00481373

Embed Size (px)

Citation preview

  • 8/10/2019 00481373

    1/6

    daptive

    relaying

    new direction in power system protection

    Modern electric power systems can

    deliver energy to users very reliably.

    Protective relays in the power system

    play an important role in assuring this

    continuous service. Relays monitor the

    status of the system continuously and

    detect failures or abnormalities within

    their assigned zone of protection. The

    control action takes place by opening a

    minimum number of circuit breakers to

    isolate the defective element. An ele-

    ment that would have otherwise caused

    excessive damage or possibly collapse

    o f the power system.

    Although protective relays should

    detect all system abnormalities quickly,

    other considerations might detract from

    this primary objective. In general, a

    relay system is designed to achieve the

    highest levels of speed, reliability,

    selectivity, simplicity, and economics.

    Since it is impractical to satisfy all

    requirements simultaneously, compro-

    mises must be made.

    A typical conflictory objective is

    embedded in the reliability of a relay

    system. The dependability and security

    of a relay system establish its reliabili-

    ty. Dependability is a measure

    of

    the

    relay system to perform properly in

    removing system faults. Security is a

    measure of the relay tendency in

    not

    initiating an incorrect trip action. There

    is always a compromise between secu-

    rity and dependability. The dependabili-

    ty or security can be enhanced

    significantly by utilizing redundant

    relays. If the contact of the redundant

    relay is connected in parallel with the

    original relay, then the dependability is

    increased. On the other hand, if the con-

    tacts are connected in series, the securi-

    ty is enhanced.

    With conventional relays, the pro-

    tective system design is either biased

    toward the dependability or the secur-

    ty. Therefore, the highest levels of

    dependability and security cannot be

    achieved at the same time.

    In

    addition, the compromises among

    the desirable characteristics will lead to

    a reIay system design which is far from

    optimum. Performance degradation will

    become more transparent

    as

    the network

    topology changes. general, the ten-

    dency

    of

    a relay system not perfomsing

    in an optim~~rnanner is attributed to:

    1.

    Evolving relaying philosophies

    over the past

    80

    years.

    2.

    Designs heavily relying

    on

    electromechanical technologies.

    3.

    Limitation in use

    of

    local vari-

    ables, such as current or voltages,

    as

    the

    relay inputs.

    The major weaknesses are the hard-

    wares inadequacy and limited capabili-

    ty in adapting

    to

    the changing

    environment of a power system.

    Adaptive relaying

    Adaptive relaying considers the fact

    that the status of a power system can

    change. Thus, the setting of relays will

    be changed on-line

    to

    accommodate

    these changes.

    The adaptive relaying concept

    requires the microprocessor-based digi-

    tal relays. The digital relays are pro-

    grammable devices with extensive

    logic, memory, data transfer, communi-

    cation, and reporting capabilities. These

    features make them excellent candi-

    dates for implementing the adaptive

    relaying concepts.

    However, this concept poses new

    challenges in developing algorithms

    that allow proper adaptability to

    changes in system conditions. Addi-

    tionally, since

    a

    power system is highly

    integrated, it might not be possible to

    detect all system loading and topologi-

    cal changes at a local bus within the

    power system. Therefore, system-wide

    communication capability might

    become a fundamental requirement.

    Application areas

    A recent paper summarized the

    results of a survey on satisfaction of

    practicing relay engineers with the

    existing relays. In addition, this paper

    investigated the areas where improve-

    ments are desirable, and reliability

    enhancements which can be made by

    incorporating the adaptive features.

    The following summarizes the

    16

    iden-

    tified areas:

    1. Operating time as a function of

    the distance to fault,

    28

    0278-6648/96/ 5.00 1996

    IEEE

    IEEE POTENTIALS

  • 8/10/2019 00481373

    2/6

    2.

    Mutual coupling compensation in

    3. High source impedance ratio

    4. Remote-end open-breaker detec-

    5. Load flow compensation,

    6.

    Fault type changing speed of oper-

    7.

    Multi-terminal distance relay cov-

    8.

    Variable breaker failure timing,

    9. Permissive reclosing,

    10. Adaptive reclosing,

    11. Sympathy trip reclosing,

    12. Adaptive synchronism check

    13. Proactive load shedding,

    14. Adaptive transformer differential

    15. Voltage change supervision of

    16. Bus protection restraint for

    ground impedance protection,

    changing,

    tion for high-speed sequential tripping,

    ation,

    erage,

    angle for reclosing,

    protection,

    differential unit,

    arrester applications.

    Adaptive digital

    distance protection

    In a digital relaying scheme, voltage

    and current samples are taken at the

    relaying point and used to compute the

    apparent impedance of the line seen by

    the relay. If the impedance is inside a

    predetermined boundary, the decision is

    made to disconnect or trip the line. This

    system works well for

    a

    zero-resistance

    fault situation. The voltage and current

    samples are taken and the apparent

    impedance is determined to be the

    impedance of the line from the relay

    point to the fault. If this impedance is

    less than the expected line impedance,

    the line is tripped.

    The problem occurs in the case of

    non-zero resistance fault situations. The

    voltage that is sampled is the sum of the

    line voltage and the fault voltage. The

    voltage drop across the fault is a func-

    tion of the current from the relay termi-

    nal and the current from the remote-end

    terminal. The current contribution from

    the remote end cannot be measured at

    the relaying point. It is possible to mea-

    sure the remote-end current and send it

    back to the relay end by a high speed

    communication channel; however, this

    has not been very practical.

    Traditional systems only incorporat-

    ed a margin of error to account for the

    unknown current in order to keep the

    relay from overreaching. This resulted

    in a certain amount of the line at the far

    end not being protected by the first zone

    of protection. In

    order to protect the

    line properly, the

    amount of unpro-

    tected line must be

    minimized.

    An alternative

    method is to deter-

    mine the apparent

    line impedance as a

    function of known

    parameters such as

    positive and zero

    45

    -

    40 .

    I

    50 1 15 200

    R ohms)

    sequence imped-

    Fig. R Xplane

    ance components,

    terminal voltages, and the unknown

    fault resistance. Computer simulation

    may then be performed to determine an

    ideal trip boundary, for several fault

    resistance values. A typical example of

    these boundaries is shown in Fig. 1.

    Multi-terminal lines can be protected

    in a similar manner

    as

    two terminal

    lines. The difference is that the apparent

    impedance as seen at a relay location is

    not just a function of the parameters of

    one line and two terminals, but a func-

    tion of two or more lines and three or

    more terminals. These line and terminal

    parameters can be determined in

    advance. Computer simulation may

    then be used to determine ideal trip

    boundaries for several fault resistances

    in different parts of the line. These

    boundaries do change with changing

    system conditions.

    Thus, the adaptive approach of mea-

    suring system conditions and updating

    the ideal trip boundaries can be very

    useful. The protection algorithm will

    measure the voltage and current sam-

    ples at the relay location. The apparent

    impedance is then calculated and the

    computer refers to the most recent trip

    boundaries and determines occurrence

    of a fault and its locations.

    Relays should adapt to ever chang-

    ing system conditions, whether it is a

    two-terminal or multi-terminal line. By

    using a computer or microprocessor

    based detection scheme, the reliability

    and system stability is greatly

    improved.

    During the normal operation of a

    system, unexpected events can affect

    the overall performance of the system.

    If an abnormal condition should arise,

    such as frequency deviations, the pro-

    tective devices may not be prepared to

    handle the obscurity of parameter

    changes due to the pre-set inputs.

    A solution is to use real-time data to

    reset any relay input settings. Therefore,

    of

    distance relay

    it is possible to develop control rules for

    automatically adapting to the system

    changes. Components are added to the

    control law aimed at unpredictable fac-

    tors that affect the states of the protected

    line. This improves the effectiveness of

    a distance protection scheme.

    Power system frequency deviations

    are expected within certain limits. Two

    undesirable consequences of frequency

    excursions in digital distance protection

    are the influence on sampling period

    and the computed value of the reac-

    tance. To translate the input signals

    properly, the digital signals after sam-

    pling should be sinusoidal sequences

    with a period

    of

    N when line currents or

    voltages are sinusoidal. In the case of

    frequency deviations, the sampIe signals

    will not belong to a 50 or 60 Hz signal.

    As

    a

    result, the computations will be in

    error.

    Also, when the frequency of the line

    varies by a certain percentage, the reac-

    tance of the line will also change by a

    proportional amount. To correct for this,

    adaptive revising of sampling period

    and line reactance calculation

    on

    the

    basis of frequency measurement should

    be considered. This is accomplished by

    calculating the period increment. The

    sampling period is then adaptively

    revised for use of the next cycle of the

    waveform. Accordingly, a new setting

    can be computed. The reactance setting

    can also be revised adaptively.

    Single-phase to ground faults may

    have a major effect on the performance

    of the protective devices. The most seri-

    ous and instantaneous faults are faults in

    the vicinity of the switch-gear in the

    protected direction, and faults in the

    vicinity

    of

    the end of the protected line.

    Faults in these areas may lead to the

    FEBRUARY/MARCH 1996

    29

  • 8/10/2019 00481373

    3/6

    operation

    of

    the wrong relays.

    To

    avoid

    these false operations, an adaptive

    method will change the operating char-

    acteristics of the relays on-line.

    Power swings may cause improper

    operation of distance protection. An

    adaptive method can be used to immo-

    bilize the protection during power sys-

    tem swings. This method is called the

    incremental rate discrimination of

    instantaneous current values. The prin-

    ciple is that the rate of change of instan-

    taneous value of line current has a limit

    under normal conditions but increases

    suddenly when faults occur. According

    to such a difference in changing rates,

    one may distinguish the fault condition

    erally, thiis inrush current

    is

    prevented

    from being recognized as a fault condi-

    tion by the fact that the inrush current is

    dominated by the second harmonic. The

    rnagnitudle of the second harmonic

    depends

    on

    residual magneiism and the

    voltage switching angle.

    Current differential relays, however,

    are affected by factors such

    as

    i m s h

    current, ewer excitation, transformer

    taps, and current transformer mismatch-

    es. A digital scheme for differential pro-

    tection would be the ideal way to

    account for these

    affects,

    and to control

    ratio mismatches. Such a digital system

    also could be faster, and can make deci-

    sions that

    ;Ire

    much more secure.

    then the algorithm transfers control to

    the two state filter.

    Once the transformer is operating

    under normal conditions, a two state

    Kalman filter samples the primary and

    secondary currents and creates a refer-

    ence phasor for each. These phasors are

    rotated with respect to time and then

    compared to new current measurements.

    If

    a

    significant difference exists, a tran-

    sient is detected and control is trans-

    ferred to the three state Kalman filter

    that uses estimates from the two state fil-

    ters. The three state filter creates esti-

    mates of the fundamental component of

    the differential current. These estimates

    are then used in a differential motection

    from a no fault condition.

    The rate-of-change of cur-

    rent feature can classify the sta-

    tus of the power system to

    normal operation, swing condi-

    tion, and faulted condition.

    During normal conditions, the

    current and its rate of change

    both vary sinusoidally, and thelr

    amplitude values are level with

    each other. The current is near-

    ly periodic under power swing

    conditions. The amplitude of

    the rate change per cycle varies

    slowly

    as

    an envelope curve of

    the current.

    For a fault, the current

    increases suddenly and the rate

    change will be large. The adap-

    method

    suggests

    that

    a

    detecting unit be used and its

    setting adjusted adaptively in real-time

    according to the change in current

    amplitude Therefore, the protection

    will be able to differentiate between the

    faults and power system swings. This

    will involve measunng and also memo-

    nzing the amplitude of the load current

    per cycle, and adaptively resetting the

    protecbon devices.

    equation similar to the one used

    by the five state filter. If no

    fault is detected, new samples

    are taken and the process is

    repeated by the three state filter

    until

    a

    set time period has

    elapsed. If no trip signal is

    issued, the control is transferred

    back to the two state filter.

    By changing monitoring

    states, the algonthm can adapt to

    different operating conditions

    and apply the precise model

    needed. Test results for such a

    scheme have been promsing on

    a 1 KVA,

    120

    VI120 V single

    phase transformer.

    Different voltage taps were

    used at the secondary of this

    transformer to simulate internal

    faults in conjunction with an

    electronic switch to select different taps.

    Current and voltage transducers were

    used to supply current signals to a data

    acquisition system and host computer.

    The algorithm was executed at 16 sam-

    ples/cycle. A fault decision had to be

    consistent for at least three samples

    before trip signals were issued. In six-

    teen test cases involving internal faults

    across the secondary during switching

    Fig

    2 ix

    step

    loud

    shedding scheme

    Recent work has proposed such a

    computer al go ri th that

    is

    adaptive and

    utilizes Kalman filtering. The computer

    algorithm relies

    on

    the monitoring of

    transformer currents to determine the

    state of thle transformer. Different order

    Kalman filters a re then initialized

    depending on the state of the trans-

    former. A de-energized transformer is

    monitored until switchng occurs. Upon

    Protecting power

    transformers

    Differential protection has become

    the standard protection method for

    power transformers over 10 MVA. It is

    well known that the fundamental com-

    ponent of the differential current during

    an internal fault becomes much greater

    than during normal loading conditions.

    Another aspect of differential protec-

    tion deals with the transformer during a

    switching period. During this switching

    period, inrush current will also create a

    discrepancy in the current balance. Gen-

    switching, a five state Kalman filter is

    used to estimate the dc, fundamental,

    and second harmonic components of the

    current.

    Tlhe

    fundamental component is

    used for the differential protection. If

    the differential current exceeds a pre-

    determined percentage of the through

    current, a ]possible fault condition exists.

    The second harmonic component of the

    current is then compared to the funda-

    mental of the differential current. If the

    second harmonic content of the current

    is not high enough, then an internal fault

    has occuned and a trip signal is issued.

    If the second harmonic criteria is met,

    conditions, the algorithm initiated a trip

    signal in 3/4 to 1 cycle. In nearly one

    hundred tests involving internal faults,

    turn-to-tum faults, and capacitor switch-

    ing operations, the average correct oper-

    ating time for the algorithm was

    5

    ms

    with minimum and maximum times of

    3 ms and 9 ms, respectively.

    Adaptive reclosing

    Despite attempts to maintain impec-

    cable reliability in a high voltage trans-

    mission system, faults will and do

    occur.

    To

    minimize their effect and the

    consequent interruption of service, the

    3 IEEE POTENTIALS

  • 8/10/2019 00481373

    4/6

    system must be brought back on-line as

    quickly and effortlessly as possible. It is

    in this capacity that automatic reclosing

    of circuit breakers are employed.

    If a fault was determined to be per-

    manent, the recloser would lockout after

    a predetermined number of operations,

    eventually isolating the faulted segment.

    However, the vast majority of faults are

    temporary in nature. The recloser usual-

    ly will close the line without having to

    lockout.

    The two main methods of reclosing

    are high speed reclosing

    HSR)

    and

    delayed reclosing. In the first case, the

    line is reclosed as quickly as possible

    with no checking of voltage magnitudes

    or phase angles. The only delay intro-

    duced in this fashion is that required for

    extinguishing the arc.

    On the other hand, delayed automat-

    ic reclosing imposes more of a delay.

    This allows for adequate checking to

    determine if desirable system conditions

    are present. Although both methods

    have fulfilled their purposes, the advent

    of the digital computer can take this

    ability one step further.

    Conventional methods are limited by

    their inability to adjust their actions to

    real-time changes in the system. Adaptive

    reclosing allows a safer and more easily

    monitored method of closing onto faulted

    sections of a system. By applying adap-

    tive techniques, the voltage of a faulted

    system can be utilized to determine the

    severity as well as the location of the

    fault, and further, whether or not the sys-

    tem should be brought back online.

    In

    fact, adaptive relaying could effectively

    prohibit closing into any fault unless it is

    a line to ground or line to line fault.

    Adaptive reclosing involves detect-

    ing the nature and location of a fault by

    re-energizing an unfaulted (or presum-

    ably unfaulted) phase and observing the

    phase voltages on the other unenergized

    lines. Simple logic can be employed to

    determine which phase should be ini-

    tially reclosed. Any given fault can be

    classified into one of the following four

    categories:

    1. three-phase,

    2. line-to-line,

    3. line-to-ground,

    4. internal.

    In the case of a three-phase fault, the

    selection of the initial phase to reclose is

    purely arbitrary. When a line-to-line

    fault occurs, obviously the third, unin-

    volved, phase would be chosen. In the

    third case, either of the two other phases

    could be re-energized. The final case

    implies a permanent fault, which would

    warrant the recloser to lockout, isolating

    the defective equipment.

    After the single-phase reclosing

    action, the voltages of the other phases

    can be monitored to determine the nature

    and seventy of the fault.A variety of sce-

    narios can arise after the initial reclosing:

    a. If the reclosed line voltage equals

    the source voltage and the voltage on

    either of the remaining phases is zero,

    then there is obviously a line-to-ground

    fault on that respective phase.

    b. If the reclosed line voltage equals

    the source voltage and the voltage on

    either of the other two is equal to the

    reclosed line, then we can assume a

    line-to-line fault between this phase and

    the initial reclosed line.

    c. If the reclosed line voltage equals

    the source voltage and the voltage of the

    other two phases are equal, then a line-

    to-line fault exists between them.

    d. If the reclosed line voltage equals

    the source voltage and the voltages on

    the other two phases non zero and nei-

    ther equal to each other or to the re-

    energized phase, then the system is

    normal and the phases can be reclosed

    immediately.

    Since these measurements can be

    made almost instantaneously, the effect

    of an incorrect trip can easily be mini-

    mized. Another issue is not only which

    phases to reclose, but at what time to

    reclose them. In order to minimize the

    dc offset in case of permanent fault, the

    initial reclosing should occur at maxi-

    mum voltage across the breaker. On the

    other hand, the other phases should be

    reclosed at the minimum voltage across

    the breaker to eliminate the arc and pro-

    long the life of the contacts.

    Adaptive reclosing also helps protect

    the breakers upon opening. Digital

    relays allow precise control of the open-

    ing as well as the reclosing operations

    of circuit breakers.

    If

    the breakers are

    opened when the current

    is

    zero, this

    eliminates not only system transients,

    but also eradicates arcing which mini-

    mizes maintenance and prolongs the life

    of the device. Also, digital control aids

    in disbursing the workload among vari-

    ous breakers to balance out the wear

    and tear imposed on each. This is most

    advantageous in the ring bus situation,

    where it is very difficult to apportion

    the reclosing action equally by the con-

    ventional methods.

    Underfrequency protection

    As a consequence of switching large

    loads or

    loss

    of generation, a power sys-

    tem can experience a decay in the sys-

    tem frequency. When the total load is

    greater than the total generation, the

    generator speed will decrease causing

    the system frequency to decrease.

    One major concern during low fre-

    quency periods is the safety of the tur-

    bine-generators. Operating in low

    frequency regions for a prolonged peri-

    od of time will damage the turbine

    blades. Electric utility companies use

    underfrequency load shedding relays to

    prevent drastic drops in the system fre-

    quency.

    The current method of preventing the

    frequency decay is to shed a predeter-

    mined amount of load when the system

    frequency

    drops

    below a preset value.

    Typically 57 Hz will be used as the

    lowest safe operating level. (This value

    was chosen from an industry survey in

    1966 by the IEEE Power System Relay-

    ing Committee-57

    Hz

    being the most

    popular value.)

    The problem with shedding

    a

    pre-set

    amount is that each system disturbance

    is different. For a particular disturbance,

    the amount of load that needs to be shed

    to correct the problem may be different

    than what the company has specified for

    other conditions.

    If the amount of load shed is not

    enough to correct the problem, the fre-

    quency will continue to decline until the

    next load shedding step is initiated. Due

    to the large inertia of the turbine-gener-

    ators, the frequency will continue to

    decline for a short time after the abnor-

    mality has been corrected. This may

    cause the frequency to decay past the

    minimum value, even though the

    amount of load shed is sufficient. Fast

    and efficient load shedding is required

    to account for both the generator inertia

    and various system disturbances.

    If the frequency is not monitored

    throughout the system, load shedding

    outside the disturbance area will reduce

    the system reliability. Another problem

    with local frequency measurement is

    that the frequency at one end of the sys-

    tem could be below 57 Hz, while the

    frequency at the other end could be

    above

    57

    Hz.

    A large integrated system consists of

    many interconnected systems. When

    there is a major disturbance in one of

    the

    smaller systems, the

    last

    line of

    defense is to isolate this system from

    the main system via the existing inter-

    ties. As a result, an island is formed.

    The smaller system that experienced an

    FEBRUARY/MARCH 1996 31

  • 8/10/2019 00481373

    5/6

  • 8/10/2019 00481373

    6/6

    S.H. Horowitz, A.G. Phadke, and

    J.S. Thorp, Adaptive Transmission

    Relaying, I E E E T r ans ac t i ons

    on

    Power Delivery Vol. 3, No. 4, October

    M. Adamiak, et. al, Feasibility of

    Adaptive Protection and Control, IEEE

    PES 1992 Summer Meeting Paper.

    Y.Q.

    Xia,

    K.K.

    Li, A.K. David,

    Adaptive Relay Setting for Stand-

    Alone Digital Distance Protection,

    IEEE PES 1993 Winter Meeting.

    Zhizhe, Zhang, Deshu, Chen, An

    Adaptive Approach in Digital Distance

    Protection, I E E E T r ans ac t ions on

    Power Delivery Vol. 6,

    No.

    1, January

    Chang, W.B., Girgis, Adly A., and

    Hart, D. David, An Adaptive Scheme

    for Digital Protection of Power Trans-

    formers, IEEE Transactionson Power

    Delivery Vol. 7

    No. 2,

    April 1992.

    Girgis, Adly A., Brown, R. Grover,

    Adaptive Kalman Filtering in Comput-

    er Relaying: Fault Classification Using

    Voltage Models, IEEE Transactions

    on Power Apparatus and Systems Vol.

    PAS-104, No.

    5,

    May 1985.

    P.M. Anderson and M. Mirheydar,

    1988, pp. 1436-1445.

    1991, pp. 135-141.

    An Adaptive Method

    fo r

    setting

    Underfrequency Load Shedding

    Relays, Transactions on Power Sys-

    tems Vol. 7 No.

    2

    May 1992.

    Jampala A.K., Venkata S.S.

    Damborg M.J., Adaptive Transmission

    Protection: Concepts and Computation-

    al Issues, IEEE TransactionsonPower

    Delivery Vol. PD-4, January 1989, pp.

    177-185.

    About the authors

    Jamie Codling is an undergraduate

    student at Rose-Hulman Institute of

    Technology. He will be receiving a B.S.

    in Electrical Engineering and would like

    to work in the power engineering field.

    Spencer House is a senior Electrical

    Engineering student at Rose-Hulman

    Institute of Technology. Upon complet-

    ing his degree he would like to obtain

    employment in the power industry. Joe

    Joice is a member of IEEE and a mem-

    ber of IEEE Power Engineering Soci-

    ety. He will receive his B.S. degree in

    Electrical Engineering in May of 1994

    from Rose-Hulman Institute of Tech-

    nology. Upon graduation he wishes to

    work for a power engineering consult-

    ing

    fm

    Kenneth M. Labhart is a senior

    at Rose-Hulman Institute of Technology

    pursing a B.S. in Electrical Engineering.

    He is an IEEE student member and a

    member

    of

    the IEEE Power Engineer-

    ing Society. Jon Richards is a student of

    Electrical Engineering at Rose-Hulman

    Institute of Technology. After complet-

    ing his schooling, he would like to work

    in the power engineering field. John

    Tenbush is an Electrical Engineering

    student at Rose-Hulman Institute of

    Technology. After graduation, he wish-

    es to work for an automotive company

    in the area of product design and devel-

    opment. Matthew D. Tullis is presently

    finishing his undergraduate studies at

    Rose-Hulman. After receiving a B.S.

    degree in Electrical Engineering, he

    plans to work for a public utility. Todd

    Wilkerson is presently finishing his B.S.

    in Electrical Engineering at Rose-Hul-

    man Institute of Technology. Upon his

    graduation, he plans to join the Techni-

    cal Services division of Anderson Con-

    sulting in Chicago, IL. Dr. Rostamkolai

    is the Associate Professor of Electrical

    Engineering at Rose-Hulamn Institute

    of Technology.

    O N E OF T H E

    MOST

    CTIVE IEEE SO CIE TIE S

    The Microwave Theory and Techniques Society

    BENEFITS OF MTT S MEMBERSHIP

    W - S )

    ofthe

    IEEE is the

    premier

    OW

    for microwaves and applicationsover a frequency range

    typically 1

    to

    3 GEIZ.

    m sepresents

    the

    entire

    microwave

    community

    including all industrid, academic

    and government activities

    from basic

    scientific research

    through applied engineering There are

    over

    75 h4TT-S

    local chaptersand

    over

    9,000

    members

    worldwide.

    Worlds Largest nmlal Microwave Conference and Exhibition

    Student Paper Contest

    q &adUte F e ~ o ~ ~ p s ,

    m

    ~

    Local chapter activities nclude

    opportunities o

    participate n

    technical meetiugs, meet

    wth

    industry leaders, hear

    distinguished lecturers, etc.

    Student m embership iskee for the first

    year and

    includes

    the

    MTT-S

    Newsletter.

    To:

    IEEE

    Service Center, EO

    Box

    1331

    445

    Hoes Lane, Piscataway, NJ

    08855-1

    331

    SA:

    Yes Im an IEEE Student Member and Iwant to

    join MTT S (free for the

    first

    year).

    . _ _ _ _ _ _ _ _ _ _ _ _

    Membership number ........................................

    I

    Name ................................................................ I

    Address ............................................................. ,

    I

    Quarterly Newsletter included in membership

    Transactionson Microwave Theory and Techniques, Microwave

    and Guided Wave Letters available at greatly reduced rate

    AREAS

    OF

    ACfVITY

    Solid-state Devices

    Integrated Circuits

    Monolithic Circuits

    Superconductivity

    Millimeter waves

    Network Theory

    Field Theory

    Wireless Components

    &

    Systems

    AutomatedR Techniques

    ARFTG

    Digital Microwave Systems

    Fiber and Integrated Optics

    Computer Aided Design

    Low Noise Techniques

    High

    Power Techniques

    ........................... .......................... x Femte Components Biological

    &

    Medical Applications

    City

    Statelzip

    AcN19170744001 PPOT1795 8999

    FEBRUARY/MARCH

    1996 33