� Functional Safety

� Safety Integrity Levels – SIL

� SIL Capability

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 3: Sil 3 systems ppt.pdf

3

Functional Safety� Functional Safety describes the behaviour of a safety

device – meaning HW and SW – in case of an internal failure occurring

� The target is – "reaching a safe state”

WHAT DOES IT MEAN?

It means internal faults in the safety device should be detected by the device itself and shall be indicated and signalled.

The only requirement of the standards is safety!

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 4: Sil 3 systems ppt.pdf

4

Safety and Availability

� A safety device, which will shut down the monitored production line or better the whole plant

� In any case of the smallest probability of a potential failure, this is safe and will comply to the standards reaching a high SIL

BUT will The Customer be happy with it?

What about the system’s availability?

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 5: Sil 3 systems ppt.pdf

5

The standards requires safety …

… The Customer requests availability

� Safety and availability must not be a contradiction!

� The solution stays in systems with fault tolerance, which is typically related to high SIL

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 6: Sil 3 systems ppt.pdf

6

Fault Tolerance

� Fault tolerance means the safety device is still in operation and in measuring mode after the fault situation has been detected

� Operation will proceed eventually with reduced functionality

.. which leads to the Emergency Mode

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 7: Sil 3 systems ppt.pdf

7

Emergency Mode

� The SIL-standard in gas detection (EN 50402) permits explicitly an “emergency mode”

� Defined for a specified period of time for redundant systems.

� After detection of an internal fault the system is not longer redundant but still fully operational.

This allows time to repair for the safety device without the need to shut down the monitored system.

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 8: Sil 3 systems ppt.pdf

8

SIL = Safety Integrity Level

� SIL describes the different levels of “Functional Safety” on a safety device

� The values are defined from SIL-1 (lowest) up to SIL-4 (highest)

� Which doesn’t mean SIL1 is (too) low

Example: A typical gas detection device (system) with ATEX-Certificate including the functional approval according IEC 61779, with regular maintenance is equivalent to SIL-1

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 9: Sil 3 systems ppt.pdf

9

Typical examples of SIL levels

� SIL 1 A typical gas detection device / system with ATEX-Certificate

� SIL-2 typically reached by

– self testing facilities for HW.

– reduced maintenance intervals

– specific SW requirements and documentation.

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 10: Sil 3 systems ppt.pdf

10

Typical examples of SIL levels

� SIL-3 The main requirement: One failure shall not cause an unsafe state

Therefore a SIL 3 is a fail-safe system

- Step SIL 2 – SIL 3 is typically reached by redundancy

- Specific SW requirements are added

� SIL-4 Sometimes requires triple redundancy

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 11: Sil 3 systems ppt.pdf

11

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Different Classes of Faults

� Safe detected

� Safe undetected� Dangerous detected

� Dangerous undetected

Above classification important in design to determine the “Safe Failure Fraction”, specific for each SIL level

Which may be classified as:

� Random faults

� Systematic faults

Page 12: Sil 3 systems ppt.pdf

12

Different Classes of Faults

� Random faults – occur occasionally

� Systematic faults – occur at specific conditions

Reproducible should the same conditions apply

HW features both random and systematic faults

SW features only systematic faults

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 13: Sil 3 systems ppt.pdf

13

SIL - Capability of modules

� Simple modules –

� Relays

� Sensor element

� any simple analogue electronics circuit

� Complex modules

� microprocessor based systems

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 14: Sil 3 systems ppt.pdf

14

SIL - Combination of modules

In a complex system different modules are combined together

� SIL capability is determined by the modules combination

� series modules – “weakest” module gives the combination SIL

� parallel modules – SIL capability may increase by one level

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 15: Sil 3 systems ppt.pdf

15

SIL – Capability of a Safety function

Safety function – the combination of modules

In a gas detection system:

Ex. Gas detection system: combination of modules from gas inlet (sensor) to the output device (relay)

� Different options in the modules combinations lead to different safety functions

HW and SW combinations are evaluated in

different ways

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 16: Sil 3 systems ppt.pdf

16

SIL – Capability of a Safety function

HW SIL-2

SW SIL-2

HW SIL-2

SW SIL-2

HW SIL-3SW SIL-2

In combination

SIL 2

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 17: Sil 3 systems ppt.pdf

17

SIL – Capability of a Safety function

HW SIL-2

SW SIL-3

HW SIL-2

SW SIL-3

HW SIL-3SW SIL-3

In combination

SIL 3

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 18: Sil 3 systems ppt.pdf

18

� To increase the availability, redundancy should be implemented – double processor system.

� If one processor is faulty – emergency mode – still fully operational

� SW developed according to SIL 3� With redundant detectors and redundant relays the

systems may reach SIL 3

… as a consequence, the items above describe Galileo Multisystem

Logical consequences for a new system

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 19: Sil 3 systems ppt.pdf

19

The new control unit GALILEO Multisystem was designed in accordance with the SIL standard, so the system hereby

presented would comply with the various SIL levels according to the standard EN 50402.

Where not detailed in the above mentioned standard, the

various chapters of the IEC61508 were followed, especially:

- IEC61508 - 2 for the E/E/PES

- IEC61508 – 3 for the SW requirements

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 20: Sil 3 systems ppt.pdf

20

� All decisions are taken at the CPU level

� Configuration data are redundant and may be found at

three levels:� CPU

� Module

� Detector – where available intelligent detector

� Devices to be monitored may be� standard 4..20mA analogue output devices

� addressable devices communicating in RS485 loop

� simple switches through digital inputs

� Full system structure is based on RS485 communication

loop

PrePrePrePrePrePrePrePre--------requisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisitesrequisites

Page 21: Sil 3 systems ppt.pdf

21

Main features 1/2Main features 1/2Main features 1/2Main features 1/2Main features 1/2Main features 1/2Main features 1/2Main features 1/2

� 4 RS485 loops;

� up to 256 programmable field inputs;

� up to 512 programmable field outputs;

� Mother Board redundancy;

� Loop redundancy - optional;

� RS232 PC interface;

� Display/Signalling user interface;

Page 22: Sil 3 systems ppt.pdf

22

Main features Main features Main features Main features Main features Main features Main features Main features –––––––– 2/22/22/22/22/22/22/22/2

� “Low battery” supervising circuit and “NO battery”

signalling.

� Auxiliary power outputs 12/24VDC fuse protected;

� Output modules with relays.

� Loop configuration self-check.

� 6 main operating conditions, implemented in

accordance with the CEI standards and EN50402

Page 23: Sil 3 systems ppt.pdf

23

Operation states 1/2Operation states 1/2Operation states 1/2Operation states 1/2Operation states 1/2Operation states 1/2Operation states 1/2Operation states 1/2

Three operation states:

� Normal – usual operative state, no particular events,

everything working properly;

� Alarm – one or more channels are exceeding one or more

of the gas alarm levels;

� Emergency – any of the situations which guide to

degrading from SIL3 or SIL2 system to SIL2 or SIL1 respectively.

Page 24: Sil 3 systems ppt.pdf

24

Operation states 2/2Operation states 2/2Operation states 2/2Operation states 2/2Operation states 2/2Operation states 2/2Operation states 2/2Operation states 2/2

And three special states:

� Fault – one or more devices in the system are in fault

condition or malfunctioning state;

� Test/Maintenance– this status is up to the operator in order

to test various parts of the installation and for Calibration purpose also;

� Unset – total or partial unset of the various parts or the system.

Page 25: Sil 3 systems ppt.pdf

25

System configurations 1/3System configurations 1/3System configurations 1/3System configurations 1/3System configurations 1/3System configurations 1/3System configurations 1/3System configurations 1/3

4 serial ports RS485 and the whole capacity to all

loops as follows:

� 256 analogue inputs and addressable detectors

� 64 digital inputs

� 256 analogue outputs – further development

� 512 relay outputs.

Page 26: Sil 3 systems ppt.pdf

26

System configurations 2/3System configurations 2/3System configurations 2/3System configurations 2/3System configurations 2/3System configurations 2/3System configurations 2/3System configurations 2/3

All devices connected in loop will be galvanic

isolated so that the loop may be automatically

closed if any discontinuity occurs (mechanical cut-

off, or open/short circuit):

� Analogue inputs module;

� Loop modules

� Relay outputs modules;

� Analogue outputs modules – further development

� Monitor module – further development

Page 27: Sil 3 systems ppt.pdf

27

System configurations 3/3System configurations 3/3System configurations 3/3System configurations 3/3System configurations 3/3System configurations 3/3System configurations 3/3System configurations 3/3

There are several options to connect the field modules to

CPU:1. 2 closed loops, redundant one to the other, case in which the system will

feature whole capacity per each loop, monitoring both the same modules.

Control Unit

Galvanic isolation

Galvanic isolation

Field Module

Galvanic isolation

Galvanic isolation

Field Module

Galvanic isolation

Galvanic isolation

Field Module

Galvanic isolation

Galvanic isolation

Page 28: Sil 3 systems ppt.pdf

28

Details CPUDetails CPUDetails CPUDetails CPUDetails CPUDetails CPUDetails CPUDetails CPU

� The Main Board’s architecture is designed

around two microprocessor which are making

redundancy one to the other.

� Each microprocessor is monitoring one loop

� On the two corresponding loops are connected

all the field modules.

� This way both microprocessors are monitoring in

the same time all field devices.

Page 29: Sil 3 systems ppt.pdf

29

Details CPUDetails CPUDetails CPUDetails CPUDetails CPUDetails CPUDetails CPUDetails CPU

Control U

nit

SIGNAL

SYSTEM

OVER-RANGE

ALARM 3

ALARM 2

ALARM 1

UNDER-SCALE

FAULT

POWER

TEST

UNSET

BATTERY

FAULT

1

4

7

ESC

2

5

8

0

3

6

9

ENT

Galvanic isolation

Page 30: Sil 3 systems ppt.pdf

30

Signalling interfaceSignalling interfaceSignalling interfaceSignalling interfaceSignalling interfaceSignalling interfaceSignalling interfaceSignalling interface-- frontfront--end LED signallingend LED signalling --

� 3 red LED - three general ALARM thresholds .

� 1 red LED - “Over-Range”situation

� 1 yellow LED - “Under-Scale”situation .

� 1 yellow LED - loop FAULTS .

� 1 yellow LED – general FAULT.

� 1 yellow LED - general “Unset”

� 1 yellow LED - general Test/Maintenance.

� 1 green LED - power supply.

� 1 yellow LED - Emergency Mode

SIGNAL LED’s

OVER-RANGE

ALARM 3

ALARM 2

ALARM 1

UNDER-SCALE

FAULT

SYSTEM LED’s

POWER

TEST

UNSET

EMERGENCY

FAULT

Page 31: Sil 3 systems ppt.pdf

31

Signalling interface Signalling interface Signalling interface Signalling interface Signalling interface Signalling interface Signalling interface Signalling interface

-- Basic relaysBasic relays --

� 3 programmable relays corresponding to the three general alarm thresholds .

� 2 relays - general Fault (System Fault) – 1 relay redundant for the other

� 1 relay - Test/Maintenance mode .

� 2 relay - Emergency Mode – 1 relay redundant for the other .

Page 32: Sil 3 systems ppt.pdf

32

General Philosophy General Philosophy General Philosophy General Philosophy General Philosophy General Philosophy General Philosophy General Philosophy

� The two µP are communicating one to

each other in the way that each one is

updated with the other’s status.

� NONE of the two µP can switch off

the other one;

� Yet EACH of the two µP can decide to switch off itself if something goes

wrong.

� In the case on µP is switching off, the other one continues monitoring also

the second loop by means of the

redundant microprocessors on all field

modules.

Control Unit

Galvanic isolation

Page 33: Sil 3 systems ppt.pdf

33

µµµµµµµµP NP NP NP NP NP NP NP Noooooooo. 1. 1. 1. 1. 1. 1. 1. 1Provided with peripherals - responsible for

the management of:

� external PC – by means of an RS 232

port;

� external printer by means of a parallel

port;

� signalling LED’s on the front panel;

� basic relays on central unit’s level;

� two serial loops LOOP A / LOOP A

RETURN - RS 485 ports.

µP1

µP2

External PCExternal Printer

Page 34: Sil 3 systems ppt.pdf

34

µµµµµµµµP NP NP NP NP NP NP NP Noooooooo. 2. 2. 2. 2. 2. 2. 2. 2Provided with peripherals - responsible

for the management of:

� graphical display LCD – by means

of an RS 232 port;

� 24 keys keypad;

� signalling LED’s on the front panel;

� basic relays on central unit’s level,

by means of a SPI port;

� two serial loops LOOP B / LOOP B

RETURN - RS 485 ports.

Control Unit

Galvanic isolation

1

4

7

ESC

2

5

8

0

3

6

9

ENT

Page 35: Sil 3 systems ppt.pdf

35

Loop devicesLoop devicesLoop devicesLoop devicesLoop devicesLoop devicesLoop devicesLoop devices

All loop devices are addressable, each address

identifies uniquely one input or output, as follows:� Analogue inputs module AIM – 8 analogue + 2 digital address

points (out of the 256 + 64 system inputs);

� Loop module – programmable 32 addressable detectors on local loop + 2 digital inputs (out of the 256 + 64 system inputs);

� Relay outputs module – 8 or 16 address points (out of the 512 relay outputs) - basic board or basic + extension respectively)

� Analogue outputs module – 8 address points (out of the 256 analogue outputs) – further development

� Monitor module – 1 address point (out of the 256 + 512 system outputs) – further development

Page 36: Sil 3 systems ppt.pdf

36

Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module –––––––– AIM 1/5AIM 1/5AIM 1/5AIM 1/5AIM 1/5AIM 1/5AIM 1/5AIM 1/5

This module is designed to accommodate 8 analogue

inputs (4-20mA type) and two digital inputs.

Configuration:

� Each of the 8 inputs on the board is seen

individually by CPU, therefore each AIM is

occupying 8 addresses in the loop.

� Each input is separately programmable by means

of the software.

� The maximum number of such boards in this

configuration is 32.

Page 37: Sil 3 systems ppt.pdf

37

Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module –––––––– AIM 2/5AIM 2/5AIM 2/5AIM 2/5AIM 2/5AIM 2/5AIM 2/5AIM 2/5

Such board will accommodate:

� - 4-20mA output gas detectors – on the

analogue inputsNOTE: RS485 communication provided for all 8 channels – 5 poles

connection provided for each channel

� used for setting up de detector’s configuration at system setup and to retrieve further details in case of FAULT

� - remote push buttons or switching outputs– on

the digital inputs

Page 38: Sil 3 systems ppt.pdf

38

Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module –––––––– AIM 3/5AIM 3/5AIM 3/5AIM 3/5AIM 3/5AIM 3/5AIM 3/5AIM 3/5

AIM’s architecture is designed also around two microprocessors making redundancy to each other.

� the two µP of AIM are connected separately on two loops.

� the two µP are sharing status data to each other, by means of I2C bus;

� NONE of the two µP is physically connected also to the second loop.

� Each µP has an internal A/D converter;

� All 8 analogue inputs connected to both µP through 2 external MUX, switching the communication to the 8 channels, one at a time;.

� EACH of the two MUX is connected to BOTH microprocessors on board;

� RS 485 MUX will point towards µP № 1 ONLY;

Page 39: Sil 3 systems ppt.pdf

39

Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module –––––––– AIM 4/5AIM 4/5AIM 4/5AIM 4/5AIM 4/5AIM 4/5AIM 4/5AIM 4/5

Control Unit

AIM Module

30 30 30 30

30 30 30 30

Galvanic isolation

Galvanic isolation

Galvanic isolation

Page 40: Sil 3 systems ppt.pdf

40

Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module Analogue Inputs Module –––––––– AIM 5/5AIM 5/5AIM 5/5AIM 5/5AIM 5/5AIM 5/5AIM 5/5AIM 5/5

The module is designed so that it might be used also as

an independent central unit. Therefore it is be provided also with the possibility of being connected to:

� an external PC – RS 232 port on µP № 1;

� digital display – RS232 port on µP № 2;

� LED’s board – connected through SPI ports on both µP;

� Relays board - connected through SPI ports on both µP

� Keypad – parallel port on µP № 2.

� Same as in the system, the two µP are sharing status data to each other, by means of I2C bus;

Page 41: Sil 3 systems ppt.pdf

41

Loop Module 1/5Loop Module 1/5Loop Module 1/5Loop Module 1/5Loop Module 1/5Loop Module 1/5Loop Module 1/5Loop Module 1/5

� Designed to accommodate one loop of 32 addresses. The loop cycle expected is 0.5s.

� In plus two digital inputs are available.

Configuration:

� Each of 32 addressable detectors on loop will be seen individually, therefore each such board is occupying 32

addresses in the main loop of the system.

� This way each input will be set separately by means of the software.

� The maximum number of such boards in this configuration is 8.

� Such board will accommodate addressable gas detectors SMART type.

� Local loop is a closed loop, RS485 type.

Page 42: Sil 3 systems ppt.pdf

42

Loop module 2/5Loop module 2/5Loop module 2/5Loop module 2/5Loop module 2/5Loop module 2/5Loop module 2/5Loop module 2/5

Such board will accommodate:

� - addressable SMART gas detectors – on the

local loop

� - remote push buttons or switching outputs– on

the digital inputs

Page 43: Sil 3 systems ppt.pdf

43

Loop Module 3/5Loop Module 3/5Loop Module 3/5Loop Module 3/5Loop Module 3/5Loop Module 3/5Loop Module 3/5Loop Module 3/5

Loop module’s architecture is designed around two microprocessors making redundancy to each other.

� the two µP of Loop module are connected separately on two loops.

� the two µP are sharing status data to each other, by means of I2C bus;

� NONE of the two µP is physically connected also to the second loop.

� The two ends of the local loop are connected each one to one µP through RS485 ports;

� This way BOTH microprocessors see the local loop;

Page 44: Sil 3 systems ppt.pdf

44

Loop Module 4/5Loop Module 4/5Loop Module 4/5Loop Module 4/5Loop Module 4/5Loop Module 4/5Loop Module 4/5Loop Module 4/5

LOOP Module

30 30 30

30 30 30

Galvanic isolation

Control Unit

Galvanic isolation

Galvanic isolation

Galvanic isolation

Page 45: Sil 3 systems ppt.pdf

45

Loop Module 5/5Loop Module 5/5Loop Module 5/5Loop Module 5/5Loop Module 5/5Loop Module 5/5Loop Module 5/5Loop Module 5/5

The module is designed so that it might be used also as

an independent central unit. Therefore it is be provided also with the possibility of being connected to:

� an external PC – RS 232 port on µP № 1;

� digital display – RS232 port on µP № 2;

� LED’s board – connected through SPI ports on both µP;

� Relays board - connected through SPI ports on both µP

� Keypad – parallel port on µP № 2.

� Same as in the system, the two µP are sharing status data to each other, by means of I2C bus;

Page 46: Sil 3 systems ppt.pdf

46

Relay Module 1/3Relay Module 1/3Relay Module 1/3Relay Module 1/3Relay Module 1/3Relay Module 1/3Relay Module 1/3Relay Module 1/3

The module is meant to be used as output device, managing up to 16 relays.

Basic board is microprocessor based, provided with 2 microprocessors each being connected to one of the two loops coming from the central unit.

� Each of the 8 outputs on the board will be assigned an individual address from 1 to 512, therefore such board will occupy 8

addresses (or 16 in case basic board is provided with extension

module of 8 relays).

� Each output will be this way separately set, by means of the

programming software.

� The maximum number of such boards is 32 (or 16 in case basic

board is provided with extension module of 8 relays).

Page 47: Sil 3 systems ppt.pdf

47

Relay Module 2/3Relay Module 2/3Relay Module 2/3Relay Module 2/3Relay Module 2/3Relay Module 2/3Relay Module 2/3Relay Module 2/3

� 2 µP’s on board, connected separately on two loops, and none of them physically connected on the second loop

� both µP’s are managing 8 relays on the basic board or 16 relays in case the extension board is used.

� On the main board - 8 relays, rated 4A@250V; DIP switches for each of the 8 relays to set the NO/NC operation mode;

� On the extension board - 8 relays, rated 16A@250V;

� galvanic isolated connection with the two loops communicating with the central unit;

� provided with connectors to accommodate superposed extension board with additional 8 relays;

Page 48: Sil 3 systems ppt.pdf

48

Relay Module 3/3Relay Module 3/3Relay Module 3/3Relay Module 3/3Relay Module 3/3Relay Module 3/3Relay Module 3/3Relay Module 3/3

Control Unit

AIM Module

8 RELAYS

Galvanic isolation

Galvanic isolation

Galvanic isolation

8 RELAYS – extension board

Page 49: Sil 3 systems ppt.pdf

49

SIL 2 configurationSIL 2 configurationSIL 2 configurationSIL 2 configurationSIL 2 configurationSIL 2 configurationSIL 2 configurationSIL 2 configuration

� Loop A redundant with loop B

� µP № 1 redundant with µP № 2

� NO redundancy on detectors level

30

30

30

30

Control Unit

Galvanic isolation

Galvanic isolation

AIM Module

Galvanic isolation

AIM Module

Galvanic isolation

Page 50: Sil 3 systems ppt.pdf

50

SIL 3 configurationSIL 3 configurationSIL 3 configurationSIL 3 configurationSIL 3 configurationSIL 3 configurationSIL 3 configurationSIL 3 configuration

� Loop A redundant with loop B

� µP № 1 redundant with µP № 2

� Redundancy on detectors level

30

30

30

30

LOCATION 1

LOCATION 2

LOCATION 3

LOCATION 8

Control Unit

µP1

µP2 Galvanic isolation

Galvanic isolation

AIM Module

µP1

µP2Galvanic isolationLOOP A

LOOP 2-0

AIM Module

µP1

µP2Galvanic isolation

LOOP 2

LOOP 1

LOOP 2-1 (RETURN)

LOOP 1-1 (RETURN)

Page 51: Sil 3 systems ppt.pdf

51

SIL configurations SIL configurations SIL configurations SIL configurations SIL configurations SIL configurations SIL configurations SIL configurations -------- optionoptionoptionoptionoptionoptionoptionoption

� Loop A redundant with loop B

� µP № 1 redundant with µP № 2

� Redundancy on detectors level

30LOCATION 1

LOCATION 2

LOCATION 3

Control Unit

µP1

µP2 Galvanic isolation

Galvanic isolation

AIM Module

µP1

µP2Galvanic isolationLOOP 1-0

LOOP 2-0

30

30

30

30

30

30

30LOCATION 4

30LOCATION 5

LOCATION 6

LOCATION 7

AIM Module

µP1

µP2Galvanic isolation

30

30

30

30

30

30

30LOCATION 8

LOOP 1

LOOP 2

LOOP 1-1 (RETURN)

LOOP 2-1 (RETURN)

Page 52: Sil 3 systems ppt.pdf

52

System setupSystem setupSystem setupSystem setupSystem setupSystem setupSystem setupSystem setup

Whole system configuration is done by means of PC software