    Date : 26 April, 2016

    Reference: DC Inmedio

    Issued by : Dumitriu Mircea

    S2GDA + 1 x HCR51

    Sea level 0 mUnit inlet air temperature 24.0 C

    Unit inlet air relative humidity 50.0 % Refrigerant R410A

    Unit airflow 5330 m/h Unit power supply 400 V/3 ph/50 Hz

    ESP 0 Pa

    Unit performances

    Unit power input 8.12 kWUnit S2GDA + 1 x HCR51

    Unit EER 2.81Total cooling capacity 22.8 kW

    Sensible cooling capacity 21.0 kW System power input 9.22 kW

    SHR 0.92 System EER 2.47

    Internal filter class (EN779 std) G4Off coil air temperature 12.3 CWidth 750 mmOff coil air relative humidity 99.2 %

    Depth 750 mmRoom SPL (@ 2m, f.f) 61.2 dB(A)

    Condensing temperature 54.0 C Height 1950 mm

    Weight 270 kg

    Fans

    Operating Ampere 1 x 2.15 AQuantity 1 n

    Type Normal Full load Ampere 1 x 4.00 A

    Locked rotor Amp. 1 x 0.10 APower supply 400 V/3 ph/50 Hz

    Power input 1 x 1.34 kW Room fan modulation (%) 8.5

    Compressors

    Compressors COP 3.36Quantity 1 n

    Power supply 400 V/3 ph/50 Hz Operating Ampere 1 x 12.34 A

    Full load Ampere 1 x 16.20 APower input 1 x 6.78 kW

    Locked rotor Amp. 1 x 101.00 A

    Relevant data for each CONDENSER

    Condenser model HCR51 Max outdoor SPL (@ 5m,f.f.) 53.0 dB(A)

    Version Standard Actual outdoor SPL (@ 5m,f.f.) 53.0 dB(A)

    Air discharge Vertical Power input 1.10 kWFull load Ampere 5.00 APower supply 230 V/1 ph/50 Hz

    Locked rotor Amp. 9.60 AVariex Yes

    Heat load 29.6 kW Width 1112 mm

    Outdoor air temperature 45.0 C Depth 2340 mm

    Condenser airflow (@ max speed) 17000 m/h Height 907 mm

    Weight 93 kgCondenser actual airflow 17000 m/h

    Condenser ESP (@ max speed) 0 Pa

    Cooling capacities are gross. To obtain the net cooling capacities the fan heat load must be subtracted

    Declared performances for only cooling units according to EN 14511:2011. Products in accordance with the following Dire

    2006/95/EC; 97/23/EC2006/42/EC; 2004/108/EC;

    Rel. 9.1 Page: 1 / 1

  • 7/26/2019 S2GDA + 1 x HCR51

    2/2

    Date : 26 April, 2016

    Reference: DC Inmedio

    Issued by : Dumitriu Mircea

    S2GDA + 1 x HCR51

    OPTIONS

    Rel. 9.1

    Electrical heating

    Max heating capacity 5.85 kW Outlet air temperature 15.5 C

    Outlet air relative humidity 81.0 %FLA 8.4 A

    Inlet air temperature 12.3 C

    Inlet air relative humidity 99.2 %

    Humidifiers

    Power supply 400/3/50 Quantity 1 n

    Max capacity steam 1x4.5 Kg/h Nominal power input 1x3 kW

    Max absorbition current 1x4.6 AMin capacity steam 1x2.7 Kg/h

    Type of Humidifier electrodes immersed