Upload
yigit-sarikaya
View
216
Download
0
Embed Size (px)
Citation preview
8/10/2019 00481373
1/6
daptive
relaying
new direction in power system protection
Modern electric power systems can
deliver energy to users very reliably.
Protective relays in the power system
play an important role in assuring this
continuous service. Relays monitor the
status of the system continuously and
detect failures or abnormalities within
their assigned zone of protection. The
control action takes place by opening a
minimum number of circuit breakers to
isolate the defective element. An ele-
ment that would have otherwise caused
excessive damage or possibly collapse
o f the power system.
Although protective relays should
detect all system abnormalities quickly,
other considerations might detract from
this primary objective. In general, a
relay system is designed to achieve the
highest levels of speed, reliability,
selectivity, simplicity, and economics.
Since it is impractical to satisfy all
requirements simultaneously, compro-
mises must be made.
A typical conflictory objective is
embedded in the reliability of a relay
system. The dependability and security
of a relay system establish its reliabili-
ty. Dependability is a measure
of
the
relay system to perform properly in
removing system faults. Security is a
measure of the relay tendency in
not
initiating an incorrect trip action. There
is always a compromise between secu-
rity and dependability. The dependabili-
ty or security can be enhanced
significantly by utilizing redundant
relays. If the contact of the redundant
relay is connected in parallel with the
original relay, then the dependability is
increased. On the other hand, if the con-
tacts are connected in series, the securi-
ty is enhanced.
With conventional relays, the pro-
tective system design is either biased
toward the dependability or the secur-
ty. Therefore, the highest levels of
dependability and security cannot be
achieved at the same time.
In
addition, the compromises among
the desirable characteristics will lead to
a reIay system design which is far from
optimum. Performance degradation will
become more transparent
as
the network
topology changes. general, the ten-
dency
of
a relay system not perfomsing
in an optim~~rnanner is attributed to:
1.
Evolving relaying philosophies
over the past
80
years.
2.
Designs heavily relying
on
electromechanical technologies.
3.
Limitation in use
of
local vari-
ables, such as current or voltages,
as
the
relay inputs.
The major weaknesses are the hard-
wares inadequacy and limited capabili-
ty in adapting
to
the changing
environment of a power system.
Adaptive relaying
Adaptive relaying considers the fact
that the status of a power system can
change. Thus, the setting of relays will
be changed on-line
to
accommodate
these changes.
The adaptive relaying concept
requires the microprocessor-based digi-
tal relays. The digital relays are pro-
grammable devices with extensive
logic, memory, data transfer, communi-
cation, and reporting capabilities. These
features make them excellent candi-
dates for implementing the adaptive
relaying concepts.
However, this concept poses new
challenges in developing algorithms
that allow proper adaptability to
changes in system conditions. Addi-
tionally, since
a
power system is highly
integrated, it might not be possible to
detect all system loading and topologi-
cal changes at a local bus within the
power system. Therefore, system-wide
communication capability might
become a fundamental requirement.
Application areas
A recent paper summarized the
results of a survey on satisfaction of
practicing relay engineers with the
existing relays. In addition, this paper
investigated the areas where improve-
ments are desirable, and reliability
enhancements which can be made by
incorporating the adaptive features.
The following summarizes the
16
iden-
tified areas:
1. Operating time as a function of
the distance to fault,
28
0278-6648/96/ 5.00 1996
IEEE
IEEE POTENTIALS
8/10/2019 00481373
2/6
2.
Mutual coupling compensation in
3. High source impedance ratio
4. Remote-end open-breaker detec-
5. Load flow compensation,
6.
Fault type changing speed of oper-
7.
Multi-terminal distance relay cov-
8.
Variable breaker failure timing,
9. Permissive reclosing,
10. Adaptive reclosing,
11. Sympathy trip reclosing,
12. Adaptive synchronism check
13. Proactive load shedding,
14. Adaptive transformer differential
15. Voltage change supervision of
16. Bus protection restraint for
ground impedance protection,
changing,
tion for high-speed sequential tripping,
ation,
erage,
angle for reclosing,
protection,
differential unit,
arrester applications.
Adaptive digital
distance protection
In a digital relaying scheme, voltage
and current samples are taken at the
relaying point and used to compute the
apparent impedance of the line seen by
the relay. If the impedance is inside a
predetermined boundary, the decision is
made to disconnect or trip the line. This
system works well for
a
zero-resistance
fault situation. The voltage and current
samples are taken and the apparent
impedance is determined to be the
impedance of the line from the relay
point to the fault. If this impedance is
less than the expected line impedance,
the line is tripped.
The problem occurs in the case of
non-zero resistance fault situations. The
voltage that is sampled is the sum of the
line voltage and the fault voltage. The
voltage drop across the fault is a func-
tion of the current from the relay termi-
nal and the current from the remote-end
terminal. The current contribution from
the remote end cannot be measured at
the relaying point. It is possible to mea-
sure the remote-end current and send it
back to the relay end by a high speed
communication channel; however, this
has not been very practical.
Traditional systems only incorporat-
ed a margin of error to account for the
unknown current in order to keep the
relay from overreaching. This resulted
in a certain amount of the line at the far
end not being protected by the first zone
of protection. In
order to protect the
line properly, the
amount of unpro-
tected line must be
minimized.
An alternative
method is to deter-
mine the apparent
line impedance as a
function of known
parameters such as
positive and zero
45
-
40 .
I
50 1 15 200
R ohms)
sequence imped-
Fig. R Xplane
ance components,
terminal voltages, and the unknown
fault resistance. Computer simulation
may then be performed to determine an
ideal trip boundary, for several fault
resistance values. A typical example of
these boundaries is shown in Fig. 1.
Multi-terminal lines can be protected
in a similar manner
as
two terminal
lines. The difference is that the apparent
impedance as seen at a relay location is
not just a function of the parameters of
one line and two terminals, but a func-
tion of two or more lines and three or
more terminals. These line and terminal
parameters can be determined in
advance. Computer simulation may
then be used to determine ideal trip
boundaries for several fault resistances
in different parts of the line. These
boundaries do change with changing
system conditions.
Thus, the adaptive approach of mea-
suring system conditions and updating
the ideal trip boundaries can be very
useful. The protection algorithm will
measure the voltage and current sam-
ples at the relay location. The apparent
impedance is then calculated and the
computer refers to the most recent trip
boundaries and determines occurrence
of a fault and its locations.
Relays should adapt to ever chang-
ing system conditions, whether it is a
two-terminal or multi-terminal line. By
using a computer or microprocessor
based detection scheme, the reliability
and system stability is greatly
improved.
During the normal operation of a
system, unexpected events can affect
the overall performance of the system.
If an abnormal condition should arise,
such as frequency deviations, the pro-
tective devices may not be prepared to
handle the obscurity of parameter
changes due to the pre-set inputs.
A solution is to use real-time data to
reset any relay input settings. Therefore,
of
distance relay
it is possible to develop control rules for
automatically adapting to the system
changes. Components are added to the
control law aimed at unpredictable fac-
tors that affect the states of the protected
line. This improves the effectiveness of
a distance protection scheme.
Power system frequency deviations
are expected within certain limits. Two
undesirable consequences of frequency
excursions in digital distance protection
are the influence on sampling period
and the computed value of the reac-
tance. To translate the input signals
properly, the digital signals after sam-
pling should be sinusoidal sequences
with a period
of
N when line currents or
voltages are sinusoidal. In the case of
frequency deviations, the sampIe signals
will not belong to a 50 or 60 Hz signal.
As
a
result, the computations will be in
error.
Also, when the frequency of the line
varies by a certain percentage, the reac-
tance of the line will also change by a
proportional amount. To correct for this,
adaptive revising of sampling period
and line reactance calculation
on
the
basis of frequency measurement should
be considered. This is accomplished by
calculating the period increment. The
sampling period is then adaptively
revised for use of the next cycle of the
waveform. Accordingly, a new setting
can be computed. The reactance setting
can also be revised adaptively.
Single-phase to ground faults may
have a major effect on the performance
of the protective devices. The most seri-
ous and instantaneous faults are faults in
the vicinity of the switch-gear in the
protected direction, and faults in the
vicinity
of
the end of the protected line.
Faults in these areas may lead to the
FEBRUARY/MARCH 1996
29
8/10/2019 00481373
3/6
operation
of
the wrong relays.
To
avoid
these false operations, an adaptive
method will change the operating char-
acteristics of the relays on-line.
Power swings may cause improper
operation of distance protection. An
adaptive method can be used to immo-
bilize the protection during power sys-
tem swings. This method is called the
incremental rate discrimination of
instantaneous current values. The prin-
ciple is that the rate of change of instan-
taneous value of line current has a limit
under normal conditions but increases
suddenly when faults occur. According
to such a difference in changing rates,
one may distinguish the fault condition
erally, thiis inrush current
is
prevented
from being recognized as a fault condi-
tion by the fact that the inrush current is
dominated by the second harmonic. The
rnagnitudle of the second harmonic
depends
on
residual magneiism and the
voltage switching angle.
Current differential relays, however,
are affected by factors such
as
i m s h
current, ewer excitation, transformer
taps, and current transformer mismatch-
es. A digital scheme for differential pro-
tection would be the ideal way to
account for these
affects,
and to control
ratio mismatches. Such a digital system
also could be faster, and can make deci-
sions that
;Ire
much more secure.
then the algorithm transfers control to
the two state filter.
Once the transformer is operating
under normal conditions, a two state
Kalman filter samples the primary and
secondary currents and creates a refer-
ence phasor for each. These phasors are
rotated with respect to time and then
compared to new current measurements.
If
a
significant difference exists, a tran-
sient is detected and control is trans-
ferred to the three state Kalman filter
that uses estimates from the two state fil-
ters. The three state filter creates esti-
mates of the fundamental component of
the differential current. These estimates
are then used in a differential motection
from a no fault condition.
The rate-of-change of cur-
rent feature can classify the sta-
tus of the power system to
normal operation, swing condi-
tion, and faulted condition.
During normal conditions, the
current and its rate of change
both vary sinusoidally, and thelr
amplitude values are level with
each other. The current is near-
ly periodic under power swing
conditions. The amplitude of
the rate change per cycle varies
slowly
as
an envelope curve of
the current.
For a fault, the current
increases suddenly and the rate
change will be large. The adap-
method
suggests
that
a
detecting unit be used and its
setting adjusted adaptively in real-time
according to the change in current
amplitude Therefore, the protection
will be able to differentiate between the
faults and power system swings. This
will involve measunng and also memo-
nzing the amplitude of the load current
per cycle, and adaptively resetting the
protecbon devices.
equation similar to the one used
by the five state filter. If no
fault is detected, new samples
are taken and the process is
repeated by the three state filter
until
a
set time period has
elapsed. If no trip signal is
issued, the control is transferred
back to the two state filter.
By changing monitoring
states, the algonthm can adapt to
different operating conditions
and apply the precise model
needed. Test results for such a
scheme have been promsing on
a 1 KVA,
120
VI120 V single
phase transformer.
Different voltage taps were
used at the secondary of this
transformer to simulate internal
faults in conjunction with an
electronic switch to select different taps.
Current and voltage transducers were
used to supply current signals to a data
acquisition system and host computer.
The algorithm was executed at 16 sam-
ples/cycle. A fault decision had to be
consistent for at least three samples
before trip signals were issued. In six-
teen test cases involving internal faults
across the secondary during switching
Fig
2 ix
step
loud
shedding scheme
Recent work has proposed such a
computer al go ri th that
is
adaptive and
utilizes Kalman filtering. The computer
algorithm relies
on
the monitoring of
transformer currents to determine the
state of thle transformer. Different order
Kalman filters a re then initialized
depending on the state of the trans-
former. A de-energized transformer is
monitored until switchng occurs. Upon
Protecting power
transformers
Differential protection has become
the standard protection method for
power transformers over 10 MVA. It is
well known that the fundamental com-
ponent of the differential current during
an internal fault becomes much greater
than during normal loading conditions.
Another aspect of differential protec-
tion deals with the transformer during a
switching period. During this switching
period, inrush current will also create a
discrepancy in the current balance. Gen-
switching, a five state Kalman filter is
used to estimate the dc, fundamental,
and second harmonic components of the
current.
Tlhe
fundamental component is
used for the differential protection. If
the differential current exceeds a pre-
determined percentage of the through
current, a ]possible fault condition exists.
The second harmonic component of the
current is then compared to the funda-
mental of the differential current. If the
second harmonic content of the current
is not high enough, then an internal fault
has occuned and a trip signal is issued.
If the second harmonic criteria is met,
conditions, the algorithm initiated a trip
signal in 3/4 to 1 cycle. In nearly one
hundred tests involving internal faults,
turn-to-tum faults, and capacitor switch-
ing operations, the average correct oper-
ating time for the algorithm was
5
ms
with minimum and maximum times of
3 ms and 9 ms, respectively.
Adaptive reclosing
Despite attempts to maintain impec-
cable reliability in a high voltage trans-
mission system, faults will and do
occur.
To
minimize their effect and the
consequent interruption of service, the
3 IEEE POTENTIALS
8/10/2019 00481373
4/6
system must be brought back on-line as
quickly and effortlessly as possible. It is
in this capacity that automatic reclosing
of circuit breakers are employed.
If a fault was determined to be per-
manent, the recloser would lockout after
a predetermined number of operations,
eventually isolating the faulted segment.
However, the vast majority of faults are
temporary in nature. The recloser usual-
ly will close the line without having to
lockout.
The two main methods of reclosing
are high speed reclosing
HSR)
and
delayed reclosing. In the first case, the
line is reclosed as quickly as possible
with no checking of voltage magnitudes
or phase angles. The only delay intro-
duced in this fashion is that required for
extinguishing the arc.
On the other hand, delayed automat-
ic reclosing imposes more of a delay.
This allows for adequate checking to
determine if desirable system conditions
are present. Although both methods
have fulfilled their purposes, the advent
of the digital computer can take this
ability one step further.
Conventional methods are limited by
their inability to adjust their actions to
real-time changes in the system. Adaptive
reclosing allows a safer and more easily
monitored method of closing onto faulted
sections of a system. By applying adap-
tive techniques, the voltage of a faulted
system can be utilized to determine the
severity as well as the location of the
fault, and further, whether or not the sys-
tem should be brought back online.
In
fact, adaptive relaying could effectively
prohibit closing into any fault unless it is
a line to ground or line to line fault.
Adaptive reclosing involves detect-
ing the nature and location of a fault by
re-energizing an unfaulted (or presum-
ably unfaulted) phase and observing the
phase voltages on the other unenergized
lines. Simple logic can be employed to
determine which phase should be ini-
tially reclosed. Any given fault can be
classified into one of the following four
categories:
1. three-phase,
2. line-to-line,
3. line-to-ground,
4. internal.
In the case of a three-phase fault, the
selection of the initial phase to reclose is
purely arbitrary. When a line-to-line
fault occurs, obviously the third, unin-
volved, phase would be chosen. In the
third case, either of the two other phases
could be re-energized. The final case
implies a permanent fault, which would
warrant the recloser to lockout, isolating
the defective equipment.
After the single-phase reclosing
action, the voltages of the other phases
can be monitored to determine the nature
and seventy of the fault.A variety of sce-
narios can arise after the initial reclosing:
a. If the reclosed line voltage equals
the source voltage and the voltage on
either of the remaining phases is zero,
then there is obviously a line-to-ground
fault on that respective phase.
b. If the reclosed line voltage equals
the source voltage and the voltage on
either of the other two is equal to the
reclosed line, then we can assume a
line-to-line fault between this phase and
the initial reclosed line.
c. If the reclosed line voltage equals
the source voltage and the voltage of the
other two phases are equal, then a line-
to-line fault exists between them.
d. If the reclosed line voltage equals
the source voltage and the voltages on
the other two phases non zero and nei-
ther equal to each other or to the re-
energized phase, then the system is
normal and the phases can be reclosed
immediately.
Since these measurements can be
made almost instantaneously, the effect
of an incorrect trip can easily be mini-
mized. Another issue is not only which
phases to reclose, but at what time to
reclose them. In order to minimize the
dc offset in case of permanent fault, the
initial reclosing should occur at maxi-
mum voltage across the breaker. On the
other hand, the other phases should be
reclosed at the minimum voltage across
the breaker to eliminate the arc and pro-
long the life of the contacts.
Adaptive reclosing also helps protect
the breakers upon opening. Digital
relays allow precise control of the open-
ing as well as the reclosing operations
of circuit breakers.
If
the breakers are
opened when the current
is
zero, this
eliminates not only system transients,
but also eradicates arcing which mini-
mizes maintenance and prolongs the life
of the device. Also, digital control aids
in disbursing the workload among vari-
ous breakers to balance out the wear
and tear imposed on each. This is most
advantageous in the ring bus situation,
where it is very difficult to apportion
the reclosing action equally by the con-
ventional methods.
Underfrequency protection
As a consequence of switching large
loads or
loss
of generation, a power sys-
tem can experience a decay in the sys-
tem frequency. When the total load is
greater than the total generation, the
generator speed will decrease causing
the system frequency to decrease.
One major concern during low fre-
quency periods is the safety of the tur-
bine-generators. Operating in low
frequency regions for a prolonged peri-
od of time will damage the turbine
blades. Electric utility companies use
underfrequency load shedding relays to
prevent drastic drops in the system fre-
quency.
The current method of preventing the
frequency decay is to shed a predeter-
mined amount of load when the system
frequency
drops
below a preset value.
Typically 57 Hz will be used as the
lowest safe operating level. (This value
was chosen from an industry survey in
1966 by the IEEE Power System Relay-
ing Committee-57
Hz
being the most
popular value.)
The problem with shedding
a
pre-set
amount is that each system disturbance
is different. For a particular disturbance,
the amount of load that needs to be shed
to correct the problem may be different
than what the company has specified for
other conditions.
If the amount of load shed is not
enough to correct the problem, the fre-
quency will continue to decline until the
next load shedding step is initiated. Due
to the large inertia of the turbine-gener-
ators, the frequency will continue to
decline for a short time after the abnor-
mality has been corrected. This may
cause the frequency to decay past the
minimum value, even though the
amount of load shed is sufficient. Fast
and efficient load shedding is required
to account for both the generator inertia
and various system disturbances.
If the frequency is not monitored
throughout the system, load shedding
outside the disturbance area will reduce
the system reliability. Another problem
with local frequency measurement is
that the frequency at one end of the sys-
tem could be below 57 Hz, while the
frequency at the other end could be
above
57
Hz.
A large integrated system consists of
many interconnected systems. When
there is a major disturbance in one of
the
smaller systems, the
last
line of
defense is to isolate this system from
the main system via the existing inter-
ties. As a result, an island is formed.
The smaller system that experienced an
FEBRUARY/MARCH 1996 31
8/10/2019 00481373
5/6
8/10/2019 00481373
6/6
S.H. Horowitz, A.G. Phadke, and
J.S. Thorp, Adaptive Transmission
Relaying, I E E E T r ans ac t i ons
on
Power Delivery Vol. 3, No. 4, October
M. Adamiak, et. al, Feasibility of
Adaptive Protection and Control, IEEE
PES 1992 Summer Meeting Paper.
Y.Q.
Xia,
K.K.
Li, A.K. David,
Adaptive Relay Setting for Stand-
Alone Digital Distance Protection,
IEEE PES 1993 Winter Meeting.
Zhizhe, Zhang, Deshu, Chen, An
Adaptive Approach in Digital Distance
Protection, I E E E T r ans ac t ions on
Power Delivery Vol. 6,
No.
1, January
Chang, W.B., Girgis, Adly A., and
Hart, D. David, An Adaptive Scheme
for Digital Protection of Power Trans-
formers, IEEE Transactionson Power
Delivery Vol. 7
No. 2,
April 1992.
Girgis, Adly A., Brown, R. Grover,
Adaptive Kalman Filtering in Comput-
er Relaying: Fault Classification Using
Voltage Models, IEEE Transactions
on Power Apparatus and Systems Vol.
PAS-104, No.
5,
May 1985.
P.M. Anderson and M. Mirheydar,
1988, pp. 1436-1445.
1991, pp. 135-141.
An Adaptive Method
fo r
setting
Underfrequency Load Shedding
Relays, Transactions on Power Sys-
tems Vol. 7 No.
2
May 1992.
Jampala A.K., Venkata S.S.
Damborg M.J., Adaptive Transmission
Protection: Concepts and Computation-
al Issues, IEEE TransactionsonPower
Delivery Vol. PD-4, January 1989, pp.
177-185.
About the authors
Jamie Codling is an undergraduate
student at Rose-Hulman Institute of
Technology. He will be receiving a B.S.
in Electrical Engineering and would like
to work in the power engineering field.
Spencer House is a senior Electrical
Engineering student at Rose-Hulman
Institute of Technology. Upon complet-
ing his degree he would like to obtain
employment in the power industry. Joe
Joice is a member of IEEE and a mem-
ber of IEEE Power Engineering Soci-
ety. He will receive his B.S. degree in
Electrical Engineering in May of 1994
from Rose-Hulman Institute of Tech-
nology. Upon graduation he wishes to
work for a power engineering consult-
ing
fm
Kenneth M. Labhart is a senior
at Rose-Hulman Institute of Technology
pursing a B.S. in Electrical Engineering.
He is an IEEE student member and a
member
of
the IEEE Power Engineer-
ing Society. Jon Richards is a student of
Electrical Engineering at Rose-Hulman
Institute of Technology. After complet-
ing his schooling, he would like to work
in the power engineering field. John
Tenbush is an Electrical Engineering
student at Rose-Hulman Institute of
Technology. After graduation, he wish-
es to work for an automotive company
in the area of product design and devel-
opment. Matthew D. Tullis is presently
finishing his undergraduate studies at
Rose-Hulman. After receiving a B.S.
degree in Electrical Engineering, he
plans to work for a public utility. Todd
Wilkerson is presently finishing his B.S.
in Electrical Engineering at Rose-Hul-
man Institute of Technology. Upon his
graduation, he plans to join the Techni-
cal Services division of Anderson Con-
sulting in Chicago, IL. Dr. Rostamkolai
is the Associate Professor of Electrical
Engineering at Rose-Hulamn Institute
of Technology.
O N E OF T H E
MOST
CTIVE IEEE SO CIE TIE S
The Microwave Theory and Techniques Society
BENEFITS OF MTT S MEMBERSHIP
W - S )
ofthe
IEEE is the
premier
OW
for microwaves and applicationsover a frequency range
typically 1
to
3 GEIZ.
m sepresents
the
entire
microwave
community
including all industrid, academic
and government activities
from basic
scientific research
through applied engineering There are
over
75 h4TT-S
local chaptersand
over
9,000
members
worldwide.
Worlds Largest nmlal Microwave Conference and Exhibition
Student Paper Contest
q &adUte F e ~ o ~ ~ p s ,
m
~
Local chapter activities nclude
opportunities o
participate n
technical meetiugs, meet
wth
industry leaders, hear
distinguished lecturers, etc.
Student m embership iskee for the first
year and
includes
the
MTT-S
Newsletter.
To:
IEEE
Service Center, EO
Box
1331
445
Hoes Lane, Piscataway, NJ
08855-1
331
SA:
Yes Im an IEEE Student Member and Iwant to
join MTT S (free for the
first
year).
. _ _ _ _ _ _ _ _ _ _ _ _
Membership number ........................................
I
Name ................................................................ I
Address ............................................................. ,
I
Quarterly Newsletter included in membership
Transactionson Microwave Theory and Techniques, Microwave
and Guided Wave Letters available at greatly reduced rate
AREAS
OF
ACfVITY
Solid-state Devices
Integrated Circuits
Monolithic Circuits
Superconductivity
Millimeter waves
Network Theory
Field Theory
Wireless Components
&
Systems
AutomatedR Techniques
ARFTG
Digital Microwave Systems
Fiber and Integrated Optics
Computer Aided Design
Low Noise Techniques
High
Power Techniques
........................... .......................... x Femte Components Biological
&
Medical Applications
City
Statelzip
AcN19170744001 PPOT1795 8999
FEBRUARY/MARCH
1996 33