02-BSC Hardware Data

Embed Size (px)

Citation preview

  • 7/28/2019 02-BSC Hardware Data

    1/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Chapter 2 BSC Hardware Data

    2.1 Overview

    BSC hardware data configuration includes device property configuration, AM/CM data

    configuration and BM data configuration.

    2.2 Configuring Device Property

    Select [File/Set Device Property] in BSC Data Auto Configuration System, as shown

    in Figure 1.1.

    Figure 1.1 [Set Device Property] menu item

    The user can also click in the [Hardware] tab page, or click the

    button in the toolbar of BSC Data Auto Configuration System. The system

    pops up the [Set Device Property] interface. See Figure 1.2.

    1

  • 7/28/2019 02-BSC Hardware Data

    2/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Figure 1.2 Set Device Property

    As shown in Figure 1.2, [Device Type] is set as "Single Module Device" by default. If

    "Use SM Board Multiplex Mode" is selected, A interface trunk resources can be

    saved.

    It is recommended that single module devices should not be adopted. Therefore,

    "Multi-module Device" is taken as an example in the following data configuration

    procedures.

    Note:

    "Single Module Device" denotes single-module BSC. "Multi-module Device" denotes multi-module BSC.

    After [Device Type] is set as "Multi-Module Device", [Module Number] should be set

    according to each actual on-site device configuration. For example, in case of full

    configuration, this parameter should be set to "8", as shown in Figure 1.3.

    Figure 1.3 Example of device property configuration

    2

  • 7/28/2019 02-BSC Hardware Data

    3/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Then click to complete the device property configuration.

    Caution:

    If the device type is changed from multi-module to single module (vice versa), the old configuration data

    will be cleared. This operation is unrecoverable.

    2.3 Configuring AM/CM Data

    2.3.1 Overview

    AM/CM data configuration includes the configuration of communication control frame,

    transmission interface frame and clock frame.

    The full configuration of AM/CM is shown in Figure 1.1.

    Figure 1.1 Full configuration of AM/CM

    3

  • 7/28/2019 02-BSC Hardware Data

    4/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    2.3.2 Transmission Interface Frame

    I. Configuring Hardware Device

    There are two interface frames, i.e., frame 2 and frame 3, which are located in

    module 0. The number of boards contained can be automatically adjusted by the

    system according to the number of every BM. The full configuration of interface

    frames is shown in Figure 2-5.

    Figure 1.1 Full configuration of interface frames

    The number of E3Ms and GFBIs in an interface frame can be automatically adjusted

    according to the number of every BM. Generally, 2 GCTNs and 4 PWCs are

    configured.

    To add a board, the user can right click an empty slot and select [Select Board], as

    shown in Figure 1.2.

    Figure 1.2 Add a board

    There are two modes to delete a board.

    Right click the to-be-deleted board, and select [Delete Board], as shown inFigure 1.3.

    Figure 1.3 Delete a board

    4

  • 7/28/2019 02-BSC Hardware Data

    5/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Select the to-be-deleted board, and then press from the keyboard.

    Note:In BSC, the operations of adding or deleting a board are basically the same.

    When there are 4 BMs, the system will automatically adjust the number of E3Ms and

    GFBIs, as shown in Figure 1.4.

    Figure 1.4 Automatic adjustment of the number of E3Ms and GFBIs

    When there are 2 BMs, two adjacent GFBIs are required. E3M should be configured

    as per the number of TCMSs of in the BMs. Each E3M can be connected with 4

    TCSMs. When each BM is configured with 8 TCSMs, 2 E3Ms are required.

    II. Configuring SS7 Link

    For a multi-module BSC, SS7 links need be configured in the [Set E3M Board

    Property] dialog box. Each port (corresponding to a TCSM) on E3M can be

    configured with one SS7 link.

    Double click an E3M in IFigure 1.1, the system pops up an interface, as shown in

    Figure 1.1.

    5

  • 7/28/2019 02-BSC Hardware Data

    6/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Figure 1.1 Set E3M Board Property

    See Table 1.1 for the description of the parameters in [Set E3M Board Property].

    Table 1.1 Description of the parameters in [Set E3M Board Property]

    Parameter name Default value Description

    MSM TS None It must be consistent with that at MSC side.

    Generally, it is configured as "16".

    BIE TS None It is to specify the timeslots used by SS7 signaling

    in the transparent-transmission BIE. If multiple SS7

    links are configured in the same module, BIE

    timeslots cannot be the same. It cannot be

    configured as "0". Generally, it is configured as "16".

    FTC No. None No. of the FTC corresponding to the E1 on which

    SS7 is transmitted. It must be consistent with that at

    MSC side.

    Signaling Link 4 For No. 1 LPN7, the corresponding number of

    signaling links is No.4

    No.7. For No. 2 LPN7, thecorresponding number of signaling links is No.8

    No.11. The link number configured on the E3Ms in

    the same module cannot be the same.

    Connect TCSM Selected Automatically adjusted by the system.

    Interface Type A Interface When PCU is to be connected, "Pb Interface"

    should be selected.

    6

  • 7/28/2019 02-BSC Hardware Data

    7/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Parameter name Default value Description

    Trunk Work Mode A Interface CCS

    Mode

    When PCU is to be connected, "Pb Interface CCS

    Mode" should be selected. The parameter valuemust be consistent with that of the peer end.

    Transparent

    Transmission BIE

    Port No. for SS7

    Signaling

    Port 0 of Transparent

    Transmission BIE

    The port on transparent-transmission BIE that is to

    connect port 4 on E3M.

    Reference:

    [E3M E1 Configuration Table] in M900/M1800 Base Station Controller Data

    Configuration Reference - Engineering Parameters

    III. Configuring Clock Reference Source

    Click as shown in IIFigure 1.1. The system

    pops up an interface, as shown Figure 1.1.

    Figure 1.1 Set E3M clock reference source

    See Table 1.1 for the description of the parameters in [Board Clock Reference

    Source].

    Table 1.1 Description of the parameters in the [Board Clock Reference Source] dialog box

    Parameter name Default value Description

    Clock Reference Source 8k Clock

    Use Clock Reference Source's E1

    No.

    No. 0 E1 Port The port from which clock reference

    source is input from TCSM. The specified

    port must be connected with TCSM.

    7

  • 7/28/2019 02-BSC Hardware Data

    8/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Parameter name Default value Description

    Reference Source Name None Reference source can be named as per

    the actual requirement.

    Reference:

    [E3M CLK Source Output Selection Table] in M900/M1800 Base Station Controller

    Data Configuration Reference - Engineering Parameters

    2.3.3 Communication Control Frame

    The full configuration of the communication control frame is shown in Figure 1.1.

    Figure 1.1 Full configuration of the communication control frame

    I. Configuring GMCC

    The number of GMCCs can be automatically adjusted by the system as per thenumber of BMs. The GMCCs in Slot15 and Slot16 must be configured.

    See Table 1.1 for the corresponding relationship between GMCC and BM.

    Table 1.1 The corresponding relationship between GMCC and BM.

    Number of BMs Number of GMCCs

    12 4

    34 6

    56 8

    78 10

    II. Configuring GALM

    1 GALM is configured. Double click GALM to pop up the [AM Alarm Environment

    Variable Table] interface, as shown in Figure 1.1.

    8

  • 7/28/2019 02-BSC Hardware Data

    9/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Figure 1.1 AM Alarm Environment Variable Table

    For the alarm parameters, the default values are adopted.

    Reference:

    [AM Alarm Environment Variable Table] in M900/M1800 Base Station Controller Data

    Configuration Reference - Engineering Parameters

    III. Configuring GSNT

    2 GSNTs are configured by default.

    2.3.4 Clock Frame

    The clock frame is located in Frame5 of Module0, and is configured as "CKS Clock

    Frame" by default. The full configuration of the clock frame is shown in Figure 1.1.

    Figure 1.1 Full configuration of the clock frame

    For details, please refer to Chapter 4 Clock Data.

    2.3.5 Inter-module Link

    Click in 2.3.1 IFigure 1.1. The system pops up an interface,

    as shown in Figure 1.1.

    9

  • 7/28/2019 02-BSC Hardware Data

    10/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Figure 1.1 Set Inter-Module Link

    The setting of inter-module links includes two aspects.

    I. Set AM/CM Links

    Configure [GCTN Link Property] in the [AM/CM] tab page, as shown in Figure 1.1. It is

    recommended that the default configuration be adopted.

    Reference:

    [AM Adjacent Module OPT Table] of M900/M1800 Base Station Controller Data

    Configuration Reference Engineering Parameters

    II. Set BM Links

    Select the [BM] tab page, as shown in Figure 1.1.

    10

  • 7/28/2019 02-BSC Hardware Data

    11/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Figure 1.1 BM Module

    [Optical Link 1] and [Optical Link 2] should be set as per the physical connection of

    BM. [GMCC 1] and [GMCC 2] should be set as per the corresponding relationship

    between GMCC and BM. Generally, BM 1 and BM 2 respectively correspond toGMCC 2 and GMCC 3. By analog, the other corresponding relations can be obtained.

    It is recommended that the default settings be adopted.

    The default value of [Link Rate with AM/CM] is "512k".

    Reference:

    [AM Adjacent Module OPT Table] in M900/M1800 Base Station Controller Data

    Configuration Reference - Engineering Parameters

    2.4 Configure BM Data

    2.4.1 Overview

    Because the application of single module BSC is comparatively limited, here, only the

    BM data configuration of multi-module BSC is introduced.

    BM comprises main control frame, BIE frame and TCSM frame. 1 BM can be

    configured with 1 main control frame, 1 BIE frame and 12 TCSM frames. The full

    configuration of BM is shown in Figure 1.1.

    11

  • 7/28/2019 02-BSC Hardware Data

    12/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Figure 1.1 Full configuration of BM

    2.4.2 Main Control Frame

    The main control frame is located in Frame1 and Frame2 of BM. The full configuration

    is shown in Figure 1.1.

    Figure 1.1 Full configuration of the main control frame

    I. GMPU

    GMPU is the main processing unit of BM. Each BM is configured with 2 GMPUs,

    which are respectively configured in Slot10 of Frame1 and Frame2 of the main control

    frame. The two GMPUs work in active/standby mode. The active GMPU refers to the

    one which is under the control of GEMA. The GMPU in Frame2 serves as an active

    board by default. If switchover takes place, the previous standby GMPU will serve as

    the active board.

    12

  • 7/28/2019 02-BSC Hardware Data

    13/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    II. GEMA

    GEMA controls the active/standby working mode and switchover of GMPU. Each BM

    is fixedly configured with 1 GEMA.

    III. GNOD

    GNOD is used to provide mailbox communication between BIE and GMPU. Each

    GNOD can provide 4 master nodes, support 4 BIE groups (Each BIE group requires 1

    master node). In the case of full configuration, each BM contains 9 BIE groups, and

    requires 3 GNODs. Generally, the default settings can be adopted.

    IV. GMEM

    GMEM is a cell broadcast interface board, and provides cell broadcast function. Each

    BM is configured with 2 GMEMs by default, which work in active/standby mode. The

    one in Frame2 serves as the active board, and the one in Frame1 serves as a

    standby board. However, the standby GMEM is currently not supported. Generally,

    the GMEM is only configured to Frame2. To delete the GMEM in Frame1, please right

    click the GMEM and select [Delete Board]. Double click a GMEM to pop up the [Set

    GMEM Board Property] interface, as shown in Figure 1.1.

    Figure 1.1 Set GMEM Property

    Only when the cell broadcast function is required, GMEM property should be

    configured. For specific configuration, please refer to M900/M1800 Cell Broadcast

    System User Manual.

    13

  • 7/28/2019 02-BSC Hardware Data

    14/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    V. LPN7

    LPN7 is used to process SS7. Each LPN7 provides 4 SS7 links. The links provided by

    No. 1 LPN7 (in Slot17) are numbered 47. The links provided by No. 2 LPN7 (in

    Slot18) are numbered 811.

    VI. GLAP

    GLAP provides the LAPD links which connect BM and BTS. Each GLAP provides 32

    LAPD links. Numbering of the LAPD links provided by each board complies with the

    following rule.

    Board No. 32 + (031)

    For example, the LAPD links provided by GLAP 3 are numbered as 96127.

    Each BM can provide up to 192 LAPD links, and can support 64 BTSs and 128 TRXs.

    Double click GLAP to pop up the [Set GLAP Board Property] interface as shown in

    Figure 1.1.

    Figure 1.1 Set GLAP Property

    As shown in Figure 1.1, the number of assigned links is 29, which indicates that 29

    links of the GLAP are already in use.

    Reference:

    [LAPD Signaling Connection Table] in M900/M1800 Base Station Controller Data

    Configuration Reference - Engineering Parameters

    14

  • 7/28/2019 02-BSC Hardware Data

    15/26

  • 7/28/2019 02-BSC Hardware Data

    16/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Figure 1.2 Alarm Environment Variables Configuration Items

    Reference:

    [AM Alarm Environment Variable Table] in M900/M1800 Base Station Controller Data

    Configuration Reference Engineering Parameters.

    2.4.3 BIE Frame

    The BIE frame can be configured with max. 9 BIE groups (sequentially numbered as

    08 from left to right). Groups 07 each comprise 2 BIEs. There is only one BIE in

    Group8. The left board of each group is an active board, and the right one is a

    standby board. The full configuration of the BIE frame is shown in Figure 1.1.

    Figure 1.1 Full configuration of the BIE frame

    Double click the left board of a BIE group to pop up the [Set BIE Board Property]

    interface as shown in Figure 1.2.

    16

  • 7/28/2019 02-BSC Hardware Data

    17/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Figure 1.2 BIE Port Networking Property

    In the [BIE Port Networking Property] tab page, user can set BTS networking mode,

    number of the TRXs in BTS, etc. For specific configuration methods, please refer to

    Chapter 7 BTS Data and Chapter 8 BTS Networking Data.

    Double click the right board, e.g., BIE 1, in a BIE group in Figure 1.1. The system

    pops up the [Set BIE Board Property] interface as shown in Figure 1.3.

    17

  • 7/28/2019 02-BSC Hardware Data

    18/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Figure 1.3 Set BIE Board Property

    As shown in Figure 1.3, the basic information of BIE 1 is as follows. Each BIE group

    occupies 1 master node. The master node No. is "0". The slave node number is "1",

    i.e., the board number. [First HW] is configured as "0". [HW Number] is configured as

    "8", i.e., the board occupies HWs 07.

    There are total 64 HWs (No.0 No.47, No.76 No.91) allocated to a BIE group.

    Generally, groups 06 each occupy 8 HWs, and groups 78 each occupy 4 HWs.

    Note: If 4 HWs are merely configured, for an ordinary BIE in the corresponding trunk mode, the number of

    available ports is reduced by half. For example, if the trunk mode is "4E1 Port*6TRX/Port", Port0 and

    Port1 are available, while port 2 and port 3 are unavailable.

    For a transparent transmission BIE, only ports 03 are available.

    [Invisible]: It can be selected if there are empty slots (with no BIE plugged in).

    18

  • 7/28/2019 02-BSC Hardware Data

    19/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    [Port Self-Healing]: If selected, it indicates that the self-healing function provided by

    the system is enabled.

    [Board BIE Position Information]: It indicates the physical position of the BIE in the

    system.

    [BIE Active/Standby Property]: It indicates whether the BIE is an active or standby

    board.

    Select the [Basic Information] tab page in the [Set BIE Board Property] tab page in

    Figure 1.2.

    Figure 1.4 Basic Information

    Compared with Figure 1.3, there are 2 additional parameters, [CRC4 Check [000000]]

    and [Transparent Transmission of SS7 Signaling] in the [Basic Information] tab page

    of the active BIE.

    [CRC4 Verification [000000]] is used to configure whether CRC4 is to be performed

    for the ports on BIE. The six 0s respectively correspond to 6 E1 ports. If an E1 port is

    selected, the corresponding bit will be changed into 1, indicating that CRC4 will be

    performed for this port.

    19

  • 7/28/2019 02-BSC Hardware Data

    20/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    [Transparent Transmission of SS7 Signaling] indicates whether BIE is to transparently

    transmit SS7 signaling. If it is selected, the [BIE Port Networking Property] tab page

    will disappear. BIE Group9 (in Slot23) is configured as a transparent-transmission BIE

    by default.

    2.4.4 TCSM Frame

    TCSM implements the functions of transcoding/data rate adaptation (implemented by

    FTC) and submultiplexing (implemented by MSM). In the case of full configuration,

    there are 2 TCSM frames in a BM, containing total 8 TCSMs. Each TCSM comprises

    1 MSM and 4 FTCs. The full configuration of TCSM frame is shown in Figure 1.1.

    Figure 1.1 Full configuration of TCSM frame

    Note:In actual application, the hardware of TCSM frame is placed independently on the TCSM rack, instead of

    in Frame4 and Frame5 of the BM rack. If BSC is far from MSC, the TCSM rack and MSC are usually

    placed together to save transport resources.

    2.4.5 Current Rack

    Select different racks of BM

    For the multi-module BSC, the parameter [Current Rack] is not invalid. For the single

    module BSC, Rack1 of BM is configured with TCSM frames.

    2.5 Hardware Data Configuration Instance

    Here, take multi-module BSC configuration as an example. 1 AM/CM and 2 BMs need

    be configured. Each BM is to be configured with 4 TCSMs. The other boards are to be

    fully configured.

    20

  • 7/28/2019 02-BSC Hardware Data

    21/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    2.5.1 Configuring BSC Type

    Click in the [Hardware] tab page to pop up the [Set Device

    Property] interface, as shown in Figure 1.1.

    Figure 1.1 Set Device Property

    Set [Device Type] as "Multi-Module Device", and [Module Number] as "2", and then

    click .

    2.5.2 Configuring AM/CM Data

    I. Configuring Board

    Figure 1.1 shows the AM/CM hardware configuration automatically generated by the

    system.

    Figure 1.1 AM/CM data configuration

    21

  • 7/28/2019 02-BSC Hardware Data

    22/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    II. Modifying E3M Property

    Double click No.0 E3M, and configure the data properly in the pop-up [Set E3M Board

    Property] dialog box, as shown in Figure 1.1.

    Figure 1.1 Configure No.0 E3M

    Double click No.1 E3M, and configure the data properly, as shown in Figure 1.2.

    Figure 1.2 Configure No.1 E3M

    See Table 2.1 the description of E3M property configuration.

    Table 2.1 Description of E3M property configuration

    Parameter Name Default value Description

    E1 Port None Each E3M is configured with 1 SS7 link. Port0 is selected.

    22

  • 7/28/2019 02-BSC Hardware Data

    23/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Parameter Name Default value Description

    MSM TS None It is configured as "16". The value must be consistent with

    that at MSC side.

    BIE TS None It is configured as "16". It can be configured as any

    timeslot except for TS0.

    FTC No. None It is configured as "Board 0". The value must be consistent

    with that at MSC side.

    Signaling Link None No.0 E3M is configured with Link4. No.1 E3M is configured

    with Link8. The two E3Ms in the same BM are respectively

    configured with Link4 and Link8.

    Connect TCSM None Because 1 BM is configured with 8 TCSMs and there are 2

    E3Ms configured 1 BM, each E3M should be configured

    with 2 ports to connect TCSMs. "No. 0" and "No. 1" should

    be selected.

    Transparent

    Transmission BIE

    Port No. for SS7

    Signaling

    None No.3 E3M is configured withPort0. No.1 E3M is configured

    with Port1.

    Interface Type A Interface None

    Trunk Work Mode A Interface

    CCS Mode

    None

    III. Setting E3M Clock Reference Source

    Click to pop up a dialog box, as shown in

    Figure 1.1.

    23

  • 7/28/2019 02-BSC Hardware Data

    24/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    Figure 1.1 Set E3M clock reference source

    The default value is adopted for each parameter.

    2.5.3 Configuring BM Data

    I. Deleting Standby GMEM

    The standby GMEM is currently not supported. Right click the GMEM in Frame1 and

    select [Delete Board] in the short-cut menu to delete the board.

    II. Setting the TCSM with no Physical Configuration as "Invisible"

    If the visibility of an MSM is to be modified, double click the MSM and select

    "Invisible" in the pop-up [Set MSM Board Property] interface, as shown in Figure 1.1.

    Figure 1.1 Modify the visibility of MSM

    If the visibility of an FTC is to be modified, double click the FTC to pop up the [Set

    24

  • 7/28/2019 02-BSC Hardware Data

    25/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    FTC Board Property] interface. Select "Invisible" in the [Basic Information] tab page,

    as shown in Figure 1.2.

    Figure 1.2 Modify the visibility of FTC

    Repeat the operations if there are other boards to be modified. Figure 1.3 shows the

    physical configuration of BM after modification.

    Figure 1.3 Physical configuration of BM

    25

  • 7/28/2019 02-BSC Hardware Data

    26/26

    Initial ConfigurationM900/M1800 BSC Data Configuration Manual Chapter 2 BSC Hardware Data

    So far, AM/CM data configuration is completed.

    26