Wind, Water & Sun MIX Barcelona Metropolitan Area Project maig 2016

Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

Wind, Water & Sun MIXBarcelona Metropolitan Area Project

maig 2016

Page 2: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

Index

Wind, Water & Sun MIX

1. Recurs ER

2. Demanda d’Electricitat i Energia

3. LCOE, PV i Vent

4. Generació Renovable i Emmagatzematge d’Energia

5. Centrals Hidroelèctriques Reversibles

6. MIX RE WWS – Dades

7. Localitzacions

2J. Rebollo, Enginyer de Camins

Page 3: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

1. Recurs ER

Wind, Water & Sun MIX 3

Figura 1: Mapa de Recurs Eòlic d’Europa. Alçada d’eix a 80 m. AWS Truepower

J. Rebollo, Enginyer de Camins

Page 4: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

1. Recurs ER

Wind, Water & Sun MIX 4

Figura 2 Mapa de Recurs PV d’Europa.

J. Rebollo, Enginyer de Camins

Page 5: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

1. Recurs ER

Wind, Water & Sun MIX 5

Figura 3 Serie de viento horario del año 2013, del punto SIMAR (WANA) 2130146. Ministerio de Fomento.

J. Rebollo, Enginyer de Camins

Page 6: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

1. Recurs ER

Wind, Water & Sun MIX 6

Figura 4 Generación horaria. De 1 GW instalado en Barcelona (1.500 GWh/año). Año 2013.. Fuente J Rebollo 2015.

J. Rebollo, Enginyer de Camins

Page 7: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

2. Demanda d’Electricitat i Energia

7

Diagrama de Sankey Espanya (1 EJ = 277.777 GWh)

Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

Figura 6 Font: Universitat Pontifícia de Comillas 2013

Xarxa Elèctrica 1 EJ

Combustibles (Transport, Industria, altres,...)2 EJ

Figura 5 Distribución de Energía Consumida Mundial. Energy Statistics. IEA.2015.

El consumo mundial de energía de 9.301 MToe/año, equivalen a 108.170 TWh/año o 389,5 EJ/año

Page 8: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

2. Demanda d’Electricitat i Energia

8

Year Demand and RE Energy delivered Summary

Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

Figura 7 Demanda d’energia elèctrica (mesurada en barres) a Catalunya, acumulada en els últims 8 anys, Font: Institut Català de l’Energia 2015.

Page 9: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

9

Year Demand and RE Energy delivered Summary

Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

Figura 8 Evolució de la demanda acumulada de carburant (ktep) per a automoció, Institut Català de l’Energia 2015.. Al gener2008 màxim de 5.250 ktep (61.058 GWh); el mínim de 2013 amb 4.050 ktep (47.102 GWh); última dadaa finals del 2015 4.300 ktep (50.009 GWh). Per a convertir en VE x0,25 a x0,30. Font: Institut Català de l’Energia 2015.

2. Demanda d’Electricitat i Energia

Page 10: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

3. LCOE, PV i Vent

10Wind, Water & Sun MIX

Levelized Cost of Energy, LCOE, Cost Anivellat de l ’Energia, COE

J. Rebollo, Enginyer de Camins

Picture 9 Source: Wikipedia

Page 11: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

3. LCOE, PV i Vent

11Wind, Water & Sun MIX

Scenarios 1 & 2 , PV CAPEX & OPEX Reference

Energy Cost Analysis, LCOE: PV Standalone & 1-Axis Track

1-Axis Track

Stand Alone

J. Rebollo, Enginyer de Camins

Picture 10 Source: J Rebollo 2016

Page 12: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

12Wind, Water & Sun MIX

Energy Cost Analysis, LCOE: Wind On-Shore & Wind Of fshore

Scenarios 1 & 2 , Wind Offshore CAPEX & OPEX Reference

Wind Offshore

Wind On-shore

J. Rebollo, Enginyer de Camins

Picture 11 Source: J Rebollo 2016

3. LCOE, PV i Vent

Page 13: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

13Wind, Water & Sun MIX

Parity Grid, ¿sense abocament o amb abocament?

J. Rebollo, Enginyer de Camins

Picture 12 Source: EuPD Research & BDEW

3. LCOE, PV i Vent

Page 14: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

14Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

DESPLAÇAMEN EN EL

TEMPS DEL CONSUM

D’ENERGIA

GENERACIÓSUPERIOR A LA DEMANDA,AL MAGATZEM O ABOCAMENT

¿QUÉ PASSA AMB LA RESTA DE DEMANDA?

Picture 13 Source: J Rebollo 2016

4. Generació Renovable i Emmagatzematge

¿ABOCAMENT?

Page 15: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

15Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

GENERACIÓPV,INTERMITENT

Figura 14 Variabilidad generación PV. Campeche. Fuente EMAS CNA

4. Generació Renovable i Emmagatzematge

Page 16: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

16Wind, Water & Sun MIX

3. RE Generation, Grid & Storage

J. Rebollo, Enginyer de Camins

Figura 15 “The Duck Curve” Fuente CAISO

Page 17: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

17

Esquema de generació i demanda superposats.

Pictures representing Demand and RE Generation: Wind & PV

Operations between RE Generation & Storage (Time Shifting).

Wind, Water & Sun MIX

WIND

WIND

WIND

WIND

FROM STORAGE

STORAGE

J. Rebollo, Enginyer de Camins

Picture 16 Source: J Rebollo 2016

4. Generació Renovable i Emmagatzematge

Page 18: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

18

Year Demand and RE Energy delivered Summary

Picture 17 a (Energy Demand Year 2014 ) - (PV Generation with variable installed Power). X = Hour (1 year = 8760 h) ; Y = Power in MW; . Area = MWh. Y(+) Demand not covered with RE; Y(-); Energy Spilled. Source: J Rebollo, 2016

Picture 17 b (Energy Demand Year 2014 ) - (Offshore Wind Generation with variable installed Power). X = Hour (1 year = 8760 h); Y = Power in MW; Area = MWh. Y(+) Demand not covered with RE; Y(-); Energy Spilled. Source: J Rebollo, 2016

Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

4. Generació Renovable i Emmagatzematge

Page 19: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

5. Centrals Hidroelèctriques Reversibles

19

PHES World data (Cheapest Projects)

Figura Corba de Cost per MW instal·lat, C=0,6154 P. Elaboració pròpia.

Wind, Water & Sun MIX

Cheapest PHES in the world

0,615 MEur/MW

PHES in Scenario 1:

CAPEX (Loop) = 64,77 Eur/kWh

1,04 MEur/MW

PHES in Scenario 2:

CAPEX = 0

J. Rebollo, Enginyer de Camins

Picture 18 Source: J Rebollo 2016

Page 20: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

5. Centrals Hidroelèctriques Reversibles

20

Benchmarking CCGT (Barcelona)

Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

Picture 18 Source: J Rebollo 2016

Figura Resum de producció i facturació segons conceptes de serveis al Sistema Elèctric, de les CCGT de St. Adrià i el Port de BCN. Descomposicióentre mercat de Restriccions i mercat diari. Font: Elaboració Pròpia.

Page 21: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

5. Centrals Hidroelèctriques Reversibles

21Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

Energia

Restriccions

"a subir" Facturació % Preu Mig

(MWh) (Eur) (Eur/MWh)

139.254MWh 38.026.727 € 51% 273,07 Eur/MWh

1.409.764MWh 224.060.385 € 47% 158,93 Eur/MWh

604.704MWh 121.333.722 € 52% 200,65 Eur/MWh

451.839MWh 94.466.503 € 39% 209,07 Eur/MWh

399.119MWh 71.740.991 € 41% 179,75 Eur/MWh

3.004.681MWh 549.628.329 € 46% 182,92 Eur/MWh

Una CHR de 873 MW,

a 25 anys,

(per un r=5% i un Equity del 25%)

Project IRR del 9,5%

i TIR a l’inversor del 13,5%.

Figura Detall de figura anterior, dels pagaments per Serveis al Sistema en les Restriccions. Font: Elaboració Pròpia

Page 22: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

5. Centrals Hidroelèctriques Reversibles

22Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

Figura Resum Anàlisi fitxers P48 facturació Centrals Reversibles

2011 DATOS ANÁLISIS, (en el que parte del Turbinado no se conoce, por realizarse con unidades Hidráulicas)

Bombeo Turbinado T - B CB/VT

-95.972.666,03 € 122.124.520,40 € 26.151.854,37 € 0,786

-95.972.666,03 € P48 122.124.520,40 €

Rendimiento

Beneficio Hidroeléctrico

Bombeo B/Compra Turbinado T/Venta MWh Turbinado T/B PB/PT

-3.507.481 MWh 27,36 €/MWh 1.966.564 MWh 62,10 €/MWh 13,30 €/MWh <= 0,561 0,441

2010 DATOS ANÁLISIS, (en el que parte del Turbinado no se conoce, por realizarse con unidades Hidráulicas)

Bombeo Turbinado T - B CB/VT

-88.805.843,22 € 160.843.659,81 € 72.037.816,59 € 0,552

Rendimiento

Beneficio Hidroeléctrico

Bombeo B/Compra Turbinado T/Venta MWh Turbinado T/B PB/PT

-4.813.067 MWh 18,45 €/MWh 2.576.853 MWh 62,42 €/MWh 27,96 €/MWh <= 0,535 0,296

Page 23: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

23

Representació de les despeses unitàries dels Project es de CHR de l’entorn de Barcelona

Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

Picture 19 Source: J Rebollo 2016

Co

st p

er M

W I

nst

al·l

at

5. Centrals Hidroelèctriques Reversibles

Page 24: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

24

¿COM OPERA UNA CENTRAL HIDROELÈCTRICA AMB BOMBAMENT ?

Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

Picture 20 Source: Andritz 2012

5. Centrals Hidroelèctriques Reversibles

Page 25: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

25

RE MIX – Scenario 1 & 2

Wind, Water & Sun MIX

Picture 22 Source: J Rebollo 2016

5. RE MIX WWS - Dades

SISTEMA

ELÈCTRIC

GENERACIÓABOCAMENT

DEMANDA

TURBINATBOMBAMENT

XARXA

Page 26: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

26

Energy Cost Resume: 2 scenarios

Wind, Water & Sun MIX

5. RE MIX WWS - Dades

CAPEX SCENARIO 1 SCENARIO 2

PV Cost 1,30MEur/MW 1,30MEur/MW

Wind Offshore Cost 2,50MEur/MW 2,50MEur/MW

Turbin Cost 0,30MEur/MW 0,00MEur/MW

Pump Cost 0,35MEur/MW 0,00MEur/MW

Hores Magatzem Cost 25,00MEur/hGW 0,00MEur/hGW

O&M

Project Time Analisys 25years 25years

Demand Operation 1,0Eur/MWh 1,0Eur/MWh

PV Maintenance 6.500,0Eur/MW 6.500,0Eur/MW

PV Operation 9,0Eur/MWh 9,0Eur/MWh

Wind Offshore Maintenance 40.000,0Eur/MW 40.000,0Eur/MW

Wind Offshore Operation 7,0Eur/MWh 7,0Eur/MWh

Turbin Maintenance 12.000,0Eur/MW 12.000,0Eur/MW

Turbin Operation 6,0Eur/MWh 6,0Eur/MWh

Pump Maintenance 14.000,0Eur/MW 14.000,0Eur/MW

Pump Operation 1,0Eur/MWh 1,0Eur/MWh

Spill Operation 0,0Eur/MWh 0,0Eur/MWh

Importation Cost 200,0Eur/MWh 200,0Eur/MWh

Discount Rate, r 5% 5%

RE Sources Capacity Factor

Scenario 1 & 2:

PV = 1,500 h/year

Wind Offshore = 4,200 h/year

J. Rebollo, Enginyer de Camins

Picture 21 Source: J Rebollo 2016

Page 27: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

27

RE MIX – Scenario 1 & 2

Wind, Water & Sun MIX

RE MIX, pv=Photovoltaic; WOFFs = Wind Ofshore; T=Turbine; B=Pump % ENERGY

FROM GRID

PUMPED STORE TIME ON A CLOSED LOOP ON TOP RESERVOIR

8,00h/GW 12,00h/GW 16,00h/GW 20,00h/GW 24,00h/GW 30,00h/GW 40,00h/GW

12,35GW 11,24GW 10,50GW 9,83GW 9,50GW 9,05GW 8,10GW PV 0,00%

10,82GW 8,18GW 6,99GW 6,11GW 5,74GW 5,28GW 4,86GW WOFFs

4,15GW 4,15GW 4,15GW 4,15GW 4,15GW 4,15GW 4,15GW T

18,19GW 14,87GW 13,16GW 11,79GW 11,18GW 10,39GW 9,20GW B

10,67GW 10,49GW 10,03GW 10,10GW 9,84GW PV 2,50%

4,56GW 3,83GW 3,53GW 3,20GW 3,18GW WOFFs

4,15GW 4,15GW 4,15GW 4,15GW 4,15GW T

11,12GW 10,30GW 9,65GW 9,41GW 9,16GW B

9,12GW 8,56GW 8,25GW 8,07GW 8,02GW PV 5,00%

4,14GW 3,81GW 3,61GW 3,44GW 3,36GW WOFFs

4,15GW 4,15GW 4,15GW 4,15GW 4,15GW T

9,42GW 8,64GW 8,19GW 7,89GW 7,77GW B

7,48GW 7,29GW 7,26GW 7,22GW 7,22GW PV 10,00%

3,49GW 3,27GW 3,11GW 3,05GW 3,01GW WOFFs

4,15GW 4,15GW 4,15GW 4,15GW 4,15GW T

7,43GW 7,06GW 6,89GW 6,81GW 6,77GW B

8,07GW 8,01GW 7,98GW 7,96GW 7,96GW PV 15,00%

2,58GW 2,49GW 2,45GW 2,43GW 2,42GW WOFFs

4,15GW 4,15GW 4,15GW 4,15GW 4,15GW T

7,12GW 6,98GW 6,92GW 6,88GW 6,87GW B

7,63GW 7,63GW 7,62GW 7,62GW 7,61GW PV 25,00%

1,96GW 1,93GW 1,92GW 1,92GW 1,91GW WOFFs

4,16GW 4,16GW 4,16GW 4,16GW 4,16GW T

6,18GW 6,15GW 6,14GW 6,13GW 6,12GW B

5,50GW 5,46GW 5,49GW 5,46GW 5,45GW PV 50,00%

1,09GW 1,10GW 1,08GW 1,09GW 1,09GW WOFFs

4,21GW 4,21GW 4,21GW 4,21GW 4,21GW T

3,57GW 3,55GW 3,56GW 3,54GW 3,53GW B

Picture 22 Source: J Rebollo 2016

5. RE MIX WWS - Dades

Page 28: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

28

Year Demand with RE Energy MIX delivered (10% elect ricity from grid)Picture 23 (Energy Demand Year 2014 ) - (PV & Offshore Wind Generation with variable installed Power). X = Hour (1 year = 8760 h); Y = Power in MW; Area = MWh. Y(+) Demand not covered with RE; Y(-); Energy Spilled. Source: J Rebollo, 2016

Wind, Water & Sun MIX

5. RE MIX WWS - Dades

Page 29: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

29

Year Demand with RE Energy MIX delivered (10% elect ricity from grid)Picture 24 The Pumps work 3604 h/year & the turbines 3441 h/year (CF=41%). Source: J Rebollo, 2016

Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

5. RE MIX WWS - Dades

Page 30: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

30

Year Demand with RE Energy MIX delivered (10% elect ricity from grid)Picture 25 Source: J Rebollo, 2016

Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

5. RE MIX WWS - Dades

Page 31: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

31

Year Demand with RE Energy MIX delivered (10% elect ricity from grid)Picture 26 Source: J Rebollo, 2016

Wind, Water & Sun MIX

DEMANDED ELECTRICITY COST (Eur/MWh), with spill of obvergenerated energy

0=Storage Battery

PV+W OffShore PV+W OffShore 0=PV 0=WOff

% ENERGY

FROM GRID 0,00h/GW 5,00h/GW 8,00h/GW 8,00h/GW

0,00% 487,9Eur/MWh 415,0Eur/MWh 311,8Eur/MWh

2,50% 235,4Eur/MWh 263,4Eur/MWh 199,3Eur/MWh

5,00% 1.036,4Eur/MWh 219,5Eur/MWh 231,2Eur/MWh 169,8Eur/MWh

10,00% 307,9Eur/MWh 197,2Eur/MWh 170,5Eur/MWh 154,9Eur/MWh

15,00% 185,1Eur/MWh 196,0Eur/MWh 190,2Eur/MWh 142,2Eur/MWh

25,00% 122,2Eur/MWh 190,7Eur/MWh 127,1Eur/MWh 146,8Eur/MWh

50,00% 135,9Eur/MWh 136,6Eur/MWh 138,0Eur/MWh 162,2Eur/MWh

ELECTRICITY COST, EV included, without spill

0=Storage Battery

PV+W OffShore PV+W OffShore 0=PV 0=WOff

% ENERGY

FROM GRID 0,00h/GW 5,00h/GW 8,00h/GW 8,00h/GW

0,00% 243,0Eur/MWh 71,2Eur/MWh 108,8Eur/MWh

2,50% 144,1Eur/MWh 72,5Eur/MWh 111,0Eur/MWh

5,00% 62,9Eur/MWh 165,6Eur/MWh 78,1Eur/MWh 113,8Eur/MWh

10,00% 66,2Eur/MWh 165,7Eur/MWh 78,2Eur/MWh 117,6Eur/MWh

15,00% 72,0Eur/MWh 174,3Eur/MWh 109,8Eur/MWh 115,3Eur/MWh

25,00% 90,6Eur/MWh 177,5Eur/MWh 98,2Eur/MWh 131,2Eur/MWh

50,00% 132,2Eur/MWh 132,7Eur/MWh 138,2Eur/MWh 153,4Eur/MWh

J. Rebollo, Enginyer de Camins

5. RE MIX WWS - Dades

Page 32: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

32

Energy Investment and needed Storage in a loop – Sce nario 1

Wind, Water & Sun MIX

TOTAL INVESTMENT t=0 (MEur)

PUMPED STORE TIME ON A CLOSED LOOP ON TOP RESERVOIR % ENERGY

8,00h/GW 12,00h/GW 16,00h/GW 20,00h/GW 24,00h/GW 30,00h/GW 40,00h/GW FROM GRID

54.365,54MEur 45.985,78MEur 42.232,85MEur 39.317,79MEur 38.570,43MEur 37.647,04MEur 36.352,41MEur 0,00%

32.629,31MEur 31.144,47MEur 30.339,59MEur 30.377,14MEur 30.676,51MEur 2,50%

28.847,45MEur 27.722,25MEur 27.326,94MEur 27.240,05MEur 27.652,13MEur 5,00%

23.779,16MEur 23.480,50MEur 23.623,57MEur 24.051,31MEur 24.579,84MEur 10,00%

22.101,22MEur 22.426,93MEur 22.929,38MEur 23.513,00MEur 24.160,39MEur 15,00%

19.456,97MEur 19.987,28MEur 20.564,65MEur 21.148,56MEur 21.736,82MEur Investment 25,00%

13.092,63MEur 13.406,84MEur 13.785,19MEur 14.093,75MEur 14.423,38MEur 50,00%

TOTAL STORAGE (MWh) = Pump Power x Time x 0,8 (complet loop losses)

PUMPED STORE TIME ON A CLOSED LOOP ON TOP RESERVOIR % ENERGY

8,00h/GW 12,00h/GW 16,00h/GW 20,00h/GW 24,00h/GW 30,00h/GW 40,00h/GW FROM GRID

116.444,4MWh 142.767,9MWh 168.431,8MWh 188.699,4MWh 214.693,9MWh 249.292,4MWh 294.285,1MWh 0,00%

71.159,7MWh 98.918,8MWh 123.468,3MWh 150.533,7MWh 175.894,0MWh 2,50%

60.280,3MWh 82.950,7MWh 104.793,6MWh 126.181,0MWh 149.175,9MWh 5,00%

47.546,7MWh 67.812,7MWh 88.244,4MWh 108.989,6MWh 129.996,9MWh 10,00%

45.539,3MWh 67.040,5MWh 88.562,9MWh 110.103,9MWh 131.937,5MWh 15,00%

39.530,7MWh 59.048,1MWh 78.565,5MWh 98.047,3MWh 117.493,5MWh Needed Storage 25,00%

22.850,6MWh 34.043,5MWh 45.595,7MWh 56.607,7MWh 67.764,2MWh 50,00%

J. Rebollo, Enginyer de Camins

Picture 27 Source: J Rebollo, 2016

5. RE MIX WWS - Dades

Page 33: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

33

Energy Cost Resum – Scenario 1

Wind, Water & Sun MIX

5. RE MIX WWS - DataDEMANDED ELECTRICITY COST (Eur/MWh), with spill of obvergenerated energy

PUMPED STORE TIME ON A CLOSED LOOP ON TOP RESERVOIR % ENERGY

8,00h/GW 12,00h/GW 16,00h/GW 20,00h/GW 24,00h/GW 30,00h/GW 40,00h/GW FROM GRID

213,8Eur/MWh 179,2Eur/MWh 163,4Eur/MWh 151,2Eur/MWh 147,4Eur/MWh 142,6Eur/MWh 136,3Eur/MWh 0,00%

132,6Eur/MWh 125,7Eur/MWh 121,9Eur/MWh 121,1Eur/MWh 121,6Eur/MWh 2,50%

123,1Eur/MWh 118,0Eur/MWh 115,9Eur/MWh 114,9Eur/MWh 115,8Eur/MWh 5,00%

113,8Eur/MWh 112,0Eur/MWh 112,0Eur/MWh 113,0Eur/MWh 114,4Eur/MWh 10,00%

125,3Eur/MWh 125,5Eur/MWh 126,7Eur/MWh 128,3Eur/MWh 130,1Eur/MWh 15,00%

126,2Eur/MWh 127,7Eur/MWh 129,3Eur/MWh 131,0Eur/MWh 132,7Eur/MWh Average Cost 25,00%

151,2Eur/MWh 152,1Eur/MWh 153,2Eur/MWh 154,1Eur/MWh 155,0Eur/MWh 50,00%

ELECTRICITY COST, EV included, without spill

PUMPED STORE TIME ON A CLOSED LOOP ON TOP RESERVOIR % ENERGY

8,00h/GW 12,00h/GW 16,00h/GW 20,00h/GW 24,00h/GW 30,00h/GW 40,00h/GW FROM GRID

81,7Eur/MWh 85,5Eur/MWh 88,6Eur/MWh 91,5Eur/MWh 93,9Eur/MWh 97,5Eur/MWh 102,3Eur/MWh 0,00%

90,6Eur/MWh 94,8Eur/MWh 97,7Eur/MWh 101,2Eur/MWh 103,4Eur/MWh 2,50%

93,1Eur/MWh 96,0Eur/MWh 98,5Eur/MWh 101,1Eur/MWh 103,4Eur/MWh 5,00%

98,2Eur/MWh 101,0Eur/MWh 103,7Eur/MWh 105,8Eur/MWh 107,9Eur/MWh 10,00%

115,0Eur/MWh 117,3Eur/MWh 119,5Eur/MWh 121,4Eur/MWh 123,4Eur/MWh 15,00%

119,6Eur/MWh 121,6Eur/MWh 123,3Eur/MWh 125,1Eur/MWh 126,8Eur/MWh Average Cost Etot 25,00%

147,5Eur/MWh 148,5Eur/MWh 149,6Eur/MWh 150,6Eur/MWh 151,6Eur/MWh 50,00%

J. Rebollo, Enginyer de Camins

Picture 28 Source: J Rebollo, 2016

Page 34: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

34

Investment Resum – Scenario 2

Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

Picture 29 Source: J Rebollo, 2016

5. RE MIX WWS - Dades

PUMPED STORE TIME ON A CLOSED LOOP ON TOP RESERVOIR % ENERGY

8,00h/GW 12,00h/GW 16,00h/GW 20,00h/GW 24,00h/GW 30,00h/GW 40,00h/GW FROM GRID

43.113,53MEur 35.074,13MEur 31.118,73MEur 28.048,07MEur 26.702,49MEur 24.976,07MEur 22.692,20MEur 0,00%

25.268,96MEur 23.201,78MEur 21.860,05MEur 21.134,97MEur 20.728,35MEur 2,50%

23.667,12MEur 22.105,80MEur 21.186,69MEur 20.536,68MEur 20.271,03MEur 5,00%

18.448,06MEur 17.643,95MEur 17.207,93MEur 17.016,17MEur 16.902,63MEur 10,00%

16.942,62MEur 16.642,66MEur 16.495,08MEur 16.418,66MEur 16.387,17MEur 15,00%

14.811,68MEur 14.740,69MEur 14.712,55MEur 14.691,06MEur 14.674,55MEur Investment 25,00%

9.866,25MEur 9.839,34MEur 9.850,85MEur 9.823,95MEur 9.807,89MEur 50,00%

0=PV 0=WOff

8,00h/GW 8,00h/GW

85.050,00MEur 60.512,18MEur

52.631,48MEur 37.353,20MEur

55.240,39MEur 31.957,27MEur

30.340,48MEur 25.689,78MEur

23.066,03MEur 22.868,56MEur

15.238,00MEur 18.335,67MEur

7.263,14MEur 11.763,90MEur

Page 35: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

35

Energy Cost Resum – Scenario 2

Wind, Water & Sun MIXJ. Rebollo, Enginyer de Camins

Picture 29 Source: J Rebollo, 2016

5. RE MIX WWS - Dades

PUMPED STORE TIME ON A CLOSED LOOP ON TOP RESERVOIR % ENERGY

8,00h/GW 12,00h/GW 16,00h/GW 20,00h/GW 24,00h/GW 30,00h/GW 40,00h/GW FROM GRID

181,0Eur/MWh 147,4Eur/MWh 131,0Eur/MWh 118,4Eur/MWh 112,8Eur/MWh 105,7Eur/MWh 96,5Eur/MWh 0,00%

111,2Eur/MWh 102,6Eur/MWh 97,2Eur/MWh 94,2Eur/MWh 92,6Eur/MWh 2,50%

108,0Eur/MWh 101,7Eur/MWh 98,0Eur/MWh 95,3Eur/MWh 94,3Eur/MWh 5,00%

98,3Eur/MWh 95,0Eur/MWh 93,3Eur/MWh 92,5Eur/MWh 92,1Eur/MWh 10,00%

110,3Eur/MWh 108,6Eur/MWh 108,0Eur/MWh 107,6Eur/MWh 107,5Eur/MWh 15,00%

112,7Eur/MWh 112,4Eur/MWh 112,3Eur/MWh 112,2Eur/MWh 112,1Eur/MWh Average Cost 25,00%

141,8Eur/MWh 141,7Eur/MWh 141,7Eur/MWh 141,6Eur/MWh 141,6Eur/MWh 50,00%

ELECTRICITY COST, EV included, without spill

PUMPED STORE TIME ON A CLOSED LOOP ON TOP RESERVOIR % ENERGY

8,00h/GW 12,00h/GW 16,00h/GW 20,00h/GW 24,00h/GW 30,00h/GW 40,00h/GW FROM GRID

69,2Eur/MWh 70,4Eur/MWh 71,0Eur/MWh 71,6Eur/MWh 71,9Eur/MWh 72,3Eur/MWh 72,4Eur/MWh 0,00%

76,0Eur/MWh 77,3Eur/MWh 77,9Eur/MWh 78,7Eur/MWh 78,8Eur/MWh 2,50%

81,7Eur/MWh 82,7Eur/MWh 83,3Eur/MWh 83,9Eur/MWh 84,2Eur/MWh 5,00%

84,8Eur/MWh 85,7Eur/MWh 86,4Eur/MWh 86,6Eur/MWh 86,9Eur/MWh 10,00%

101,2Eur/MWh 101,6Eur/MWh 101,8Eur/MWh 101,9Eur/MWh 101,9Eur/MWh 15,00%

106,8Eur/MWh 107,0Eur/MWh 107,1Eur/MWh 107,1Eur/MWh 107,2Eur/MWh Average Cost Etot 25,00%

138,4Eur/MWh 138,4Eur/MWh 138,4Eur/MWh 138,4Eur/MWh 138,5Eur/MWh 50,00%

Page 36: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

6. Localitzacions

36

Àrea màxima disponible per a generació offshore flotant, fins a 2.000 m de fondària. 4.210 km2. Possibles distribucions d’aerogeneradors amb una densitat de potència de 5

MW/km2.

Wind, Water & Sun MIX

Page 37: Wind, Water & Sun MIX Barcelona Metropolitan Area …Figura 2 Mapa de Recurs PV d’Europa. J. Rebollo, Enginyer de Camins 1. Recurs ER Wind, Water & Sun MIX 5 Figura 3 Serie de viento

37

Picture: PHES Locations and Transport Grid

Wind, Water & Sun MIX

6. Localitzacions