00225647

Embed Size (px)

Citation preview

  • 8/13/2019 00225647

    1/5

    A SIMULATION MODEL FOR TRANSFORMER INTERNAL FAULTS, BASE FOR THE STUDY OF PROTECTION ANDMONITORINGSYSTEMS

    P. Bertrand *, A. Devalland **, P. Bastard **** Merlin-Gerin, ** France-Transfo, *** Ecole Sue rie ure dElectrici t6. FranceINTRODUCTIONThe s tudy of in temal faul t s in transformers, i .e. thecalculation of the fault current and i ts external detection(phase currents) as a function of the location and theamplitude of the fault, is of great interest from severalpoints of view :- evaluation of protection devices efficiency in order to

    get improvement.diagnosis of a true fault using cu rrent recordings.preventive action when manufacturing transformers,and at f i rs t heavy duty ones (e .g . arc furnacetransformers), consist ing of reinforced insulation inmeas where faults may be difficult to detect.

    --

    Our main purpose was to develop a transformer differentialprotection, with improved internal fault detection. It is thereason why we have tried to get a deep insight into thephenomenon.Although several measuring results appear in publications((11, [2]), the studies are recent and the papers remainincomplete [31.This situation has led us to manufacture a special, multipleoutput transformer. This device, designed on the basis of a100 kVA M V LV transformer, has enabled us to cany outnumerous turn-to-turn and turn-to-earth short-circuits.In association with these tests we have developed a digitalmodel of the t ransformer , val idated by the actualmeasurements.This model, when applied to a HV network transformer, hasenabled the efficiency of the usual protection devices to beexamined, in particular that of the transformer differentialprotection.1.CARRIEDOUT M E A S U R E EDescriotion of the test transformerThis transformer was manufactured by France-Transfo onthe basis of a distribution transformer for which thespecification is as follows :

    rated power : 100 kVAtransformation ratio : 5500V / 410Vcoupling : y nshort-circuit voltage : 3.96%LV winding : 67 turns wound in 2 layers

    -The external coil is fitted with taps as shown in figure 1.

    HV winding : 1556 turns wound in 8 layers

    layer : 1 2 3 4 5 6 7f igure : detai l s of a n H V wi n d i n gRecordind methodThe short circuits were simulated by closing a contactor.The tested transformer was supplied at reduced voltage by anautot ransformer wi red in ser ies wi th an i so lat ingtransformer.Eight measurement channels connected to a PC enabledrecording of the supply voltages, the phase currents and thefault current, triggered by the contactor closing.Turn-to-tum faults

    f i g u re 2 : c u r r e n t d i s t r ib u t i o n i n t h e w i n d i n g sThe recorded currents are reduced to the rated voltage, thenexpressed in per unit values, taking the primary ratedcurrent as reference.At first, the origin of the fault is fixed as being on a phaseterminal of the transformer and the number of short-circuited turns varies. The current in one phase and thecurrent in the fault are shown in figure 3.When a largenumber of turns are short-circuited, the current is mostlyl imi ted by the short c i rcui t power supplying thetransformer; the high values of recorded current show thatthis short-circuit power is high.

    . L I .

  • 8/13/2019 00225647

    2/5

    x In I6

    4

    200

    20 4 6 80 100span of the fault

    figure 3 : turn-to-turn fault : span influenceThen, the span of the fau lt remains fixed to half a layer (thatis 6 25 of the winding), and its origin moves. It can benoticed that the fault position in the winding has very littleeffect, at least for this type of winding technology.

    xInso

    4

    30

    2010

    2 4 6 8 100location of the fault

    figure 4 : turn-to-turn fault : location influence

    20 40 60 80 100location of the faultf i g ure : t urn- t o - ea r t h f a u l t : l o c a t i o ni n f l u e n c eConclus ienThe results presented here give a synthetic view of themeasurements carried out. Nevertheless, it is difficult toreach any practical conclusion because the results depend alot both o n the testing conditions (short circuit power ofthe test circuit) and on the transformer (low power, thushigh winding resistance). It is essential to generalize theresults by calculation.2. MODEL OF I NTERN LFAULTPurpose of the modelThis digital model enables the results obtained with the 100kVA test transformer to be extended to HV networktransformers.It has been validated by the measurements. It thus fits wellto tranformers wound in l o n g layers. It could also beextended to other types of windings, through an additionalexperimental validation operation.

    Tum-to-earth faults Two requirements have steered us in the production of themodel :- ease of use, which implies first the use of available data

    o n l y ,compatibility with a standard transient program.

    Consequently, the model produced is an extension of thetransformer model of EMTP (Electromagnetic Transient

    2 E Program).Calculation nnnc&EMTP gives the opportunity of modeling the transformerby coupled circuits. An auxil iary routine, BCTRAN,calculates the [R.L] matrix from the results of the no-loadand short circuit tests of the transformer [4]

    . . .

    ET$E

    figure 5 : current distribution in the windingsThe position of the fault along the winding moves. Thefault current and the current in one phase are shown infigure 6.

    The principle used to calculate a turn-to-turn or turn-to-earthfault is to split the faulty winding. Thus the initial matrixrepresenting a three phase transformer (6 windings) is a

    1 . 2 1 . 2

  • 8/13/2019 00225647

    3/5

    6x6 matrix;it becom es a 7x7 matrix to study a turn-to-earthfault and an 8x8 matrix for a turn-to-turn fault. Oncecalculated, these matrices are directly used by E M F , as anyother element.

    of a windine.

    In order to explain the calculationcarried out, we chose as an example tosplit winding nO1.The initial values calculated from the no-load and shortcircuit tests of the transformer are the self inductances ofthe w indings, L 1 et L2. a s well as the mutual inductanceM12. Splitting winding 1 involves calculating the new selfinductances, L1' et L1 and mutual inductances, M1'1 ,M i 7 3 M i 2 .These inductances can be calculated from two leakagefactors; these factors are of great importance ; the precisionof the model is directly linked to the precision of theirevaluation.- 01'1 is the leaka ge factor between windings 1' and 1 .- 01'2 is the leakage factor between the largest of the twowindings 1' and 1 and the secondary winding.Using these factors, calculations can be carried on, basedon two simple principles :- self-consistency : the connection in series of windings

    1' and 1 must enable the initial results to be met.- proportionality : the transformation ratio between

    windings 1' and 1 is equal to the turn ratio (goodapproximation in equation 5 below).

    M;ls, dispersions1 q , l , ,= l - -L1, .LIS.

    Table o f init ia l equat ions

    1 0 M y , = M l z - M r ~Table of f inal equat ions

    The leakage inductance between two coils can be calculatedfrom the electromagnetic energy stored in the coils. This issimplified by the following hypotheses :

    - no saturation phenomena occurs.

    current density is constant in the windings,field H is parallel to the axis of the core,field H is symmetric in relation to the core axis,

    This calculation has been extensively detailed. We givebelow a reminder of the way to get the leakage inductancebetween the primary and the secondary winding of atransformer:

    first of all, the shape of field is plotted (figure 8).- the stored energy in the windings can then be calculated

    depending on their dimensions :W = h j j j H 2 d v + ~ ~ j j H Z d v + h j j j H 2 d v ,where va,vb and vc are the respective volumes of theinternal winding, the inter-winding space and of theexternal winding.- f inally the total leakage inductance reduced towinding 1, LCC, is calculated using the equationW =-Lcc .i?, where il is the current in winding 1 usedto plot the shape of field H .

    a v b C

    12

    figure 8 : f ie ld shape created by two concentricc o i l sUsually, the result of this calculation, LC C, s corrected by acoefficient. Here, we can determine exactly this coefficient,since the short-circuit test has enabled the actual value ofLcc to be calculated.k1 = Lcct,,/Lccis thus a first corrective factor.When the windings are not of the same height, a secondcorrective factor is applied [ 6 ] )

    a b c

    1 . 2 1 . 3

  • 8/13/2019 00225647

    4/5

    Using the tools described above, it becomes possible toevaluate the leakage factors that we need. As an example,consider the leakage factor between the two parts 1' and 1of the external winding 1 created by a turn-to-earth fault.

    0,020 -

    I

    0,015

    figure 9 : f ie ld shape created during a turn-to-earth fault

    L n /c

    The plot of the field shape (figure 9) enables the storedenergy W in the faulty winding to be calculated and thus thetotal leakage inductance Lccl' reduced to winding 1'. Thisinductance is corrected by the factor k l previouslycalculated and by the factor k2 if one of the coils 1' and 1spans over less than a layer.The leakage factor between the two coils 1 ' et 1 iscalculated by (J,,,~~2 he self inductance of portion1' being evaluated from the self inductance of the wholewinding : L . =Ll

    he result of this calculation applied to the test transformeris shown in figure 10. The leakage factor rapidly increaseswhen the fault occurs on an outer layer. Moreover, there is aslight decrease in leakage when the 2 winding parts areoverlapped.

    LCCL .

    [nr :n l , , r

    0 00 0.20 0.40 0,60 0.80 1.00location of the fault

    figure 1 : calculated leakage factorComoarison between calculation and measurementBy reprodu cing 16 turn-to-earth fau lts and several tens ofturn-to-turn faults, we have noticed a difference between thecalculated currents and the recorded currents which neverexceeds 10 in modulus and 10 in phase. The correlationbetween tests and simulation is even better when the fault

    only involves windings spanning at least once the fullwinding height.3. APPLICATION : S T v R K U U U R Y FAULTS IN A

    .escriDtioIL;rated power : 15 MVAshort-circuit voltage : 9.8%

    - no-load current : 0,46%- no-load losses : 11.3 kW- short-circuit losses : 98.5 kW- rated voltage : 33000V & 12% with 17 taps

    8 layers of 8 0 turns + 1 layer of 80 turns (tap changer)- internal diameter : 590 mm, radial thickness : 77 mm,height : 780 mm- rated voltage : 16100V- 5 layers of 36 turns- internal diameter : 436 mm, radial thickness : 64 mm,height : 780 mm

    HV winding : (delta)

    LV winding : (star)

    Turn-to-earth faultsThe differential current in a phase and the residual current(which is also the fault current) are shown in figures 11 and12 for a fault with 1 Q resistance and for two differentearthing systems :- for a directly earthed system, the zero-sequence current

    depends only few on the fault position and isessentially limited by the zero-sequence short circuitpower (150 MVA for this calculation).for a neutral earthed through an impedance of highenough value (fault current limited to 500 A or less), thezero-sequence current varies between 0.5 and 1 time thelimited current ; t is well known that a zero-sequenceovercurrent protection is the best way of detecting thisfault.

    -

    l8

    0 20 40 60 80 100location of the faultfigure 11 : turn-to-earth fault ; direct ly eartheds y s t e m

    1 . 2 1 . 4

  • 8/13/2019 00225647

    5/5

    .location of the faultf igure 12 : turn-to-earth fault : neutral currentl imited to 500ATun-to-turn faultsThe turn-to- tum fault current has been calculated by varyingthe fault span, the short circuit power of the system and thefault resistance.As soon as the number of short-circuited turns is large, thevalue of differential current depends basically on thesystem's short-circuit power. When the fault involves lessthan 10 of the winding, this current is very sensitive tothe fault resistance , the value of w hich is not controlled.A turn-to-turn fault is usually detected by a differentialprotection relay. Indeed, this is the main reason for usingthis protection. Its sensitivity, of around 30 , enablesdetection, in the simulated case, of faults involving at least13 turns.This example shows how useful the protection is : the faultbetween two layers is easily detected. It also shows itsperformance limit : detection of a fault between two turnsseems impossible. It would, however, be interesting toimprove the sensitivity of such a relay. Indeed, the shortcircuiting of one adjusting step, i.e. 1.5 of the winding,creates a differential current of 20 to 50 of rated current,depending on the fault resistance ; n order to ensure correctdetection, a sensitivity of 10% would be required.

    - curve 1 :R fault = O.OOlQ infinite SC pow ercurve 2 : R fault = 0,OOlQ. SC power = 15OMVA

    ~ cuwe 3 : R fault = 0,lQ ; infinite SC powercurve 4 : R fault = 0,lQ SC power = 15OMVA

    -2 -./ 4. /. /.7

    r ///.

    1 2 3 4I

    span of the faultfigure 14 : detail for faults of small spanCONCLUSIONThe calculation of currents during an internal fault in atransformer requires a model validated by measurements. Inorder to be of general use , his model must be compatiblewith a standard transient software and only require datawhich are available. The model presented meets all theserequirements. It would be worth improving it, in order totake in to account d i f ferent t ransformer windingtechnologies.In the third part of this report, we have shown with anexample the use that could be made of such a model : itenables quant i t a t ive evaluat ion of the qual i ty of atransformer protection. Other uses are planned such as theevaluat ion by the t ransformer manufacturer of theconsequences of possible faults, and the diagnosis of actualfaults by the user.BIBLIOGRAPHY

    [I ] GEC ALSTHOM MEASUREMENTS Protective RelayApplication Guide. 1987[2] S AUSTEN STIGANT A.C. FRANKL IN The J&P

    Transformer Book. Newnes-Butterworths[3] J .L. BINARD J .C . MAUN Power Transformer

    Simulation including Inrush C urrents and Internal Faults3 me confkrence internationale IMACS-TCI P O Nancy,France 1990

    [4] V. BRADWADJN H.W. DOMM EL 1.1 DOMM ELMatr ix Representat ion of Three-phase N-WindingTransformers. IEEE Transactions, vol PAS-I01 n06 ,1 9 8 2

    [ ] M. DENIS-PAPIN La pratique Indus tr iel l e desTransformateurs. Editions Alibin Michel. 1951

    figure 13 : differential current in a turn-to-turnfault of variable span

    1 . 2 1 . 5