Upload
luis-cifuentes
View
219
Download
0
Embed Size (px)
Citation preview
7/29/2019 04039447
1/5
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 311
Detrimental Effects of Capacitors in DistributionNetworks in the Presence of Harmonic Pollution
Nicola Locci, Carlo Muscas, Member, IEEE, and Sara Sulis, Student Member, IEEE
AbstractThe main goal of this paper is to analyze the behaviorof an electric power network in the presence of harmonic distor-tion, when capacitors are installed. The work starts from a casestudy, where failure and malfunctioning of an industrial plant aredescribed with the help of experimental measurements. The theo-retical and mathematical details of thephenomena involvedare an-alyzed by suitable computer simulations. The study is performedby considering some important electrical quantities, evaluated ac-cording to the definitions proposed by the standard IEEE 1459.The results put in evidence that using some typical quantities, suchas the power factor, could lead to ambiguous conclusions in evalu-ating the actual quality of the loads, and this can assume specialimportance in virtue of the economic relevance of such quantities.
Index TermsCapacitors, harmonic distortion, power factor,power quality (PQ).
I. INTRODUCTION
CAPACITORS are widely used in distribution power net-
works to obtain reactive compensation of the inductive
loads. The root-mean-square (rms) value of the current in
the power line feeding the customers loads is reduced by
employing capacitors, so that both the generation capability of
the power plant and the losses in the distribution network are
minimized.However, the behavior of such compensation systems is op-
timal only under sinusoidal conditions. These days, the actual
operating conditions of power networks (in particular, distri-
bution networks) may significantly differ from the pure sinu-
soidal steady state, which is the reference condition for which
the plants and the electrical devices are usually designed, real-
ized, and applied.
This paper focuses on some implications of the harmonic dis-
tortion existing in modern distribution networks, when capaci-
tors are installed in some of the nodes, since there is growing ev-
idence that, under nonsinusoidal conditions, the presence of ca-
pacitors is associated with the partial or overall malfunctioning
of the plants (see, for instance, [1] and [2]).Furthermore, let us consider penalties for polluting loads and
power-quality indexes needed to assign responsibility for dis-
turbances in electric power systems. Doubts arise as to how the
role of capacitors should be taken into account when such ac-
knowledged indexes will be used to qualify the polluting be-
havior of loads. In particular, there is a possibility that some in-
dexes may penalize polluting consumers with capacitors in their
Manuscript received April 1, 2005; revised February 13, 2006. Paper no.TPWRD-00185-2005.
The authors are withthe Department of Electricaland ElectronicEngineering,University of Cagliari, Cagliari 9123, Italy (e-mail: [email protected]).
Digital Object Identifier 10.1109/TPWRD.2006.877088
plants [3][5], even if they are used for the reactive compensa-
tion of the fundamental component of the current.
In order to prove the relevance of these topics, we will con-
sider a case study consisting of an industrial plant with signifi-
cant harmonic pollution and the presence of capacitors.
First, the drawbacks that arose during preliminary tests will
be reported. It is shown that the nonsinusoidal conditions of the
network seriously affect the performance of the portion of the
plant where the capacitors are positioned, leading to interven-
tion of the protection relays and, thus, inhibiting the normal
plant operation. Then, the analysis of the network will be car-
ried out by means of proper simulations in order to investigatedifferent possible configurations by evaluating, for each test,
several electrical parameters defined in the IEEE 1459-2000
trial-use standard [6]. In particular, a well known and commonly
used parameter will be considered: the power factor, for which
different definitions are proposed in [6], according to different
measurement purposes and different network conditions. It is
well known that the power factor has important economic im-
plications since its value is related to the penalties applied by
utilities to consumers. The results of this study show that, if the
involved phenomena are not well understood and the proper pa-
rameters are not considered, it is possible to make significant er-
rors in the assignment of the responsibility for low-power factor.
II. CASE STUDY
A. Plant Layout
The experimental investigation was performed on the
network supplying the forge unit of a metallurgic plant for man-
ufacturing steel pieces. Fig. 1 shows the general scheme of the
plant. The industrial plant is supplied by two identical 1-MVA
medium-voltage (MV)/low-voltage (LV) transformers (referred
to as Tr1 and Tr2 in the following), having a common primary
MV (15 kV) bus. In the studied situation, the low-voltage
outputs of the transformers are independent of each other: the
feeder leaving from Tr1 is dedicated to the forge division (bymeans of its distribution center, named DC1 in Fig. 1), while
Tr2 supplies the other loads of the plant (distribution centers
DC2 and DC3).
The supply line from Tr1 to the distribution center of the forge
unit is 140 m long and is made by an EPR cable ( mm
for each phase plus the neutral conductor).
The power supply to the forge is provided by a three-phase
rectifier bridge, realized by thyristors, followed by a dc/ac high-
frequencyconverter (10 kHz) realized by means of a high-power
insulated-gate bipolar transistor (IGBT) inverter.
The nominal current of the device is 870 A, with a rated
voltage of 380 V. This nonlinear load is named Nlin in Fig. 1.
0885-8977/$20.00 2006 IEEE
7/29/2019 04039447
2/5
312 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007
Fig. 1. Plant layout.
From the same distribution center, a different feeder supplies
a linear load (Lin) representing the service circuits of the unit.
These circuits mainly include lighting circuits, consisting of
groups of 400-W metal halide lamps, equipped with capacitors
for reactive power compensation. The protection for the lighting
circuits is guaranteed by automatic circuit breakers (CBs).
During the preliminary tests, performed before starting the
normal operation of the industrial process, overload conditions
always occurred in the lighting circuit, thus causing the auto-
matic CBs to open in less than a minute after the forge was
triggered, even if CBs were designed and installed according to
standard requirements. Such problems have prevented the plant
from becoming operational.
B. Voltage and Current Measurement
To examine the nature and origin of the reported malfunc-
tioning, both the voltages and the currents in the crucial points
of the plant have been measured. A digital phosphor oscillo-scope Tektronix 3014 (sample rate 1.25 GSamples/s on each
channel, 9 b for the vertical resolution) was used to acquire the
waveforms. Voltage transduction is guaranteed by an active dif-
ferential probe Tektronix P5200 with a bandwidth ( 3 dB) up
to 25 MHz and accuracy 5%. Current transduction for currents
up to 100 A is ensured by a Hall effect clamp-on probe Tek-
tronix A622 with a frequency range up to 100 kHz and accu-
racy . The current feeding the distribution center
DC1 (whose rated value is 870 A) was directly measured on the
output of transformer Tr1, acquiring the voltage at the output ter-
minals of the current transformer installed in the power center.
Theaccuracy of themeasurement systemis quite low, owingtothe uncertainty introduced by both the transducers and the ver-
tical channels of the oscilloscope. According to Standard IEC
61000-4-30 [6], the instrument specifications could be marked
as class B performance.However, this accuracy class canbe con-
sidered sufficient for the troubleshooting purpose of these mea-
surementsand for the technical analysis reported in Section II-C.
As for the evaluation of the power quantities described in [7] and
discussed in Section III, more accurate data are necessary. To
calculate such quantities, the experimental tests have been sub-
stituted with suitable computer simulations that reproduce with
good approximation theactual situation. In this way, thedata pro-
cessed are not corrupted by any measurement uncertainty.
Fig. 2 shows the acquired waveform of the current supplyingthe forge distribution center and its spectral content.
Fig. 2. Current absorbed by the forge: (a) waveform and (b) frequency spec-trum.
Fig. 3. Line-to-neutral voltage in the division distribution center.
The significant distortion of the signal can be clearly ob-
served. The relevant total harmonic distortion (THD) is about
23%.
Fig. 3 shows the line-to-neutral voltage waveform measured
on the terminals of the feeder supplying the forge in the distri-
bution center. We can observe the significant distortion arising
fromthe highly distorted current absorbed by the nonlinear load.
In particular, the sudden commutations occurring in the cur-
rent cause voltage drops in the inductive impedance of the sup-
plying network, thus leading to the noticeable voltage spikes in
the waveform of Fig. 3. The THD of this waveform is 14%. Inorder to get a more exhaustive view over the voltage profile in
7/29/2019 04039447
3/5
LOCCI et al.: DETRIMENTAL EFFECTS OF CAPACITORS IN DISTRIBUTION NETWORKS 313
Fig. 4. Line-to-neutral voltage on the low-voltage terminals of the transformerTr1.
Fig. 5. Line-to-neutral voltage on the low-voltage terminals of the transformerTr2.
the overall plant, Fig. 4 shows the voltage waveform acquired
directly on the low-voltage side of Tr1.
The voltage distortion, caused by the harmonic current
flowing into the equivalent series impedance of both trans-
former Tr1 and supply network, is reduced with respect to the
voltage at distribution center DC1, which was also affected by
the voltage drop on the cable. This is confirmed by the fact that
the THD of this waveform is 11.6%.
Finally, Fig. 5 shows the voltage on low-voltage (LV) termi-
nals of transformer Tr2. This waveform is even less disturbed
than the one shown in Fig. 4, since it is not influenced by thedistorted voltage drop caused by the harmonic currents in Tr1.
As a consequence, the voltage on the LV bars of Tr2 has a THD
equal to 3%.
C. Failure Report and Analysis
In the distribution center DC1, as well as in the overall plant,
the protection for the lighting circuits was designed following
the usual rule of thumb. Malfunctioning and inefficiency of the
protection plant occurred during the tests as untimely operation.
The experimental acquisitions, along with the following consid-
erations, allowed us to explain the situation. Each 400-W metal
halide lamp of the lighting circuits is compensated with a 40- Fcapacitor and the combination absorbs 1.7-A rms line current
Fig. 6. Current absorbed by the three lamps lighting circuit.
with rated voltage 220 V. Each feeder supplies a group com-
posed of six lamps directly from the division distribution center.
The applied voltage is the one represented in Fig. 3.
In order to perform the experimental survey without causingthe untimely intervention of the protection, three of the six
lamps supplied by a single feeder where purposely bypassed.
Fig. 6 shows the current absorbed by this reduced load. The
rms current is 15 A, while the fundamental harmonic has an
amplitude of 5 A. There are current peaks up to 50 A, with
THD .
Therefore, the actual current in the feeder with the original
load (six lamps) is about 30 A rms, with peaks up to 100 A.
These values should be compared to the rms current that would
be absorbed by the same load under sinusoidal conditions,
which is .
One can notice that the ratio between the rms value of the dis-torted current and the nominal one
is around three.
Let us consider a thermal-magnetic CB, following the nor-
malized curve C (according to [9]) for the modular CBs, with
rated current . The same breaker in a polluted system
works with a ratio and, therefore, in this condition,
trips in 1 min. These considerations correspond perfectly with
that which was experimentally observed.
III. EVALUATION OF IEEE 1459 QUANTITIES
A. Simulations
The aim of this section is to closely examine the situation il-
lustrated in Section II by evaluating a few significant parameters
defined in the IEEE standard [7] in different realistic operating
conditions. Therefore, different network configurations should
be tested to compare the results. These tests were performed by
simulating the distribution plant under examination by means of
the PSCAD/EMTDC program, produced by Manitoba HVDC.
As stated before, the use of simulations also allows possible
problems arising from inadequate measurement accuracy to be
avoided in the evaluation of the meaningful parameters.
Nominal data from manufacturers, as well as experimental
results, were used to obtain a realistic model of the actual
system, so that a very good agreement exists between the ac-quired voltage and current waveforms and the simulated ones.
7/29/2019 04039447
4/5
314 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007
In particular, each lamp was modeled with a
model (where , ,
and F). The nonlinear load was modeled by means
of an equivalent circuit consisting of a linear load shunted with
harmonic current generators, whose values were extracted from
the experimental waveforms.
The IEEE Trial Use Standard 1459 provides definitions forthe measurement of electric power quantities under sinusoidal,
nonsinusoidal, balanced, or unbalanced conditions. Besides
the mathematical expressions that were used in the past, this
standard defines new expressions aimed at accounting for the
important changes that have occurred in the electric distribution
network during the last decades. In the introductive note of
the document, there is the claim that the new definitions
were developed to give guidance with respect to the quantities
that should be measured or monitored for revenue purposes,
engineering economic decisions, and determination of major
harmonic polluters.
The power factor definitions used here are as follows, with
the variables as defined in the Appendix:1) fundamental (50/60 Hz) power factor ;
2) total power factor .
To achieve the desired quantities, suitable signal processing has
been performed in the LabVIEW software package. One period
of the steady-state waveforms has been extracted from the simu-
lations to avoid spectral leakage problems in the frequency anal-
ysis performed by means of a discrete Fourier transform (DFT)
[9].
B. Results and Discussion
As shown in Fig. 1, the network has a linear load (Lin),namely the lighting circuits, and a strongly nonlinear load
(NLin), the forge, connected to the bus. In this specific situ-
ation, both loads are managed by the same customer, but, for
the purposes of this work, it is interesting to consider them as
if they would be representative of different users supplied by
the same bars, which could play the role of a point of common
coupling (PCC).
The measurement of both applied voltages and absorbed cur-
rents has been achieved at the departure of the relevant feeders
for each load.
The first tests were conducted by considering only one load
connected at a time.As for the linear lighting circuits, the two power factor defi-
nitions lead, as was expected, to the same numerical result.
In particular, when capacitors are not present, the inductive
nature of the load is clearly evidenced by a low power factor
, while the reactive compensation
achieved with the capacitors increases this value up to 0.954
for both indexes.
As for the nonlinear load, it is characterized by the following
values: and .
These results should be compared to the ones obtained when
both loads are supplied at the same time, which is the normal
operating condition of the plant.
When the forge is on, the noncompensated lighting circuitsfeature and . The similar values of
the two quantities can be explained by the fact that the induc-
tive lamps smooth the harmonic currents and, therefore, the har-
monic powers have little effect on the total power quantities.
In any case, the value is so low that the use of capacitors for
power factor correction seems to be mandatory. However, this
correction is valid for quantities at the fundamental frequency,
whereas it can introduce dramatic collateral effects, dependingon the strong increase of the harmonic distortion on the network,
as clearly shown in Section II-B. This is confirmed by the
results: the fundamental power factor is increased again
up to 0.954, whereas the total power factor falls down
to 0.180.
To complete the survey, it should be considered that on the
forge side the effects of the reactive compensation on the lamps
are significantly less noticeable: when the lighting circuit is not
compensated, the forge features and ,
while the introduction of the capacitors leads to
and .
The results achieved on this simple network emphasize the
need for carefully stating the most suitable definitions to be im-plemented in measurement instruments designed to analyze the
behavior of electric systems under nonsinusoidal conditions, es-
pecially when such results are used to establish penalties for
loads that contribute to the power-quality (PQ) degradation.
IV. CONCLUSION
This work focuses on an engineering problem related to the
effects of the capacitors in electric power networks in the pres-
ence of harmonic pollution. Starting from a real case in an ac-
tual low-voltage industrial plant, the study remarks that, owing
to the pervasiveness in the use of capacitors in such systems,
strong nonlinear loads could have serious implications on theoperation of neighboring plants.
In addition, by evaluating quantities purposely defined to be
measured for either revenue purposes or determination of major
harmonic polluters, it has been shown that customers with linear
loads, besides suffering from malfunctioning of their plants,
could also be penalized for the low-power factor, depending on
the definition implemented in the utility measurement station.
These considerations could be more complex when both linear
and nonlinear consumers take responsibility for harmonic pollu-
tion. In the assumption of sinusoidal conditions, the authorities
enforce penalties to avoid the low-power factor in the network.
Under nonsinusoidal conditions, the same penalties should be
enforced according to parameters solidly acknowledged, whose
recognized reliability would make the possible economical ef-
fects acceptable from the customers point of view.
APPENDIX
Let us indicate the rms value of the line to neutral voltage
as , the rms value of the line to line voltage as , the
rms value of the line current as , and the rms value of the
neutral current as , the fundamental positive-sequence voltage
component as , the fundamental positive-sequence current
component as , and the relevant phase angle as . On these
base meanings, the standard IEEE 1459 provides the following
definitions for power factors in three-phase nonsinusoidal andunbalanced four-wire systems.
7/29/2019 04039447
5/5
LOCCI et al.: DETRIMENTAL EFFECTS OF CAPACITORS IN DISTRIBUTION NETWORKS 315
1) Fundamental positive-sequence power factor
where
is the fundamental positive-sequence apparent power
is the fundamental positive-sequence active power
is the fundamental positive-sequence reactive power.
2) Total power factor
where is the total active power and
is the effective apparent power.
The rms effective current and voltage are defined as
REFERENCES
[1] M. Mamdouh Abdel Aziz, E. El-Din Abou El-Zahab, A. M. Ibrahim,and A. F. Zobaa, Effect of connecting shunt capacitor on nonlinearload terminals,IEEE Trans. Power Del., vol.18,no.4, pp. 14501454,Oct. 2003.
[2] R. H. Simpson, Misapplication of powercapacitorsin distribution sys-tems with nonlinear loads-three case histories,IEEE Trans. Ind. Appl.,vol. 41, no. 1, pp. 134143, Jan./Feb. 2005.
[3] D. Castaldo, A. Ferrero, S. Salicone, and A. Testa, An index for as-sessing the responsibility for injecting periodic disturbances, in Proc.6th Int. Workshop Power Definitions and Measurement Under Non-Si-nusoidal Conditions, Milano, Italy, Oct. 2003.
[4] E. J. Davis, A. E. Emanuel, and D. J. Pileggi, Evaluation of single-point measurements method for harmonic pollution cost allocation,
IEEE Trans. Power Del., vol. 15, no. 1, pp. 1418, Jan. 2000.[5] N. Locci, C. Muscas, and S. Sulis, On the measurement of power
quality indexes for harmonic distortion in the presence of capacitors,in Proc. IEEE IMTC, Ottawa, ON, Canada, May 1719, 2005, pp.16001605.
[6] Electromagnetic Compatibility ( EMC)Part 4: Testing and Measure-ment TechniquesSection 30: Power Quality Measurement Methods ,IEC Std. 61000-4-30, 2003.
[7] Trial-Use Standard: Definitions for the Measurement of Electric PowerQuantities Under Sinusoidal, Nonsinusoidal, Balanced or UnbalancedConditions, IEEE Std. 1459-2000, Jan. 2000.
[8] Electrical AccessoriesCircuit-Breakers for Overcurrent Protectionfor Household and Similar InstallationsPart 1: Circuit-Breakers fora.c. Operation, IEC 60898-1, 2003.
[9] A. V. Oppenheim and R. W. Schafer, Digital Signal Processing. En-glewood Cliffs, NJ: Prentice-Hall, 1975.
Nicola Locci received the Laurea degree in mechanical engineering from theUniversity of Cagliari, Cagliari, Italy, in 1974.
Currently, he is Associate Professor of electrical measurements with the De-partment of Electrical and Electronic Engineering, University of Cagliari. Hewas Professor of communication systems and his research topics are coding,photovoltaic systems, losses measurement in power electronics, and high-fre-quency (HF) transformers, variable reluctance motor parameters measurement,
and nonactive energy compensation. His research interests include measurementon power systems with distorted waveforms, transducers performance improve-ment, and accuracy evaluation in signal processing of data-acquisition systems.
Carlo Muscas (M98) wasborn in Cagliari, Italy, in 1969. He received the M.S.degree in electrical engineering from the University of Cagliari, Cagliari, Italy,in 1994.
He was Assistant Professor in the Electrical and Electronic MeasurementsGroup with the University of Cagliari from 1996 to 2001. Currently, he is Asso-
ciate Professor of electrical and electronic measurement. His research activitymainly focuses on the study of power-quality phenomena, including the de fini-tion of electrical quantities used to characterize the behavior of power systemsunder nonsinusoidal conditions, along with the metrological qualification of therelevant measurement processes. He is author or co-author of many scientificpapers.
Sara Sulis (S04) received the degree in electrical engineering from the Uni-versity of Cagliari, Cagliari, Italy, in 2002 and is currently pursuing the Ph.D.
degree in industrial engineering at the University of Cagliari.Her main research activity is in the field of power-quality measurements, with
particular attention to the definition and measurement of electrical quantities inpower systems under nonsinusoidal conditions and to the metrological qualifi-cation of the measurement processes involved.