TP3 toplotna pumpa

Embed Size (px)

Citation preview

  • 7/25/2019 TP3 toplotna pumpa

    1/24

    Model shown is withlow-noise option

    www.eurovent-certification.com

    www.certiflash.com

    Air-to-Water Heat Pumps with Integrated Hydronic Module

    30RQ 182-522

    Nominal cooling capacity 175-470 kW

    Nominal heating capacity 184-554 kW

    The Aquasnap heat pump range features the latest techno-logical innovations: ozone-friendly refrigerant R410A, scrollcompressors, low-noise fans made of a composite material,auto-adaptive microprocessor control. The Aquasnap canbe equipped with an integrated hydronic module (option),limiting the installation to straightforward operations likeconnection of the power supply and the chilled water supplyand return piping.

    Features

    Quiet operation

    Compressors- Low-noise scroll compressors with low vibration level- The compressor assembly is installed on an independent

    chassis and supported by flexible anti-vibration mountings- Dynamic suction and discharge piping support, minimising

    vibration transmission (Carrier patent)- Acoustic compressor enclosure, reducing radiated noise

    emissions (option) Air heat exchanger

    - Heat exchanger coils in V-shape with an open angle,

    allowing quieter air flow across the coil- Low-noise 4th generation Flying Bird fans, made of a

    composite material (Carrier patent) are now even quieterand do not generate intrusive low-frequency noise

    - Rigid fan mounting prevents start-up noise (Carrier patent)

    Easy and fast installation

    Integrated hydronic module (option)- Centrifugal low or high-pressure water pump (as

    required), based on the pressure loss of the hydronicinstallation

    - Single or dual pump (as required) with operating timebalancing and automatic changeover to the back-uppump if a fault develops

    - Water filter protecting the water pump againstcirculating debris

    - High-capacity membrane expansion tank ensurespressurisation of the water circuit

    - Thermal insulation and frost protection down to -20C,using an electric resistance heater (see table of options)

    - Pressure gauge to check filter pollution and measure thesystem water flow rate (option)

    - Water flow control valve (option) Simplified electrical connections

    - A single power supply point without neutral- Main disconnect switch with high trip capacity (see table

    of options)- 24 V control circuit without risk from a transformer

    included Fast commissioning

    - Systematic factory operation test before shipment- Quick-test function for step-by-step verification of the

    instruments, electrical components and motors

  • 7/25/2019 TP3 toplotna pumpa

    2/24

    2

    Superior reliability

    State-of-the-art concept- Cooperation with specialist laboratories and use of limit

    simulation tools (finite element calculations) for thedesign of the critical components, e.g. motor supports,suction/discharge piping

    - Compressor control box installed on the cold side of thecompressor (Carrier patent)

    Refrigerant circuit

    - Two independent refrigerant circuits- Filter drier/refrigerant storage tank (Carrier patent) for

    optimised unit operation in both cooling and heatingmode by controlling the refrigerant charge.

    Auto-adaptive control- Control algorithm prevents excessive compressor

    cycling and permits reduction of the water quantity inthe hydronic circuit (Carrier patent)

    - Automatic compressor unloading in case of abnormallyhigh condensing pressure. If an anomaly occurs (e.g.fouled air heat exchanger coil, fan failure) Aquasnapcontinues to operate, but at reduced capacity.

    Exceptional endurance tests- Corrosion resistance tests in salt mist in the laboratory- Accelerated aging test on components that are submitted

    to continuous operation: compressor piping, fan supports- Transport simulation test in the laboratory on a vibrating

    table. The test is based on a military standard andequivalent to 4000 km by truck.

    Pro-Dialog Plus control

    Pro-Dialog Plus combines intelligence with operatingsimplicity. The control constantly monitors all machineparameters and precisely manages the operation ofcompressors, expansion devices, fans and of the water heatexchanger water pump for optimum energy efficiency.

    Energy management- Internal time schedule clock: permits heat pump on/off

    control and operation at a second set-point- Automatic heating/cooling change-over based on the air

    temperature- Set-point reset based on the outside air temperature or

    the return water temperature- Master/slave control of two heat pumps operating in

    parallel with operating time equalisation and automaticchange-over in case of a unit fault.

    Ease-of-use- User interface with synoptic diagram for intuitive display

    of the principal operating parameters: number ofcompressors operating, suction/discharge pressure,compressor operating hours, set-point, air temperature,entering/leaving water temperature

    - Ten menus for direct access to all machine commands,

    including fault history, allowing fast and complete heatpump diagnostics.

    Economical operation

    Increased energy efficiency at part load- The refrigerant circuit includes several compressors

    connected in parallel. At part load, around 99% of theoperating time, only the compressors that are absolutelynecessary operate. At these conditions the compressorsoperating are even more energy efficient, as they use thetotal air heat exchanger and water heat exchangercapacity.

    - The electronic expansion device (EXV) allows operation ata lower condensing pressure (EER and COP optimisa-tion).

    - Dynamic superheat management for better utilisation ofthe heat exchange surface of the water heat exchangerand optimised compressor protection.

    Reduced maintenance costs- Maintenance-free scroll compressors- Fast diagnosis of possible incidents and their history via

    the Pro-Dialog Plus control- R410A refrigerant is easier to use than other refrigerant

    blends

    Environmental care

    Refrigerant R410A- Chlorine-free refrigerant of the HFC group with zeroozone depletion potential

    - Very efficient offers a very high coefficient ofperformance (EER/COP)

    Leak-tight refrigerant circuit- Brazed refrigerant connections for increased leak-

    tightness- Reduction of leaks as no capillary tubes and flare

    connections are used- Verification of pressure transducers and temperature

    sensors without transferring refrigerant charge- Discharge shut-off valve allows storage of the refrigerant

    charge in the air heat exchanger for simplified mainte-nance.

    Pro-Dialog Plus operator interface

  • 7/25/2019 TP3 toplotna pumpa

    3/24

    3

    Energy Management Module EMM (option)

    - Room temperature: permits set-point reset based on thebuilding indoor air temperature (with Carrier thermostat)

    - Set point reset: ensures reset of the cooling set-pointbased on a 4-20 mA or 0-5 V signal

    - Demand limit: permits limitation of the maximum heatpump demand based on a 4-20 mA or 0-5 V signal

    - Demand limit 1 and 2: closing of these contacts limitsthe maximum heat pump capacity to three predefined

    values- User safety: this contact can be used for any customer

    safety loop, closing of the contact generates a specificalarm

    - Time schedule override: closing of this contact cancelsthe time schedule effects

    - Out of service: this signal indicates that the heat pump iscompletely out of service

    - Heat pump capacity: this analogue output (0-10 V) givesan immediate indication of the heat pump capacity

    - Compressor operation: this contact signals that one orseveral compressors are in operation

    Pro-Dialog Plus operator interface

    RS 485 serial portHeat pump control by communication bus offers multipleremote control, monitoring and diagnostic possibilities.Carrier offers a vast choice of control products, speciallydesigned to control, optimise and supervise the operationof an air conditioning system. Please consult your Carrierrepresentative for more information on these products.

    Control terminal block

    - Start/stop: opening of this contact will shut down theunit

    - Operating mode control: heating or cooling- Dual set-point: closing of this contact activates a second

    set-point (example: unoccupied mode)- Demand limit: closing of this contact limits the maximum

    heat pump capacity to a predefined value- User safety: this contact is connected in series with the

    water flow switch and can be used for any customersafety loop

    - Water pump 1 and 2 control*: these outputs control thecontactors of one or two water heat exchanger waterpumps

    - Water pump on reversal*: these contacts are used todetect a water pump operation fault and automaticallychange over to the other pump

    - Operation indication: this volt-free contact indicates thatthe heat pump is operating (heating or cooling load) orthat it is ready to start

    - Alert indication: this volt-free contact indicates thepresence of a minor fault

    - Alarm indication: this volt-free contact indicates thepresence of a major fault that has led to the shut-downof one or two refrigerant circuits

    * contacts already supplied with the hydronic module option

  • 7/25/2019 TP3 toplotna pumpa

    4/24

    4

    OptionsOptions No. Description Advantages Use

    Corrosion protection, traditional

    coils

    3A Fins made of pre-treated aluminium (polyurethane

    or epoxy)

    Improved corrosion resistance, recommended for

    marine, moderate or urban environments

    30RQ 182-522

    Unit for indoor installation with air

    discharge duct

    12 Fans with available pressure Ducted air heat exchanger air discharge, optimised

    condensing temperature control, based on the

    operating conditions and system characteristics

    30RQ 182-522

    Low noise level 15 Acoustic compressor enclosure Noise emission reduction 30RQ 182-522

    Grilles 23 Metallic grilles on all four unit faces (this optionincludes the supply of enclosure panels)

    Improved aesthetics 30RQ 182-522

    Enclosure panels 23A Side panels on each end of the coils Improved aesthetics 30RQ 182-522

    Electronic starter 25 Electronic starter on each compressor Reduced start-up current 30RQ 182-522

    Winter operation down to -20C 28 Fan speed control via f requency converter Stable unit operat ion when the air temperature is

    between 0C and -20C

    30RQ 182-522

    Water heat exchanger frost

    protection

    41 Electric heater on the water heat exchanger Water heat exchanger frost protect ion down to

    -20C outside temperature

    30RQ 182-522

    Water heat exchanger andhydronic module frost protection

    42A Electric heaters on the water heat exchanger andhydronic module

    Water heat exchanger and hydronic module frostprotection down to -20C outside temperature

    30RQ 182-522

    Partial heat reclaim 49 Partial heat reclaim by desuperheating thecompressor discharge gas

    Free high-temperature hot-water productionsimultaneously with chilled water production

    30RQ 182-522

    Master/slave operation 58 Unit equipped with an addit ional eld-installed leavingwater temperature sensor, allowing master/slave

    operation of two heat pumps connected in parallel

    Optimised operation of two units connected inparallel with operating time equalisation

    30RQ 182-522

    Main disconnect switch without

    fuse (standard for sizes 182-262)

    70 Factory-installed main electric disconnect switch in

    the control box

    Ease-of-installation and compliance with local

    electrical regulations

    30RQ 302-522

    Main disconnect switch with fuse 70D Factory-installed main electric disconnect switch withfuse in the control box

    Same advantage as main disconnect switch andreinforced anti-short circuit protection

    30RQ 302-522

    Water heat exchanger withaluminium jacket

    88 Water heat exchanger thermal insulation protectionby aluminium sheets

    Improved resistance to climatic aggression 30RQ 182-522

    Water heat exchanger andhydronic module with aluminium

    jacket

    88A Water heat exchanger and water piping thermalinsulation protection by aluminium sheets

    Improved resistance to climatic aggression 30RQ 302-522

    High-pressure single-pump

    hydronic module

    116B Single high-pressure water pump, water lter,

    expansion tank, pressure gauge, water ow control

    valve. See hydronic module option.

    Easy and fast installation 30RQ 182-522

    High-pressure dual-pump

    hydronic module

    116C Dual high-pressure water pump, water lter,

    expansion tank, pressure gauge, water ow controlvalve. See hydronic module option.

    Easy and fast instal lation, operating safety 30RQ 182-522

    Low-pressure single-pump

    hydronic module

    116F Single low-pressure water pump, water lter, expansion

    tank, pressure gauge, water ow control valve. Seehydronic module option.

    Easy and fast installation 30RQ 182-522

    Low-pressure dual-pumphydronic module

    116G Dual low-pressure water pump, water lter, expansiontank, pressure gauge, water ow control valve. See

    hydronic module option.

    Easy and fast installat ion, operating safety 30RQ 182-522

    High-pressure single-pump

    hydronic module

    116M Single high-pressure water pump, water lter,

    expansion tank, pressure taps. See hydronic module

    option.

    Easy and fast installation 30RQ 182-522

    High-pressure dual-pump

    hydronic module

    116N Dual high-pressure water pump, water lter, expansion

    tank, pressure ports. See hydronic module option.

    Easy and fast installat ion, operat ing safety 30RQ 182-522

    Low-pressure single-pump

    hydronic module

    116P Single low-pressure water pump, water lter, expansion

    tank, pressure ports. See hydronic module option.

    Easy and fast installation 30RQ 182-522

    Low-pressure dual-pump

    hydronic module

    116Q Dual low-pressure water pump, water lter, expansion

    tank, pressure ports. See hydronic module option.

    Easy and fast installat ion, operat ing safety 30RQ 182-522

    JBus gateway 148B Two-directional communications board, complies

    with JBus protocol

    Easy connection by communication bus to a

    building management system

    30RQ 182-522

    Bacnet gateway 148C Two-directional communications board, complies

    with Bacnet protocol

    Easy connection by communication bus to a

    building management system

    30RQ 182-522

    LonTalk gateway 148D Two-directional communications board, complies

    with LonTalk protocol

    Easy connection by communication bus to a

    building management system

    30RQ 182-522

    Energy Management moduleEMM

    156 See controls manual Easy connection by wired connection to a buildingmanagement system

    30RQ 182-522

    Safety valve with three-way valvetted

    194 Three-way valve upstream of the safety valves (notcompatible with BPHE version)

    Safety valve inspection and replacement facilitatedwithout refrigerant loss

    30RQ 182-522

    Conformance with Australianregulations

    200 Heat exchanger approved to Australian code - 30RQ 182-522

    Euro Pack 221 This option contains the options enclosure panels,

    water heat exchanger frost protection, maindisconnect switch and low noise level

    Aesthetics, ease-of-installation and low operating

    noise

    30RQ 262-302

    Storage unit above 48C 241 Refrigerant charge stored in the air heat exchangers Unit transport by container only possible with thisoption

    30RQ 182-522

    Coil defrost resistance heaters 252 Electric heaters under the coils and thecondensate pans

    Prevents frost formation on the coils; compulsoryin the heating mode, if the outdoor temperature is

    below 0C

    30RQ 182-522

    Traditional Cu/Al coils 254 Coils with copper tubes and aluminium ns Possibility to add special treatments 30RQ 182-522

    Connection sleeve 266 Piping to be welded with Victaulic connection Ease-of-installation 30RQ 182-522Shell-and-tube water heat

    exchanger

    280 Dierent heat exchanger type Ensures compatibility with other options than those

    available with the standard unit (see Electronic

    Catalogue)

    30RQ 182-262

    Power cable connection side

    extension

    283 Side extension on the power control to allow a

    reduced cable bend radius

    Use of thicker power cables 30RQ 302-522

  • 7/25/2019 TP3 toplotna pumpa

    5/24

    5

    Units with fans with available pressure for indoor installation(option 12)

    Cooling capacity variations for operating conditionsthat dier from Eurovent conditions

    EER variations for operating conditions that dierfrom Eurovent conditions

    EERvariationcoefcient

    Duct pressure drop, Pa

    Coolingcapacityvaria

    tioncoefcient

    Duct pressure drop, Pa

    Each refrigerant circuit (A and B) must have a separateducting system to prevent any air recycling between theair heat exchangers of the different refrigerant circuits.

    In 30RQ units with option 12 each fan is equipped with afactory-installed connection interface, allowing the connec-tion to the ducting system for the specific circuit (A and B)for each fan. Please refer to the unit dimensional drawingsfor the exact dimensions of the connection interface.

    Important:To collect the defrost water from the coils in the heatingmode, the 30RQ units must be installed on an appropriatesurface to permit efficient condensate drainage andevacuation and to prevent any risk of flooding at the site.

    The unit cooling capacity and energy efficiency ratio (EER)in the cooling mode varies depending on the duct pressure

    drops:- between 0 and 100 Pa the unit cooling capacity is onlyslightly affected,

    - between 100 and 200 Pa the unit cooling capacity fallsconsiderably depending on the operating conditions(outdoor air temperature and water conditions).

    Please refer to the curves below to evaluate the impact ofthe estimated duct system pressure drop for the installationand the impact of different full load operating conditionson the 30RQ unit cooling capacity and EER.

    This option applies to 30RQ units installed inside thebuilding in a plant room. For this type of installation thecold or hot air leaving the air-cooled air heat exchangers isdischarged by the fans to the outside of the building, usinga duct system.

    30RQ units equipped with fans with available pressure aredesigned to operate with air discharge ducts with maximumpressure drops of 200 Pa.

    To compensate for these pressure drops 30RQ units withoption 12 are equipped with variable-speed fans with amaximum speed of 19 r/s, instead of 15.8 r/s and fixed-speedfans as for the standard units.

    All fans in the same refrigerant circuit are controlled by asingle speed variator and therefore all run at the same speed.

    In the cooling mode, the full-load or part-load speed iscontrolled by a patented algorithm that permanentlyoptimises the condensing temperature to ensure the bestunit energy efficiency (EER) whatever the operatingconditions and pressure drops of the system ductwork.

    In the heating mode, the full-load or part-load speed ofeach circuit is fixed and at the configured maximum (rangeconfigurable from 13.3 r/s to 19 r/s) based on the constraintsand characteristics of the installation site. The maximumconfigured speed applies to both the heating and coolingmode.

  • 7/25/2019 TP3 toplotna pumpa

    6/24

    6

    Operating conditions

    Curve No. Outsidetemperature,

    C

    Entering watertemperature,

    C

    Leaving watertemperature,

    C

    Load%

    1 25 15 10 100

    2 25 10 5 100

    3 Eurovent 35 12 7 100

    4 45 15 10 100

    5 45 10 5 100

    The unit heating capacity and energy efficiency ratio(COP) in the heating mode vary depending on the ductpressure drops:- there is no reduction in the unit heating capacity and the

    COP compared to a standard unit,- in the heating mode the fan speed is fixed and 19 r/s

    maximum, and allows maintaining or even increasingthe performances and the COP.

    Sound power level at the discharge duct outlet for circuits A and B of the 30RQ units

    30RQ 182 202 232 262 302 342 372 402 432 462 522

    Sound power level 10-12W dB(A) 93 93 93 93 94 94 95 95 95,5 96 96

    Physical data, 30RQ units with partial heat reclaim

    30RQ - partial heat reclaim mode 182 202 232 262 302 342 372 402 432 462 522

    Cooling capacity* kW 176 190 221 256 280 310 334 370 394 437 472

    Heating capacity reclaimed at the desuperheater

    in cooling mode*

    kW 49 68 70 104 108 126 157 153 140 151 174

    Unit power input* kW 61 72 77 100 105 125 126 147 150 166 194

    Energy eciency ratio* kW/kW 2,90 2,65 2,89 2,56 2,67 2,49 2,65 2,52 2,62 2.63 2.43

    Heating capacity, air heat exchanger +

    desuperheater in heating mode**

    kW 190 213 230 284 302 335 366 407 445 505 551

    Operating weight***

    Standard unit + desuperheater option kg 2180 2330 2340 2510 3140 3330 3340 3560 4140 4300 4520

    Unit with options 15 and desuperheater kg 2250 2500 2530 2700 3380 3570 3650 3820 4440 4530 4830

    Unit with options 15 and desuperheater +

    hydronic module with dual high-pressure pump

    kg 2600 2740 2770 2950 3580 3780 3870 4040 4650 4770 5110

    Desuperheater in circuits A/B Plate heat exchanger

    Water volume circuit A l 2 2 3.75 3.75 5.5 5.5 7.5 7.5 7.5 7.5 7.5

    Water volume circuit B l 3.5 3.5 3.75 3.75 3.75 3.75 3.5 3.5 5.5 5.5 7.5

    Max. water-side operating pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

    Water connections Cylindrical male gas thread

    Connection in 2 2 2 2 2 2 2 2 2 2 2

    Outside diameter mm 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3

    * Nominal conditions: Water heat exchanger entering and leaving water temperature 12C/7C, desuperheater entering and leaving water temperature 50C/60C, outside air temperature 35C Gross performances, not in accordance with EN14511-3:2011. These performances do not take into account the correction for the proportional heating capacity and power input generated by the

    water pump to overcome the internal pressure drop in the heat exchanger. ** Nominal conditions: Air heat exchanger entering and leaving water temperature 40C/45C, desuperheater entering and leaving water temperature 50C/60C, outside air temperature 7C/87% rh Gross performances, not in accordance with EN14511-3:2011. These performances do not take into account the correction for the proportional heating capacity and power input generated by the

    water pump to overcome the internal pressure drop in the heat exchanger. *** Weights shown are a guideline only.

    Partial heat reclaim using desuperheaters (option 49)

    This option permits the production of free hot water usingheat reclaim by desuperheating the compressor discharge

    gases. The option is available for the whole 30RQ range.

    A plate heat exchanger is installed in series with the airheat exchanger coils on the compressor discharge line of

    each circuit.

    Nominal and maximum air flows per circuit

    30RQ Nominal/maximum air ow, l/s

    Circuit A Circuit B

    182-262 9030/11110 9030/11110

    302-342 13540/16670 9030/11110

    372-402 18060/22220 9030/11110

    432 18060/22220 13540/16670

    462-522 18060/22220 18060/22220

    Units with fans with available pressure for indoor installation(option 12) - continued

  • 7/25/2019 TP3 toplotna pumpa

    7/24

    7

    Hydronic module (option 116)

    Typical hydronic circuit diagram

    Legend

    Components of unit and hydronic module1 Victaulic screen lter2 Expansion tank3 Safety valve4 Available pressure pump5 Pressure tap valve6 Pressure gauge to measure the component pressure loss option7 System vent valve, pressure gauge8 Drain valve9 Water ow control valve option10 Heat exchanger11 Water heat exchanger heater option12 Hydronic module heater option13 Air vent water heat exchanger

    14 Water purge water heat exchanger16 Flow switch17 Water temperature sensor

    System components18 Air vent19 Flexible connection20 Shutdown valves21 Charge valve Hydronic module units with hydronic module

    Notes With option 42A the unit hydronic module is protected against frost by electric heaters The unit water heat exchanger must be protected against frost antifreeze solution or

    optional electric heater

    Hydronic module

    1

    2

    3

    4

    5

    5

    6

    7

    9

    20

    19

    21

    12

    1212

    14

    13

    16

    55 8

    18

    17

    17

    19

    10

    11

    20

    The hydronic module option saves a lot of installation time.The heat pump is factory-equipped with the main componentsfor the hydronic system: screen filter, water pump, expansiontank, safety valve and water flow control valve (option).

    Several water pump types are available to suit any application:

    primary single or dual low-pressure pump or single or dualhigh-pressure pump (30RQ 182-522).

    An automatic pump start-up algorithm protects the heatexchanger and the hydronic module piping against frostdown to -10C outside temperature, if the evaporator frostprotection option is installed. If necessary increased frostprotection down to -20C is possible by adding the heateroption to the hydronic module piping (see options 41 and42A).

    The hydronic module option is integrated into the heatpump without increasing its dimensions and saves the spacenormally used for the water pump.

    Electrical data, units with hydronic modules

    The pumps that are factory-installed in these units havemotors with efficiency class IE2. The additional electricaldata required by regulation 640/2009 is given in theinstallation, operation and maintenance manual.

    This regulation concerns the application of directive2005/32/EC on the eco-design requirements for electricmotors.

  • 7/25/2019 TP3 toplotna pumpa

    8/24

    8

    Physical data30RQ 182-262 B standard units

    30RQ 182 202 232 262

    Air conditioning application as per EN14511-3:2011*

    Nominal cooling capacity kW 177 198 217 250

    EER kW/kW 2.93 2.70 2.84 2.62

    Eurovent class, cooling B C C D

    ESEER kW/kW 3.97 3.68 4.18 3.67Air conditioning application**

    Nominal cooling capacity kW 178 199 217 251

    EER kW/kW 2.98 2.75 2.89 2.66

    ESEER kW/kW 4.16 3.83 4.38 3.84

    Heating application as per EN14511-3:2011*

    Nominal heating capacity kW 184 205 221 268

    COP kW/kW 2.85 2.83 2.98 2.85

    Eurovent class, heating C C C C

    Heating application**

    Nominal heating capacity kW 184 205 221 267

    COP kW/kW 2.88 2.85 3.00 2.87

    Operating weight***

    Standard unit with option 15 and hydronic module with dualhigh-pressure pump

    kg 1934 2036 2099 2299

    Standard unit with option 15 kg 1758 1860 1915 2115

    Standard unit without option**** kg 1683 1785 1820 2020

    Sound levels

    Unit with option 15 (low noise level)

    Sound power level 10-12W dB(A) 89 89 89 89

    Sound pressure level at 10 m distance dB(A) 57 57 57 57

    Unit without option 15 and without hydronic module

    Sound power level 10-12W dB(A) 91 91 91 91

    Sound pressure level at 10 m distance dB(A) 59 59 59 59

    Dimensions

    Length x depth x height mm 2457 x 2253 x 2297 2457 x 2253 x 2297 2457 x 2253 x 2297 2457 x 2253 x 2297

    Compressors Hermetic scroll 48.3 r/s

    Circuit A 1 1 2 2

    Circuit B 2 2 2 2

    Number of capacity stages 3 3 4 4

    Refrigerant R410A

    Circuit A kg 25.8 25.8 26.3 26.3Circuit B kg 27.7 27.7 26.3 26.3

    Control Pro-Dialog Plus

    Minimum capacity % 28 33 25 25

    Air heat exchangers Grooved copper tubes and aluminium ns

    Fans Axial Flying Bird 4 with rotating shroud

    Quantity 4 4 4 4

    Total air ow l/s 18056 18056 18056 18056

    Speed r/s 15.7 15.7 15.7 15.7

    Water heat exchanger Twin-circuit plate heat exchanger

    Water volume l 10.76 12.64 16.69 21.2

    Max. water-side operating pressure without hydronic module kPa 1000 1000 1000 1000

    Hydronic module (option) Pump, Victaulic screen lter, safety valve, expansion tank, pressure gauge, purge valves(water and air) and water ow control valve

    Water pump Centrifugal, monocell, 48,3 r/s, low or high pressure (as required), single or dual pump

    Quantity 1 1 1 1Expansion tank volume l 50 50 50 50

    Max. water-side operating pressure with hydronic module kPa 400 400 400 400

    Water connections, unit without hydronic module Victaulic

    Connections inch 2 1/2 2 1/2 2 1/2 2 1/2

    Outside diameter mm 76.1 76.1 76.1 76.1

    Water connections, unit with hydronic module Victaulic

    Connections inch 3 3 3 3

    Outside diameter mm 88.9 88.9 88.9 88.9

    Chassis paint colour Colour code: RAL 7035

    * Eurovent-certied performances in accordance with standard EN14511-3:2011. Cooling mode conditions: evaporator water entering/leaving temperature 12C/7C, outside air temperature 35C, evaporator fouling factor 0 m2K/W Heating mode conditions: water heat exchanger water entering/leaving temperature 40C/45C, outside air temperature 7C, rh= 87%, water heat exchanger fouling factor 0 m2K/W ** Gross performances, not in accordance with EN14511-3:2011. These performances do not take into account the correction for the proportional heating capacity and power input generated by the

    water pump to overcome the internal pressure drop in the heat exchanger. Cooling mode conditions: evaporator water entering/leaving temperature 12C/7C, outside air temperature 35C, evaporator fouling factor 0 m2K/W Heating mode conditions: water heat exchanger water entering/leaving temperature 40C/45C, outside air temperature 7C, rh= 87%, water heat exchanger fouling factor 0 m2K/W *** Weight shown is a guideline only. To nd out the unit refrigerant charge, please refer to the unit nameplate.

    **** Standard unit = base unit without Euro Pack and hydronic module options. In accordance with ISO 9614-1 and certied by Eurovent. Average sound pressure level, unit in a free eld on a reective surface.

  • 7/25/2019 TP3 toplotna pumpa

    9/24

    9

    Physical data30RQ 182-262 B units with options 280 and 30RQ 302-522 units

    30RQ 182 202 232 262 302 342 372 402 432 462 522

    Air conditioning application as per EN14511-3:2011*

    Nominal cooling capacity kW 175 190 220 255 279 309 333 368 392 435 470

    EER kW/kW 2.88 2.62 2.86 2.54 2.63 2.46 2.63 2.49 2.59 2.59 2.40

    Eurovent class, cooling C D C D D E D E D D E

    ESEER kW/kW 3.95 3.61 4.24 3.86 4.03 3.75 3.50 3.54 3.61 3.43 3.25Air conditioning application**

    Nominal cooling capacity kW 176 190 221 256 280 310 334 370 394 437 472

    EER kW/kW 2.90 2.65 2.89 2.56 2.67 2.49 2.65 2.52 2.62 2.63 2.43

    ESEER kW/kW 4.05 3.69 4.39 4.00 4.20 3.87 3.60 3.66 3.75 3.58 3.40

    Heating application as per EN14511-3:2011*

    Nominal heating capacity kW 190 214 231 285 303 336 367 408 446 507 554

    COP kW/kW 3.00 2.86 2.97 2.94 2.73 2.79 2.84 2.74 2.79 2.79 2.72

    Eurovent class, heating B C C C D D C D D D D

    Heating application**

    Nominal heating capacity kW 190 213 230 284 302 335 366 407 445 505 551

    COP kW/kW 3.01 2.87 2.99 2.96 2.75 2.81 2.86 2.75 2.81 2.81 2.74

    Operating weight***

    Standard unit with option 15 and hydronic module withdual high-pressure pump

    kg 2276 2367 2406 2588 3221 3408 3535 3689 4142 4449 4666

    Standard unit with option 15 kg 2160 2191 2222 2404 2919 3103 3213 3367 3820 4077 4251

    Standard unit without option**** kg 2025 2116 2127 2309 2799 2986 3079 3233 3669 3909 4083

    Sound levels

    Unit with option 15 (low noise level)

    Sound power level 10 -12W dB(A) 89 89 89 89 90 90 91 91 92 92 92

    Sound pressure level at 10 m distance dB(A) 57 57 57 57 58 58 59 59 60 60 60

    Unit without option 15 and without hydronic module

    Sound power level 10-12W dB(A) 91 91 91 91 92 92 93 93 94 94 94

    Sound pressure level at 10 m distance dB(A) 59 59 59 59 60 60 61 61 62 62 52

    Dimensions

    Length x depth x height mm 2457 x 2253 x 2297 3604 x 2253 x 2297 4798 x 2253 x 2297

    Compressors Hermetic scroll 48.3 r/s

    Circuit A 1 1 2 2 3 3 4 4 4 4 4

    Circuit B 2 2 2 2 2 2 2 2 3 4 4

    Number of capacity stages 3 3 4 4 5 5 6 6 7 8 8

    Refrigerant R410A

    Circuit A kg 27 27 27 27 41 41 53 54 54 53 54Circuit B kg 27 27 27 27 27 27 32 32 47 53 53

    Control Pro-Dialog Plus

    Minimum capacity % 28 33 25 25 18 20 15 17 13 11 13

    Air heat exchangers Grooved copper tubes and aluminium ns

    Fans Axial Flying Bird 4 with rotating shroud

    Quantity 4 4 4 4 5 5 6 6 7 8 8

    Total air ow l/s 18056 18056 18056 18056 22569 22569 27083 27083 31597 36111 36111

    Speed r/s 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15,7 15,7

    Water heat exchanger Direct-expansion twin-circuit. shell-and-tube heat exchanger

    Water volume l 110 110 110 110 110 125 113 113 113 113 113

    Max. water-side operating pressure without hydronic

    module

    kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

    Hydronic module (option) Pump, Victaulic screen lter, safety valve, expansion tank, pressure gauge, purge valves (water and

    air) and water ow control valve

    Water pump Centrifugal, monocell, 48,3 r/s, low or high pressure (as required), single or dual pump

    Quantity 1 1 1 1 1 1 1 1 1 1 1Expansion tank volume l 50 50 50 50 80 80 80 80 80 80 80

    Max. water-side operating pressure with hydronic

    module

    kPa 400 400 400 400 400 400 400 400 400 400 400

    Water connections, unit without hydronic module Victaulic

    Connections inch 3 3 3 3 4 4 6 6 6 6 6

    Outside diameter mm 88.9 88.9 88.9 88.9 114.3 114.3 168.3 168.3 168.3 168,3 168,3

    Water connections, unit with hydronic module Victaulic

    Connections inch 3 3 3 3 4 4 4 4 5 5 5

    Outside diameter mm 88.9 88.9 88.9 88.9 114.3 114.3 139.7 139.7 139.7 139,7 139,7

    Chassis paint colour Colour code: RAL 7035

    * Eurovent-certied performances in accordance with standard EN14511-3:2011. Cooling mode conditions: evaporator water entering/leaving temperature 12C/7C, outside air temperature 35C, evaporator fouling factor 0 m2K/W Heating mode conditions: water heat exchanger water entering/leaving temperature 40C/45C, outside air temperature 7C, rh= 87%, water heat exchanger fouling factor 0 m2K/W ** Gross performances, not in accordance with EN14511-3:2011. These performances do not take into account the correction for the proportional heating capacity and power input generated by the

    water pump to overcome the internal pressure drop in the heat exchanger. Cooling mode conditions: evaporator water entering/leaving temperature 12C/7C, outside air temperature 35C, evaporator fouling factor 0 m2K/W Heating mode conditions: water heat exchanger water entering/leaving temperature 40C/45C, outside air temperature 7C, rh= 87%, water heat exchanger fouling factor 0 m2K/W *** Weight shown is a guideline only. To nd out the unit refrigerant charge, please refer to the unit nameplate.**** Standard unit = base unit without Euro Pack and hydronic module options. In accordance with ISO 9614-1 and certied by Eurovent. Average sound pressure level, unit in a free eld on a reective surface.

  • 7/25/2019 TP3 toplotna pumpa

    10/24

    10

    Electrical data30RQ 182-262 "B" standards units and units with option 280, and 30RQ 302-522 units

    30RQ 182 202 232 262 302 342 372 402 432 462 522

    Power circuit

    Nominal power supply V-ph-Hz 400-3-50

    Voltage range V 360-440

    Control circuit supply 24 V, via internal transformer

    Nominal unit current draw*Circuit A + B (one power supply) A 113 129 135 167 185 209 219 251 269 302 334

    Maximum unit power input**

    Circuit A + B (one power supply) kW 85 98 102 127 140 159 166 191 204 229 255

    Unit power factor at max. capacity** 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84

    Maximum unit current draw (Un-10%)***

    Circuit A + B (one power supply) A 159 183 191 239 263 299 311 359 383 430 478

    Maximum unit current draw (Un)****

    Circuit A + B (one power supply) A 146 168 175 219 241 274 285 329 351 394 438

    Max. start-up current, standard unit (Un)

    Circuit A + B A 353 375 348 426 448 481 492 536 558 601 645

    Max. start-up current, unit with soft starter (Un)

    Circuit A + B A 283 305 323 356 378 411 433 466 489 521 575

    * Standardised Eurovent conditions: water heat exchanger entering/leaving water temperature 12C/7C, outside air temperature 35C ** Power input of the compressor(s) + fan(s) at maximum unit operating conditions saturated suction temperature 10C, saturated condensing temperature 65C at 400 V nominal voltage (Values

    given on the unit name plate). *** Maximum unit operating current at maximum unit power input and 360 V.

    **** Maximum unit operating current at maximum unit power input and 400 V (Values given on the unit name plate). Maximum instantaneous starting current at operating limit values (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor).

    Fan motor electrical data: current draw used in the tables above units at Eurovent conditions and 50C ambient air temperature around the motor at 400 V: 3.8 A, start-up current 20 A, powerinput 1.75 kW. These values are indicated on the motor name plate.

    Short-circuit stability current (TN system*)

    30RQ 182 202 232 262 302 342 372 402 432 462 522

    Unit without main disconnect (except 30RQ 182 to 262 that have the disconnect installed as standard)

    With fuses upstream - maximum fuse values assigned (gL/gG)

    Circuits A and B A - - - - 500 500 500 500 630/500 630/500 630/500

    With fuses upstream - admissible rms current value (gL/gG)

    Circuits A and B kA - - - - 70 70 70 70 60/70 60/70 60/70

    Unit with optional main disconnect without fuse (standard for 30RQ 182 to 262 and optional for 30RQ 302 to 522)

    Short-time assigned current lcw** (1s) rms value/peak lpk***

    Circuits A and B kA/kA 9/26 9/26 9/26 9/26 13/26 13/26 13/26 13/26 15/30 15/30 15/30

    With fuses upstream - maximum fuse values assigned (gL/gG)

    Circuits A and B A 200 200 200/250 250/315 250/315 400 400 400 500 630 630With fuses upstream - conditional short-circuit assigned current Icc/Icf

    Circuits A and B kA 50 50 50 50 50 50 50 50 50 50 50

    Unit with optional main disconnect with fuse (not available for 30RQ 182 to 262 and optional for 30RQ 302 to 522)

    Short-circuit stability current Icc/Icf increased with fuses - maximum fuse values assigned (gL/gG)

    Circuits A and B kA - - - - 315 315 400 400 400 630 630

    Short-circuit stability current Icc/Icf increased with fuses - admissible rms current value (gL/gG)

    Circuits A and B kA - - - - 50 50 50 50 50 50 50

    * Type of system earthing ** Icw: assigned short-time current *** Ipk: assigned current, admissible peak

    Icc/Icf: assigned conditional short-circuit current

    IT system: The short circuit current stability values given above for the TN system are also valid for IT for units 30RQ 302 to 522. For units 30RQ 182-262 modications are required.

  • 7/25/2019 TP3 toplotna pumpa

    11/24

    11

    Electrical data notes for 30RQ units: 30RQ 182-522 units have a single power connection point. The control box includes the following standard features:

    - a main disconnect switch

    - starter and motor protection devices for each compressor, the fan(s) andthe pump

    - control devices

    Field connections: All connections to the system and the electrical installations must be in full

    accordance with all applicable local codes. The Carrier 30RQ units are designed and built to ensure conformance with

    these codes. The recommendations of European standard EN 60 204-1

    (corresponds to IEC 60204-1) (machine safety - electrical machine components- part 1: general regulations) are specically taken into account, when designing

    the electrical equipment.

    Electrical reserves: Circuit A has disconnect switches and branch sections, designed to supply the

    water heat exchanger pump power input.

    IMPORTANT:

    Generally the recommendations of IEC 60364 are accepted as compliance

    with the requirements of the installation directives. Conformance with EN 60204is the best means of ensuring compliance with the Machines Directive 1.5.1.

    Annex B of EN 60204-1 describes the electrical characteristics used for theoperation of the machines.

    1. The operating environment for the 30RQ units is specied below:

    Environment* - Environment as classied in EN 60721 (corresponds to IEC

    60721): - outdoor installation*

    - ambient temperature range: -20C to +48C 1 K, class 4K3*

    - altitude: 2000 m (for hydronic kit see chapter 5.3 of the installation manual)

    - presence of hard solids, class 4S2 (no signicant dust present)

    - presence of corrosive and polluting substances, class 4C2 (negligible) - vibration and shock, class 4M2

    Competence of personnel, class BA4* (trained personnel - IEC 60364)

    2. Power supply frequency variation: 2 Hz.3. The neutral (N) line must not be connected directly to the unit (if necessary use

    a transformer).

    4. Overcurrent protection of the power supply conductors is not provided with the

    unit.5. The factory-installed disconnect switch/circuit breaker is of a type suitable for

    power interruption in accordance with EN 60947-3 (corresponds to IEC 60947-3).6. The units are designed for simplied connection on TN(s) networks (IEC 60364).

    For IT networks derived currents may interfere with network monitoring elements,and it is recommended to create an IT type divider for the system units that

    require this and/or a TN type divider for Carrier units. Please consult the

    appropriate local organisations to dene the monitoring and protection elementsand to complete the electrical installation.

    7. 30RQ units comply with the requirements of general standard EN 61000-6-3

    (residential, commercial and light industrial applications).

    NOTE: If particular aspects of an actual installation do not conform to

    the conditions described above, or if there are other conditions whichshould be considered, always contact your local Carrier representative.

    * The required protection level for this class is IP43B (according to referencedocument IEC 60529). All 30RQ units are protected to IP44CW and full this

    protection condition.

  • 7/25/2019 TP3 toplotna pumpa

    12/24

    12

    Part load performancesWith the rapid increase in energy costs and the care aboutenvironmental impacts of electricity production, the powerconsumption of air conditioning equipment has becomean important topic. The energy efficiency of a unit at fullload is rarely representative of the actual performance of theunits, as on average a unit works less than 5% of the time

    at full load.IPLV (in accordance with AHRI 550/590)

    The IPLV (integrated part load value) allows evaluationof the average energy efficiency based on four operatingconditions defined by the AHRI (Air Conditioning, Heatingand Refrigeration Institute). The IPLV is the averageweighted value of the energy efficiency ratios (EER) atdifferent operating conditions, weighted by the operatingtime.

    IPLV (integrated part load value)

    Load % Air temperature C Energy eciency Operating time %

    100 35 EER1

    1

    75 26.7 EER2

    42

    50 18.3 EER3

    45

    25 12.8 EER4

    12

    ESEER = EER1x 1% + EER

    2x 42% + EER

    3x 45% + EER

    4x 12%

    The heat load of a building depends on many factors, suchas the outside air temperature, the exposure to the sunand the building occupancy.

    Consequently it is preferable to use the average energyefficiency, calculated at several operating points that are

    representative for the unit utilisation.ESEER (in accordance with EUROVENT)

    The ESEER (European seasonal energy efficiency ratio)permits evaluation of the average energy efficiency at partload, based on four operating conditions defined byEurovent. The ESEER is the average value of energyefficiency ratios (EER) at different operating conditions,weighted by the operating time.

    ESEER (European seasonal energy efficiency ratio)

    Load % Air temperature C Energy eciency Operating time %

    100 35 EER1

    3

    75 30 EER2

    33

    50 25 EER3

    41

    25 20 EER4 23

    ESEER = EER1x 3% + EER

    2x 33% + EER

    3x 41% + EER

    4x 23%

    Part load performances

    30RQ 182-262 B standard units

    30RQ 182 202 232 262

    IPLV kW/kW 4.60 4.22 4.86 4.20

    ESEER kW/kW 3.97 3.68 4.18 3.67

    30RQ 182-262 B units with option 280 and 30RQ 302-522 units

    30RQ 182 202 232 262 302 342 372 402 432 462 522

    IPLV kW/kW 4.48 4.06 4.86 4.40 4.77 4.33 4.12 4.11 4.21 4.09 3.85

    ESEER kW/kW 3.95 3.61 4.24 3.86 4.03 3.75 3.50 3.54 3.61 3.43 3.25

    ESEER Calculations according to standard performances (in accordance with EN14511-3:2011) and certied by Eurovent. IPLV Calculations according to standard performances (in accordance with AHRI 550-590).

    30RQ 182-262 "B" standard units

    Octave bands, Hz Sound powerlevels125 250 500 1k 2k 4k

    182 dB 92 90 89 86 81 75 dB(A) 91

    202 dB 92 90 89 86 81 75 dB(A) 91

    232 dB 93 90 90 86 82 75 dB(A) 91

    262 dB 93 90 90 86 82 75 dB(A) 91

    30RQ 182-262 "B" units with option 280 and 30RB 302-522 units

    Octave bands, Hz Sound powerlevels125 250 500 1k 2k 4k

    182 dB 92 90 89 86 81 75 dB(A) 91

    202 dB 92 90 89 86 81 75 dB(A) 91

    232 dB 93 90 90 86 82 75 dB(A) 91

    262 dB 93 90 90 86 82 75 dB(A) 91

    302 dB 94 91 91 87 83 76 dB(A) 92

    342 dB 94 91 91 87 83 76 dB(A) 92

    372 dB 94 92 92 88 83 77 dB(A) 93

    402 dB 94 92 92 88 83 77 dB(A) 93

    432 dB 95 92 93 88 84 78 dB(A) 94

    462 dB 96 93 93 89 85 78 dB(A) 94

    522 dB 96 93 93 89 85 78 dB(A) 94

    Sound spectrum

  • 7/25/2019 TP3 toplotna pumpa

    13/24

    13

    Operating limitsWater heat exchanger water flow rate

    30RQ 182-262 B standard units

    30RQ Min. water ow, l/s Max. water ow*, l/s

    182 2.8 13.0

    202 2.8 14.3

    232 3.0 16.3

    262 3.5 18.0

    30RQ 182-262 B units with option 280 and 30RQ302-522 units

    30RQ Min. water ow, l/s Max. water ow*, l/s

    182 2.8 26.7

    202 2.8 26.7

    232 3.0 26.7

    262 3.5 26.7

    302 3.9 26.7

    342 4.4 29.4

    372 4.9 31.1

    402 5.2 31.1

    432 5.8 31.1462 6.1 31.1

    522 6.9 31.1

    * Maximum ow rate for a heat exchanger pressure drop of 100 kPa heat exchanger withouthydronic module

    EnteringairtemperatureC

    Leaving water temperature C

    EnteringairtemperatureC

    Leaving water temperature C

    Minimum and maximum temperatures

    Cooling mode

    Water heat exchanger (evaporator) Minimum Maximum

    Entering water temperature at start-up C 6.8* 30

    Leaving water temperature during operation C 5 15

    Entering water temperature at shut-down C - 60

    Air heat exchanger (condenser)**

    Air entering temperature C 0 46

    Available static pressure

    Standard unit (for outdoor installation) Pa 0 0

    Unit with option 12 (for indoor installation) Pa 0*** 200

    Heating mode

    Water heat exchanger (condenser) Minimum Maximum

    Entering water temperature at start-up C 8 45

    Leaving water temperature during operation C 20 50

    Entering water temperature at shut-down C 3 60

    Air heat exchanger (evaporator)

    Air entering temperature** C -10 35

    Available static pressure

    Standard unit (for outdoor installation) Pa 0 0

    Unit with option 12 (for indoor installation) Pa 0*** 200

    * For an application that requires operation below a minimum of 6.8C, please contact Carrier. ** For operation down to -20C the unit must be equipped with option 28 (winter operation). In

    addition the unit must either be equipped with the frost protection option or the water loopmust be protected by the installer by adding a frost protection solution.

    Maximum outside temperatures: During storage and transport the minimum and maximumtemperatures must not exceed -20C and +48C. It is recommended to observe thesetemperatures during transport by container.

    *** Unit with option 12 with fans with available pressure up to 200 Pa.

    Note:Do not exceed the maximum operating temperature.

    Note: Water heat exchanger and air heat exchanger t = 5 K

    Operating range, standard unit Operating range, unit equipped with option 28 (winter operation). In addition the unit musteither be equipped with the frost protection option for the water heat exchanger and thehydronic module (if used), or the water loop must be protected against frost by the installer,using an anti-freeze solution.

    Operating range cooling mode Operating range heating mode

  • 7/25/2019 TP3 toplotna pumpa

    14/24

    14

    0

    25

    50

    75

    100

    125

    150

    175

    200

    3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33

    Available static system pressureLow-pressure pump (hydronic module option) High-pressure pump (hydronic module option)

    Availablestaticpressure,kP

    a

    Availablestaticpressure,kP

    a

    Legend1 30RQ 1822622 30RQ 3023 30RQ 3424 30RQ 3724325 30RQ 462522

    Legend1 30RQ 1822022 30RQ 2322623 30RQ 3024 30RQ 3425 30RQ 3724326 30RQ 462522

    Water ow rate, l/sWater ow rate, l/s

    50

    75

    100

    125

    150

    175

    200

    225

    250

    275

    300

    325

    350

    375

    400

    3 5 7 9 11 1 3 15 1 7 19 2 1 23 2 5 27 2 9 31 3 3

    Water loop water volumeMinimum volume

    The minimum water loop volume for air conditioningapplications can be determined using the followingformula: Volume (l) = CAP (kW) x 2.5.

    Volume = Water loop volume with closed water controlvalves

    CAP = Cooling capacity at the selection conditions

    Maximum volume

    Units with hydronic option are equipped with an expansiontank. The expansion tank is sized for the maximum watervolume below.

    Max. water loop volume, l

    30RQ 182-262 302 - 522

    Static pressure (bar) 1 2 2.5 1 2 2.5

    Pure water 2400 1600 1200 3960 2640 1980

    10% ethylene glycol 1800 1200 900 2940 1960 1470

    20% ethylene glycol 1320 880 660 2100 1400 1050

    30% ethylene glycol 1080 720 540 1740 1160 870

    40% ethylene glycol 900 600 450 1500 1000 750

    Instantaneous heatingcapacity

    Heating capacity at low outdoor temperature

    The published heating capacities are instantaneous

    capacities. They do not take account of the decrease of theheating capacity, resulting from the formation of frost onthe coil and the effect of the defrost cycles. The integratedheating capacity takes these effects into account. Theydepend on the temperature and the relative humidity (rh)of the outdoor air.

    Correction factor to obtain integrated heating capacitiesRelative humidity: 90%

    LWT Air temperature, C

    C -10 -5 0 5 7

    25 0.87 0.88 0.9 0.92 1

    35 0.84 0.86 0.88 0.90 1

    40 0.83 0.84 0.86 0.88 1

    45 0.80 0.82 0.84 0.86 1

    50 0.79 0.80 0.82 0.84 1LWT Leaving water temperature

    Note The Carrier electronic selection program permits calculating the integrated heatingcapacity as a function of the actual humidity conditions at the installation site Contact Carrierfor your personalised heat pump selection

  • 7/25/2019 TP3 toplotna pumpa

    15/24

    15

    Dimensions/clearances30RQ 182-262 B standard units

    For user control connection

    Power connection

    Unit with hydronic module

    Unit without hydronic module

    Legend:

    All dimensions are given in mm.

    Required clearances for maintenance and air ow

    Recommended space for water heat exchanger tube removal

    Recommended space for heat exchanger removal

    Water inlet

    Water outlet

    Air outlet, do not obstruct

    Note: Drawings are not contractually binding. Before designingan installation, consult the certied dimensional drawings,

    available on request.

  • 7/25/2019 TP3 toplotna pumpa

    16/24

    16

    Dimensions/clearances30RQ 182-262 B units with option 280

    Power connectionUnit with hydronic module

    Unit without hydronic module

    For user control connection

    Legend:

    All dimensions are given in mm.

    Required clearances for maintenance andair ow

    Recommended space for water heatexchanger tube removal

    Recommended space for heat exchanger

    removal

    Water inlet

    Water outlet

    Air outlet, do not obstruct

    Note: Drawings are not contractually binding. Before

    designing an installation, consult the certieddimensional drawings, available on request.

  • 7/25/2019 TP3 toplotna pumpa

    17/24

    17

    Dimensions/clearances30RQ 302-522

    30RQ X Y

    302-402 3604 200

    432-522 4798 0

    Unit without hydronic module

    Power connection

    For user control connection

    Unit with hydronic module

    Note: Drawings are not contractually binding. Before designing an installation,

    consult the certied dimensional drawings, available on request.

    Legend:

    All dimensions are given in mm.

    Required clearances for maintenance and

    air ow

    Recommended space for water heatexchanger tube removal

    Recommended space for heat exchanger

    removal

    Water inlet

    Water outlet

    Air outlet, do not obstruct

  • 7/25/2019 TP3 toplotna pumpa

    18/24

    18

    Cooling capacities in accordance with EN14511-3 : 2011

    Cooling capacities

    30RQ 182-262 B standard units

    Condenser entering air temperature, C

    20 25 30 35 40 46

    LWT Qc EER q p Qc EER q p Qc EER q p Qc EER q p Qc EER q p Qc EER q p

    C kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa

    182 5 192 4.15 9.0 57 183 3.66 8.6 52 174 3.20 8.1 47 164 2.77 7.7 43 153 2.37 7.1 38 138 1.93 6.5 32

    202 215 3.83 9.7 55 205 3.38 9.3 50 194 2.95 8.8 46 183 2.55 8.3 41 170 2.18 7.7 36 154 1.78 7.0 30

    232 237 4.10 11.3 55 226 3.60 10.8 51 215 3.14 10.2 46 202 2.71 9.6 42 188 2.32 9.0 37 170 1.88 8.1 31

    262 273 3.75 12.6 58 260 3.30 12.0 53 247 2.88 11.4 48 231 2.49 10.7 43 215 2.13 9.9 38 195 1.75 9.0 32

    182 7 207 4.37 9.7 64 197 3.85 9.2 58 187 3.36 8.7 53 176 2.91 8.2 48 164 2.50 7.7 42 148 2.04 6.9 35

    202 230 4.00 10.5 61 219 3.52 10.0 56 208 3.08 9.4 51 196 2.69 8.9 46 183 2.31 8.3 41 166 1.88 7.5 34

    232 252 4.26 12.0 61 240 3.74 11.5 56 228 3.27 10.9 51 214 2.82 10.2 46 199 2.40 9.5 40 179 1.95 8.6 34

    262 291 3.89 13.4 64 278 3.43 12.9 59 265 3.00 12.2 54 248 2.60 11.5 48 231 2.23 10.7 43 210 1.83 9.7 36

    182 10 228 4.66 10.7 74 218 4.12 10.2 68 207 3.62 9.7 62 195 3.14 9.1 56 181 2.69 8.5 50 164 2.20 7.7 41

    202 255 4.27 11.6 72 243 3.78 11.1 66 231 3.31 10.5 60 217 2.87 9.9 54 202 2.46 9.2 48 183 2.02 8.3 40

    232 277 4.50 13.3 71 265 3.97 12.7 65 251 3.47 12.0 59 236 3.00 11.3 53 219 2.57 10.5 47 198 2.09 9.5 39

    262 316 4.04 14.6 73 301 3.57 13.9 67 286 3.13 13.2 61 269 2.73 12.4 55 252 2.35 11.6 49 178 2.11 8.2 27

    30RQ 182-262 B standard units

    Condenser entering air temperature, C

    20 25 30 35 40 46LWT Qc EER q p Qc EER q p Qc EER q p Qc EER q p Qc EER q p Qc EER q p

    C kW kW/kW

    l/s kPa kW kW/kW

    l/s kPa kW kW/kW

    l/s kPa kW kW/kW

    l/s kPa kW kW/kW

    l/s kPa kW kW/kW

    l/s kPa

    182 5 193 4.26 9.0 57 184 3.74 8.6 52 175 3.26 8.1 47 165 2.82 7.7 43 153 2.40 7.1 38 139 1.95 6.5 32

    202 216 3.91 9.7 55 206 3.45 9.3 50 195 3.00 8.8 46 184 2.59 8.3 41 171 2.21 7.7 36 155 1.80 7.0 30

    232 238 4.20 11.3 55 227 3.68 10.8 51 216 3.20 10.2 46 203 2.75 9.6 42 189 2.35 9.0 37 171 1.90 8.1 31

    262 274 3.84 12.6 58 261 3.37 12.0 53 248 2.93 11.4 48 232 2.53 10.7 43 216 2.16 9.9 38 196 1.76 9.0 32

    182 7 208 4.50 9.7 64 198 3.95 9.2 58 187 3.44 8.7 53 176 2.97 8.2 48 165 2.54 7.7 42 149 2.07 6.9 35

    202 231 4.10 10.5 61 220 3.60 10.0 56 209 3.14 9.4 51 197 2.74 8.9 46 184 2.34 8.3 41 166 1.90 7.5 34

    232 253 4.37 12.0 61 242 3.83 11.5 56 229 3.33 10.9 51 215 2.87 10.2 46 200 2.44 9.5 40 180 1.97 8.6 34

    262 293 3.99 13.4 64 280 3.51 12.9 59 266 3.06 12.2 54 249 2.64 11.5 48 232 2.26 10.7 43 211 1.85 9.7 36

    182 10 229 4.82 10.7 74 219 4.24 10.2 68 208 3.71 9.7 62 196 3.21 9.1 56 182 2.74 8.5 50 165 2.23 7.7 41

    202 256 4.40 11.6 72 244 3.87 11.1 66 232 3.38 10.5 60 218 2.92 9.9 54 202 2.50 9.2 48 183 2.05 8.3 40

    232 279 4.64 13.3 71 266 4.08 12.7 65 253 3.55 12.0 59 237 3.06 11.3 53 220 2.61 10.5 47 199 2.11 9.5 39

    262 318 4.16 14.6 73 303 3.66 13.9 67 287 3.19 13.2 61 271 2.77 12.4 55 253 2.39 11.6 49 179 2.13 8.2 27

    Application data

    Standard units, refrigerant: R-410A Evaporator entering/leaving water temperature difference: 5 K Evaporator fluid: chilled water Fouling factor: 0.18 x 10-4(m2K)/W

    Performances in accordance with EN14511-3:2011.

    Legend LWT Leaving water temperature, C Qc Cooling capacity, kW

    EER Energy eciency ratio, kW/kW q Evaporator water flow rate, l/s p Evaporator pressure drop, kPa

    Application data

    Standard units, refrigerant: R-410A Evaporator entering/leaving water temperature difference: 5 K Evaporator fluid: chilled water Fouling factor: 0.18 x 10-4(m2K)/W

    Gross performances, not in accordance with EN14511-3:2011. These performances do not takeinto account the correction for the proportional heating capacity and power input generated by thewater pump to overcome the internal pressure drop in the heat exchanger.

    Legend LWT Leaving water temperature, C Qc Cooling capacity, kW

    EER Energy eciency ratio, kW/kW q Evaporator water flow rate, l/s p Evaporator pressure drop, kPa

  • 7/25/2019 TP3 toplotna pumpa

    19/24

    19

    Cooling capacities in accordance with EN14511-3 : 2011

    30RQ 182-262 B units with option 280 and 30RQ 302-522

    Condenser entering air temperature, C

    20 25 30 35 40 46

    LWT Qc EER q p Qc EER q p Qc EER q p Qc EER q p Qc EER q p Qc EER q p

    C kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa

    182 5 190 4.10 9.0 20 181 3.60 8.6 19 172 3.14 8.1 17 162 2.72 7.7 15 151 2.32 7.1 13 137 1.89 6.5 11

    202 206 3.72 9.7 23 197 3.28 9.3 22 186 2.86 8.8 20 175 2.47 8.3 17 163 2.11 7.7 15 148 1.72 7.0 13

    232 241 4.13 11.3 32 230 3.63 10.8 30 219 3.16 10.2 28 206 2.73 9.6 26 191 2.33 9.0 23 173 1.89 8.1 20

    262 279 3.65 13.0 39 266 3.21 12.4 37 252 2.80 11.8 34 236 2.42 11.0 31 220 2.07 10.3 28 200 1.70 9.3 25

    302 305 3.80 14.4 46 292 3.35 13.8 43 278 2.93 13.1 40 262 2.54 12.4 37 244 2.17 11.6 33 222 1.77 10.5 29

    342 341 3.58 16.1 39 325 3.14 15.4 36 308 2.73 14.6 33 289 2.36 13.7 29 268 2.01 12.7 26 243 1.64 11.5 22

    372 361 3.79 17.0 35 345 3.32 16.2 32 328 2.89 15.4 29 310 2.49 14.6 26 289 2.13 13.6 23 216 1.87 10.2 13

    402 407 3.62 19.3 44 389 3.18 18.4 40 369 2.78 17.5 37 348 2.41 16.4 33 325 2.07 15.4 29 298 1.71 14.1 25

    432 433 3.76 20.5 49 414 3.31 19.6 45 393 2.89 18.6 41 370 2.50 17.5 37 344 2.14 16.3 32 311 1.73 14.7 27

    462 486 3.80 23.0 61 462 3.33 21.8 56 437 2.89 20.6 50 409 2.49 19.3 44 379 2.11 17.9 38 340 1.70 16.0 31

    522 522 3.50 24.7 70 496 3.07 23.5 64 470 2.68 22.3 58 441 2.32 20.9 51 409 1.98 19.4 45 369 1.61 17.4 37

    182 7 205 4.32 9.7 23 195 3.79 9.2 21 185 3.31 8.7 19 174 2.86 8.2 17 162 2.45 7.7 15 147 2.00 6.9 12

    202 221 3.89 10.5 26 211 3.42 10.0 24 200 2.99 9.4 22 188 2.61 8.9 20 176 2.23 8.3 17 159 1.82 7.5 14

    232 256 4.30 12.0 35 245 3.78 11.5 33 232 3.29 10.9 30 218 2.84 10.2 28 203 2.42 9.5 25 183 1.96 8.6 22

    262 296 3.77 13.8 42 283 3.32 13.2 40 268 2.90 12.5 37 253 2.52 11.8 34 235 2.16 11.0 31 214 1.77 10.0 27

    302 323 3.88 15.3 49 308 3.44 14.6 46 293 3.01 13.9 43 277 2.62 13.1 39 259 2.25 12.3 36 236 1.85 11.2 31342 361 3.70 17.1 42 344 3.25 16.3 39 326 2.84 15.5 35 306 2.45 14.5 32 285 2.09 13.5 28 257 1.71 12.2 24

    372 383 3.95 18.0 39 367 3.47 17.3 36 350 3.02 16.5 33 330 2.61 15.6 29 308 2.23 14.5 26 231 1.97 10.9 15

    402 424 3.70 20.1 47 407 3.27 19.3 44 387 2.85 18.3 40 365 2.48 17.3 36 341 2.13 16.2 31 312 1.76 14.8 27

    432 448 3.84 21.2 52 429 3.38 20.3 48 410 2.96 19.4 44 388 2.57 18.4 40 363 2.21 17.2 35 332 1.82 15.7 30

    462 495 3.85 23.4 63 474 3.38 22.4 58 452 2.95 21.4 53 428 2.56 20.2 48 400 2.20 18.9 42 365 1.80 17.2 35

    522 535 3.56 25.4 73 513 3.13 24.3 67 490 2.74 23.2 62 463 2.38 21.9 55 434 2.05 20.6 49 398 1.69 18.8 42

    182 10 226 4.61 10.7 27 215 4.07 10.2 25 205 3.56 9.7 23 193 3.09 9.1 20 180 2.64 8.5 18 162 2.15 7.7 15

    202 245 4.17 11.6 31 233 3.68 11.1 29 221 3.22 10.5 26 208 2.79 9.9 23 193 2.39 9.2 20 175 1.96 8.3 17

    232 283 4.56 13.3 39 270 4.01 12.7 37 256 3.50 12.0 34 240 3.02 11.3 31 223 2.58 10.5 28 202 2.10 9.5 24

    262 323 3.92 15.1 47 308 3.46 14.4 44 292 3.03 13.6 41 274 2.64 12.8 37 256 2.27 11.9 34 138 2.55 6.4 14

    302 353 4.06 16.8 55 337 3.57 16.0 51 320 3.12 15.2 48 301 2.70 14.3 44 279 2.34 13.3 39 255 1.93 12.1 34

    342 393 3.81 18.6 48 374 3.36 17.8 44 356 2.95 16.9 40 334 2.58 15.9 36 311 2.22 14.7 32 233 1.95 11.1 20

    372 419 4.17 19.8 45 403 3.68 19.0 42 384 3.21 18.1 38 363 2.78 17.1 34 339 2.38 16.0 30 254 2.12 12.0 18

    402 458 3.85 21.8 54 440 3.40 20.9 50 419 2.98 19.9 45 396 2.59 18.8 41 371 2.24 17.6 36 286 1.93 13.6 22

    432 486 4.03 23.1 60 467 3.56 22.2 55 446 3.12 21.2 51 422 2.71 20.0 46 395 2.33 18.7 40 360 1.91 17.1 34

    462 542 4.09 25.7 73 522 3.61 24.7 68 499 3.16 23.6 63 472 2.74 22.4 56 441 2.35 20.9 50 402 1.92 19.0 42

    522 583 3.75 27.7 84 560 3.30 26.6 78 533 2.89 25.4 71 503 2.50 23.9 64 470 2.15 22.3 56 430 1.77 20.4 48

    Application data

    Standard units, refrigerant: R-410A Evaporator entering/leaving water temperature difference: 5 K Evaporator fluid: chilled water Fouling factor: 0.18 x 10-4(m2K)/W

    Performances in accordance with EN14511-3:2011.

    Legend LWT Leaving water temperature, C Qc Cooling capacity, kW

    EER Energy eciency ratio, kW/kW q Evaporator water flow rate, l/s p Evaporator pressure drop, kPa

  • 7/25/2019 TP3 toplotna pumpa

    20/24

    20

    Cooling capacities

    30RQ 182-262 B units with option 280 and 30RQ 302-522

    Condenser entering air temperature, C

    20 25 30 35 40 46

    LWT Qc EER q p Qc EER q p Qc EER q p Qc EER q p Qc EER q p Qc EER q p

    C kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa

    182 5 191 4.15 9.0 20 182 3.64 8.6 19 172 3.17 8.1 17 163 2.74 7.7 15 151 2.34 7.1 13 137 1.90 6.5 11202 207 3.77 9.7 23 197 3.32 9.3 22 187 2.89 8.8 20 176 2.49 8.3 17 164 2.13 7.7 15 148 1.73 7.0 13

    232 242 4.20 11.3 32 231 3.68 10.8 30 219 3.20 10.2 28 206 2.76 9.6 26 192 2.35 9.0 23 173 1.90 8.1 20

    262 280 3.71 13.0 39 267 3.26 12.4 37 253 2.83 11.8 34 237 2.45 11.0 31 221 2.09 10.3 28 200 1.71 9.3 25

    302 306 3.87 14.4 46 293 3.41 13.8 43 279 2.97 13.1 40 263 2.57 12.4 37 245 2.20 11.6 33 222 1.79 10.5 29

    342 342 3.63 16.1 39 326 3.18 15.4 36 309 2.76 14.6 33 290 2.38 13.7 29 269 2.03 12.7 26 244 1.65 11.5 22

    372 362 3.84 17.0 35 346 3.36 16.2 32 329 2.92 15.4 29 311 2.52 14.6 26 290 2.14 13.6 23 217 1.88 10.2 13

    402 409 3.68 19.3 44 390 3.23 18.4 40 370 2.81 17.5 37 349 2.44 16.4 33 326 2.09 15.4 29 298 1.72 14.1 25

    432 434 3.83 20.5 49 415 3.36 19.6 45 395 2.93 18.6 41 371 2.53 17.5 37 345 2.16 16.3 32 312 1.75 14.7 27

    462 488 3.89 23.0 61 464 3.39 21.8 56 439 2.94 20.6 50 411 2.52 19.3 44 380 2.13 17.9 38 341 1.71 16.0 31

    522 524 3.58 24.7 70 499 3.14 23.5 64 472 2.72 22.3 58 442 2.35 20.9 51 410 2.00 19.4 45 370 1.62 17.4 37

    182 7 205 4.38 9.7 23 195 3.84 9.2 21 185 3.34 8.7 19 174 2.89 8.2 17 163 2.47 7.7 15 147 2.01 6.9 12

    202 222 3.95 10.5 26 211 3.47 10.0 24 200 3.02 9.4 22 189 2.64 8.9 20 176 2.25 8.3 17 159 1.83 7.5 14

    232 257 4.38 12.0 35 246 3.84 11.5 33 233 3.33 10.9 30 219 2.87 10.2 28 203 2.44 9.5 25 183 1.98 8.6 22

    262 297 3.83 13.8 42 283 3.37 13.2 40 269 2.94 12.5 37 254 2.55 11.8 34 236 2.18 11.0 31 214 1.79 10.0 27

    302 325 3.96 15.3 49 310 3.50 14.6 46 294 3.06 13.9 43 278 2.65 13.1 39 260 2.28 12.3 36 237 1.87 11.2 31

    342 362 3.76 17.1 42 345 3.30 16.3 39 327 2.87 15.5 35 307 2.47 14.5 32 285 2.11 13.5 28 258 1.72 12.2 24

    372 384 4.01 18.0 39 369 3.52 17.3 36 351 3.06 16.5 33 331 2.64 15.6 29 309 2.25 14.5 26 232 1.98 10.9 15

    402 426 3.77 20.1 47 408 3.32 19.3 44 388 2.88 18.3 40 366 2.50 17.3 36 342 2.15 16.2 31 313 1.77 14.8 27

    432 450 3.92 21.2 52 431 3.44 20.3 48 411 3.00 19.4 44 389 2.60 18.4 40 365 2.23 17.2 35 333 1.83 15.7 30

    462 498 3.94 23.4 63 476 3.45 22.4 58 454 3.00 21.4 53 430 2.60 20.2 48 402 2.22 18.9 42 366 1.81 17.2 35

    522 538 3.64 25.4 73 516 3.20 24.3 67 492 2.79 23.2 62 465 2.42 21.9 55 436 2.07 20.6 49 399 1.71 18.8 42

    182 10 226 4.69 10.7 27 216 4.13 10.2 25 205 3.61 9.7 23 193 3.12 9.1 20 180 2.66 8.5 18 163 2.17 7.7 15

    202 246 4.24 11.6 31 234 3.73 11.1 29 222 3.26 10.5 26 209 2.82 9.9 23 194 2.41 9.2 20 176 1.97 8.3 17

    232 284 4.65 13.3 39 271 4.08 12.7 37 257 3.55 12.0 34 241 3.06 11.3 31 224 2.61 10.5 28 202 2.11 9.5 24

    262 324 4.00 15.1 47 309 3.52 14.4 44 293 3.08 13.6 41 275 2.67 12.8 37 256 2.29 11.9 34 138 2.57 6.4 14

    302 355 4.15 16.8 55 339 3.64 16.0 51 321 3.17 15.2 48 302 2.74 14.3 44 280 2.37 13.3 39 255 1.95 12.1 34

    342 394 3.88 18.6 48 376 3.41 17.8 44 357 2.99 16.9 40 335 2.61 15.9 36 312 2.24 14.7 32 234 1.96 11.1 20

    372 421 4.25 20 45 404 3.74 19.0 42 385 3.26 18.1 38 364 2.82 17.1 34 340 2.41 16.0 30 255 2.13 12.0 18

    402 460 3.93 22 54 441 3.46 20.9 50 421 3.02 19.9 45 397 2.63 18.8 41 372 2.26 17.6 36 287 1.95 13.6 22

    432 488 4.13 23 60 469 3.63 22.2 55 448 3.17 21.2 51 423 2.75 20.0 46 396 2.35 18.7 40 361 1.93 17.1 34

    462 545 4.20 25.7 73 524 3.70 24.7 68 501 3.22 23.6 63 474 2.78 22.4 56 443 2.38 20.9 50 403 1.94 19.0 42522 587 3.85 27.7 84 563 3.38 26.6 78 536 2.95 25.4 71 506 2.55 23.9 64 472 2.18 22.3 56 431 1.79 20.4 48

    Application data

    Standard units, refrigerant: R-410A Evaporator entering/leaving water temperature difference: 5 K Evaporator fluid: chilled water Fouling factor: 0.18 x 10-4(m2K)/W

    Gross performances, not in accordance with EN14511-3:2011. These performances do not takeinto account the correction for the proportional heating capacity and power input generated by thewater pump to overcome the internal pressure drop in the heat exchanger.

    Legend LWT Leaving water temperature, C Qc Cooling capacity, kW

    EER Energy eciency ratio, kW/kW q Evaporator water flow rate, l/s p Evaporator pressure drop, kPa

  • 7/25/2019 TP3 toplotna pumpa

    21/24

    21

    Heating capacities in accordance with EN14511-3 : 2011

    Heating capacities

    30RQ 182-262 B standard units

    Outside air dry-bulb (wet-bulb) temperature, C

    -15 (-16) -10 (-11) -7 (-8) 2 (1) 7 (6) 12 (11)

    LWT Qh COP q p Qh COP q p Qh COP q p Qh COP q p Qh COP q p Qh COP q p

    C kW kW/ kW

    l/s kPa kW kW/ kW

    l/s kPa kW kW/ kW

    l/s kPa kW kW/ kW

    l/s kPa kW kW/ kW

    l/s kPa kW kW/ kW

    l/s kPa

    182 30 97 2.05 5.1 18 109 2.27 5.8 22 118 2.43 6.3 26 154 3.10 8.1 40 195 3.92 9.3 51 226 4.51 10.8 66

    202 107 2.00 5.6 17 120 2.20 6.4 22 130 2.35 7.0 25 170 3.00 9.0 39 216 3.85 10.3 50 248 4.29 11.9 64

    232 118 2.18 6.2 16 132 2.41 7.1 20 143 2.64 7.7 24 186 3.36 9.8 36 235 4.15 11.2 46 271 4.64 12.9 58

    262 140 2.04 7.4 19 157 2.24 8.4 24 170 2.38 9.1 28 221 3.03 11.6 42 280 3.88 13.4 54 321 4.30 15.3 68

    182 35 96 1.86 5.1 17 107 2.04 5.8 22 116 2.18 6.3 25 150 2.77 8.0 38 192 3.53 9.2 48 221 4.06 10.6 62

    202 106 1.81 5.7 17 119 1.99 6.4 21 128 2.12 7.0 24 166 2.69 8.9 37 212 3.48 10.2 48 243 3.88 11.6 60

    232 117 1.96 6.2 16 130 2.16 7.0 20 140 2.36 7.6 23 181 2.99 9.7 34 231 3.72 11.1 43 266 4.16 12.7 55

    262 139 1.85 7.4 19 155 2.02 8.4 24 167 2.14 9.1 27 216 2.71 11.5 41 276 3.50 13.2 52 315 3.88 15.1 65

    182 40 94 1.66 5.2 17 105 1.82 5.8 21 112 1.93 6.3 24 144 2.43 7.9 36 188 3.17 9.0 46 216 3.65 10.4 58

    202 104 1.63 5.7 17 116 1.78 6.4 21 124 1.88 6.9 24 160 2.37 8.8 36 209 3.14 10.0 45 239 3.49 11.4 57

    232 115 1.75 6.3 16 126 1.91 7.0 19 136 2.08 7.6 22 174 2.62 9.5 33 227 3.33 10.9 41 260 3.72 12.5 52

    262 137 1.66 7.5 19 152 1.80 8.4 23 163 1.90 9.1 26 209 2.39 11.4 39 272 3.16 13.1 49 310 3.49 14.8 62

    182 45 29 1.46 1.6 2 102 1.61 5.8 20 109 1.71 6.2 23 138 2.13 7.7 34 184 2.84 8.8 43 211 3.26 10.1 55

    202 35 1.47 2.0 2 78 1.60 4.5 11 121 1.67 6.9 23 154 2.09 8.6 34 205 2.82 9.9 43 233 3.13 11.2 54

    232 59 1.51 3.3 5 123 1.69 7.0 19 131 1.82 7.5 21 167 2.29 9.4 31 221 2.97 10.6 39 253 3.30 12.1 49

    262 71 1.50 4.0 6 79 1.65 4.5 8 158 1.69 9.1 25 201 2.10 11.3 37 267 2.84 12.9 47 303 3.12 14.6 58182 50 - - - - 32 1.43 1.8 3 75 1.51 4.4 12 132 1.85 7.6 32 179 2.52 8.6 40 204 2.90 9.8 51

    202 - - - - 38 1.44 2.2 3 81 1.51 4.8 12 147 1.83 8.5 32 200 2.52 9.6 40 227 2.79 10.9 50

    232 - - - - 63 1.47 3.7 6 67 1.57 3.9 7 160 1.99 9.2 29 215 2.62 10.4 36 244 2.92 11.8 45

    262 - - - - 77 1.47 4.5 7 82 1.55 4.8 8 193 1.84 11.1 36 262 2.54 12.6 44 296 2.79 14.2 55

    30RQ 182-262 B standard units

    Outside air dry-bulb (wet-bulb) temperature, C

    -15 (-16) -10 (-11) -7 (-8) 2 (1) 7 (6) 12 (11)

    LWT Qh COP q p Qh COP q p Qh COP q p Qh COP q p Qh COP q p Qh COP q p

    C kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa

    182 30 107 2.27 5.1 18 122 2.55 5.8 22 132 2.74 6.3 26 169 3.45 8.1 40 194 3.97 9.3 51 225 4.60 10.8 66

    202 117 2.21 5.6 17 134 2.47 6.4 22 146 2.65 7.0 25 187 3.33 9.0 39 215 3.90 10.3 50 247 4.37 11.9 64

    232 130 2.41 6.2 16 147 2.71 7.1 20 160 2.98 7.7 24 204 3.74 9.8 36 234 4.20 11.2 46 269 4.72 12.9 58

    262 154 2.26 7.4 19 175 2.51 8.4 24 190 2.69 9.1 28 242 3.37 11.6 42 278 3.93 13.4 54 319 4.38 15.3 68

    182 35 107 2.08 5.1 17 121 2.32 5.8 22 131 2.49 6.3 25 166 3.11 8.0 38 191 3.57 9.2 48 220 4.13 10.6 62

    202 118 2.03 5.7 17 134 2.26 6.4 21 145 2.42 7.0 24 184 3.02 8.9 37 212 3.52 10.2 48 242 3.93 11.6 60

    232 130 2.19 6.2 16 146 2.46 7.0 20 158 2.69 7.6 23 201 3.36 9.7 34 230 3.76 11.1 43 264 4.22 12.7 55

    262 155 2.07 7.4 19 175 2.29 8.4 24 189 2.44 9.1 27 240 3.04 11.5 41 275 3.54 13.2 52 314 3.94 15.1 65

    182 40 107 1.90 5.2 17 121 2.11 5.8 21 130 2.25 6.3 24 164 2.79 7.9 36 187 3.21 9.0 46 215 3.70 10.4 58

    202 118 1.86 5.7 17 134 2.06 6.4 21 144 2.20 6.9 24 182 2.72 8.8 36 208 3.17 10.0 45 237 3.53 11.4 57

    232 130 2.00 6.3 16 146 2.22 7.0 19 157 2.43 7.6 22 198 3.01 9.5 33 226 3.36 10.9 41 258 3.76 12.5 52

    262 155 1.90 7.5 19 175 2.09 8.4 23 188 2.22 9.1 26 237 2.74 11.4 39 271 3.19 13.1 49 308 3.53 14.8 62

    182 45 34 1.70 1.6 2 120 1.91 5.8 20 129 2.04 6.2 23 161 2.50 7.7 34 183 2.86 8.8 43 210 3.30 10.1 55

    202 41 1.71 2.0 2 93 1.90 4.5 11 143 2.00 6.9 23 179 2.44 8.6 34 204 2.84 9.9 43 232 3.16 11.2 54

    232 68 1.76 3.3 5 145 2.00 7.0 19 156 2.17 7.5 21 194 2.68 9.4 31 220 2.99 10.6 39 251 3.34 12.1 49

    262 83 1.75 4.0 6 93 1.95 4.5 8 188 2.02 9.1 25 234 2.47 11.3 37 266 2.86 12.9 47 302 3.16 14.6 58

    182 50 - - - - 38 1.73 1.8 3 91 1.84 4.4 12 157 2.22 7.6 32 178 2.53 8.6 40 204 2.92 9.8 51

    202 - - - - 46 1.74 2.2 3 99 1.84 4.8 12 175 2.19 8.5 32 199 2.53 9.6 40 226 2.81 10.9 50

    232 - - - - 76 1.79 3.7 6 82 1.91 3.9 7 190 2.38 9.2 29 214 2.64 10.4 36 243 2.94 11.8 45

    262 - - - - 93 1.78 4.5 7 99 1.90 4.8 8 230 2.21 11.1 36 261 2.55 12.6 44 294 2.81 14.2 55

    Legend LWT Leaving water temperature, C Qh Heating capacity, kW

    COP Coecient of performance, kW/kW q Condenser water flow rate, l/s p Condenser pressure drop, kPa

    Application data

    Standard units, refrigerant: R-410A Condenser entering/leaving water temperature difference: 5 K for LWT values

  • 7/25/2019 TP3 toplotna pumpa

    22/24

    22

    30RQ 182-262 B units with option 280 and 30RQ 302-522

    Outside air dry-bulb (wet-bulb) temperature, C

    -15 (-16) -10 (-11) -7 (-8) 2 (1) 7 (6) 12 (11)

    LWT Qh COP q p Qh COP q p Qh COP q p Qh COP q p Qh COP q p Qh COP q p

    C kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa

    182 30 100 2.05 5.3 10 112 2.31 6.0 12 121 2.50 6.5 13 155 3.27 8.2 18 195 4.04 9.3 22 224 4.54 10.7 26

    202 112 1.98 5.9 8 125 2.23 6.7 10 135 2.40 7.3 12 173 3.09 9.1 18 217 3.79 10.4 23 248 4.27 11.9 30

    232 123 2.22 6.5 13 137 2.45 7.3 15 148 2.62 7.9 17 190 3.29 10.0 24 240 4.08 11.5 29 276 4.64 13.2 35

    262 147 2.19 7.7 16 165 2.41 8.8 19 178 2.56 9.6 22 232 3.20 12.2 31 290 3.93 13.9 37 333 4.46 15.9 45

    302 159 2.11 8.4 19 177 2.31 9.5 22 192 2.46 10.3 25 247 3.02 13.0 35 308 3.67 14.7 41 352 4.22 16.8 50

    342 174 2.07 9.2 13 196 2.29 10.5 16 213 2.41 11.5 19 272 2.99 14.4 28 339 3.72 16.3 34 387 4.15 18.5 43

    372 190 2.14 10.1 12 214 2.36 11.5 15 231 2.52 12.5 17 296 3.11 15.7 26 372 3.81 17.8 33 425 4.25 20.4 43

    402 212 2.09 11.2 14 239 2.30 12.8 18 258 2.45 13.9 21 329 2.97 17.4 32 410 3.61 19.6 40 469 4.11 22.5 51

    432 233 2.13 12.3 17 263 2.35 14.1 21 284 2.50 15.3 25 358 3.03 18.9 37 447 3.67 21.4 47 511 4.16 24.5 60

    462 266 2.13 14.0 21 299 2.35 16.0 27 323 2.51 17.4 32 410 3.05 21.6 48 512 3.70 24.5 60 586 4.18 28.0 77

    522 287 2.09 15.2 25 324 2.30 17.4 32 352 2.45 18.9 37 444 2.95 23.4 55 553 3.55 26.4 69 633 4.06 30.2 89

    182 35 100 1.84 5.3 10 111 2.07 6.0 11 119 2.23 6.5 13 153 2.94 8.0 38 193 3.66 9.3 21 220 4.10 10.6 25

    202 111 1.80 6.0 8 124 2.01 6.7 10 134 2.16 7.3 12 172 2.80 8.9 37 215 3.44 10.3 22 245 3.87 11.7 28

    232 122 2.01 6.5 13 135 2.20 7.3 15 145 2.35 7.9 17 187 2.94 9.7 34 236 3.66 11.3 28 271 4.15 13.0 34

    262 146 1.99 7.8 16 163 2.17 8.8 19 176 2.31 9.6 21 229 2.88 11.5 41 288 3.57 13.8 36 328 4.02 15.7 43

    302 158 1.92 8.4 18 175 2.08 9.5 22 189 2.21 10.3 24 245 2.71 8.2 18 306 3.32 14.7 40 347 3.81 16.6 48342 173 1.89 9.3 13 195 2.07 10.6 16 212 2.16 11.5 19 270 2.70 9.2 18 337 3.37 16.2 33 382 3.75 18.3 41

    372 189 1.94 10.1 11 212 2.12 11.5 14 228 2.26 12.5 17 294 2.81 10.0 23 368 3.43 17.6 32 419 3.82 20.1 41

    402 211 1.90 11.3 14 237 2.08 12.8 18 255 2.21 13.9 21 327 2.70 12.2 30 407 3.27 19.5 38 463 3.71 22.2 49

    432 232 1.93 12.4 17 260 2.12 14.1 21 281 2.25 15.3 25 357 2.75 13.1 34 443 3.32 21.2 45 504 3.75 24.1 57

    462 264 1.93 14.1 21 296 2.12 16.1 27 320 2.26 17.5 31 407 2.76 14.4 27 507 3.35 24.3 58 577 3.77 27.6 73

    522 286 1.90 15.3 24 322 2.08 17.5 31 348 2.21 19.0 36 444 2.68 15.7 26 549 3.22 26.3 67 625 3.67 29.9 85

    182 40 38 1.65 2.1 2 108 1.83 6.0 11 116 1.97 6.5 12 149 2.57 17.5 31 192 3.32 9.2 20 217 3.70 10.4 24

    202 38 1.63 2.1 1 122 1.79 6.8 10 131 1.92 7.3 11 167 2.47 19.1 37 216 3.15 10.4 22 242 3.50 11.6 27

    232 119 1.79 6.5 12 132 1.95 7.3 15 141 2.07 7.9 16 181 2.59 21.8 47 234 3.30 11.2 27 265 3.71 12.7 32

    262 77 1.79 4.2 6 159 1.94 8.9 19 171 2.05 9.5 21 222 2.55 23.7 55 288 3.24 13.8 35 323 3.62 15.5 41

    302 129 1.73 7.1 14 172 1.86 9.5 21 185 1.96 10.3 24 239 2.40 7.9 36 305 3.00 14.6 39 343 3.42 16.4 46

    342 139 1.71 7.6 9 191 1.85 10.6 16 207 1.91 11.6 18 264 2.40 8.8 36 337 3.07 16.2 32 378 3.39 18.2 39

    372 - - - - 207 1.89 11.5 14 223 2.01 12.4 16 288 2.50 9.5 33 368 3.12 17.7 31 412 3.43 19.8 38

    402 - - - - 232 1.86 12.9 17 249 1.97 13.9 20 321 2.41 11.4 39 408 2.98 19.6 38 456 3.34 21.9 47

    432 - - - - 254 1.89 14.1 21 274 2.00 15.3 24 353 2.47 8.2 17 443 3.03 21.3 44 496 3.37 23.8 54

    462 227 1.75 12.4 16 290 1.89 16.1 26 312 2.00 17.4 31 402 2.47 9.2 17 506 3.04 24.3 56 568 3.39 27.2 70

    522 216 1.73 11.8 15 315 1.86 17.5 31 340 1.97 19.0 36 439 2.41 9.9 22 550 2.95 26.4 66 616 3.31 29.5 81

    182 45 - - - - 41 1.65 2.4 3 113 1.74 6.5 12 144 2.24 12.1 29 190 2.98 9.2 20 214 3.32 10.3 23

    202 - - - - 42 1.63 2.4 1 88 1.69 5.1 6 162 2.17 13.1 33 213 2.84 10.3 21 240 3.17 11.6 26

    232 61 1.55 3.4 5 129 1.72 7.3 14 137 1.82 7.8 16 173 2.26 14.4 27 231 2.95 11.1 26 260 3.31 12.5 31

    262 - - - - 84 1.77 4.8 8 166 1.82 9.5 20 214 2.25 15.8 25 284 2.92 13.7 34 320 3.27 15.4 40

    302 66 1.47 3.7 5 105 1.70 6.0 11 180 1.74 10.3 23 231 2.12 17.6 31 303 2.71 14.6 38 338 3.07 16.3 44

    342 72 1.48 4.0 3 117 1.68 6.7 7 162 1.76 9.3 12 256 2.12 19.3 37 336 2.78 16.2 32 374 3.06 18.0 38

    372 - - - - 172 1.69 9.8 10 217 1.77 12.4 16 279 2.19 22.0 47 367 2.83 17.7 31 407 3.09 19.6 37

    402 - - - - - - - - 243 1.75 13.9 20 311 2.13 24.0 55 408 2.72 19.6 37 451 3.02 21.7 45

    432 - - - - 183 1.71 10.4 11 267 1.78 15.3 23 343 2.18 7.7 34 447 2.77 21.5 44 490 3.04 23.5 52

    462 97 1.45 5.5 3 247 1.70 14.1 20 266 1.80 15.2 23 391 2.18 8.6 34 507 2.78 24.4 56 558 3.04 26.8 66

    522 - - - - 236 1.69 13.4 18 332 1.75 19.0 35 426 2.13 9.4 31 554 2.70 26.6 65 609 2.99 29.2 78

    182 50 - - - - - - - - 43 1.57 2.5 3 138 1.95 11.3 37 187 2.65 9.0 19 211 2.99 10.2 22

    202 - - - - - - - - 43 1.55 2.6 2 157 1.91 8.1 16 210 2.55 10.1 20 238 2.86 11.4 25

    232 - - - - 66 1.52 3.9 6 70 1.62 4.1 6 166 1.96 9.1 17 226 2.62 10.9 25 256 2.95 12.4 29262 - - - - - - - - 87 1.67 5.1 8 207 1.98 9.7 21 280 2.62 13.5 32 316 2.94 15.2 38

    302 - - - - 72 1.46 4.2 6 109 1.60 6.4 12 225 1.86 12.0 28 300 2.43 14.5 37 335 2.75 16.1 43

    342 - - - - 78 1.47 4.6 4 83 1.56 4.9 4 249 1.86 13.0 32 333 2.49 16.1 31 372 2.76 17.9 37

    372 - - - - - - - - 110 1.58 6.5 5 270 1.92 14.4 26 365 2.52 17.6 30 406 2.78 19.5 36

    402 - - - - - - - - 124 1.59 7.3 6 302 1.89 15.7 24 405 2.46 19.5 36 449 2.74 21.6 44

    432 - - - - - - - - - - - - 333 1.92 17.5 30 446 2.51 21.5 43 490 2.76 23.6 51

    462 - - - - 105 1.44 6.2 4 187 1.60 11.0 12 380 1.92 19.2 36 508 2.52 24.4 55 556 2.75 26.8 65

    522 - - - - - - - - - - - - 414 1.89 21.9 46 552 2.45 26.6 64 608 2.72 29.2 76

    Heating capacities in accordance with EN14511-3 : 2011

    Legend LWT Leaving water temperature, C Qh Heating capacity, kW

    COP Coecient of performance, kW/kW q Condenser water flow rate, l/s p Condenser pressure drop, kPa

    Application data

    Standard units, refrigerant: R-410A Condenser entering/leaving water temperature difference: 5 K for LWT values

  • 7/25/2019 TP3 toplotna pumpa

    23/24

    23

    Heating capacities

    30RQ 182-262 B units with option 280 and 30RQ 302-522

    Outside air dry-bulb (wet-bulb) temperature, C

    -15 (-16) -10 (-11) -7 (-8) 2 (1) 7 (6) 12 (11)

    LWT Qh COP q p Qh COP q p Qh COP q p Qh COP q p Qh COP q p Qh COP q p

    C kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa kW kW/

    kW

    l/s kPa

    182 30 110 2.26 5.3 10 125 2.59 6.0 12 135 2.81 6.5 13 171 3.62 8.2 18 195 4.07 9.3 22 223 4.59 10.7 26

    202 123 2.19 5.9 8 140 2.50 6.7 10 151 2.71 7.3 12 190 3.42 9.1 18 216 3.82 10.4 23 247 4.31 11.9 30

    232 135 2.46 6.5 13 153 2.75 7.3 15 165 2.95 7.9 17 209 3.65 10.0 24 239 4.12 11.5 29 275 4.69 13.2 35

    262 161 2.42 7.7 16 184 2.70 8.8 19 199 2.89 9.6 22 254 3.55 12.2 31 289 3.97 13.9 37 332 4.52 15.9 45

    302 174 2.34 8.4 19 197 2.59 9.5 22 215 2.78 10.3 25 271 3.35 13.0 35 307 3.71 14.7 41 350 4.27 16.8 50

    342 191 2.29 9.2 13 219 2.57 10.5 16 239 2.72 11.5 19 299 3.32 14.4 28 338 3.75 16.3 34 385 4.19 18.5 43

    372 209 2.36 10.1 12 239 2.64 11.5 15 259 2.84 12.5 17 326 3.45 15.7 26 371 3.84 17.8 33 424 4.30 20.4 43

    402 233 2.31 11.2 14 266 2.58 12.8 18 289 2.76 13.9 21 361 3.30 17.4 32 409 3.64 19.6 40 467 4.17 22.5 51

    432 256 2.35 12.3 17 293 2.63 14.1 21 318 2.82 15.3 25 393 3.36 18.9 37 445 3.71 21.4 47 509 4.22 24.5 60

    462 292 2.36 14.0 21 334 2.64 16.0 27 362 2.83 17.4 32 450 3.39 21.6 48 509 3.75 24.5 60 582 4.25 28.0 77

    522 315 2.31 15.2 25 362 2.58 17.4 32 394 2.76 18.9 37 487 3.28 23.4 55 550 3.60 26.4 69 629 4.14 30.2 89

    182 35 111 2.06 5.3 10 125 2.34 6.0 11 135 2.55 6.5 13 170 3.30 8.2 18 193 3.68 9.3 21 219 4.14 10.6 25

    202 124 2.00 6.0 8 140 2.28 6.7 10 151 2.46 7.3 12 191 3.13 9.2 18 215 3.46 10.3 22 244 3.90 11.7 28

    232 135 2.24 6.5 13 152 2.49 7.3 15 164 2.67 7.9 17 207 3.29 10.0 23 235 3.69 11.3 28 270 4.20 13.0 34

    262 162 2.22 7.8 16 184 2.47 8.8 19 199 2.63 9.6 21 254 3.23 12.2 30 287 3.60 13.8 36 327 4.07 15.7 43

    302 176 2.14 8.4 18 198 2.36 9.5 22 214 2.52 10.3 24 272 3.04 13.1 34 305 3.34 14.7 40 346 3.85 16.6 48342 192 2.10 9.3 13 220 2.35 10.6 16 240 2.46 11.5 19 300 3.03 14.4 27 336 3.40 16.2 33 381 3.79 18.3 41

    372 211 2.16 10.1 11 239 2.41 11.5 14 259 2.58 12.5 17 327 3.14 15.7 26 367 3.46 17.6 32 417 3.86 20.1 41

    402 234 2.12 11.3 14 267 2.35 12.8 18 289 2.52 13.9 21 363 3.02 17.5 31 406 3.29 19.5 38 461 3.75 22.2 49

    432 257 2.16 12.4 17 293 2.40 14.1 21 318 2.57 15.3 25 396 3.08 19.1 37 441 3.35 21.2 45 502 3.80 24.1 57

    462 294 2.16 14.1 21 334 2.40 16.1 27 363 2.57 17.5 31 452 3.10 21.8 47 504 3.38 24.3 58 574 3.82 27.6 73

    522 318 2.12 15.3 24 363 2.36 17.5 31 394 2.52 19.0 36 492 3.01 23.7 55 546 3.26 26.3 67 621 3.73 29.9 85

    182 40 43 1.88 2.1 2 125 2.12 6.0 11 135 2.30 6.5 12 170 2.94 8.2 17 191 3.33 9.2 20 216 3.72 10.4 24

    202 43 1.86 2.1 1 141 2.07 6.8 10 151 2.24 7.3 11 190 2.82 9.2 17 215 3.16 10.4 22 241 3.53 11.6 27

    232 136 2.04 6.5 12 152 2.26 7.3 15 164 2.41 7.9 16 205 2.96 9.9 22 233 3.32 11.2 27 265 3.74 12.7 32

    262 87 2.04 4.2 6 184 2.25 8.9 19 198 2.39 9.5 21 252 2.92 12.1 29 287 3.26 13.8 35 322 3.65 15.5 41

    302 147 1.97 7.1 14 198 2.15 9.5 21 214 2.29 10.3 24 271 2.76 13.1 33 304 3.02 14.6 39 341 3.45 16.4 46

    342 159 1.95 7.6 9 220 2.14 10.6 16 240 2.23 11.6 18 300 2.74 14.4 27 336 3.09 16.2 32 377 3.42 18.2 39

    372 - - - - 239 2.19 11.5 14 258 2.34 12.4 16 328 2.86 15.8 25 367 3.14 17.7 31 410 3.46 19.8 38

    402 - - - - 267 2.15 12.9 17 289 2.29 13.9 20 365 2.76 17.6 31 406 3.00 19.6 38 454 3.37 21.9 47

    432 - - - - 293 2.19 14.1 21 318 2.33 15.3 24 401 2.83 19.3 37 442 3.05 21.3 44 494 3.41 23.8 54

    462 258 1.99 12.4 16 334 2.19 16.1 26 362 2.34 17.4 31 456 2.84 22.0 47 503 3.07 24.3 56 565 3.43 27.2 70

    522 246 1.97 11.8 15 363 2.16 17.5 31 394 2.30 19.0 36 498 2.77 24.0 55 548 2.97 26.4 66 612 3.35 29.5 81

    182 45 - - - - 49 1.95 2.4 3 134 2.07 6.5 12 167 2.62 8.1 16 190 3.00 9.2 20 213 3.34 10.3 23

    202 - - - - 49 1.93 2.4 1 105 2.02 5.1 6 188 2.54 9.1 17 213 2.86 10.3 21 239 3.19 11.6 26

    232 71 1.81 3.4 5 152 2.04 7.3 14 163 2.17 7.8 16 202 2.64 9.7 21 230 2.97 11.1 26 260 3.33 12.5 31

    262 - - - - 99 2.10 4.8 8 197 2.18 9.5 20 249 2.63 12.0 28 284 2.94 13.7 34 319 3.29 15.4 40

    302 77 1.72 3.7 5 124 2.02 6.0 11 213 2.07 10.3 23 269 2.48 13.0 32 302 2.73 14.6 38 337 3.09 16.3 44

    342 84 1.73 4.0 3 138 1.99 6.7 7 192 2.10 9.3 12 298 2.48 14.4 26 335 2.79 16.2 32 373 3.08 18.0 38

    372 - - - - 203 2.01 9.8 10 258 2.12 12.4 16 324 2.56 15.7 24 366 2.84 17.7 31 406 3.11 19.6 37

    402 - - - - - - - - 289 2.09 13.9 20 362 2.50 17.5 30 407 2.74 19.6 37 449 3.04 21.7 45

    432 - - - - 216 2.03 10.4 11 317 2.12 15.3 23 398 2.55 19.2 36 445 2.79 21.5 44 488 3.07 23.5 52

    462 113 1.70 5.5 3 292 2.01 14.1 20 315 2.15 15.2 23 454 2.56 21.9 46 505 2.80 24.4 56 556 3.07 26.8 66

    522 - - - - 279 2.01 13.4 18 394 2.09 19.0 35 494 2.50 23.8 53 552 2.72 26.6 65 605 3.02 29.2 78

    182 50 - - - - - - - - 52 1.91 2.5 3 165 2.33 8.0 16 186 2.66 9.0 19 210 3.00 10.2 22

    202 - - - - - - - - 53 1.89 2.6 2 187 2.28 9.0 16 210 2.56 10.1 20 237 2.87 11.4 25

    232 - - - - 80 1.84 3.9 6 86 1.97 4.1 6 198 2.35 9.6 20 225 2.64 10.9 25 256 2.97 12.4 29262 - - - - - - - - 105 2.04 5.1 8 246 2.37 11.9 27 279 2.64 13.5 32 315 2.96 15.2 38

    302 - - - - 87 1.77 4.2 6 132 1.95 6.4 12 267 2.23 12.9 31 299 2.45 14.5 37 334 2.77 16.1 43

    342 - - - - 95 1.78 4.6 4 102 1.91 4.9 4 297 2.23 14.3 25 332 2.50 16.1 31 370 2.78 17.9 37

    372 - - - - - - - - 134 1.93 6.5 5 322 2.30 15.6 24 364 2.53 17.6 30 404 2.79 19.5 36

    402 - - - - - - - - 151 1.94 7.3 6 360 2.26 17.4 29 404 2.47 19.5 36 448 2.75 21.6 44

    432 - - - - - - - - - - - - 396 2.30 19.1 35 444 2.52 21.5 43 489 2.78 23.6 51

    462 - - - - 128 1.74 6.2 4 227 1.95 11.0 12 451 2.30 21.8 44 505 2.54 24.4 55 553 2.78 26.8 65

    522 - - - - - - - - - - - - 493 2.26 23.8 52 550 2.47 26.6 64 605 2.75 29.2 76

    Legend LWT Leaving water temperature, C Qh Heating capacity, kW

    COP Coecient of performance, kW/kW q Condenser water flow rate, l/s p Condenser pressure drop, kPa

    Application data

    Standard units, refrigerant: R-410A Condenser entering/leaving water temperature difference: 5 K for LWT values

  • 7/25/2019 TP3 toplotna pumpa

    24/24

    Order No.: 13445-20.10.2012. Supersedes order No.: 13445-20.04.2011. Manufactured by: Carrier SCS, Montluel, France.