics, Durmayaz et al.[23]pre-

    sented an extensive review on optimization of thermal systems.

    The conclusion of the authors was that finite-time thermoeconomic

    analysisneededmore workin fundamentaltheorydevelopmentand

    applications as it was still in its early stages.

    It was found through the literature review that, for the endore-

    versible case of a power cycle with one feedwater heater, cost opti-

    mization has not been considered for design and performance

    evaluation purpose. Therefore, this paper aims to develop the rel-

    evant endoreversible models and then perform thermoeconomic

    analysis of this system. The scenarios of constant heat addition

    and rejection rates, power as well as rate of heat transfer in the

    open feedwater heater will be studied.

    2. Mathematical framework

    Following the methodology of Bejan[4] and Antar and Zubair

    [5], the endoreversible form of the power cycle with one open

    feedwater heater is now considered. The schematic of system

    under consideration is shown in Fig. 1(a) while Fig. 1(b) shows

    its T-s diagram. The purpose of the current study is to determinethe minimum of the total cost of conductance (UA) for the follow-

    ing scenarios: constant rate of heat addition, power, heat transfer

    in the preheater and heat rejection. The Heat Exchanger Inventory

    Cost Equation (HEICE) can be written in terms of heat exchanger

    unit cost parameters as[5]:

    C cHUAH cLUAL cOFHUAOFH 1wherecH, cL, and cOFHare unit cost of conductance for the boiler,condenser and preheater, respectively, such that C has units of

    dollars. Next,

    _QH UAHTH THC 2

    _QL

    UA

    L

    T01

    TL

    3

    _QOFH UAOFHT02 TOFH 4a

    whereTOFH is the average preheating temperature and is given by:

    TOFH T02 DTOFH;avg 4bwhereDTOFH,avgis the average amount of preheating and considered

    as half of the total achieved. Putting Eqs. (2)(4)in Eq.(1)results in

    C cH_QH

    TH THC cL_QL

    T01 TL cOFH_QOFH

    DTOFH;avg5

    Dividing throughout bycH, we get

    C

    cH

    _QH

    TH THCcL

    cH

    _QL

    T01 TL cOFH

    cH

    _QOFH

    DTOFH;avg 6

    Nomenclature

    A area (m2)F non-dimensional cost function ()G unit cost conductance ratio ()K non-dimensional quantity defined by Eq.(15f)()k1 ratio of feedwater heater to condenser entropy

    change ()_m mass flow rate (kg s1)_Q rate of heat transfer (kW)s specific entropy (kJ kg1 K1)T absolute temperature (K)U overall heat transfer coefficient (kW m2 K1)

    GreekC total cost ($)c unit conductance cost ($kW1 K)U1 Carnot temperature ratio ()U2 phase-change absolute temperature ratio for the

    feedwater heater ()

    h1 high-side absolute temperature ratio ()h2 average preheating absolute temperature ratio ()n absolute temperature ratio ()

    Subscripts01 at condenser02 at phase-change in feedwater heatera constant rate of workb constant rate of heat rejection from the condenserC reversible compartmentc constant rate of heat addition in the boilerd constant rate of heat transfer in the open feedwater

    heaterH hot endL cold endmin minimumOFH open feedwater heatertot total

    380 B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/10/2019 Qureshi 2014

    3/9

    Let cLcH GL and

    cOFHcH

    GOFH, thus Eq.(6) becomes

    C

    cH _QH

    TH THC GL_QL

    T01 TL GOFH_QOFH

    DTOFH;avg 7Factoring out _QH, we get

    C

    cH _QH 1

    TH THC GL_QL=_QHT01 TL GOFH

    _QOFH=_QHDTOFH;avg

    " # 8

    Now, fromFig. 1(b), we see that

    _QOFH _m01TOFHs3 s2 9a

    _Q36 _m02T02s6 s3 9b

    _QL _m01T01s7 s1 9c

    But _

    QOFH _

    Q36 since they are exchanging heat with each other

    exclusively in the feedwater heater. Thus,

    _QOFH_QL

    _m02T02s6 s3_m01T01s7 s1 10

    We see fromFig. 1(b) that, in general, (s6 s3) = k1(s7 s1) wherek1can be any number less than one. Now, Eq. (10)becomes

    _QOFH_QL

    k1_m02T02_m01T01

    11

    Applying the Clausis inequality to the internally reversible cycle

    gives us

    _QHTHC

    _QLT01

    ; 12a

    _QL_QH

    T01THC

    12b

    Combining Eqs.(11), (12a), (12b), we get

    _QOFH_QH

    k1_m02T02_m01THC

    13

    Putting Eqs. (12b) and (13) into Eq. (8), we get after dividing the

    right hand side by TH/TH,

    C

    cH

    _QHTH

    1

    1 THCTH

    GLT01THC

    T01TH

    TLTH

    GOFHk1

    _m02T02_m01THC

    DTOFH;avgTH

    24

    35 14

    Introducing the following non-dimensional quantities:

    h1 THCTH

    15a

    h2 DTOFH;avgTH

    15b

    U1

    T01THC

    15c

    U2T02

    THC15d

    n TLTH

    15e

    K k1_m02_m01

    15f

    Putting Eqs.(15a), (15b), (15c), (15d), (15e), (15f)into Eq.(14), and

    multiplying both sides by THgives us

    C

    cHTH _QH 1

    1

    h1

    GL U1U1h1

    n

    GOFHKU2h2 16

    Beginning from Eq. (16), the next section discussesthe following

    scenarios: constant power, heat addition and rejection capacities as

    well as heat transfer rate in the open feedwater heater.

    3. Results and discussion

    In those situations in which the unit cost conductance ratios are

    considered unity, it is expected that minimization of the dimen-

    sionless HEICE will result in the same for the total conductance

    (UAtot).

    3.1. Constant power

    The non-dimensional equation resulting from dividing Eq.(16)by the power is:

    Fig. 1. Endoreversible power cycle with an open feedwater heater: (a) Schematic

    and (b)T sdiagram.

    B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387 381

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/10/2019 Qureshi 2014

    4/9

    Fa CcH

    _WTH

    _QH_W

    1

    1 h1 GLU1

    U1h1 n GOFHKU2h2

    17

    Keeping Fig. 1(a) in mind and using the First Law of

    Thermodynamics, we get

    _W _QH _QL 18

    where _

    Wis the total power consumed by the pumps. Now, dividingboth sides by _QHgives us

    _W_QH

    1 _QL_QH

    19

    Putting Eq.(12)in Eq.(19)gives us

    _W_QH

    1 T01THC

    20a

    The reciprocal of the above equation gives us

    _QH_W

    11 T01

    THC

    20b

    Combining Eqs. (15c) and (20b) and putting them into Eq. (17)results in

    Fa 11 U1

    1

    1 h1 GLU1

    U1h1 n GOFHKU2h2

    21

    Eq. (21) is the non-dimensional HEICE for an endoreversible

    power cycle with one open feedwater heater for the constant

    power output scenario. We see that there is a direct relationship

    between Fa and n as well as U2 and an inverse one with respect

    to h2 and, thus, these parameters do not exhibit minima. It is

    unclear whether minima exist with respect to U1 and h1. Deter-

    mining the derivative ofFa with respect to U1 and then equating

    it to zero gives us:

    @Fa

    @U1 1

    1 U11

    1 h1 GL

    U1

    U1h1 n GOFH

    KU2

    h2

    GL nU1h1 n2" #

    0 22aor

    U1;min cn

    ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffin1 c cn

    p1 ch1 22b

    where

    c 11 h1 GOFH

    KU2h2

    1

    GL

    Fig. 2(a) shows a plot of the cost function Faagainst U1for differentvalues ofn. It is found that the minimum value ofU1as well as the

    cost rise asn increases. The reason for the increasing cost is evident

    from Eq.(21)wheren is seen in the second term inside the brackets

    only. As n increases, this term increases in value and, thus, Faas well.

    Regardingthe minimum value ofU1 (that provides a minimum cost),

    it can be seen from Eq.(22b)that this is due to the fact that U1,minis

    directly proportionalto n. Furthermore,thisshowsthata lowerambi-

    ent temperature would result in a lower cost if all other quantities

    remained the same. Fig. 2(b) shows a plot of the cost function Faagainst U1 for different values ofh1. It is found that the minimum

    value ofU1 decreases ash1 increases but the cost rises. The reason

    for the increasing cost is understood from Eq. (21)where h1is seen

    in the first and second terms inside the brackets. The first term con-

    tainingh1is the dominant term, therefore, as h1increases, this termincreasesin value and, thus, Fa as well. Regardingthe minimum value

    ofU1, it can be seen from Eq.(22b)that this is due to the fact that

    U1,min is inversely proportional to h1. Also, the (1 +c) term, which

    contains h1 as well, dominates the quantities containing c in the

    numerator. Furthermore, this shows that a higher furnace tempera-

    ture may result in a lower cost if all other quantities remained the

    same. Fig. 2(c) shows a plot of the cost function Faagainst U1for dif-

    ferent values ofU2. It was noted that lower values ofU2produced

    lower costs while the minimum value ofU1 was not affected by

    change in U2. The reason for the decreasing cost is understood from

    Eq.(21)where U2 is seen in the last term inside the bracket only

    and directly proportional to Fa. Regarding the minimum value ofU1not changing significantly, it can be explained from the fact that

    the effect of variation in U2 is very small on c. Furthermore, this

    shows that a lower feedwater heater temperature (T02) may resultin a lower cost if all other quantities remained the same.

    Fig. 2. Dimensionless HEICE for specified power versus U1: (a) effect of varying n,

    (b) effect of varying h1and (c) effect of varying U2.

    382 B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387

  • 8/10/2019 Qureshi 2014

    5/9

    The function Fa seems to have a minimum with respect to the

    parameter h1. Putting oFa/ oh1 equal to zero and solving, we get

    h1;min 1U1

    n ffiffiffiffiffiGLp 1 U1GL ffiffiffiffiffiGLp GL 1

    23

    It should be noted that Eq.(23)is identical to the respective deriva-

    tive found by Antar and Zubair [5] though they did not plot it.

    Fig. 3(a) shows the effect of different values ofn as Favaries againsth1. It is found that the optimum point ofh1shifts to a greater value

    as n increasesas well as thecost.Thisbehavior issimilar to that found

    in Fig. 2(a). As can be seen from Eq. (23), thisis simply due to the fact

    thatn is directlyproportional toh1,min. Fig.3(b)shows theeffectof dif-

    ferentvaluesofU1 as Fa varies against h1. It isseenthatthe costfunc-

    tion andh1,min shift to a lower value as U1increases. This is because

    U1is inversely proportional toh1,min (See Eq.(23)) and, as far as the

    cost is concerned, it can be explained from the fact that, in Eq. (21),

    thesecond term insidethe brackets isdominantand theterm outside

    is not significantly affected by the variation in U1. It shows that

    increasing the condenser temperature may result in a lower cost if

    all other quantities remained the same. Fig. 3(c) shows a plot of the

    cost functionFaagainsth1for different values ofU2. It is found that

    the minimum value ofU1

    is not affected by change in U2

    and this is

    because the term U2 does not exist in the expression for h1,min. It

    wasnoted that highervalues ofU2 producedhigher costs and the rea-

    sons are the same as was explained earlier for Fig. 2(c). Furthermore,

    it shows that a lower feedwater heater temperature may result in a

    lower cost if all other quantities remained the same.

    3.2. Constant heat rejection rate

    The non-dimensional cost equation resulting from dividing Eq.

    (16)by the condenser heat transfer rate is:

    Fb CcH

    _QLTH

    _QH_QL

    1

    1 h1 GLU1

    U1h1 n GOFHKU2h2

    24

    After the relevant substitutions, we get

    Fb 1U1

    1

    1 h1 GLU1

    U1h1 n GOFHKU2h2

    25

    Eq.(25)is the non-dimensional HEICE for an endoreversible power

    cycle with one open feedwater heater for the constant heat rejec-

    tion rate scenario. We wish to find out whether the function Fbhas minima with respect to n, U1, U2, h1 and h2. Fb is directly pro-

    portional to n as well as U2 and inversely proportional to h2 and,

    thus, no minima exist. Determining the derivative ofFbwith respect

    to U1 and then equating it to zero gives us:

    @Fb@U1

    1U1

    1

    1 h1 GLU1

    U1h1 n GOFHKU2h2

    GL nU1h1 n2" #

    0 26In the above equation, all terms are positive and, therefore, a prac-

    tical minimum is not possible. The result of taking the derivative of

    Fbwith respect toh1, in this case, is identical to Eq.(23).Fig. 4(a)(c)

    are plotted for conditions identical to those of Fig. 3(a)(c). It is

    found that the behavior for this cost function is qualitatively the

    same as Fa and the only difference is in the values. It can be

    explained from the fact that the terms inside the brackets for both

    the cost functions are identical while there is a minor difference in

    the term outside it for both the cost functions are identical while

    there is a minor difference in the second bracketed term.

    3.3. Constant heat addition rate

    The non-dimensional cost equation resulting from dividing Eq.

    (16)by the boiler heat transfer rate is:

    Fc CcH

    _QHTH 1

    1 h1 GLU1

    U1h1 n GOFHKU2h2

    27

    Eq.(27)is the non-dimensional HEICE for an endoreversible power

    cycle with one open feedwater heater for the constant heat addition

    rate scenario. No minima exist for Fcwith respect to n , U2 and h2.

    Determining the derivative ofFcwith respect to U1and then equat-

    ing it to zero gives us:

    @Fc

    @U1 n

    n U1h120

    28

    Fig. 3. Dimensionless HEICE for specified power versus h1: (a) effect of varyingn, (b)effect of varying U1 and (c) effect of varying U2.

    B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387 383

    http://-/?-http://-/?-http://-/?-
  • 8/10/2019 Qureshi 2014

    6/9

    As all terms in the equation are clearly positive on one side, there-

    fore, no minimum exists. The result of taking the derivative of Fcwith respect to h1, in this case, is identical to Eq. (23).Fig. 5(a)(c)

    are plotted for conditions identical to those of Fig. 3(a)(c). It is

    found that the behavior for this cost function is qualitatively the

    same as Fa and the only difference is in the values. The reason for

    this is that the quantities inside the brackets for both the cost

    functions (i.e. Fa and Fc) are identical while there is a small

    difference outside it which is a multiplying factor only.

    3.4. Constant heat transfer rate in feedwater heater

    The non-dimensional cost equation resulting from dividing Eq.

    (16)by the rate of heat transfer in the open feedwater heater is:

    Fd C

    cH _QOFHTH

    _QH

    _QOFH

    1

    1 h1 GLU1

    U1h1 n GOFHKU2h2

    29a

    Substituting Eqs.(13), (15d) and (15f)in Eq.(29a), we get

    Fd CcH

    _QOFHTH 1

    KU2

    1

    1 h1 GLU1

    U1h1 n GOFHKU2h2

    29b

    The functionFdis also found to have no minimum with respect to n

    and h2 as it is clearly inversely proportional to them. Determining

    the derivative ofFdwith respect to U1and then setting it equal to

    zero results in Eq. (28) and, therefore, no minimum exists. Now,

    determining the derivative of Fd with respect to U2 and equating

    it to zero gives:

    @Fd@U2

    GOFH 1h2U2

    1KU2

    2

    1

    1 h1 GLU1

    U1h1 n GOFHKU2h2

    0

    30a

    or, after simplification, gives

    Fig. 4. Dimensionless HEICE for specified heat rejection rate versus h1: (a) effect of

    varying n, (b) effect of varying U1 and (c) effect of varying U2.

    Fig. 5. Dimensionless HEICE for specified heat addition rate versus h1: (a) effect of

    varying n, (b) effect of varying U1 and (c) effect of varying U2.

    384 B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387

  • 8/10/2019 Qureshi 2014

    7/9

    @Fd@U2

    11 h1 GL

    U1U1h1 n 0 30b

    As all terms in the equation are clearly positive, therefore, no min-

    imum exists. Finally, oFd/oh1was found to be the same as in Eq. (23).

    Fig. 6(a)(c) are plotted for conditions identical to those ofFig. 3(a)

    (c). It is found that the behavior for this cost function is qualitatively

    the same asFaand the only difference is in the values. This is due to

    the fact that the quantities inside the brackets for both the costfunctions (i.e. Fa and Fd) are the same and, although the term out-

    side it is different, it only acts a multiplying factor resulting in a

    change of value but not the behavior.

    3.5. Effect of unit cost ratios

    The purpose of the analysis in this section is determining the

    minimum of the total conductance for specified power production

    and this scenario is chosen due to its practical nature. Optimum

    values for U1 and h1 will be determined from Eqs. (22b) and (23),

    respectively.

    In order to provide an illustrative example for the purpose of

    showing model applicability, it is required that ratios of the con-

    ductance costs of each heat exchanger to the total cost be deter-

    mined. For the sake of brevity, only the final expressions are

    shown below:cHUAH

    C 1 GLU11 h1

    U1h1 n GOFHKU21 h1

    h2

    131

    cLUALC

    1GL

    U1h1 nU11 h1 1

    GOFHGL

    KU2h2

    U1h1 nU1

    132

    Fig. 6. Dimensionless HEICE for specified heat transfer rate in the feedwater heaterversush1: (a) effect of varying n, (b) effect of varying U1and (c) effect of varying U2.

    Fig. 7. Example of all conductances versus unit cost ratio of cold to hot end: (a) atGOFH= 1, (b) at GOFH= 0.5 and (c) at GOFH= 0.1.

    B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387 385

    http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/10/2019 Qureshi 2014

    8/9

    cOFHUAOFHC

    1GOFH

    h2

    KU21 h1 GLGOFH

    h2

    KU2

    U1U1h1 n 1

    133

    A comparison of the above equations with the work of Antar and

    Zubair[5]clearly shows that, due to the presence of the feedwater

    heater unit conductance ratio (GOFH) term, Eqs.(31) and (32)do not

    reduce to mere dependence onGL. Now, we use the same values for

    TH, cL, n and _W; as used by Antar and Zubair [5], for our example(SeeFig. 7(a)(c)). It should be noted that, in power systems, the

    unit cost of the boiler (cH) would be higher than the other heatexchangers. Therefore, it is appropriate to focus on values less than

    unity for GOFHin our investigation. It is noted that, in Fig. 7(a)(c),

    compared to Antar and Zubair [5], the total conductance curve isslightly asymmetric. This is due to the fact that the conductance

    of the feedwater heater is larger than the other heat exchangers

    and varies non-linearly with GL. The difference at the ends is

    1.32 kW/K when GOFHis unity; though it increase to 4.25 kW/K at

    GOFH= 0.1. See Table 1 for a more detailed comparison. It is also

    noted that when all unit cost ratios are at unity, the minimum total

    conductance is also obtained at unity. The reason is that, in this

    case, the unit cost of each heat exchanger becomes the same which,

    in turn, results in all conductances influencing the total cost (See Eq.

    (1) by equal weightage. Another observation is that, as GOFHdecreases, the minimum of the total conductance required

    increases and that it is obtained at lower values ofGL. These varia-

    tions are found to be non-linear such that when GOFH decreases

    from 1 to 0.5, there is only a 0.88% increase in the minimum totalconductance while it increases by 5.7% when GOFH decreases from

    0.5 to 0.1.

    4. Conclusions

    The optimization problem studied for power cycles with one

    feedwater heater has two significant minima i.e. h1 and U1. Some

    important conclusions are as follows:

    Since theF-value is based on an endoreversible power cycle, for

    specified temperatures and flow rates, it predicts the minimum

    initial heat exchanger cost.

    All cost functions displayed a minimum for the parameter h1

    that was the same for all cases. Only the value of the cost func-tions was different.

    For variation of all F-values with respect to h1and U1, the smal-

    ler the value ofU2, lower the cost at the minima.

    For variation of all F-values with respect to h1, the effect of dif-

    ferent values ofn is qualitatively the same. This is found to be

    respectively true for the effect of different values of U1 and

    U2. Furthermore, in these cases, the constant heat addition sce-

    nario resulted in the lowest value cost function.

    For the system investigated, the minimum with respect toU

    1exists only for the scenario of specified power cost function

    i.e.Fa.

    No minima were found with respect to n, h2and U2.

    While taking into account the effect of the unit cost ratios, the

    following conclusions can be made:

    Ratios of the conductance costs of each heat exchanger to the

    total cost were attained.

    If cold and hot end heat exchanger unit costs are the same i.e.

    GL= 1, the total conductance was minimized at GOFH= 1.

    At optimum conditions, the total conductance is not equally

    divided among the heat exchangers. But when all unit cost

    ratios are unity, the hot and cold end conductances are equal

    in value.

    Acknowledgements

    The authors acknowledge the support provided by King Fahd

    University of Petroleum & Minerals through the project IN121042.

    References

    [1] The Babcock & Wilcox. Steam: its generation and use. 41st ed. Babcock &Wilcox Company, 2005.

    [2] Cengel YA, Boles MA. Thermodynamics: an engineering approach. 7thed. McGraw-Hill Inc.; 2010.

    [3] Bejan A. Theory of heat transfer-irreversible power plants. Int J Heat MassTransf 1988;31:12119.

    [4] Bejan A. Power and refrigeration plants for minimum heat exchangerinventory. J Energy Resour Technol 1993;115:14850.

    [5] Antar MA, Zubair SM. Thermoeconomic considerations in the optimumallocation of heat exchanger inventory for a power plant. Energy ConversManag 2001;42:116979.

    [6] Sahin B, Kodal A. Performance analysis of an endoreversible heat engine basedon a new thermoeconomic optimization criterion. Energy Convers Manag2001;42:108593.

    [7] Kodal A, Sahin B. Finite size thermoeconomic optimization for irreversible heatengines. Int J Therm Sci 2003;42:77782.

    [8] Chen L, Sun F, Wu C. Maximum-profit performance for generalized irreversibleCarnot-engines. Appl Energy 2004;79:1525.

    [9] Bandyopadhyay S, Bera NC, Bhattacharyya S. Thermoeconomic optimization ofcombined cycle power plants. Energy Convers Manag 2001;42:35971.

    [10] Rovira A, Snchez C, Muoz M, Valds M, Durn MD. Thermoeconomic

    optimisation of heat recovery steam generators of combined cycle gas turbinepower plants considering off-design operation. Energy Convers Manag2011;52:18409.

    [11] Baghernejad A, Yaghoubi M. Exergoeconomic analysis and optimization of anIntegrated Solar Combined Cycle System (ISCCS) using genetic algorithm.Energy Convers Manag 2011;52:2193203.

    [12] Ahmadi P, Dincer I. Thermodynamic analysis and thermoeconomicoptimization of a dual pressure combined cycle power plant with asupplementary firing unit. Energy Convers Manag 2011;52:2296308.

    [13] Kaviri AG, Jaafar MNM, Lazim TM. Modeling and multi-objective exergy basedoptimization of a combined cycle power plant using a genetic algorithm.Energy Convers Manag 2012;58:94103.

    [14] Silveira JL, Tuna CE. Thermoeconomic analysis method for optimization ofcombined heat and power systemspart II. Prog Energy Combust Sci2004;30:6738.

    [15] Al-Sulaiman FA, Dincer I, Hamdullahpur F. Thermoeconomic optimization ofthree trigeneration systems using organic Rankine cycles: Part I Formulations. Energy Convers Manag 2013;69:199208.

    [16] Al-Sulaiman FA, Dincer I, Hamdullahpur F. Thermoeconomic optimization of

    three trigeneration systems using organic Rankine cycles: Part II Applications. Energy Convers Manag 2013;69:20916.

    Table 1

    Comparison of Antar and Zubair[5]with current work for total conductance required.

    GL cLcH

    UAtota UAtot

    b (GOFH= 1) UAtotb (GOFH= 0 .5) UAtot

    b (GOFH= 0.1)

    0.1 26.783 79.403 76.757 78.084

    0.2 22.895 73.261 71.932 74.580

    0.3 21.380 70.878 70.175 73.390

    0.4 20.599 69.654 69.345 72.876

    0.5 20.148 68.949 68.922 72.650

    0.6 19.875 68.525 68.713 72.5720.7 19.711 68.270 68.630 72.577

    0.8 19.616 68.123 68.625 72.632

    0.9 19.568 68.050 68.672 72.719

    1 19.555 68.029 68.756 72.828

    2 20.148 68.922 70.220 74.218

    3 21.067 70.272 71.808 75.579

    4 21.999 71.610 73.263 76.800

    5 22.895 72.870 74.580 77.904

    6 23.748 74.047 75.783 78.915

    7 24.559 75.149 76.890 79.851

    8 25.333 76.183 77.918 80.726

    9 26.073 77.160 78.880 81.550

    10 26.783 78.084 79.785 82.331

    a Antar and Zubair [5].b Current work.

    386 B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387

    http://refhub.elsevier.com/S0196-8904(14)00439-7/h0010http://refhub.elsevier.com/S0196-8904(14)00439-7/h0010http://refhub.elsevier.com/S0196-8904(14)00439-7/h0010http://refhub.elsevier.com/S0196-8904(14)00439-7/h0015http://refhub.elsevier.com/S0196-8904(14)00439-7/h0015http://refhub.elsevier.com/S0196-8904(14)00439-7/h0015http://refhub.elsevier.com/S0196-8904(14)00439-7/h0020http://refhub.elsevier.com/S0196-8904(14)00439-7/h0020http://refhub.elsevier.com/S0196-8904(14)00439-7/h0025http://refhub.elsevier.com/S0196-8904(14)00439-7/h0025http://refhub.elsevier.com/S0196-8904(14)00439-7/h0025http://refhub.elsevier.com/S0196-8904(14)00439-7/h0030http://refhub.elsevier.com/S0196-8904(14)00439-7/h0030http://refhub.elsevier.com/S0196-8904(14)00439-7/h0030http://refhub.elsevier.com/S0196-8904(14)00439-7/h0035http://refhub.elsevier.com/S0196-8904(14)00439-7/h0035http://refhub.elsevier.com/S0196-8904(14)00439-7/h0035http://refhub.elsevier.com/S0196-8904(14)00439-7/h0040http://refhub.elsevier.com/S0196-8904(14)00439-7/h0040http://refhub.elsevier.com/S0196-8904(14)00439-7/h0045http://refhub.elsevier.com/S0196-8904(14)00439-7/h0045http://refhub.elsevier.com/S0196-8904(14)00439-7/h0050http://refhub.elsevier.com/S0196-8904(14)00439-7/h0050http://refhub.elsevier.com/S0196-8904(14)00439-7/h0050http://refhub.elsevier.com/S0196-8904(14)00439-7/h0050http://refhub.elsevier.com/S0196-8904(14)00439-7/h0055http://refhub.elsevier.com/S0196-8904(14)00439-7/h0055http://refhub.elsevier.com/S0196-8904(14)00439-7/h0055http://refhub.elsevier.com/S0196-8904(14)00439-7/h0055http://refhub.elsevier.com/S0196-8904(14)00439-7/h0060http://refhub.elsevier.com/S0196-8904(14)00439-7/h0060http://refhub.elsevier.com/S0196-8904(14)00439-7/h0060http://refhub.elsevier.com/S0196-8904(14)00439-7/h0060http://refhub.elsevier.com/S0196-8904(14)00439-7/h0065http://refhub.elsevier.com/S0196-8904(14)00439-7/h0065http://refhub.elsevier.com/S0196-8904(14)00439-7/h0065http://refhub.elsevier.com/S0196-8904(14)00439-7/h0070http://refhub.elsevier.com/S0196-8904(14)00439-7/h0070http://refhub.elsevier.com/S0196-8904(14)00439-7/h0070http://refhub.elsevier.com/S0196-8904(14)00439-7/h0075http://refhub.elsevier.com/S0196-8904(14)00439-7/h0075http://refhub.elsevier.com/S0196-8904(14)00439-7/h0075http://refhub.elsevier.com/S0196-8904(14)00439-7/h0075http://refhub.elsevier.com/S0196-8904(14)00439-7/h0080http://refhub.elsevier.com/S0196-8904(14)00439-7/h0080http://refhub.elsevier.com/S0196-8904(14)00439-7/h0080http://refhub.elsevier.com/S0196-8904(14)00439-7/h0080http://refhub.elsevier.com/S0196-8904(14)00439-7/h0080http://refhub.elsevier.com/S0196-8904(14)00439-7/h0080http://refhub.elsevier.com/S0196-8904(14)00439-7/h0075http://refhub.elsevier.com/S0196-8904(14)00439-7/h0075http://refhub.elsevier.com/S0196-8904(14)00439-7/h0075http://refhub.elsevier.com/S0196-8904(14)00439-7/h0070http://refhub.elsevier.com/S0196-8904(14)00439-7/h0070http://refhub.elsevier.com/S0196-8904(14)00439-7/h0070http://refhub.elsevier.com/S0196-8904(14)00439-7/h0065http://refhub.elsevier.com/S0196-8904(14)00439-7/h0065http://refhub.elsevier.com/S0196-8904(14)00439-7/h0065http://refhub.elsevier.com/S0196-8904(14)00439-7/h0060http://refhub.elsevier.com/S0196-8904(14)00439-7/h0060http://refhub.elsevier.com/S0196-8904(14)00439-7/h0060http://refhub.elsevier.com/S0196-8904(14)00439-7/h0055http://refhub.elsevier.com/S0196-8904(14)00439-7/h0055http://refhub.elsevier.com/S0196-8904(14)00439-7/h0055http://refhub.elsevier.com/S0196-8904(14)00439-7/h0050http://refhub.elsevier.com/S0196-8904(14)00439-7/h0050http://refhub.elsevier.com/S0196-8904(14)00439-7/h0050http://refhub.elsevier.com/S0196-8904(14)00439-7/h0050http://refhub.elsevier.com/S0196-8904(14)00439-7/h0045http://refhub.elsevier.com/S0196-8904(14)00439-7/h0045http://refhub.elsevier.com/S0196-8904(14)00439-7/h0040http://refhub.elsevier.com/S0196-8904(14)00439-7/h0040http://refhub.elsevier.com/S0196-8904(14)00439-7/h0035http://refhub.elsevier.com/S0196-8904(14)00439-7/h0035http://refhub.elsevier.com/S0196-8904(14)00439-7/h0030http://refhub.elsevier.com/S0196-8904(14)00439-7/h0030http://refhub.elsevier.com/S0196-8904(14)00439-7/h0030http://refhub.elsevier.com/S0196-8904(14)00439-7/h0025http://refhub.elsevier.com/S0196-8904(14)00439-7/h0025http://refhub.elsevier.com/S0196-8904(14)00439-7/h0025http://refhub.elsevier.com/S0196-8904(14)00439-7/h0020http://refhub.elsevier.com/S0196-8904(14)00439-7/h0020http://refhub.elsevier.com/S0196-8904(14)00439-7/h0015http://refhub.elsevier.com/S0196-8904(14)00439-7/h0015http://refhub.elsevier.com/S0196-8904(14)00439-7/h0010http://refhub.elsevier.com/S0196-8904(14)00439-7/h0010
  • 8/10/2019 Qureshi 2014

    9/9

    [17] Abusoglu A, Kanoglu M. Exergoeconomic analysis and optimization ofcombined heat and power production: a review. Renew Sustain Energy Rev2009;13:2295308.

    [18] Xiong J, Zhao H, Zheng C. Thermoeconomic cost analysis of a 600 MWe oxy-combustion pulverized-coal-fired power plant. Int J Greenh Gas Control2012;9:46983.

    [19] Bassily AM. Numerical cost optimization and irreversibility analysis of thetriple-pressure reheat steam-air cooled GT commercial combined cycle powerplants. Appl Therm Eng 2012;40:14560.

    [20] Rosen MA, Dincer I. Thermoeconomic analysis of power plants: an application

    to a coal fired electrical generating station. Energy Convers Manag2003;44:274361.

    [21] Silveira JL, Tuna CE, de Queiroz Lamas W, Aparecida de Castro Villela I. Acontribution for thermoeconomic modelling: a methodology proposal. ApplTherm Eng 2010;30:173440.

    [22] Seyyedi SM, Ajam H, Farahat S. A new approach for optimization of thermalpower plant based on the exergoeconomic analysis and structuraloptimization method: application to the CGAM problem. Energy ConversManag 2010;51:220211.

    [23] Durmayaz A, Sogut OS, Sahin B, Yavuz H. Optimization of thermal systemsbased on finite-time thermodynamics and thermoeconomics. Prog EnergyCombust Sci 2004;30:175217.

    B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387 387

    http://refhub.elsevier.com/S0196-8904(14)00439-7/h0085http://refhub.elsevier.com/S0196-8904(14)00439-7/h0085http://refhub.elsevier.com/S0196-8904(14)00439-7/h0085http://refhub.elsevier.com/S0196-8904(14)00439-7/h0090http://refhub.elsevier.com/S0196-8904(14)00439-7/h0090http://refhub.elsevier.com/S0196-8904(14)00439-7/h0090http://refhub.elsevier.com/S0196-8904(14)00439-7/h0095http://refhub.elsevier.com/S0196-8904(14)00439-7/h0095http://refhub.elsevier.com/S0196-8904(14)00439-7/h0095http://refhub.elsevier.com/S0196-8904(14)00439-7/h0095http://refhub.elsevier.com/S0196-8904(14)00439-7/h0100http://refhub.elsevier.com/S0196-8904(14)00439-7/h0100http://refhub.elsevier.com/S0196-8904(14)00439-7/h0100http://refhub.elsevier.com/S0196-8904(14)00439-7/h0100http://refhub.elsevier.com/S0196-8904(14)00439-7/h0105http://refhub.elsevier.com/S0196-8904(14)00439-7/h0105http://refhub.elsevier.com/S0196-8904(14)00439-7/h0105http://refhub.elsevier.com/S0196-8904(14)00439-7/h0110http://refhub.elsevier.com/S0196-8904(14)00439-7/h0110http://refhub.elsevier.com/S0196-8904(14)00439-7/h0110http://refhub.elsevier.com/S0196-8904(14)00439-7/h0110http://refhub.elsevier.com/S0196-8904(14)00439-7/h0115http://refhub.elsevier.com/S0196-8904(14)00439-7/h0115http://refhub.elsevier.com/S0196-8904(14)00439-7/h0115http://refhub.elsevier.com/S0196-8904(14)00439-7/h0115http://refhub.elsevier.com/S0196-8904(14)00439-7/h0115http://refhub.elsevier.com/S0196-8904(14)00439-7/h0115http://refhub.elsevier.com/S0196-8904(14)00439-7/h0110http://refhub.elsevier.com/S0196-8904(14)00439-7/h0110http://refhub.elsevier.com/S0196-8904(14)00439-7/h0110http://refhub.elsevier.com/S0196-8904(14)00439-7/h0110http://refhub.elsevier.com/S0196-8904(14)00439-7/h0105http://refhub.elsevier.com/S0196-8904(14)00439-7/h0105http://refhub.elsevier.com/S0196-8904(14)00439-7/h0105http://refhub.elsevier.com/S0196-8904(14)00439-7/h0100http://refhub.elsevier.com/S0196-8904(14)00439-7/h0100http://refhub.elsevier.com/S0196-8904(14)00439-7/h0100http://-/?-http://refhub.elsevier.com/S0196-8904(14)00439-7/h0095http://refhub.elsevier.com/S0196-8904(14)00439-7/h0095http://refhub.elsevier.com/S0196-8904(14)00439-7/h0095http://-/?-http://refhub.elsevier.com/S0196-8904(14)00439-7/h0090http://refhub.elsevier.com/S0196-8904(14)00439-7/h0090http://refhub.elsevier.com/S0196-8904(14)00439-7/h0090http://refhub.elsevier.com/S0196-8904(14)00439-7/h0090http://-/?-http://refhub.elsevier.com/S0196-8904(14)00439-7/h0085http://refhub.elsevier.com/S0196-8904(14)00439-7/h0085http://refhub.elsevier.com/S0196-8904(14)00439-7/h0085http://-/?-