Upload
nsw-resources-energy
View
151
Download
2
Embed Size (px)
Citation preview
www.centennialcoal.com.au
Booster Fans Angus Place Colliery
BJ Cutting
Manager of Electrical Engineering Angus Place
Centennial Angus Place
2
Scone
Rylstone
Mudgee
Muswellbrook
Singleton
Maitland
Newcastle
Lithgow
Gosford
SYDNEY Katoomba
Berrima Wollongong Port Kembla
Kiama Moss Vale
Angus Place
Introduction
3
• Mine established in 1978 • Mining the Lithgow seam • No history of methane or spontaneous combustion in Lithgow
Seam • Currently developing the Angus Place East Area which is an
expansion of Angus Place workings to 2031 • Planned production averages 3.5 Mtpa with longwall extraction • New Angus Place East ventilation facilities currently being
constructed. • Shaft No.1 due for commissioning in January 2015 • Current ventilation into Angus Place East was not sufficient to
support anticipated mining operations.
Process
4
• It was identified that a Booster Fan would be required to provide adequate ventilation to the Angus Place East area until the completion of the new ventilation shaft no.1.
• Angus Place investigated what fan options where available within the industry that would suit the Angus Place short term application. (6-9 months)
• Identified 5 possible locations where the Booster Fans could be installed.
• Ventsim software was used to model the 5 selected Booster Fan locations.
• The decision was then made to install the Booster Fan in an intake airway not a return airway like other Booster Fan installations.
Booster Fan Locations Investigated
5
1. At the intake panel entry of 910 (preferred option) 2. In the return outbye in 910 panel 3. At the 910 install road 4. Inbye 910N intake 5. Inbye 910N return
1 2 3 5
4
Mine Plan
6
Current Angus Place Workings
Future Angus Place East Workings
New Upcast and Downcast Shafts
Booster Fan Location
Process
• Angus Place conducted a risk assessment to identify the risks associated with a booster fan installation.
• Key Outcomes from the Risk Assessment. – Legislative requirements.(Design and Item Registration) – Organise meetings with key stakeholders.
• Department of Trade and Investment • Fan Manufacturers
– Develop a functional specification for the operation of the Booster Fan.
– Short timeframe for the Booster Fan Installation. – Additional work required outside the Booster Fan scope.
(ventilation devices)
• Visited other mining operations with in service booster fan installations to assist with the equipment selection process.
7
Meeting with Department of Trade and Investment
• To obtain an understanding of how the department viewed a Booster Fan Installation in an intake airway and to make the process as smooth as possible.
– Could we treat it like a conveyor installation? Not a Booster Fan installation.
– Was there a requirement to apply for Design and Item Registration?
– Was it a High Risk Activity? – How would the department see the registration process moving
forward. – Was there anything that they could see being a show stopper?
8
Equipment Selection
9
• 3 x 110 kW Clemcorp axial fans in parallel • Ability to run either 2 or 3 fans in parallel due to fitment of self
closing doors in each fan duct – Eliminates recirculation in the event of a single fan failure
• Fans used extensively in underground metalliferous mines as booster fans.
• Nickel Brass alloy impellers and mild steel ducting. • Modular design ensures quick and simple installation.
Existing Fan Installation in a Metaliferous Mine
10
Brass Nickel Impeller
11
Positives - Preferred Option
• Reduced risk compared to an installation in a return airway. • Legislation requirements.
– Less departmental requirements ? (was the thought process)
• Easier installation – Access restricted in the belt road. – Parallel Installation. – No loss of production.
• Reduced pressure across the coffin seal.
12
Negatives - Preferred Option
• Restricted access around Booster Fans – Vehicle access through double ventilation doors. – Process to get larger pieces of equipment through double
doors. – People and machine movement around and past Booster Fans.
• Airborne dust – Along 910 travelling road. – Migrating into 1000 district production units.
13
Functional Specification
• If the main vent fan stops the booster fan is to stop immediately. • If any fan selected to run stops, all other booster fans stop. • If the booster fans stop the C910 conveyor is to be inhibited. • Environmental monitoring of CH4 and CO, if levels are detected
above the pre-set values all booster fans stop. • Any failure of ventilation inbye or outbye of the booster fan
installation, will cause all booster fans to stop. – Stopping Failure – Access or by-pass doors not in their correct position.
• If ventilation pressures are outside of the intended tolerances all booster fan are to stop.
• If the booster fans stop all power inbye of booster fans is turned off.
14
Functional Safety Assessment
15
Booster Fan Setup
• Bypass Doors open if the Booster Fans are stopped – Proximity sensors to monitor position of bypass doors and machine
access doors.
• Vibration and Temperature monitoring on all fans • CO and CH4 monitoring inbye and outbye of fans • Differential pressure monitoring across
– Fan Bulkhead – Coffin Seal – 19C/T 303 District
• Fans set to trip on any one failure of system components • Monitoring alarms in control room
16
Booster Fan Setup
17
BYPASS DOORS
D
D
Belt Road
Return Road
PNEUMATIC ACCESS DOORS
COFFIN SEAL
Booster Fan Monitoring
18
PROXIMITY SENSORS
D
D
Belt Road
Return Road
PRESSURE MONITORING
CO & CH4 MONITORING
Fans Installed at Angus Place
19
Bulkhead Self Closing Fan Doors
20
Bypass Doors & Pneumatic Machine Access Doors
21
PNEUMATIC MACHINES
ACCESS DOORS
VENTILATION BYPASS DOORS
Potential Hazards Identified in Risk Assessment
22
• Booster Fan not turning off when Main Fan stops • Inability to conduct maintenance caused by insufficient access
around Booster Fan • Fire on Booster Fan • Damage to Bypass Doors • Insufficient air reaching Booster Fan due to failure of
Ventilation Control Device outbye of 910N • Complete failure of Booster Fan • Partial failure of Booster Fan • Increased dust caused by increased air velocity in 910N • Noise generated from booster fans
Citect Display / Remote Monitoring
23
Booster Fan Starter
24
Booster Fan Starter
25
Commissioning
26
Electrical Commissioning Sheet 0 Fans 1 Fan 2 Fans 3 Fans Settings (3 Fans Opperational) Reading Expected Actual Expected Actual Expected Actual Expected Actual Setting Type Setting Value
Bypass Doors Open Open Closed Closed Closed Closed Closed Closed Access Door 1 (outbye) Closed Closed Closed Closed Closed Closed
1 of 3 Closed Closed
Access Door 2 (middle) Open Open Open Open Open Open Open Access Door 3 (inbye) Closed Closed Closed Closed Closed Closed Closed Coffin Seal Pressure 1148 1270 780 784 350 490 Trip/Alarm Low Alarm/Trip High 300/400 900/1000 19 c/t, 303 Stopping Pressure 1727 1750 1500 1409 1255 1240 Trip/Alarm Low Alarm/Trip High 400/500 1600/1700 Booster Fan Pressure 0 0 890 1240 2010 2020 Trip/Alarm Low Alarm/Trip High 900/1000 2400/2500 Gas Sensor- CO inbye 0 0.2 0 0.2 0 0.2 Alarm Trip 15 ppm 25ppm Gas Sensor- CO outbye 0 0.2 0 0.2 0 0.2 Alarm Trip 15 ppm 25ppm Gas Sensor- CH4 inbye 0 0 0 0 0 0 Alarm Trip 0.25% 0.50% Gas Sensor- CH4 outbye 0 0 0 0 0 0 Alarm Trip 0.25% 0.50% Bypass Timer (minutes for pressurisation) 5 mins 5 mins 5 mins 5 mins Timer Values (T1/T2) 6 mins 6 mins Fan 1 Axial Vibration Sensor 1.01 mm/s Alarm Trip 6 mm/s 8 mm/s Radial Vibration Sensor 1.02 mm/s Alarm Trip 6 mm/s 8 mm/s DE Bearing Temperature Sensor 41 ᵒC Alarm Trip 60 ᵒC 80 ᵒC NDE Bearing Temperature Sensor 45 ᵒC Alarm Trip 60 ᵒC 80 ᵒC Winding Temperature Sensor 1 61 ᵒC Alarm Trip 85 ᵒC 120 ᵒC Winding Temperature Sensor 2 62 ᵒC Alarm Trip 85 ᵒC 120 ᵒC Winding Temperature Sensor 3 60 ᵒC Alarm Trip 85 ᵒC 120 ᵒC Fan 2 Axial Vibration Sensor 1.02 mm/s Alarm Trip 6 mm/s 8 mm/s Radial Vibration Sensor 0.90 mm/s Alarm Trip 6 mm/s 8 mm/s DE Bearing Temperature Sensor 44 ᵒC Alarm Trip 60 ᵒC 80 ᵒC NDE Bearing Temperature Sensor 44 ᵒC Alarm Trip 60 ᵒC 80 ᵒC Winding Temperature Sensor 1 59 ᵒC Alarm Trip 85 ᵒC 120 ᵒC Winding Temperature Sensor 2 60 ᵒC Alarm Trip 85 ᵒC 120 ᵒC Winding Temperature Sensor 3 60 ᵒC Alarm Trip 85 ᵒC 120 ᵒC Fan 3 Axial Vibration Sensor 1.03 mm/s Alarm Trip 6 mm/s 8 mm/s Radial Vibration Sensor 0.99 mm/s Alarm Trip 6 mm/s 8 mm/s DE Bearing Temperature Sensor 42 ᵒC Alarm Trip 60 ᵒC 80 ᵒC NDE Bearing Temperature Sensor 44 ᵒC Alarm Trip 60 ᵒC 80 ᵒC Winding Temperature Sensor 1 61 ᵒC Alarm Trip 85 ᵒC 120 ᵒC Winding Temperature Sensor 2 60 ᵒC Alarm Trip 85 ᵒC 120 ᵒC Winding Temperature Sensor 3 62 ᵒC Alarm Trip 85 ᵒC 120 ᵒC Noise Level (dBA) (Starter/Fan Guarding) 83/95 83/95
Ventilation Survey
27
Location
Ventsim Q Vensim P Measured V Measured Q Measured P Ventsim Q Vensim P Measured V Measured Q Measured P Ventsim Q Vensim P Measured V Measured Q Measured P
910N 4 - 6 C/T 14.98 65 1139 62.78 77 1600 91 2250
910N 16 - 17C/T 16 61 690 59 750 @ 17 C/T 72 970 4.6 73.6 1110 85 1362 4.85 77.6 1260
910N 35-36 C/T 15.5 49 83 45 100 @ 35 C/T 58 117 3.6 55.8 125 69 165 3.9 60.45 150
910 0-1C/T 3 hdg 15.36 78 1188 74 89 5.9 90.624 102 6.2 95.232
910N Regulator 9.6 82 78.7 92 9.8 94.08 104 10 96
910N Coffin Seal 9 1148 1270 7 780 770 5 350 490
82 91 890 1290 111 2010 2020
1
900 7 - 8 C/T 15.51 71 460 71.3 400 @ 8C/t 66 395 4.1 63.591 350 60 320 3.85 59.7135 270
LW Face 34 32 29
303 19C/T 1727 1750 1500 1400 1255 1240
Main Fan 220 223 227
303 regulator 77 960 970 740 700
No Fans Bypass Open 2 Fans Running 3 Fans Running
Fan Bulkhead (D/D Closed)
Fan Bulkhead (D/D Open)
Item Registration
28
Plant Registration - Exemption
29
Start-up Sequence
30
Acknowledgements
• Shane McClure & Scott Wyborn - Centennial Coal.
• Clemcorp Australia. • Simon Fulton & Grant Waring – ATF. • Mike Taylor – Advitech. • Marcus Punch.
31
www.centennialcoal.com.au
Thank You