66

Click here to load reader

Service Manual PCC 3201

Embed Size (px)

Citation preview

  • Service Manual

    Controller PowerCommand 3201

    English Original Instructions2010$7 (Issue )

  • iTable of Contents

    SECTION TITLE PAGE

    1. Introduction 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    ABOUT THIS MANUAL 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TEST EQUIPMENT 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HOW TO OBTAIN SERVICE 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2. Control Operation 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    GENERAL 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SEQUENCE OF OPERATION 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CONTROL PANEL POWER ON/OFF MODES 2-1. . . . . . . . . . . . . . . . . . . . . CONTROL PANEL ASSEMBLY 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . READING FAULT CODES 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MENU DISPLAY AND SWITCHES 2-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LANGUAGE/UNITS SELECTION MENU 2-8. . . . . . . . . . . . . . . . . . . . . . . . . . MAIN MENU 2-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ENGINE SUBMENUS 2-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ALTERNATOR SUBMENUS 2-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CONTROL SUBMENU 2-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HISTORY/ABOUT SUBMENUS 2-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HISTORY/ABOUT SUBMENUS (CONT.) 2-15. . . . . . . . . . . . . . . . . . . . . . . . . PARALLEL DATA SUBMENU 2-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . POWER TRANSFER MAIN/SUBMENUS 2-17. . . . . . . . . . . . . . . . . . . . . . . . . UTILITY (PWR TRAN) SUBMENUS 2-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . STATUS (PWR TRAN) SUBMENUS 2-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . TRANSFER CONTROL (PWR TRAN) SUBMENU 2-21. . . . . . . . . . . . . . . . . GENSET (PWR TRAN) SUBMENUS 2-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3. Control Calibration and Adjustment 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    GENERAL 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PARALLELING and NONPARALLELING 3-1. . . . . . . . . . . . . . . . . . . . . . . . . SOFTWARE CALIBRATIONS 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MODIFYING SETUP/ADJUST SUBMENUS 3-1. . . . . . . . . . . . . . . . . . . . . . . . SETUP MENUS 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GOVERNING/VOLT REG SUBMENU 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . CUSTOMER FAULTS SUBMENUS 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CALIBRATION SUBMENUS 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ISOLATED BUS SUBMENUS 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UTILITY SUBMENUS 3-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . POWER TRANSFER CONTROL MAIN MENUS 3-19. . . . . . . . . . . . . . . . . . . UTILITY SENSORS SUBMENUS 3-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GENSET SENSORS SUBMENUS 3-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TIMERS SUBMENU 3-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TEST/EXERCISE SUBMENU 3-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ADJUST SUBMENU 3-28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CALIBRATION PROCEDURE 3-29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • ii

    SECTION TITLE PAGECONTROL BOX WIRING 3-31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RUN RELAYS (K11, K12, K13) 3-33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ALARM RELAY (K16) 3-34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MAGNETIC SPEED PICKUP UNIT (MPU) INSTALLATION 3-35. . . . . . . . .

  • vIMPORTANT SAFETY INSTRUCTIONS

    SAVE THESE INSTRUCTIONS This manual containsimportant instructions that should be followed duringinstallation and maintenance of the generator set andbatteries.

    Before operating the generator set (genset), read theOperators Manual and become familiar with it and theequipment. Safe and efficient operation can beachieved only if the equipment is properly operatedand maintained. Many accidents are caused by failureto follow fundamental rules and precautions.

    The following symbols, found throughout this manual,alert you to potentially dangerous conditions to the oper-ator, service personnel, or the equipment.

    This symbol warns of immediatehazards which will result in severe personal in-jury or death.

    WARNING This symbol refers to a hazard or un-safe practice which can result in severe person-al injury or death.

    CAUTION This symbol refers to a hazard or un-safe practice which can result in personal injuryor product or property damage.

    FUEL AND FUMES ARE FLAMMABLE

    Fire, explosion, and personal injury or death can resultfrom improper practices.

    DO NOT fill fuel tanks while engine is running, un-less tanks are outside the engine compartment.Fuel contact with hot engine or exhaust is a potentialfire hazard.

    DO NOT permit any flame, cigarette, pilot light,spark, arcing equipment, or other ignition sourcenear the generator set or fuel tank.

    Fuel lines must be adequately secured and free ofleaks. Fuel connection at the engine should bemade with an approved flexible line. Do not use zinccoated or copper fuel lines with diesel fuel.

    Be sure all fuel supplies have a positive shutoffvalve.

    Be sure battery area has been well-ventilated priorto servicing near it. Lead-acid batteries emit a highlyexplosive hydrogen gas that can be ignited by arc-ing, sparking, smoking, etc.

    EXHAUST GASES ARE DEADLY

    Provide an adequate exhaust system to properlyexpel discharged gases away from enclosed orsheltered areas and areas where individuals arelikely to congregate. Visually and audibly inspectthe exhaust daily for leaks per the maintenanceschedule. Make sure that exhaust manifolds are se-cured and not warped. Do not use exhaust gases toheat a compartment.

    Be sure the unit is well ventilated. Engine exhaust and some of its constituents are

    known to the state of California to cause cancer,birth defects, and other reproductive harm.

    MOVING PARTS CAN CAUSE SEVEREPERSONAL INJURY OR DEATH

    Keep your hands, clothing, and jewelry away frommoving parts.

    Before starting work on the generator set, discon-nect battery charger from its AC source, then dis-connect starting batteries, negative () cable first.This will prevent accidental starting.

    Make sure that fasteners on the generator set aresecure. Tighten supports and clamps, keep guardsin position over fans, drive belts, etc.

    Do not wear loose clothing or jewelry in the vicinity ofmoving parts, or while working on electrical equip-ment. Loose clothing and jewelry can becomecaught in moving parts.

    If adjustment must be made while the unit is run-ning, use extreme caution around hot manifolds,moving parts, etc.

    DO NOT OPERATE IN FLAMMABLE ANDEXPLOSIVE ENVIRONMENTS

    Flammable vapor can cause an engine to overspeed andbecome difficult to stop, resulting in possible fire, explo-sion, severe personal injury and death. Do not operate agenset where a flammable vapor environment can becreated by fuel spill, leak, etc., unless the genset isequipped with an automatic safety device to block the airintake and stop the engine. The owners and operators ofthe genset are solely responsible for operating the gen-set safely. Contact your authorized Cummins PowerGeneration distributor for more information.

  • vi

    ELECTRICAL SHOCK CAN CAUSESEVERE PERSONAL INJURY OR DEATH

    Remove electric power before removing protectiveshields or touching electrical equipment. Use rub-ber insulative mats placed on dry wood platformsover floors that are metal or concrete when aroundelectrical equipment. Do not wear damp clothing(particularly wet shoes) or allow skin surface to bedamp when handling electrical equipment. Do notwear jewelry. Jewelry can short out electrical con-tacts and cause shock or burning.

    Use extreme caution when working on electricalcomponents. High voltages can cause injury ordeath. DO NOT tamper with interlocks.

    Follow all applicable state and local electricalcodes. Have all electrical installations performed bya qualified licensed electrician. Tag and lock openswitches to avoid accidental closure.

    DO NOT CONNECT GENERATOR SET DIRECT-LY TO ANY BUILDING ELECTRICAL SYSTEM.Hazardous voltages can flow from the generator setinto the utility line. This creates a potential for elec-trocution or property damage. Connect onlythrough an approved isolation switch or an ap-proved paralleling device.

    GENERAL SAFETY PRECAUTIONS

    Coolants under pressure have a higher boiling pointthan water. DO NOT open a radiator or heat ex-changer pressure cap while the engine is running.To prevent severe scalding, let engine cool downbefore removing coolant pressure cap. Turn capslowly, and do not open it fully until the pressure hasbeen relieved.

    Used engine oils have been identified by some stateor federal agencies as causing cancer or reproduc-tive toxicity. When checking or changing engine oil,take care not to ingest, breathe the fumes, or con-tact used oil.

    Keep multi-class ABC fire extinguishers handy.Class A fires involve ordinary combustible materialssuch as wood and cloth; Class B fires, combustibleand flammable liquid fuels and gaseous fuels; ClassC fires, live electrical equipment. (ref. NFPA No. 10).

    Make sure that rags or combustible material are notleft on or near the generator set.

    Make sure generator set is mounted in a manner toprevent combustible materials from accumulatingunder or near the unit.

    Remove all unnecessary grease and oil from theunit. Accumulated grease and oil can cause over-heating and engine damage which present a poten-tial fire hazard.

    Keep the generator set and the surrounding areaclean and free from obstructions. Remove any de-bris from the set and keep the floor clean and dry.

    Do not work on this equipment when mentally orphysically fatigued, or after consuming any alcoholor drug that makes the operation of equipment un-safe.

    Substances in exhaust gases have been identifiedby some state or federal agencies as causing can-cer or reproductive toxicity. Take care not to breathor ingest or come into contact with exhaust gases.

    Do not store any flammable liquids, such as fuel,cleaners, oil, etc., near the generator set. A fire orexplosion could result.

    Wear hearing protection when near an operatinggenerator set.

    To prevent serious burns, avoid contact with hotmetal parts such as radiator system, turbo chargersystem and exhaust system.

    KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE

  • 1-1

    1. Introduction

    ABOUT THIS MANUAL

    This manual provides PowerCommand Control3201 (PCC) calibration and adjustment proce-dures, control operation, alternator test and repairprocedures.

    Operating and maintenance instructions are in theapplicable Operators Manual.

    Read Important Safety Instructions and carefullyobserve all instructions and precautions in thismanual.

    TEST EQUIPMENTTo perform the test procedures in this manual, thefollowing test equipment must be available True RMS meter for accurate measurement of

    small AC and DC voltages. Battery Hydrometer Jumper Leads Tachometer or Frequency Meter Wheatstone Bridge or Digital Ohmmeter Variac Load Test Panel Megger or Insulation Resistance Meter InPower Service Tool (PC based genset ser-

    vice tool)

    HOW TO OBTAIN SERVICEAlways give the complete Model, Specification andSerial number of the generator set as shown on thenameplate when seeking additional service infor-mation or replacement parts. The nameplate is lo-cated on the side of the generator output box.

    WARNING Incorrect service or replacement ofparts can result in severe personal injury ordeath, and/or equipment damage. Service per-sonnel must be trained and experienced to per-form electrical and mechanical service. Readand follow Important Safety Instructions, onpages iii and iv.

  • 1-2

    THIS PAGE LEFT INTENTIONALLY BLANK

  • 2-1

    2. Control Operation

    GENERAL

    The following describes the function and operationof the PowerCommand Control 3200 (PCC). All in-dicators, control switches/buttons and graphicaldisplay are located on the face of the control panelas illustrated in Figure 2-1.

    Normally, generator set configuration options areset at the factory. When a new control is installed ona generator set or when parts are replaced, the con-trol must be configured for that generator set. Setupand calibration procedures are described in Sec-tion 3.

    SEQUENCE OF OPERATION

    When the PowerCommand control is in the AUTOmode, it will cause the generator set to start on re-ceiving a signal from a remote device. The controlwill initiate a starter cranking signal and verify thatthe engine is rotating. The control will provide suffi-cient fuel to the engine to accelerate to start discon-nect speed. On reaching that speed, the control willramp the generator set to idle (warm-up) or ratedspeed and voltage.

    On reaching rated speed and voltage, the controlchecks the system bus voltage. If no bus voltage is

    present, it will wait for a pulse from a remote MasterFirst Start Sensor. On receiving that pulse, the con-trol will signal the paralleling breaker to close.

    If bus voltage is present, the control will check forproper phase rotation, adjust the generator set tothe bus voltage and frequency level, and then syn-chronize the generator set to the system bus. Whena synchronous condition is achieved, the control willsend a signal to close the paralleling breaker.

    When the paralleling breaker is closed, the genera-tor set will assume its proportional share of the totalload on the system bus.

    CONTROL PANEL POWER ON/OFFMODES

    The power on/off modes of the control panel and op-erating software are Power On, Screen Saver andSleep/Awake.

    Power On Mode: In this mode, power is continu-ously supplied to the control panel. The controlsoperating software and control panel LEDs/graphi-cal display will remain active until the Screen Savermode is activated.

  • 2-2

    Screen Saver Mode: Power to the graphical dis-play will be removed after 10 minutes (generator setnot running or running). The 10 minute timer resetsand begins after each control panel action (any but-ton or switch selection) or signal received by the op-erating software. The bottom LEDs of the AnalogAC Metering Panel (bar graphs) may remain on dur-ing Screen Saver mode, indicating that the operat-ing software is active (Awake mode).

    When a Warning signal is sensed by the PCC (forexample, low coolant temp), the control will displaythe warning message. The control will remain activeuntil the Fault Acknowledge button is pressed toclear the warning message and start the 10 minutetimer.

    Sleep/Awake Mode: In the Sleep mode, the con-trols operating software is inactive and the LEDsand the graphical display on the control panel are alloff. Sleep mode is a feature that is used to reducebattery power consumption when the control is notbeing used.

    In Off mode, Sleep mode is activated when thereare no unacknowledged faults and Screen Savermode is active.

    In Auto mode, Sleep mode can be enabled or dis-abled. When shipped from the factory, it is disabled.You can enable Sleep mode by making thesechanges:

    Use InPower service tool to set Auto Sleep En-able to Sleep in Auto.

    Set switch S1 on the Genset/Paralleling Cardto Sleep/Off. This switch is located next to con-nector J8 and relay K9.

    If these conditions are not met, Sleep mode is dis-abled in Auto mode.

    The graphical display can enter Screen Saver modeeven if Sleep mode is disabled.

    If Sleep mode is enabled in Auto mode, Sleep modeis activated when there are no unacknowledgedfaults and Screen Saver mode is active.

    The operating software is initialized and the controlpanel LEDs and graphical display are turned on inresponse to one of the following:

    Moving/pressing any control panel switch/but-ton. (If Sleep mode is enabled in Auto mode,the control will remain asleep if Sleep modewas previously active in Off mode.)

    Receiving a remote start input signal (genera-tor set in Auto mode)

    Receiving an active DCD signal on the RS-232port.

    Modem RI latch becoming active. Digital display waking up. Lonworks (backplane) wakeup becoming ac-

    tive.

    Customer fault 2 or 3 only (shutdown or warn-ing indicator is on).

    Dial Out process becoming active.To activate the control and view the menu displaywithout starting the generator set, press any buttonon the control panel.

  • 2-3

    DISPLAY MENUSELECTION BUTTONS

    (1 of 6)

    0/MANUAL/AUTOSWITCH

    REMOTE START,NOT IN AUTO,SHUTDOWN,

    WARNINGSTATUS INDICATORS

    GRAPHICALDISPLAY

    ANALOG ACMETERING

    PANEL

    OPERATOR PANEL SWITCH PANEL

    MANUAL RUN/STOP BUTTON& INDICATOR

    EXERCISEBUTTON &INDICATOR

    FAULTACKNOWLEDGE

    BUTTON

    PANEL LAMP/LAMP TEST

    BUTTON

    EMERGENCYSTOP PUSH

    BUTTON

    0

    FIGURE 2-1. CONTROL PANEL ASSEMBLY (FULL-FEATURED)

  • 2-4

    CONTROL PANEL ASSEMBLY

    The control panel assembly (Figure 2-1) consist oftwo panels, the Operator Panel and the Switch Pan-el.

    Dependent on site requirements, the Operator Pan-el is either mounted on the control panel assembly(full-featured) as shown in Figure 2-1 or containedin a separate enclosure and mounted remotely ofthe control panel assembly.

    The function of several buttons on the control panelwill vary dependent on the location of the controlpanel (remote or local of the control panel assem-bly). If the function differs, it is noted as either re-mote or local operator panel in the button de-scription.

    Operator Panel

    The operator panel contains the following compo-nents:

    Analog AC Metering Panel: This panel simulta-neously displays 3-phase line to line AC volts andcurrent, kW, power factor and frequency.

    The meter panel is composed of a series of LEDs,that are configured in bar graphs for each function.The LEDs are color coded, with green indicatingnormal range values, amber for warning levels andred for shutdown conditions.

    Scales for each function are in % of nominal values.Resolution is 1% for values close to nominal, and in-creases at values further from nominal.

    Graphical Display: The graphical display is capa-ble of displaying up to 9-lines of data with approxi-mately 27 characters per line. The display is used toview the menus of the menu-driven operating sys-tem.

    The top three lines of the graphical display containthe following control information in the order de-scribed:

    State Line modes of operation, such asStopped, Time Delay To Start, Warm Up AtIdle, etc. (see Figure 2-2), and paralleling op-erations, such as Standby, Dead BUS Close,Synchronize, Load Share and Load Govern.

    Action Line system actions, such as Warning,Derate, Shutdown Cool-down and Shutdown,and fault codes.

    Description Line Fault code messages.Display Menu Selection Buttons: Six momentarybuttonsthree on each side of the graphical dis-play windoware used to navigate through the sys-tem control menus and to adjust generator set pa-rameters. The button is active when the messageadjacent to the button is highlighted (displayed in in-verse video).

  • 2-5

    Switch Panel

    The switch panel contains the following compo-nents:

    Emergency Stop Button: Push the button in foremergency shutdown of the engine. If the engine isnot running, pushing the button in will prevent thestarting of the engine, regardless of the start signalsource (local or remote).

    To reset:1. Pull the button out.2. Move the 0/Manual/Auto switch to 0. 3. Press the front panel Fault Acknowledge

    button.4. Select Manual or Auto, as required.

    Remote Start Indicator: This green lamp is litwhenever the control is receiving a remote run sig-nal. When flashing, it indicates a load demand stopmode.

    Not in Auto Indicator: This red lamp flashes con-tinuously when the 0/Manual/Auto switch is not inthe Auto position. (If in Auto position and lamp isflashing, service is required.)

    Shutdown Status Indicator: This red lamp is litwhenever the control detects a shutdown condition.The generator set can not be started when this lampis on. After the condition is corrected, shutdown in-dicators can be reset by turning the 0/Manual/Autoswitch to the 0 position, and pressing the Fault Ac-knowledge button.

    Dependent upon the specific fault that occurs, theengine may or may not shut down immediately. Afault that could cause engine damage, causes animmediate engine shutdown (bypasses enginecool-down sequence). All other faults would allowthe engine to run during the cool-down sequencebefore engine shutdown. In this case, the ShutdownStatus Indicator blinks during the cooldown period.

    Warning Status Indicator: This yellow lamp is litwhenever the control detects a warning condition.After the condition is corrected, warning indicatorscan be reset by pressing the Fault Acknowledgebutton. (It is not necessary to stop the generator setif the fault becomes inactive during genset opera-tion.)

    Fault Acknowledge: Press this button to acknowl-edge warning and shutdown messages after thefault has been corrected.

    To acknowledge a Warning message, the 0/Manu-al/Auto switch can be in any position. (It is not nec-essary to stop the generator set to acknowledge aninactive Warning condition.) To acknowledge ashutdown message with this button, the 0/Manual/Auto switch must be in the 0 (Off) position.

    This button is also used to blink a fault code if theShutdown or Warning Status Indicator is lit. (Thisfunction is used when the control does not contain agraphical display.) Refer to Reading Fault Codes inthis section, which describes how to use this buttonfor interpreting fault codes.

    Panel Lamp/Lamp Test Button: Press this buttonto turn on or off the panel lamp. Press and holddown this button for three seconds or more to turnall control panel LEDs on to make sure all lamps illu-minate. The illumination will shut off after releasingthe button.

    Exercise Button: Press this button to initiate a pre-programmed exercise sequence. To start the exer-cise sequence, press and hold down the Exercisebutton and move the O/Manual/Auto switch fromAuto to Manual and back to Auto or from Manual toAuto.

    Manual Run/Stop Button: This button starts andstops the set locally and will bypass Time Delay toStart and Stop sequences. The 0/Manual/Autoswitch must be in the Manual position to enable thisbutton.

    0/Manual/Auto Switch: Manual position enablesthe use of the switch panel Manual Run/Stop but-ton.

    Auto position enables start/stop control of the en-gine from a remote location. (Disables the use of theswitch panel Manual Run/Stop button.)

    0 (Off) position prevents the starting of the set (localor remote). If moved to 0 during set operation, willcause an immediate engine shutdown (bypassescool-down timers). This hot shutdown should beavoided, if possible, to help prolong the life of theengine. Hot shutdowns are logged by the systemsoftware.

  • 2-6

    READING FAULT CODES

    If the genset contains the optional graphical displayand a fault occurs, the fault code/message will bedisplayed in the display Description Line (Figure2-2). If the control does not contain the graphicaldisplay, the fault code is read from the Warning andShutdown status indicators.

    Reading Fault codes Using Warning/ShutdownIndicators: If the Warning or Shutdown status indi-cator is lit, press and hold the Fault Acknowledgebutton and release after one second or more. Afterone second, the Shutdown lamp will begin to blinkthe active fault code(s) as follows.

    The Warning lamp is used to indicate the start of anew code. The Warning lamp will remain on for 2seconds, followed by the Shutdown lamp blinkingthe fault code. This sequence occurs three times foreach code. The fourth flash of the Warning lamp in-dicates the beginning of the second fault code.

    There are distinct pauses between repetitions of thecode blink transmissions of the Shutdown lamp.

    A three digit fault code is indicated by three sets ofblinks separated by a two second pause. The firstset corresponds to the hundreds position, the sec-ond to the tens position and the third to the ones dig-it. Example for Code No. 213:

    Shutdown LED:blink-blink-pause-blink-pause-blink-blink-blink

    Warning LED:blink (2 seconds)

    The light will display the fault codes (active or inac-tive) in succession, starting with the most recent. Upto 32 (unacknowledged) fault codes can be storedin control panel memory.

    To return the control to the most recent fault code,press and release the Fault Acknowledge button(less than one second) and repeat procedure.

    When the fault code is acknowledged and cor-rected, the recorded fault will be deleted from theLED fault log, but will remain in a data log that main-tains a fault code history. (The InPower service toolis required to view this data log.)

  • 2-7

    MENU DISPLAY AND SWITCHES

    Figure 2-2 shows the graphical display and themenu selection buttons.

    Graphical Display: The graphical display is capa-ble of displaying up to 9-lines of data with approxi-mately 27 characters per line. The display is used toview the menus of the menu-driven operating sys-tem. Refer to the menu trees later in this section.The display is also used to show the following sys-tem information:

    State Line modes of operation, such asStopped, Time Delay To Start, Warm Up AtIdle, etc., and paralleling operations, such asStandby, Dead BUS Close, Synchronize, etc.

    Action Line system actions, such as Warning,Derate, Shutdown Cool-down and Shutdown,and fault codes.

    Description Line Fault code/status mes-sages.

    Menu Buttons: Six momentary buttonsthree oneach side of the graphical display windowareused to navigate through the system control menusand to adjust generator set parameters. The buttonis active when the message or symbol adjacent tothe switch is highlighted (displayed in inverse vid-eo). The displayed message or symbol indicatesthe function of the button.

    In the graphical display, the symbol indicatesthat selecting the adjacent button causes the operat-ing program to go to the next menu displayasshown in the menu diagrams.

    In the graphical display, the symbol indicatesthat selecting the adjacent button causes the operat-ing program to go back to the previous menu display.

    In the graphical display, the symbol indicatesthat selecting the adjacent button causes the operat-ing program to go back to Main Menu A (Figure 2-4).

    STATE LINE

    ACTION LINE

    MENU DISPLAYAREA

    GRAPHICALDISPLAY

    MENUBUTTONS

    DESCRIPTION LINE

    MENUBUTTONS

    FIGURE 2-2. GRAPHICAL DISPLAY AND MENU SELECTION BUTTONS

  • 2-8

    LANGUAGE/UNITS SELECTION MENU

    During any control panel operation, you can selectone of three languages and change how units aredisplayed by pressing the two lower menu buttons(one on each side of display). When pressing thesetwo buttons simultaneously, the language/unitsmenu will appear (Figure 2-3). After making desiredselections, press the ENTER button in this menu tochange and save the selections.

    Use the + buttons to select the desired option foreach field. Use the arrow () button to move to thenext field. Selected field is highlighted.

    Language: Used to select desired language (de-fault = English).

    Location: This selection must be set to Local whenthe graphical display is mounted on the generatorset front control panel or Remote when mounted re-motely from the generator set.

    The Local/Remote selection determines which but-tons in the Control submenu (page 2-13) are active(displayed).

    Temp: Used to select F or C for temperature read-ings.

    Pressure Fluid: Used to select PSI, KPA, BAR orIN for pressure readings.

    Pressure Gas: Used to select INHG or MMHG forpressure readings.

    Flow Air: Used to select CFM or CMM for air flowreadings.

    ENTER

    LANGUAGEENGLISHLOCATIONLOCAL

    TEMP FPRESS FLDPSI

    PRESS GASINHGFLOW AIRCFM

    +

    FIGURE 2-3. LANGUAGE/UNITS MENU

  • 2-9

    MAIN MENU

    Figure 2-4 shows the main menus (Menu A andMenu B) of the system control. The two main menusare used to divide the system submenus into majorcategories, such as, Engine Data, Alternator Data,Control, etc.

    To view system data, simply press the appropriatemenu button to select the category. After pressingthe desired menu button, refer to the page numbershown in Figure 2-4 for detailed information relatedto the selected category.

    In the following figures, the boxed/highlighted fieldindicates that the adjacent menu button is active.Also, the submenus are shown in the order in whichthey are displayed when scrolling up or down .

    Adjust Button

    The Adjust submenu is intended for qualified sitepersonnel only. Note that a password may be as-signed to allow only authorized operators to modifythis data. (Password is not required if not assigned.)

    Setup Button

    The Setup submenu is described in Section 3.

    The Adjust and Setup submenus can be viewed,but not modified without entering the correct pass-words.

    _\_ Button (Paralleling Applications Only)

    When displayed, indicates that the feature for gen-erator set paralleling applications is installed. Thisbutton is used to open and close the generator setcircuit breaker (CB). The symbol indicates if the CBis opened or closed. Opened _\_, push to close.Closed __, push to open.

    With the control panel 0/Manual/Auto switch in theAuto position, the opening and closing of the CB iscontrolled by the control system software. The CBsymbol will indicate an open or closed CB, but thebutton will be inactive when the control is in Auto.

    In the Manual position, the CB can only be closedby using this button. When manually closed and theCB opens, it must be closed again by using this but-ton. To close the CB, press and hold the button untilthe symbol indicates a closed CB. (CB close will oc-cur only when setup conditions allow dead bus orgenerator synchronized with bus.)

    Power Trans Button (Power TransferControl Applications Only)

    When displayed, indicates that the Power TransferControl (PTC) feature is installed. Refer to page2-17 for PTC Data submenu description. The PTCsetup submenu is described in Section 3.

  • 2-10

    ENGINE

    ALTERNATOR

    CONTROL

    MORE>>

    POWER TRAN or _\_

    HISTORY/ABOUT

    PAGE2-11

    PAGE2-12

    PAGE2-13

    PAGE2-14

    Page2-9

    MENUB

    GRAPHICALDISPLAY

    MENUBUTTONS

    MENUBUTTONS

    SETUP

    ADJUST

    PARALLEL DATA

    BACK

  • 2-11

    ENGINE SUBMENUS

    If you press the ENGINE button in Menu A, the En-gine submenus will appear (Figure 2-5).

    The first submenu displays general information thatapplies to all gensets (coolant temp, oil pressure,etc.) The data in the remaining submenu(s) will varyaccording to the type and number of sensors pro-vided with the engine.

    COOLANT TEMP 180 FOIL PRESSURE 75PSI

    ENGINE SPEED 1800RPMBATTERY 29.1VDC

    MANF TEMP 75 FMANF PRESS ABS 180INHGRAIL PRESS ABS 180PSIPUMP PRESS ABS 291PSIFUEL INLET TEMP 172 FCOOLANT PRESSURE 59PSI

    ENGINE

    BLOWBY FLOW 25CFMTIMING PRESS 50PSIAFTERCOOLER TEMP 76 FAMBIENT PRESS 88INHG

    FIGURE 2-5. ENGINE SUBMENUS

  • 2-12

    ALTERNATOR SUBMENUS

    If you press the ALTERNATOR button in Menu A,the Alternator Data submenus will appear (Figure2-6).

    Voltage L-L and L-N: Indicates voltage Line-toLine and Line-to-Neutral. Note that the Line-to-Neu-tral column will not be displayed for a 3 phase/3 wiresystem. Accuracy 1%.

    The voltage Line-to-Line (L1, L2 and L3) are mea-sured between L1 to L2, L2 to L3 and L3 to L1, re-spectively.

    Amps: All phases. Accuracy 1%.

    Frequency: Generator set output frequency.

    AVR DUTY CYCLE: Displays voltage regulator(drive) level in percentage of maximum.

    kW, kVA and PF: Displays generator set kW andkVA output (average and individual phase, and di-rection of flow) and power factor with leading/lag-ging indication. Accuracy 5%.

    The PF reading will contain an asterisk if the powerfactor is leading (for example,*.30).

    kW kVA PFL1 350 500 .80L2 350 500 .80L3 350 500 .80TOT1050 1500 .80

    ALTERNATOR

    V L-L L-NAMPSL1 480 2771340L2 480 2771290L3 480 2771260

    FREQUENCY60.0 HZAVR DUTY CYCLE10.3 %

    FIGURE 2-6. ALTERNATOR SUBMENUS

  • 2-13

    CONTROL SUBMENU

    If you press the CONTROL button in Menu A, theControl submenu will appear (Figure 2-7).

    Local CONTROL Submenu Function

    When the operator panel is mounted on the controlpanel assembly, the Run Mode Idle/Rated button isactive (displayed). Note in Figure 2-7 that this but-ton is not displayed in remote applications.

    The shaded area in Figure 2-7 displays the se-lected/active mode of operation, either IDLE orRATED.

    Remote CONTROL Submenu Functions

    When the operator panel (Figure 2-1) is mountedremotely of the control panel assembly, the menubuttons in the Control submenu are used to performthe following remote operations. (To activate thesemenu buttons for remote/local use, refer to page2-8.)

    The 0/Manual/Auto switch must be in the Auto posi-tion to activate the Remote Menu Buttons of the Con-trol submenu.

    Remote START or STOP Button: This button isused to start and stop the generator set when theoperator panel is mounted in a remote location.

    When the generator set is operating, Stop will bedisplayed for this button and Start will be displayedwhen not operating.

    When the generator set is operating in the RemoteStart mode, removing the Remote Start commanddoes not shut off the engine if the load is 10 per cent,the cooldown timer is set to zero, and the control isconfigured for a single unit (not in parallel). The gen-erator set continues to operate until it runs out offuel, the Estop button is used, or the load is re-moved.

    Fault Acknowledge Button: Used to reset inactiveWarning messages, not Shutdown messages.

    Local/Remote CONTROL SubmenuFunction

    Bargraph Test: The function of this button remainsthe same and is not dependent on operator panellocation. This button sequentially lights the LEDs totest the bar graph display.

    Enable Sync: Displayed in paralleling applicationsonly. Intended for service personnel to turn off thesynchronizer for troubleshooting/testing purposes.

    CONTROL(Remote)

    START GENSET

    FAULT ACKNOWLEDGE

    CONTROL(Local)

    + RUN MODE IDLE

    BARGRAPH TEST

    BARGRAPH TEST

    ENABLE SYNC

    ENABLE SYNC

    FIGURE 2-7. CONTROL SUBMENU

  • 2-14

    HISTORY/ABOUT SUBMENUS

    If you press the HISTORY/ABOUT button in MenuA, the History/About submenus will appear (Figure2-8).

    HISTORY: The control maintains a data log of thenumber of engine starts and number of operatinghours for the engine and control, and the megawattand maximum torque hours of the generator set.This information is stored in non-volatile memoryand will not be deleted due to loss of battery power.

    ABOUT: The About submenus provide the follow-ing generator set information.

    Genset model and wattage (kW/MW) Output voltage and WYE, DELTA or SINGLE Frequency 50 or 60 Hz Rating: Standby, Prime or Base Version level of the controller and panel operat-

    ing software.

    STARTS 533ENGINE HOURS1236CONTROL HOURS7879KWHRS 890

    HISTORY/ABOUT

    HISTORY-HRS@ %MAX TORQUE12345@0-923455@50-5912345@10-1912345@60-6912345@20-2912345@70-7912345@30-3912345@80-89

    MODEL 1750DQKBVOLTAGE416 WYE

    FREQUENCY60RATINGSTANDBY

    CONTROLLER VERSIONRTOPDN30008.DFABATSAPR 23 1999

    OP PANEL VERSIONRTOP1.09 AUG 17 1999

    BATS1.02 MAY 6 1999

    CONTINUED TO NEXT PAGE

    FIGURE 2-8. HISTORY/ABOUT SUBMENUS

  • 2-15

    HISTORY/ABOUT SUBMENUS (CONT.)

    FAULT HISTORY: The control maintains a data logof all fault conditions as they occur, and time stampsthem with the control and engine operating hours.

    Up to 32 (unacknowledged) fault codes can bestored in control panel memory. After the fault is ac-knowledged and corrected, the recorded fault willbe deleted from the control panel memory, but willremain in a data log that maintains a fault code his-tory. (The InPower service tool is required to viewthis data log.)

    The Fault History display line: 1 of 24 indicates that24 faults are recorded and that the most recent fault(1) detected by the controller is displayed.

    The Occurrences display line: In this example, 5 in-dicates that this is the fifth occurrence of this fault.(The InPower service tool is required to review thelast four faults of this code.)

    The Occurrences number is incremented for eachnew occurrence of the same fault. The controllermust detect that the original sensed fault is cor-rected before it will increment the occurrence num-ber for that fault.

    For example, when a Low Oil Pressure fault is de-tected, the controller will increment the Occurrencesnumber by 1. This fault will remain active until thefault is acknowledged and the controller detects thatthe fault is corrected. An active fault will prevent thecontroller from incrementing the Occurrences num-ber each time the engine is started. When the con-troller detects that the oil pressure is normal the faultwill become inactive, allowing the occurrences num-ber to be incremented for the next detected Low OilPressurefault.

    FAULT HISTORY: 1 OF 24CNTL HOURS459OCCURRENCES5ENGINE HOURS334FAULT CODE1437(FAULT DESCRIPTION)

    HISTORY/ABOUT (CONT.)

    +

    FIGURE 2-8. HISTORY/ABOUT SUBMENUS (CONT.)

  • 2-16

    PARALLEL DATA SUBMENUIf you press the PARALLEL DATA button in MenuB, the Parallel Data submenu will appear (Figure2-9). This menu is displayed in paralleling applica-tions only.

    PARALLEL DATA STATUS LINE: The top line ofthe graphical display is used to indicate the follow-ing PARALLEL DATA status:

    STANDBY: Indicates no paralleling activity isoccurring at present.

    DEAD BUS CLOSE: Indicates first genset insystem to close to bus.

    SYNCHRONIZE: Genset is synchronizing tobus.

    LOAD SHARE: Genset has closed to bus andis sharing load with other gensets in system.

    LOAD GOVERN: Genset closed to bus in par-allel with utility (mains).

    BUS Voltage L-L: The BUS voltage Line-to-Line(L1, L2 and L3) are measured between L1 to L2, L2to L3 and L3 to L1, respectively.

    BUS/GEN HZ: BUS/GEN hertz.

    BUS/GEN SYNC STATUS: The bottom line of thegraphical display is used to indicate the followingBUS/GEN Sync status:

    NOT SYNCHRONIZING: Genset is in servicemode that does not allow auto sync feature.(Selected via InPower service tool deactivateto allow synchronization.)

    SYNCHRONIZING: Genset is synchronizing tobus.

    READY TO CLOSE: In manual mode, push cir-cuit breaker close button to close breaker.

    _\_ Button: Used to open and close the generatorset circuit breaker (CB). The symbol indicates if theCB is opened or closed. Opened _\_, push to close.Closed __, push to open.

    With the control panel 0/Manual/Auto switch in theAuto position, the opening and closing of the CB iscontrolled by the control system software. The CBsymbol will indicate an open or closed CB, but thebutton will be inactive when the control is in Auto.

    In the Manual position, the CB must be closed bythis button. When manually closed and the CBopens, it must be closed again by using this button.To close the CB, press and hold the button until thesymbol indicates a closed CB. (CB close will occuronly when setup conditions allow dead bus orgenerator synchronized with bus.)

    _\_

    V BUS GENL1 480 480L2 480 480L3 480 480HZ60.1 60.1

    DEG 122 NOT SYNCHRONIZING

    PARALLEL DATA

    LOAD GOVERN

    FIGURE 2-9. BUS DATA SUBMENU

  • 2-17

    POWER TRANSFER MAIN/SUBMENUS

    If you press the POWER TRANS button in MenuA, the Power Transfer main menu will appear (Fig-ure 2-10). The Power Transfer Control (PTC) fea-ture must be installed to display this menu.

    The PTC feature enables the PCC to monitor theutility voltage (mains) and frequency for failure andcontrol the opening and closing of the contacts (cir-cuit breakers) for the utility (S1) and the genset(S2).

    If utility fails, the control will initiate the genset start-ing sequence, open S1 and close S2 to the load.When utility returns, the load is retransferred to theutility (S1 closes/S2 opens) and the control initiatesthe genset shutdown sequence.

    The symbol displayed in the middle of the Pow-er Transfer main menu indicates which breaker(utility or genset) is closed/opened to the load. Thesymbol presently shown indicates that the utilitybreaker is closed and supplying power to the load.

    The Power Transfer main menu also indicates if theutility and the generator set are available to acceptload. When the control detects that either source isready to accept load, UTILITY and/or GENSET willbe displayed in inverse video.

    The Power Transfer main menu has four submenugroups. Refer to the page numbers shown in Figure2-10 for the Power Transfer submenu descriptions.

  • 2-18

    PTC Status Line

    The top line of the graphical display is used to indi-cate the following PTC status:

    NOT ENABLED: PTC is not enabled. Controlpanel switch in O (Off) position.

    MANUAL: Control panel switch is in Manualposition. All PTC actions or genset start/stopactions are manually controlled.

    NORMAL UTIL: Load is connected to the util-ity.

    RETRAN: Retransfer of load to utility. RETRAN OVRD: Immediate retransfer of load

    to utility due to genset fault (e.g., warning, der-ate, or shutdown w/cooldown fault). The re-transfer timer is ignored as is the retransfer in-hibit.

    EMERG TEST: Emergency Test sequence ini-tiated through Remote Start switch with emer-gency start sequence enabled (TB8-3 terminalopened). Emergency test mode means that

    the genset will continue to run even if a gensetwarning or derate fault occurs. This test can beperformed with or without load (refer to TEST/EXERCISE submenu in Section 3).

    TEST: Test sequence initiated through RemoteStart switch with emergency start sequencedisabled (TB8-3 terminal closed). Test mode isnon-emergency, which means that a retransferto utility will occur if any problems occur withthe genset while testing with load. This test canbe performed with or without load (refer toTEST/EXERCISE submenu in Section 3).

    EXERCISE: Exercise sequence initiatedthrough control panel. This test can be per-formed with or without load (refer to TEST/EX-ERCISE submenu in Section 3). A retransfer toutility will occur if any problems occur with thegenset during the exercise sequence.

    UTILITY FAIL: Utility has failed. (Initiatestransfer of load to genset if O/MANUAL/AUTOswitch is in AUTO.)

    UTILITY

    STATUS

    TRANSFER CONTROL

    GENSET

    PAGE2-19

    PAGE2-20

    PAGE2-21

    MENUA

    PAGE2-22

    MENUBUTTONS

    MENUBUTTONS

    DEG 123 SYNCHRONIZING

    PTC STATUS LINE

    FIGURE 2-10. POWER TRANSFER MAIN MENU

  • 2-19

    UTILITY (PWR TRAN) SUBMENUS

    If you press the Utility button in the Power TransferMain menu, the Utility submenus will appear (Fig-ure 2-11).

    Voltage L-L and L-N: Indicates utility voltage Line-to Line and Line-to-Neutral. Note that the Line-to-Neutral column will not be displayed for a 3 phase/3wire system. Accuracy 1%.

    The voltage Line-to-Line (L1, L2 and L3) are mea-sured between L1 to L2, L2 to L3 and L3 to L1, re-spectively.

    Amps: L2 only. Accuracy 1%.

    Frequency: Utility frequency.

    kW, kVA and PF: Displays (L2 only) utility kW andkVA output (average and direction of flow) and pow-er factor with leading/lagging indication. Accuracy5%.

    The PF reading will contain an asterisk if the powerfactor is leading (for example, *.30).

    UTILITY:kW kVA PF

    L1L2 125 175 .96L3TOT

    UTILITY

    UTILITY:V L-L L-NAMPS

    L1480 277L2 480 2771320

    L3480 277FREQUENCY60.0 HZ

    FIGURE 2-11. UTILITY SUBMENUS

  • 2-20

    STATUS (PWR TRAN) SUBMENUS

    If you press the Status button in the Power Trans-fer Main menu, the Status submenus will appear(Figure 2-12).

    Connected: Indicates which source(s) is con-nected to the load.

    Available: Indicates when the correspondingsources have acceptable output voltage and fre-quency. Both can be available simultaneously.

    Volt L12: Indicates utility and generator set Line 1 toLine 2 voltage.

    HZ: Utility and generator set output frequency.

    KW L2: Utility and generator set Phase B (L2) kWoutput.

    Transfer Inhibit: This feature is used to controlload transfer to the genset. When activated, loadtransfer to the genset will not take place if the utilityfails.

    Transfer inhibit is controlled by connecting a remotecontact between TB3-57 and TB3-58. Closing thecontact enables the feature and opening the con-tact disables it. When enabled, the event is dis-played on the graphical display.

    Retransfer Inhibit: This feature is used to preventthe PTC from automatically transferring the loadback to the utility. When activated, load transfer willnot take place unless the genset fails (RetransferInhibit is ignored if the genset fails).

    Retransfer inhibit is controlled by connecting a re-mote contact between TB3-64 and TB3-65. Closingthe contact enables the feature and opening thecontact disables it. When enabled, the event is dis-played on the graphical display.

    TRAN INHOFFRETRAN INHON

    STATUS

    UTILGENCONNECTEDYESNOAVAILABLEYESNOVOLT L12 4800

    HZ 60.00.0KW L2 4560

    FIGURE 2-12. STATUS SUBMENUS

  • 2-21

    TRANSFER CONTROL (PWR TRAN) SUBMENU

    If you press the TRANSFER CONTROL button inthe Power Transfer Main menu, the Transfer Con-trol submenu will appear (Figure 2-13).

    The symbol displayed in the middle of theTRANSFER CONTROL submenu indicates whichbreaker (utility or genset) is closed/opened to theload. The symbol presently shown indicates that theutility breaker is closed and supplying power to theload.

    During genset operation in the manual mode, youcan manually transfer/retransfer load between theutility and the genset. To transfer load, press the ap-propriate CB ENABLE button (Utility or Genset).

    Example (Figure 2-13)

    In the example in Figure 2-13, the CB ENABLE but-ton for Utility was pressed. (If the CB ENABLEbutton for the Genset was pressed, ENABLEGEN CB would be displayed in the second subme-nu, allowing you to open or close the genset circuitbreaker.)

    After pressing the utility CB ENABLE button, thesecond submenu will be displayed allowing you toeither CANCEL or ENABLE the entered selection.

    Pressing the CANCEL button will return the displayto the previous menu.

    Pressing the ENABLE button will display the thirdsubmenu. With this submenu displayed you can re-turn to the second submenu without opening theutility circuit breaker (press

  • 2-22

    GENSET (PWR TRAN) SUBMENUS

    If you press the Genset button in the Power Trans-fer Main menu, the Genset submenus will appear(Figure 2-14).

    Voltage L-L and L-N: Indicates voltage Line-toLine and Line-to-Neutral. Note that the Line-to-Neu-tral column will not be displayed for a 3 phase/3 wiresystem. Accuracy 1%.

    The voltage Line-to-Line (L1, L2 and L3) are mea-sured between L1 to L2, L2 to L3 and L3 to L1, re-spectively.

    Amps: All phases. Accuracy 1%.

    Frequency: Generator set output frequency.

    kW, kVA and PF: Displays generator set kW andkVA output (average and individual phase, and di-rection of flow) and power factor with leading/lag-ging indication. Accuracy 5%.

    The PF reading will contain an asterisk if the powerfactor is leading (for example,*.30).

    GENSET:kW kVA PF

    L1 100 150 .97L2 125 175 .96L3 150 200 .95TOT375 525 .96

    GENSET

    GENSET:V L-L L-NAMPSL1 480 2771320L2 480 2771320L3 480 2771320

    FREQUENCY60.0 HZ

    FIGURE 2-14. GENSET SUBMENUS

  • 3-1

    3. Control Calibration and Adjustment

    GENERALThis section contains calibration and adjustmentprocedures for the generator set control.

    PARALLELING AND NONPARALLELINGIf the generator set was purchased for a parallingapplication but will be used for a nonparalling ap-plication, entering the checksum data into the Data-plate Checksum dialog in InPower is not re-quired. However, the Adjustments Paralleling Paralleling Level must be set to Basic.

    SOFTWARE CALIBRATIONSIf the base card has software assembly A026 F566v1.0 on the U33 flash memory chip, you must usethe latest software calibration for the control. If youload an earlier software calibration onto a base cardwith software assembly A026 F566 v1.0, the soft-ware calibration will fail, and the board will lock uppermanent-ly.

    FIGURE 3-1. U33 FLASH MEMORY CHIP

    CAUTION If the base card has software as-sembly A026 F566 v1.0 on the U33 flash memorychip, you must use the latest software calibra-tion for the control, or the board will lock up per-manently.

    MODIFYING SETUP/ADJUST SUBMENUS

    The Setup and Adjust submenus allow you to cali-brate the graphical display meters and to adjustsystem parameters, customer defined faults, gen-erator set voltage/frequency and paralleling ap-plications.

    CAUTION Improper calibration or adjustmentof the control can cause equipment malfunctionor damage. Calibration and adjustment must beperformed by technically qualified personnelonly.

    The Setup submenus are intended for qualified ser-vice personnel only. The Adjust submenu is in-tended for qualified service and site personnel only.For this reason, a password must be entered beforethis data can be modified. The Setup and Adjustsubmenus can be viewed, but not modified withoutentering the correct password.

    Saving Menu Changes

    Changes are automatically saved when the menu isexited.

  • 3-2

    PASSWORD Menu

    To allow the site personnel to modify only the Adjustsubmenu and not the Setup submenus, two pass-words are assigned within the system software. AnApplication password is used for the Setup sub-menus and a User password is used for the Adjustsubmenu.

    The two passwords are assigned during the initialinstallation of the generator set (via InPower) andwill vary between sites. The installer must makesure that the passwords are available to the ap-propriate personnel.

    When the generator set is first installed, the Applica-tion and User password are both set to GENSET toallow initial modification of the Setup and Adjustsubmenus. Assign new passwords when site instal-lation is complete.

    When viewing the Adjust menu, pressing the + or button will display the User Password menu.

    When viewing a Setup menu, pressing the + or button will always display the Application Passwordmenu.

    After entering the correct password, the system willallow you to modify the submenus. To help prevent

    unauthorized adjustment, the entered password isvalid for 10 minutes after the last button is pressed(i.e., the password will need to be reentered afterthe ten minute timeout.

    Entering Password

    To enter the password:

    1. Display submenu to modify.

    2. Press either the + or button within the dis-played submenu. The Password menu ap-pears.

    3. Press the + and button to select the first char-acter of the password (AZ or 09). (Enter Ap-plication password for Setup submenus; En-ter User password for Adjust submenu.)

    4. Press the button to select the next characterfield. Selected character field is highlighted.

    5. Repeat steps 3 and 4 to enter remaining pass-word characters.

    6. Press the Enter button after entering the pass-word. The submenu selected in step 1 will re-appear.

    7. After making desired changes to submenu, exitsubmenu to save changes.

    + OR BUTTON

    ENTER

    ENTER APPLICATION PASSWORD

    +

    XXXXXXXX

    + OR BUTTON

    ENTER

    ENTER USER PASSWORD

    +

    XXXXXXXX

    SETUP SUBMENU PASSWORD MENU ADJUST SUBMENU PASSWORD MENU

    FIGURE 3-2. PASSWORD MENUS

  • 3-3

    SETUP MENUS

    Figure 3-3 shows the main menus (Menu A andMenu B) of the system control and the two Setupmenus.

    The Setup procedure is intended for qualified ser-vice personnel only. The APPLICATION passwordmust be entered to modify the Setup submenufields. Refer to PASSWORD Menu in this section toenter password and to save menu changes.

    To display the two Setup menus, press the

    MORE>> button in Menu A and then the SETUPbutton in Menu B.

    To view system data or to adjust system parame-ters, press the appropriate Setup menu button todisplay the desired Setup submenu(s). Refer to thepage number shown in Figure 3-3 for detailed infor-mation related to the selected submenu(s).

    CAUTION Improper calibration or adjustmentof the control can cause equipment malfunctionor damage. Calibration and adjustment must beperformed by technically qualified personnelonly.

    GOVERNING/VOLT REG

    CUSTOMER FAULTS

    CALIBRATION

    ISOLATED BUS

    UTILITY

    ENGINE

    ALTERNATOR

    CONTROL

    MORE>>

    POWER TRAN or _\_

    HISTORY/ABOUT SETUP

    ADJUST

    PARALLEL DATA

    BACK

  • 3-4

    GOVERNING/VOLT REG SUBMENU

    If you press the GOVERNING/VOLT REG buttonin the Setup menu, the Governing/Volt Regulatorsubmenu will appear (Figure 3-4).

    Use the + and buttons to increase or decrease thevalues in the following fields. Use the arrow () but-ton to move the cursor within a field or to the nextfield. Exit menu to safe changes.

    GOV GAIN: If the gain adjustment is set too high,engine speed will hunt or oscillate. If gain is set toolow, the engine will respond too slowly to changes inload and overspeed may result. (Gain should be re-duced to 80% for paralleling installations.)

    AVR GAIN: If the gain adjustment is set too high,output voltage will be unstable. If gain is set too low,the output voltage will respond sluggishly tochanges in load and overshoot may result.

  • 3-5

    GOVERNING/VOLT REG

    GOV GAIN80%AVR GAIN100%

    +

    FIGURE 3-4. GOVERNING/VOLT REG SUBMENU

  • 3-6

    CUSTOMER FAULTS SUBMENUS

    If you press the CUSTOMER FAULTS button inthe Setup menu, the Customer Faults submenuswill appear (Figure 3-5).

    There are a total of four customer fault inputs.(Faults 3 and 4 paralleling only.) The message dis-played at the bottom of the menu can be modifiedfor each of these faults in addition to selecting thefollowing operating parameters for each fault.

    Enable On or Off Active Closed or Open Response Shutdown, Cooldown, Derate or

    Warning

    Shutdown: Genset will immediately shutdown. Normally used for engine faults.

    Cooldown: Cooldown sequence will be initi-ated before shutdown. Should not be used forengine faults.

    Derate: Used to lower kW output of genset forwarnings such as pre-high coolant tempera-ture, etc. Paralleling application controller willreduce precentage of kW load sharing on theset. Non-paralleling application controller will

    lower percentage of kW load by operating loadshed relay contacts.Warning: Display message, genset continuesto operate.

    The Enable and the Active fields apply to the Fault 1and 4 submenus only.

    With the Active field selected, pressing the + or buttons will toggle the selection between CLOSEDand OPEN. Use same operation for remaining fieldselections.

    To enter the desired customer fault message, pressthe or button to display the submenu that con-tains the customer fault message (1 through 4) to bechanged. Use the button to scroll down throughthe menu selections to the editable fault message(bottom menu line).

    Use the button to move to each character posi-tion within the fault message line.

    With the desired character position selected, use +or buttons to select the appropriate character.

    If these messages are changed, you should notethese changes in the Troubleshooting section of theOperators manual for this generator set.

  • 3-7

    CUSTOMER FAULTS

    CUSTOMER FAULT1:ENABLE ONACTIVE CLOSEDRESPONSEWARNING

    ***CUSTOMER FAULT1 ******************

    +

    CONTINUES THROUGH TWOADDITIONAL MENUS FOR ATOTAL OF FOUR POSSIBLE

    CUSTOMER FAULT MESSAGES

    +

    CUSTOMER FAULT2:

    RESPONSEWARNING

    ***CUSTOMER FAULT2 ******************

    FIGURE 3-5. CUSTOMER FAULTS SUBMENUS

  • 3-8

    CALIBRATION SUBMENUS

    If you press the CALIBRATION button in the Setupmenu, the Calibration submenus will appear (Fig-ure 3-6).

    Use the + and buttons to increase or decrease thevalues in the following fields. Use the arrow () but-ton to move the cursor within a field or to the nextfield. Exit menu to safe changes.

    The Calibration submenus allow you to calibrate thecontrol with the reading from a calibrated meter.Calibration is accomplished by using this section of

    the menu software to adjust the display so that itmatches the reading taken on an accurate, recentlycalibrated meter.

    Calibration is normally only required when replac-ing certain circuit cards. Refer to the CalibrationProcedure in this section which contains a list of thecards that require control calibration.

    When performing Bus Voltage Calibration from thegraphical display, the genset must be off and the Buslive. If the genset is running, it will synchronize to theBus.

  • 3-9

    CALIBRATION

    VOLTAGE CALIBRATIONL1 480-X.X%L2 480-X.X%L3 480-X.X%

    +

    CURRENT CALIBRATIONL1 234-X.X%L2 123-X.X%L3 562-X.X%

    +

    BUS VOLTAGE CALIBRATIONL1 480 -X.X%L2 480 -X.X%L3 480 -X.X%

    +

    FIGURE 3-6. CALIBRATION SUBMENUS

  • 3-10

    ISOLATED BUS / UTILITY Submenus(Paralleling Application)

    The Isolated BUS submenus (Figure 3-7) and theUtility submenus (Figure 3-8) adjust the control pa-rameters for generator set protection, synchroniz-ing and load sharing for both isolated bus and utility(mains) paralleling applications. Utility (mains) par-allel applications may require adjustment of boththe Isolated BUS and Utility submenus.

    Always perform ISO BUS calibration before UtilityBUS calibration.

    The sync check (permissive) function is operationalin both automatic and manual (RUN) modes. Thecontrol will make sure that the generator set is atproper voltage, within the defined sync check win-dow for the defined period of time and that phaserotation is correct. When all criteria are met, the par-alleling breaker is closed automatically by the con-trol (auto mode), or by operation of the breakerclose switch by the operator (manual mode).

    The synchronizing function of the control is enabledwhen the control has brought the generator set to90% of rated speed and voltage, and has sensedthat bus voltage is available. The control automati-cally adjusts the generator set speed and voltage tomatch the bus frequency and voltage. The controlcan force the generator set to match bus voltage

    and frequency in a range of minus 40% to plus 10%of normal bus conditions. When the parallelingbreaker has closed, the control will bring the gener-ator set back to normal voltage and frequency.

    When the generator set is paralleled to anothergenerator set, the control provides automatic loadsharing functions for both real (kW) and reactive(kVAR) loads. Load sharing is proportional betweengenerator sets based on their standby ratings. If twogenerator sets of different sizes are paralleled, theywill assume the same percentage of the systemload automatically. This can easily be verified on thekW Load LED bar graph on the front of the controlpanel.

    When the utility paralleling mode is enabled and thegenerator set paralleling breaker is closed, the gen-erator set will assume load based on external ana-log input signal. The input signal must be calibratedfrom 05 VDC. When the signal is at 0.5 to 1 VDC,the control will operate the generator at no load inparallel with the utility (mains) source. At 4.5 VDCand greater, the control will operate the generatorset at 110% of the generator set base load setting.When the load govern signal is between 1 VDC and4.5 VDC the control will operate the generator set ata load level which is determined by a linear relation-ship between the kW reference and the load governsignal.

  • 3-11

    ISOLATED BUS SUBMENUS

    If you press the ISOLATED BUS button in the Set-up menu, the Isolated BUS submenus will appear(Figure 3-7).

    Use the + and buttons to increase or decrease thevalues in the following fields. Use the arrow () but-ton to move the cursor within a field or to the nextfield. Exit menu to safe changes.

    SYNC TIME LIMIT: This parameter adjusts the timedelay in seconds before the Fail To Synchronizealarm will operate.

    REVERSE PWR LMT: Adjusts the reverse powerset point. For PowerCommand generator sets, atypical set point is 10-15%.

    REVERSE PWR TIME: Adjusts the reverse powerfunction time delay. A typical time delay which is

    suitable for PowerCommand generator sets is 3seconds.

    Lower reverse power set points can result in nui-sance reverse power shutdown faults.

    PERM WIN-PHASE: Adjusts the width of the per-missive (sync-check) acceptance window. The ad-justment range is from five to twenty electrical de-grees. Recommended set point is 20 degrees forisolated bus applications, and 15 degrees for utility(mains) paralleling applications.

    PERM WIN-TIME: Adjusts the time period (in sec-onds) for which the generator set must be synchro-nized with the system bus, before a breaker closesignal is issued by the PowerCommand control.Available range is 0.5 to 5 seconds. Recommendedvalue for PowerCommand generator sets is 0.5seconds for isolated bus applications.

  • 3-12

    ISOLATED BUS

    ISOLATED BUS:SYNC TIME LIMIT 120SEC

    REV PWR LMT 10%REV PWR TIME 3SECPERM WIN-PH 20DEGPERM WIN-TIME .5SEC

    +

    CONTINUED TO NEXT PAGE

    FIGURE 3-7. ISO BUS SUBMENUS

  • 3-13

    Adjusting the control for a smaller sync-check win-dow or longer time delay will cause synchronizingtime to be extended.

    SYNC GAIN: The sync gain adjustment controlshow quickly the governor will respond to try to mini-mize the bus/generator phase difference. Increas-ing the gain speeds up the response. If the gain istoo high instability can result.

    KW Balance and KVAR Balance changes should beequally shared among all generator sets.

    KW BALANCE: This function adjusts the kW loadsharing function of the generator set. Before adjust-ing this value, all generator set calibrations shouldbe performed. If the total load on the system is notshared proportionately, the kW Balance can beused to adjust the generator set for more preciseload sharing. Increasing the kW Balance value willcause the generator set to reduce the percentage ofthe total kW load on that set.

    KVAR BALANCE: This function adjusts the kVARload sharing function of the generator set. Beforeadjusting this value, all generator set calibrationsshould be performed. If the total load on the systemis not shared proportionately, the kVAR balance canbe used to adjust the generator set for more preciseload sharing. Increasing the kVAR balance valuewill cause the generator set to reduce the percent-age of the total kVAR load on that set.

    KW GAIN: Adjusts the rate of change of kW load onthe generator set. With a constant load on the sys-tem, if the generator set load is constantly chang-ing, reduce the gain adjustment on the generatorset. This also allows modification of the rate of loadassumption on transient load change.

    KVAR GAIN: Adjusts the rate of change of kVARload on the generator set. With a constant load onthe system, if the generator set load is constantlychanging, reduce the gain adjustment on the gener-ator set. This also allows modification of the rate ofload assumption on transient load change.

  • 3-14

    ISOLATED BUS (CONT.)

    ISOLATED BUS:SYNC GAIN 1.0KW BALANCE 0.3

    KVAR BALANCE 1.2KW GAIN 1.0KVAR GAIN 1.0

    +

    CONTINUED TO NEXT PAGE

    FIGURE 3-7. ISO BUS SUBMENUS (CONT.)

  • 3-15

    1ST FAIL TIME: Time delay in seconds after a sig-nal from the first start master is not sensed by thePCC that a FIRST START FAIL warning is dis-played.

    RAMP UNLOAD TIME: When a load demand stopinput is sensed the load is ramped down from thepresent load level on the set to the ramp unload lev-el in the time specified in seconds.

    RAMP UNLOAD LEVEL: The load demand rampunload function will ramp the load down from the

    present level on the set to this level before openingthe set circuit breaker. Value shown is in % of gensetstandby rating.

    RAMP LOAD TIME: When the load demand stopsignal is removed the load is ramped from 0kW tothe load share level in the specified time after thecircuit breaker closes.

    LOSS FIELD TIME: Adjusts the loss of field func-tion time delay. A typical delay which is suitable forPowerCommand generator sets is 2 seconds.

  • 3-16

    ISOLATED BUS (CONT.)

    ISOLATED BUS:1ST FAIL TIME 12SECRAMP UNLD 20SEC

    RAMP UNLD LEVEL 10%RAMP LOAD TIME 3SECLOSS FIELD 20SEC

    +

    FIGURE 3-7. ISO BUS SUBMENUS (CONT.)

  • 3-17

    UTILITY SUBMENUS

    If you press the UTILITY button in the Setupmenu, the Utility submenus will appear (Figure 3-8).

    Use the + and buttons to increase or decrease thevalues in the following fields. Use the arrow () but-ton to move the cursor within a field or to the nextfield. Exit menu to safe changes.

    BASE LOAD (%): This controls the maximum kWload level that the generator set will operate at whenparalleled with the utility (mains). The value shownindicates the steady state load on the generator asa percent of the generator set standby rating.

    Check generator set ratings for maximum load levelat which the generator set should operate whenparalleled with the utility (mains). Extended opera-tion at load levels in excess of the generator set rat-ing can cause abnormal engine wear or prematureengine failure.

    PF LEVEL: Adjusts the power factor that the gener-ator set will run at when paralleled to the utility(mains). Recommended setting is 1.0.

    RAMP LOAD TIME: This is the ramp time frompresent set load to level determined by the load setanalog input. This is active when the control first en-ters the load govern mode.

    RAMP UNLOAD TIME: This is the ramp time frompresent set load to 0 kW. This ramp is active whenthe load set analog input is less than 0.5 volts.

    MODE MULTIPLE/SINGLE: This controls wheth-er the set is to operate as part of a multiple set orsingle set (PLTE or PLTF) system. (Refer to LOADDEMAND SHUTDOWN and SINGLE MODE EN-ABLE function descriptions in wiring diagram,page 5-8.)

    KW GOVERN GAIN: This controls the rate that thegenerator set kW load is increased after the genera-tor set has closed to the system bus when utility(mains) paralleled. Decreasing this value will resultin slower loading of the generator set.

    KVAR GOVERN GAIN: This controls the rate thatthe generator set kVAR load is increased after thegenerator set has closed to the system bus whenutility (mains) paralleled. Decreasing this value willresult in slower loading of the generator set.

  • 3-18

    UTILITY

    UTILITY:BASE LOAD 80%PF LEVEL 1.00RAMP LOAD 3RAMP UNLD 20MODE MULTIPLE

    +

    UTILITY:KW GOVERN GAIN 1.00KVAR GOVERN GAIN1.00

    +

    FIGURE 3-8. UTILITY SUBMENUS

  • 3-19

    POWER TRANSFER CONTROL MAINMENUS

    If you press the POWER TRANSFER SETUP but-ton in the Setup menu 2 in Figure 3-3, the two mainmenus of the optional Power Transfer Control(PTC) feature will appear (Figure 3-9).

    To adjust PTC system parameters, press the ap-propriate PTC main menu button and refer to thepage number shown in Figure 3-9 for detailed infor-mation related to the submenu selected.

    UTILITY SENSORS

    GENSET SENSORS

    TIMERS

    PAGE3-13

    PAGE3-15

    PAGE3-17

    NEXTMENU

    TEST/EXERCISE PAGE3-18

    PTC MAIN MENU 1

    PTC MAIN MENU 2

    FIGURE 3-9. PTC SETUP MAIN MENUS

  • 3-20

    UTILITY SENSORS SUBMENUS

    If you press the UTILITY SENSORS button in thePTC Main Menu 1, the Utility Sensors submenuswill appear (Figure 3-10).

    The following field descriptions show the valid fieldentries and default value (shown in parenthesis) foreach field.

    Use the + and buttons to increase or decrease thevalues in the following fields. Use the arrow () but-ton to move the cursor within a field or to the nextfield. Exit menu to save changes.

    U PT VOLT LL: Enter the value of the utility line-to-line voltage which yields 100% voltage at the termi-nals of the utility (bus) PT module.

    Range: 115000V, adjustable by standard nominalvoltage values, 100V, 10V and 1V increments (1V).

    The 100% voltages for each of the four possible util-ity (bus) PT modules are as follows, based on mod-ule dash number:01 = 208 volts LL02 = 416 volts LL03 = 600 volts LL04 = 120 volts LL

    Example 1: Nominal Utility voltage is 480V. Thismeans that utility (bus) PT module number 02should be used. The voltage which will yield 100%volts at this PT module is 416 per the above table.Thus enter 416V.

    Example 2: Nominal Utility voltage is 4160V. A pri-mary stage transformer with a ratio of 4200/240 isused. This means that utility (bus) PT module num-ber 01 should be used. The voltage which will yieldthe 100% volts (208V from above table) is calcu-lated as follows:

    208 x (4200/240) = 3640. Thus enter 3640V.

    U NOM VOLT LL: Enter the nominal utility line-to-line voltage. For example, 480, 4160, etc.. Range:115000 V, adjustable by standard nominal voltagevalues, 100V, 10V and 1V increments (1V).

    U CT RATIO: Enter the CT Ratio of the Utility L2 CT.This is the Ratio to 1 Amp. Range: 118000 (1A).

    CAUTION This CT must be rated for 1 Ampoutput (e.g. NOT 5 Amp). Be sure CT secondarycircuit has burden resistor or a shorting jumperin place before putting power through the CT.Example: CT Ratio = 2650:1. Thus enter 2650.

    U SENSOR TYPE: Enter the line-to-line (L-N) for 3phase line-neutral voltage sensing or line-to-line(L-L) for 3 phase line-line voltage sensing. This ap-plies to both the utility undervoltage and overvol-tage sensors. Range: LL, LN (LN).

    U : Enter utility connection type.Range: Delta, Wye (Wye).

    U UNLOADED KW: Enter the kW on utility Line 2 atwhich the utility is considered as unloaded. This isthe L2 kW level at which a closed transition softtransfer will disconnect from the utility.

    UTILITY UNDERVOLTAGE: Non-adjustable field,always enabled.

    UTILITY OVERVOLTAGE, FREQUENCY: Used toenable or disable menu function. Choose Enabledor Disabled (Enabled).

    UV PICKUP: Enter a number between 85 and100% of the nominal voltage (90%).

    UV DROP OUT: Enter a number between 75 and98% of the under-voltage pick-up percentage(90%).

    UV DELAY: Enter a time between 0.1 and 5.0 sec-onds (0.5 seconds).

    UV MIN PHASE: Displays the lowest line voltage ofthe three utility phases.

  • 3-21

    OV PICKUP: This adjusts the over-voltage pickupas a percentage of the over-voltage drop-out. Entera number between 95 and 99% (95%).

    OV DROP OUT: Enter a percentage between 105and 135% of the nominal voltage (110%).

    OV DELAY: Enter a range between 0 and 120 sec-onds (3 seconds).

    OV MAX PHASE: Displays the highest line voltageof the three utility phases.

    CENTER (FREQ): Enter a frequency between 45and 65 Hz (60 Hz).

    PICK UP (FREQ): Enter a percentage between 5and 20% of the nominal frequency (10%).

    DROP OUT (FREQ): Enter a percentage between1 and 5% of the nominal frequency (1%).

    DELAY (FREQ): Enter a time between 0.1 and 15.0seconds (5.0 seconds).

    FREQUENCY: This field displays the sensed utilityline frequency.

    UTILITY SENSORS

    UPT VOLT LL 416UNOM VOLT LL 480UCT RATIO: 1 1000USENSOR TYPE LL

    UUNLOADED KW 50 KW

    +

    UTILITY UV:ENABLED%VLL

    PICK UP 95475DROP OUT 85465

    DELAY 0.5 SMIN PHASE 470

    +

    UTILITY OV:DISABLED%VLL

    PICK UP 95487DROP OUT 110490

    DELAY 3.0 SMAX PHASE485

    +

    UTILITY FREQ:DISABLEDCENTER 60HZPICK UP 10%DROP OUT 1%DELAY 1.0S

    FREQUENCY60.5HZ

    +

    FIGURE 3-10. UTILITY SENSORS SUBMENUS

  • 3-22

    GENSET SENSORS SUBMENUS

    If you press the GENSET SENSORS button in thePTC Main Menu 1, the Genset Sensors submenuswill appear (Figure 3-11).

    The following field descriptions show the valid fieldentries and default value (shown in parenthesis) foreach field.

    Use the + and buttons to increase or decrease thevalues in the following fields. Use the arrow () but-ton to move the cursor within a field or to the nextfield. Exit menu to save changes.

    G NOM VOLT LL: Non-adjustable field, displayscurrent setting of genset nominal voltage. (See Ad-just submenu to adjust the output voltage 5%.)G SENSOR TYPE: Enter the line-to-line (L-N) for 3phase line-neutral voltage sensing or line-to-line(L-L) for 3 phase line-line voltage sensing. This ap-plies to both the genset undervoltage and overvol-tage sensors. Range: LL, LN (LN).

    G BASE LOAD: Enter the maximum load the gen-set will carry during a closed transition. Range:0100% (80%).

    G RAMP LOAD: Enter the ramp time for the gensetramp load rate during a closed transition soft loadtransfer. Ramp rate is +100%kW divided by thistime setting. Range: 0900 seconds (20 sec).

    G RAMP UNLOAD: Enter the ramp time for thegenset ramp unload rate during a closed transtionsoft load retransfer. Ramp rate is 100%kW dividedby this time setting. Range: 0900 seconds (20sec).

    G UNLOADED KW: Enter the %kW (based onstandby rating) that the genset is considered un-loaded. This is the %kW level at which a closed tran-sition soft retransfer will disconnect from the gen-set. Range: 0100% (5%).

    GEN UNDERVOLTAGE: Non-adjustable field, al-ways enabled.

    GEN OVERVOLTAGE, FREQUENCY: Used to en-able or disable menu function. Choose Enabled orDisabled (Enabled).

    UV PICKUP: Enter a number between 85 and100% of the nominal voltage (90%).

    UV DROP OUT: Enter a number between 75 and98% of the under-voltage pick-up percentage(90%).

    UV DELAY: Enter a time between 0.1 and 5.0 sec-onds (4 seconds).

    UV MIN PHASE: Displays the lowest line voltage ofthe three genset phases.

  • 3-23

    OV PICKUP: This adjusts the over-voltage pickupas a percentage of the over-voltage drop-out. Entera number between 95 and 99% (95%).

    OV DROP OUT: Enter a percentage between 105and 135% of the nominal voltage (110%).

    OV DELAY: Enter a range between 0 and 120 sec-onds (3 seconds).

    OV MAX PHASE: Displays the highest line voltageof the three genset phases.

    CENTER (FREQ): Enter a frequency between 45and 65 Hz (60 Hz).

    PICK UP (FREQ): Enter a percentage between 5and 20% of the nominal frequency (10%).

    DROP OUT (FREQ): Enter a percentage between1 and 5% of the nominal frequency (1%).

    DELAY (FREQ): Enter a time between 0.1 and 15.0seconds (5.0 seconds).

    FREQUENCY: Displays the sensed genset line fre-quency.

    GENSET SENSORS

    GNOM VOLT LL 480GSENSOR TYPE LLGBASE LOAD 80.0%GRAMP LOAD 20 SGRAMP UNLOAD 20 SGUNLOADED KW 5 %

    +

    GEN UV: ENABLED%VLL

    PICK UP 95475DROP OUT 85465

    DELAY 1.0 SMIN PHASE 470

    +

    GEN OV: DISABLED%VLL

    PICK UP 95487DROP OUT 110490

    DELAY 8.0 SMAX PHASE485

    +

    GEN FREQ:DISABLEDCENTER 59HZPICK UP 12%DROP OUT 2%DELAY 5.0S

    FREQUENCY60.0HZ

    +

    FIGURE 3-11. GENSET SENSORS SUBMENUS

  • 3-24

    TIMERS SUBMENU

    If you press the TIMERS button in the PTC MainMenu 1, the Timers submenu will appear (Figure3-12).

    The following field descriptions show the valid fieldentries and default value (shown in parenthesis) foreach field.

    Use the + and buttons to increase or decrease thevalues in the following fields. Use the arrow () but-ton to move the cursor within a field or to the nextfield. Exit menu to save changes.

    START DELAY: Sets time delay for genset enginestart. Prevents nuisance genset starting during briefpower interruptions.

    Enter a range from 0 to 300 seconds (0 seconds).

    STOP DELAY: Sets the time delay for engine cool-down following a re-transfer. This stop delay worksin conjunction with and is activated at the same timeas the normal cooldown timer. (Will extend normalcooldown timer if entered time is greater.)

    Enter a time from 0 to 600 seconds (0 seconds).

    TRANSFER: In a Normal to Emergency transferthis function allows the genset to stabilize beforethe load is applied. Enter a time from 0 to 120 sec-onds (10 seconds).

    RETRANSFER: In a Emergency to Normal transferthis function allows the utility to stabilize before theload is applied.

    Enter a time from 0 to 1800 seconds (600 seconds).

    PGM TRANSIT: Sets the time delay for Pro-grammed Transition. A setting of 0.0 disables theprogram.

    Enter a time from 0 to 60 seconds (0 seconds).

    MAX PARALLEL: Sets the maximum time duringclosed transition that utility and genset can be paral-leled.

    Enter a time from 0 to 1800 seconds (20 seconds).

  • 3-25

    TIMERS

    START DELAY60SSTOP DELAY60STRANSFER 10SRETRANSFER900SPGM TRANSIT5SMAX PARALLEL30S

    +

    FIGURE 3-12. TIMERS SUBMENU

  • 3-26

    TEST/EXERCISE SUBMENU

    If you press the TEST/EXERCISE button in thePTC Main Menu 2, the Test/Exercise submenu willappear (Figure 3-13).

    The following field descriptions show the valid fieldentries and default value (shown in parenthesis) foreach field.

    Use the + and buttons to increase or decrease thevalues in the following fields. Use the arrow () but-ton to move the cursor within a field or to the nextfield. Exit menu to save changes.

    MODE: Indicates the generator set application typefor PTC option.

    OT-PGM TRAN Open transition load transfer.CT-MOMENT Closed transition load transferwith momentary (

  • 3-27

    TEST/EXERCISE

    MODE CT-SOFT

    TEST WITH LOADOFFEXER WITH LOADOFF

    +

    FIGURE 3-13. TIMERS SUBMENU

  • 3-28

    ADJUST SUBMENU

    Figure 3-14 shows the main menus (Menu A andMenu B) of the system control and the Adjust sub-menu.

    To display the Adjust submenu, press the MORE>>button in Menu A and then the ADJUST button inMenu B.

    The Adjust submenus are intended for qualifiedservice personnel and site personnel only and mayrequire a USER password. If a password is re-quired, the USER password menu will appear whenyou try to modify the Adjust submenus. (Refer toPASSWORD Menu in this section to enter pass-word.

    Changes are automatically saved when you exitthis menu.

    If the generator set is operating in parallel with asystem bus, the voltage and frequency adjustments

    are disabled to prevent inadvertent misadjustmentof the paralleling load sharing functions.

    Use the + and buttons to increase or decrease thevalues in the following fields. Use the arrow () but-ton to move the cursor within a field or to the nextfield. Exit menu to safe changes.

    START DELAY: This delay applies only to remotestarting in the Auto mode. The Start Delay adjust-ment range is 0 to 300 seconds.

    STOP DELAY: This delay applies only to remotestopping in the Auto mode. The Stop Delay adjust-ment range is 0 to 600 seconds.

    VOLTAGE: Used to adjust the output voltage 5%.

    FREQUENCY: Used to adjust the frequency 3 Hz.

    VOLTAGE/SPEED DROOP: These two submenusapply to a genset that has the paralleling option andis configured to operate in droop mode.

    ENGINE

    ALTERNATOR

    CONTROL

    MORE>>

    _\_

    HISTORY/ABOUT

    SETUP

    ADJUST

    BUS DATA

    BACK

  • 3-29

    CALIBRATION PROCEDURE

    There are several circuit cards/modules that, whenremoved and replaced, require you to recalibratethe control panel display for genset voltage and cur-rent and bus voltage.

    Note that the type of calibration to perform varies foreach card. The letters A, B and C are used to desig-nate which of the following three calibration proce-dures are required for each card/module.

    Genset/Parallel board (A, B & C) PT/CT board (A & B) Bus PT (C) CTs (B)

    WARNING Contacting high voltage compo-nents can cause electrocution, resulting in se-vere personal injury or death. Calibration andadjustment must be performed by technicallyqualified personnel only. Read and observe allWARNINGS and CAUTIONS in your generatorset manuals.

    CAUTION Improper calibration or adjustmentof the PowerCommand control can causeequipment malfunction or damage. Calibrationand adjustment must be performed by techni-cally qualified personnel only.

    Use a calibrated RMS multimeter for accurate mea-surements.

    (A) Genset Voltage Display Calibration

    The PowerCommand control automatically synchro-nizes to the system bus when bus voltage is avail-able and the genset is running. Consequently, it isnot possible to calibrate the genset output voltage

    display of the genset that is running when the bus isenergized. If it is necessary to adjust the output volt-age display of the genset that is running, the InPowerservice tool must be used to switch off the synchro-nizer function of the control.

    1. Display the Voltage Calibration submenu(Page 3-6).

    2. With the genset OFF, attach a calibrated volt-meter to the AC output from L1 to L2. (L1 toNeutral for single phase alternators.)

    3. Start the genset and allow it to reach normaloperating speed.

    4. Calibrate voltage reading for L1 so that thereading on the display agrees with the cali-brated voltmeter.

    5. Shut the generator set OFF.6. Repeat steps 2 through 5 for L2 and L3. (In step

    2 attach meter to the AC output from L2 to L3 tocalibrate L2 and L3 to L1 to calibrate L3.)

    7. Exit menu to safe changes.

    (B) Genset Ammeter Display Calibration

    1. Display the Current Calibration submenu(Page 3-6).

    2. With the genset OFF, attach a calibrated am-meter to L1.

    3. Start the genset and allow it to reach normaloperating speed.

    4. Load the genset to maximum rated kVA atrated voltage.

    5. Calibrate the reading for L1 current so that thereading on the display agrees with calibratedammeter.

    6. Repeat steps 2 through 5 for L2 and L3. (In step2, attach meter to L2 to calibrate L2 current andL3 to calibrate L3 current.)

    7. Exit menu to safe changes.

  • 3-30

    (C) Bus Voltage Calibration

    The PowerCommand control automatically synchro-nizes to the system bus when bus voltage is avail-able and the genset is running. Consequently, it isnot possible to calibrate the genset bus voltage dis-play of the genset that is running when the bus is en-ergized. If it is necessary to adjust the bus voltagedisplay of the genset that is running, the InPowerservice tool must be used to switch off the synchro-nizer function of the control.

    1. Display the Bus Voltage Calibration submenu(Page 3-6).

    2. With all gensets OFF, attach a calibrated volt-

    meter to TB1-A (L1) and TB1-B (L2) of the busPT module (Figure 3-15).

    3. Start another genset and allow it to reach nor-mal operating speed and voltage. Connect op-erating genset to the bus.

    4. Calibrate the voltage reading for Bus Volts L1so that the reading on the display matches thereading on the calibrated meter.

    5. Shut the generator set OFF.6. Repeat steps 2 through 5 for Bus Volts L2 and

    L3. (In step 2 attach meter to the AC outputfrom L2 to L3 to calibrate L2; L3 to L1 to cali-brate L3.)

    7. Exit menu to safe changes.

    TB1-A (L1)

    CONTROLBOX DOOR

    TB1-B (L2)

    TB1-C (L3)

    FIGURE 3-15. BUS PT MODULE

  • 3-31

    CONTROL BOX WIRING

    The generator set control box assembly, which canbe located on either side of the genset, containsconnection points for remote control and monitoroptions.

    Customer monitor/control connections are at-tached to terminal blocks TB3 and TB8 (see Figure

    3-16). Optional equipment such as a remote annun-ciator panel, sensing devices used to monitor gen-set operation, remote start/stop switches, controlbox heater, and etc. are also attached to these ter-minal blocks. Driver signals for customer suppliedrelays are also provided for several alarm and shutdown conditions. Refer to Customer Connectionsdiagram in Section 7.

  • 3-32

    TB8

    CARDCAGE

    OPTIONALSHUTDOWN

    ALARM RELAY K16

    OPTIONALRUN RELAYS

    K11, K12 & K13

    CONTROL WIRINGACCESS

    FIGURE 3-16. CONTROL BOX ASSEMBLY INTERIOR

  • 3-33

    RUN RELAYS (K11, K12, K13)

    The optional run relays are rail mounted inside thecontrol box (Figure 3-16). The rail mount allows youto easily remove and replace the snap-on relays.The generator set can be equipped with one, two orthree run relays.

    The three-pole, double-throw run relays (Figure3-17) are used to control auxiliary equipment such

    as fans, pumps and motorized air dampers. The runrelays are energized when the generator set reach-es operating speed.

    The contacts are rated:

    10 amps at 28 VDC or 120 VAC, 80%PF 6 amps at 240 VAC, 80%PF 3 amps at 480/600 VAC, 80%PF

    CUSTOMERCONNECTIONS

    TB3-7(GND)

    TB3-5(SWITCHED B+)

    NO

    COIL

    COM

    NC

    K11, K12, K13

    K11RUN RELAY

    K11, K12, K13

    K11, K12, K13

    K12RUN RELAY

    K13RUN RELAY

    NO

    NC

    NO

    NC

    FIGURE 3-17. OPTIONAL RUN RELAYS (K11, K12, K13)

  • 3-34

    ALARM RELAY (K16)

    The optional alarm relay is rail mounted inside thecontrol box (Figure 5-2). The rail mount allows youto easily remove and replace the snap-on relay.

    The three-pole, double-throw alarm relay (Figure5-4) is often used to energize warning devices such

    as audible alarms. Any generator set shutdown willenergize the alarm relay.

    The contacts are rated:

    10 amps at 28 VDC or 120 VAC, 80%PF 6 amps at 240 VAC, 80%PF 3 amps at 480/600 VAC, 80%PF

    CUSTOMERCONNECTIONS

    TB3-18(GND)

    TB3-17(COM ALARM)

    NO

    COIL

    COM

    NC

    K16

    K16

    K16

    K16SHUTDOWN ALARM

    FIGURE 3-18. OPTIONAL ALARM RELAY (K16)

  • 3-35

    MAGNETIC SPEED PICKUP UNIT (MPU)INSTALLATION

    To install the MPU sensor, bar the engine until agear tooth on the flywheel lines up in the center of

    the mounting hole. Thread the sensor in gently byhand until it just touches the gear tooth. Back it outone quarter turn and set the locknut.

    CAUTION Do not use fan blade to bar over en-gine. That can damage blades and cause prop-erty damage and personal injury.

  • 3-36

    MAGNETICPIC