Upload
wolnei-i-s-simao
View
216
Download
0
Embed Size (px)
Citation preview
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 1/32
i
Version No. 001
Electricity Safety (Electric Line Clearance)
Regulations 2005
S.R. No. 74/2005
Version as at 30 June 2005
TABLE OF PROVISIONS
Regulation Page1. Objectives 1 2. Authorising provisions 1 3. Commencement 1 4. Revocation 2 5. Definitions 2 6. Prescribed voltage 2 7. Prescribed Code of Practice 2 8. Prescribed penalty provisions 2 9. Management plans 2 10. Exemptions 7
11. Expiry 7 __________________
SCHEDULE—Code of Practice for Electric Line Clearance 8
═══════════════
ENDNOTES 29
1. General Information 29
2. Table of Amendments 30
3. Explanatory Details 31
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 2/32
1
Version No. 001
Electricity Safety (Electric Line Clearance)
Regulations 2005
S.R. No. 74/2005
Version as at 30 June 2005
1. Objectives
The objectives of these Regulations are to—
(a) prescribe the Code of Practice for Electric
Line Clearance;
(b) prescribe—
(i) standards and practices to be adopted
and observed in tree pruning or clearing
in the vicinity of electric lines and the
keeping of the whole or any part of
vegetation clear of electric lines;
(ii) management procedures to minimise
danger of electric lines causing fire or
electrocution;
(iii) other matters for or with respect to the
maintenance of electric lines;
(c) provide for management plans relating to
compliance with the Code;
(d) provide for other matters authorised under
the Act relating to electric line clearance.
2. Authorising provisions
These Regulations are made under sections 89,
151 and 157 of the Electricity Safety Act 1998.
3. Commencement
These Regulations come into operation on 30 June
2005.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 3/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
2
4. Revocation
The Electricity Safety (Electric Line Clearance)
(Interim) Regulations 20041 are revoked.
5. Definitions
In these Regulations—
"clear" means to cut and remove the whole of a
tree or plant;
"Code of Practice" means the Code of Practicein the Schedule.
6. Prescribed voltage
For the purposes of the definition of "low voltage
electric line" in section 3 of the Electricity Safety
Act 1998, the prescribed voltage is 1000 volts
alternating current or 1500 volts direct current.
7. Prescribed Code of Practice
For the purposes of Part 8 of the Electricity
Safety Act 1998, the Code of Practice in theSchedule is prescribed as the Code of Practice for
Electric Line Clearance.
8. Prescribed penalty provisions
For the purposes of section 90 of the Electricity
Safety Act 1998, clauses 2.1, 2.2, 3, 4.1, 6.1, 6.2,
7, 8.1 and 8.2 of the Code of Practice are the
prescribed provisions of the Code.
9. Management plans
(1) In this regulation, "responsible person" means a person referred to in section 84(4), (5), (6) or (7)
of the Electricity Safety Act 1998.
(2) A responsible person must take reasonable steps
to ensure that a management plan relating to
compliance with the Code of Practice has been
prepared and approved by the Office.
r. 4
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 4/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
3
(3) A responsible person must before 28 February in
each year prepare and submit to the Office for
approval a management plan relating to
compliance with the Code of Practice for the next
financial year that satisfies the requirements of
sub-regulation (4).
Penalty: 10 penalty units.
(4) The management plan must specify—
(a) the name, address and telephone number ofthe responsible person;
(b) the name, position, address and telephone
number of the person who was responsible
for the preparation of the plan;
(c) the name, position, address and telephone
number of the persons who are responsible
for carrying out the plan;
(d) the telephone number of a person who can be
contacted in an emergency that requires
clearance of an electric line that theresponsible person is required to keep clear
of vegetation;
(e) the objectives of the plan;
(f) a description and map of the land to which
the management plan applies identifying—
(i) the location of areas of vegetation and
the predominant category of vegetation
in those areas;
(ii) the location of areas of vegetation—
(A) determined by the relevant
municipal council to be
historically or culturally important
vegetation or vegetation of
outstanding aesthetic value; or
r. 9
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 5/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
4
(B) that is specified in a relevant
planning scheme to be of
botanical or ecological
significance; or
(C) that is the habitat of rare or
endangered species—
which may need to be pruned or cleared
to ensure compliance with the Code of
Practice;
(iii) the location of electric lines that the
responsible person is required to keep
clear of vegetation;
(g) details of the methods that will be used to
avoid and minimise the impact on vegetation
referred to in paragraph (f)(ii);
(h) the long term strategies to minimise—
(i) the risk of electric lines starting fires or
causing electrocution; and
(ii) the adverse effects of electric lines on
surrounding vegetation; and
(iii) the risk to the safe operation of electric
lines due to vegetation that is likely to
grow into or encroach on the clearance
space required by the Code of Practice;
(i) the methods proposed to be adopted for
maintaining the clearance space required by
the Code of Practice between electric lines
and vegetation;(j) the alternative methods that may be adopted
for maintaining the clearance space required
by the Code of Practice between electric
lines and vegetation if a person objects to the
methods proposed by the responsible person
and details of how the alternative methods
are to be implemented;
r. 9
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 6/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
5
(k) the methods to be adopted to prevent excess
pruning or clearing of vegetation;
(l) the length of the period between each
pruning or clearing of vegetation;
(m) the qualifications, proficiency and
experience that the responsible person will
require of the persons who are to carry out
the pruning or clearing of vegetation;
(n) details of the technical standards that theresponsible person will apply or have regard
to in connection with electric line clearance
work;
(o) the management procedures to be adopted by
the responsible person to ensure compliance
with the Code of Practice, which must
include details of the following—
(i) the procedures to be adopted to identify
locations where the pruning or clearing
of vegetation will be required;(ii) the methods to be used to calculate the
dimensions of the space beyond the
clearance space required by the Code of
Practice that must be pruned or cleared
to allow for anticipated vegetation
regrowth into the clearance space
between pruning or clearing;
(iii) the methods to be used to monitor
conditions in the area beyond the
regrowth space referred to in sub- paragraph (ii) to identify any vegetation
that could become a hazard to the
safety of the electric lines under the
range of weather conditions that can
reasonably be expected to prevail in
that area, having regard to the need to
r. 9
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 7/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
6
prune or clear that vegetation in
accordance with the Code;
(iv) the methods to be used to calculate the
length of the period required between
each pruning or clearing of vegetation;
(v) the methods and requirements that are
to be used to ensure that urgent pruning
or clearing to maintain the clearance
space between each clearing or pruning
time specified in the plan should not be
required;
(vi) the conditions under which urgent
pruning or clearing to maintain the
clearance space between each clearing
or pruning time specified in the plan
will be undertaken;
(p) a description of the information and
materials relating to electric line clearance
that the responsible person makes available
to the Office and the public and details of the
place and times at which they are available;
(q) a description of the measures that will be
used to assess the performance of the
responsible person under the management
plan;
(r) details of the audit processes that will be
used to determine the responsible person's
compliance with the Code of Practice;
(s) a dispute resolution procedure that—
(i) identifies the name, position, address
and telephone number of the
appropriate person who is responsible
for resolving disputes between the
responsible person and members of the
public; and
r. 9
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 8/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
7
(ii) identifies an external dispute resolution
procedure to be followed if the dispute
cannot be resolved directly with the
responsible person.
(5) The Office may require the responsible person to
provide further information or material in respect
of the management plan.
(6) A responsible person must not contravene or fail
to comply with a requirement of the management
plan that has been approved by the Office with
respect to that person.
Penalty: 20 penalty units.
(7) A responsible person must ensure that a copy of
the management plan approved by the Office is
available for inspection by the public at the
person's principal office in the State during normal
business hours.
10. Exemptions
The Office may exempt a responsible person fromany of the requirements of these Regulations
subject to any conditions specified by the Office.
11. Expiry
These Regulations cease to have any force or
effect on 30 June 2010.
__________________
r. 10
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 9/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
8
SCHEDULE
Regulations 5, 7
CODE OF PRACTICE FOR ELECTRIC LINE CLEARANCE
PART 1—PRELIMINARY
INTERPRETATION
1. Definitions
1.1 In this Code—
"aerial bundled cable" means an insulated electric line certified as being manufactured to AustralianStandard AS 3560 or Part 1 or Part 2 of AS 3599;
"affected person" means, in relation to the pruning orclearing of vegetation on land, an owner or occupier(including a person who is responsible for themanagement of public land) of abutting land wherethe pruning or clearing will affect the use of thatabutting land;
"away" in relation to a pole holding an electric line, meansthat section of the electric line that is not near the pole;
"clear" means to cut and remove the whole of a tree or plant;
"constructed" includes reconstructed or structurallyaltered;
"hazardous bushfire risk area" means—
(a) an area that a fire control authority has assigneda fire hazard rating of "high" under section 80of the Act; or
(b) any other area that is not an urban area unless afire control authority has assigned to that area afire hazard rating of "low" under section 80 of
the Act;
"insulated cable" means a low voltage, multi-core electricline insulated by a medium other than an air space;
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 10/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
9
"low bushfire risk area" means—
(a) an area that a fire control authority has assigned
a fire hazard rating of "low" under section 80 ofthe Act; or
(b) an urban area within the meaning of the Act;
"low voltage" means a voltage not exceeding 1000 voltsalternating current or 1500 volts direct current;
"near" in relation to a pole holding an electric line, meanswithin a distance to the pole of 1/6th of the span of the
electric line;"nominal voltage" means the voltage at which the electric
line is designed to operate;
"powerline" means an electric line with a nominal voltage
of 66 000 volts or less but does not include atransmission line;
"sag", in relation to a conductor, means the vertical
displacement of the conductor below the point atwhich the conductor is attached to the supportingstructure and includes any extra displacement caused by hot weather or high load current;
"sway", in relation to a conductor, means the horizontaldisplacement of the conductor caused by wind;
"the Act" means the Electricity Safety Act 1998;
"transmission line" means—
(a) an electric line with a nominal voltage of morethan 66 000 volts; or
(b) an electric line operating at 66 000 volts that issupported on a tower structure or that isadjacent to an electric line that has a nominalvoltage greater than 66 000 volts;
"vegetation" means the whole or any part of a tree or plant.
1.2 In this Code, all words and expressions have the samemeaning as in the Act.
1.3 The figures used in this Code are for illustrative purposesonly and are not intended to be a comprehensive depictionof the situation they illustrate or to extend the meaning of
the clause or Table to which they relate.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 11/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
10
PART 2—CLEARANCE SPACE REQUIREMENTS FOR ALL
ELECTRIC LINES
2. Clearance space for electric lines
2.1 A responsible person must create and maintain a clearancespace in all directions around a powerline in accordancewith—
(a) Parts 2 and 3 of this Code; and
(b) Tables 9.3, 10.1, 10.2, 10.3 and 11.1 in the Scheduleto this Code.
2.2 A responsible person that owns or operates a transmissionline must create and maintain a clearance space in alldirections around the transmission line in all conditions ofsag and sway of the conductors in accordance with—
(a) Parts 2 and 4 of this Code; and
(b) Table 13.1 in the Schedule to this Code.
3. Notice requirements
Before performing any pruning or clearing required by this
Code, a responsible person must—
(a) obtain permission from—
(i) in the case of pruning, the occupier of the landon which the vegetation is to be pruned;
(ii) in the case of clearing, the owner and theoccupier of the land on which the vegetation isto be cleared and any affected person; or
(b) give at least 14 days written notice—
(i) of pruning, to the occupier of the land on which
the vegetation is to be pruned and to anyaffected person;
(ii) of clearing, to the owner and the occupier of the
land on which the vegetation is to be clearedand to any affected person; or
(c) if, after taking reasonable steps the responsible person
is unable to give notice under paragraph (b), give21 days notice of pruning or clearing in a newspaper
circulating generally in the locality of the land onwhich the vegetation is to be pruned.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 12/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
11
4. Consultation requirements
4.1 A responsible person must ensure that before commencing
any pruning or clearing under this Code, the followingrequirements are undertaken—
(a) in the case of pruning, consultation with the occupier
of the land on which vegetation is to be pruned andwith any affected persons and the taking of reasonablesteps to negotiate—
(i) agreement with the occupier and affected
persons about the pruning to be undertaken if
the pruning will change the established practicefor that location; or
(ii) a modification of the pruning to be undertaken
or an alternative method for maintaining theclearance space if the occupier or an affected person objects to the pruning proposed in anotice under clause 3(b) or (c);
(b) in the case of pruning, consultation with the occupierof the land on which the vegetation is to be prunedand the taking of reasonable steps to negotiatemethods of disposal of debris resulting from the pruning that are acceptable to the occupier;
(c) in the case of clearing, the taking of reasonable stepsto consult and negotiate with the owner of the land onwhich vegetation is to be cleared and with affected
persons concerning—
(i) the clearing of the vegetation that is acceptableto the owner and those persons; or
(ii) a method for maintaining the clearance spaceother than clearing the vegetation that isacceptable to the owner and those persons;
(d) in the case of clearing, the taking of reasonable stepsto consult and negotiate with the owner of the land on
which the vegetation is to be cleared about methods ofdisposal of vegetation resulting from the clearing thatare acceptable to the owner;
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 13/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
12
(e) in the case of pruning or clearing, consultation withthe occupier of the land on which the vegetation is to be pruned or cleared, concerning arrangements for—
(i) access by the responsible person to clearancespaces; and
(ii) the use of chemicals.
4.2 A responsible person must have a written statement settingout the methods that the person will use to carry out theconsultation and negotiation required under clause 4.1 and
the time limits within which the consultation and negotiation
will be carried out.
4.3 A responsible person must not commence pruning orclearing the following vegetation before obtaining advice
from a qualified arborist or horticulturalist in relation to theregrowth of that vegetation—
(a) vegetation that is determined by the relevant
municipal council to be historically or culturallyimportant vegetation or vegetation of outstandingaesthetic value;
(b) vegetation that is specified in a relevant planningscheme to be of botanical or ecological significance;
(c) vegetation that is the habitat of rare or endangeredfauna or flora species.
URGENT PRUNING OR CLEARING
5. Exemptions from notice and consultation requirements—
urgent pruning or clearing
Clauses 3, 4.1, 4.2 and 4.3 do not apply to a responsible person referred to in section 84(4), 84(5), 84(6) or 84(7) of
the Act that is undertaking urgent pruning or urgent clearingrequired—
(a) as a result of encroachment or growth of vegetation
that was not anticipated in the management plan; or
(b) as a result of a tree falling or damage to a treerequiring the tree to be cleared to maintain theclearance space required by this Code; or
(c) from 1 November in any year until the end of the firedanger period declared under the Country Fire
Authority Act 1958.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 14/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
13
6. Requirements for urgent pruning or clearing
6.1 A responsible person referred to in section 84(4), 84(5),
84(6) or 84(7) of the Act that carries out urgent pruning orurgent clearing referred to in clause 5(a) or 5(c) must notclear the vegetation for a distance exceeding 1 metre beyondthe clearance space (including the distance allowed for thesag and sway of the conductors).
6.2 A responsible person referred to in section 84(4), 84(5),84(6) or 84(7) of the Act that has carried out urgent pruningor urgent clearing referred to in clause 5 must, as soon as practicable after completing the pruning or clearing,
notify—
(a) the occupier of the land on which vegetation was pruned and affected persons of the pruning; and
(b) the owner and occupier of the land on whichvegetation was cleared and affected persons of theclearing.
6.3 The responsible person referred to in section 84(4), 84(5),84(6) or 84(7) of the Act that undertakes any urgent pruningor clearing referred to in clause 5 must record details of—
(a) where and when the pruning or clearing was
undertaken;(b) details of why the pruning or clearing was required;
(c) details of the last inspection of that section of theelectric line where the pruning or clearing was
required.
6.4 The information recorded under clause 6.3 must be kept fora period of at least 2 years.
ADDITIONAL CONSULTATION BY SPECIFIC BODIES
7. Additional duties of local councils, the Roads Corporation and
others
If a responsible person referred to in section 84(4) or (6) ofthe Act is aware of the concerns of any person about thesafety of pruning or clearing vegetation near a powerline,the responsible person must consult—
(a) if a railway or tramway company owns or operatesthat powerline, the railway or tramway company; and
(b) in all other cases, the distribution company that isresponsible for distributing power to that powerline.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 15/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
14
8. Management procedures to minimise danger
8.1 A distribution company must, at least once a year, advise
occupiers of land above the surface of which there is a private electric line that is within its distribution area of thefollowing matters—
(a) the duties of the responsible person under this Code;
(b) the dangers of pruning and clearing vegetation;
(c) the precautions that should be taken to safely maintainthe line.
8.2 A distribution company must, in relation to its distributionarea, on the request of a responsible person advise that person—
(a) how to identify places where the pruning or clearing
of vegetation will be required; and
(b) where to obtain advice and information on methodsfor maintaining clearance between electric lines and
vegetation.
PART 3—POWERLINE CLEARANCE
9. Aerial bundled cables and insulated cables in all areas
9.1 The clearance spaces that must be cleared and maintained inall directions from a powerline, for all areas and for allnominal voltages of powerlines constructed with an aerial bundled cable or that are insulated cables are those set out inTable 9.3 in the Schedule to this Code being—
(a) the clearance spaces near the pole set out in column 1of Table 9.3; and
(b) the clearance spaces away from the pole for the spansset out in columns 2, 3 and 4 of Table 9.3.
9.2.1 The requirement for clearance space surrounding an aerial bundled cable or insulated cable under clause 9.1 does not
apply to small tree branches with a diameter of less than10 millimetres and leaves if, at least once a year, the branches and leaves are removed from the clearance spaceas required in clause 9.1.
9.2.2 Branches and leaves are not required to be annuallyremoved in accordance with clause 9.2.1 if the branches andleaves are not likely to abrade the cable before they are next
removed in accordance with this Code.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 16/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
15
9.3 If the responsible person complies with clause 12, therequirements of clause 9.1 do not apply to existing tree branches that exceed 130 millimetres in diameter, if the branch is more than 300 millimetres from an aerial bundledcable or insulated cable.
10. Powerlines other than aerial bundled cable or insulated cables
in low bushfire risk areas
In the case of powerlines, other than those constructed withan aerial bundled cable or that are insulated cables, theclearance spaces required in low bushfire risk areas are—
(a) if the responsible person elects not to comply withclause 12, the clearance spaces set out in Table 10.1 inthe Schedule to this Code being—
(i) the clearance spaces in all directions, exceptvertically above the line for 66 000 volt powerlines where no vegetation is permitted,near the pole set out in column 1 of Table 10.1;and
(ii) the clearance spaces in all directions, exceptvertically above the line for 66 000 volt powerlines where no vegetation is permitted, awayfrom the pole for the spans set out in columns 2
and 3 of Table 10.1;
(b) if the responsible person elects to comply withclause 12 in relation to powerlines of 22 000 volts or
less, the clearance spaces set out in Table 10.2 in theSchedule to this Code;
(c) if the responsible person elects to comply with
clause 12 for 66 000 volt powerlines, the clearancespaces set out in Table 10.3 in the Schedule to thisCode.
11. Powerlines other than aerial bundled cable or insulated cables
in hazardous bushfire risk areas
11.1 If the powerlines are not constructed with an aerial bundledcable and are not insulated cables the clearance spacesrequired in hazardous bushfire risk areas are the clearance
spaces in all directions, except vertically above the line, setout in Table 11.1 in the Schedule to this Code.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 17/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
16
11.2 The requirements of Table 11.1 in the Schedule to thisCode do not apply to tree branches above a powerline of22 000 volts or less if—
(a) the responsible person maintains a minimumclearance of 3000 millimetres above the powerline toany overhanging tree branch; and
(b) an annual risk assessment is undertaken by an arboristwho has the qualifications and experience referred toin clause 12(b); and
(c) the annual risk assessment is completed before
1 November in each year; and
(d) any overhanging branches and the trees supporting the branches do not exhibit any potentially hazardous
structural defects; and
(e) the responsible person keeps records of the annualrisk assessment on any branches and trees that are
subject to this sub-clause, including details of thecondition and possible hazards in relation to each treeand branch; and
(f) the records of the annual risk assessment are kept fora period of no less than 5 years; and
(g) the relevant powerline has mitigation measures in place that limit the phase to earth fault current or thefault duration to a level that minimizes the risk ofignition of vegetation.
12. Additional requirements for tree branches
Clauses 9.3, 10(b) and 10(c) apply in relation to tree branches if—
(a) the responsible person is a distribution company or amunicipal council that is responsible for land in anarea declared under section 81 of the Act; and
(b) the distribution company or municipal council ensuresthat an arborist, who has the qualification of NationalCertificate Level IV in Horticulture and Arboriculture
including the "Assess Trees" module, or theequivalent of that certificate, and at least 3 years of
field experience in assessing trees carries out anannual risk assessment on the tree; and
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 18/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
17
(c) the distribution company or municipal council keepsrecords of the annual risk assessment, includingdetails of the condition and possible hazards inrelation to each tree; and
(d) the records of the annual risk assessment are kept fora period of no less than 5 years.
PART 4—TRANSMISSION LINE CLEARANCE
13. Clearance space for specified directions
13.1 The clearance space vertically below a conductor of a
transmission line must be—
(a) if the conductor is at maximum sag, the distancespecified in column 1 of Table 13.1 in the Schedule tothis Code;
(b) if the conductor is in its normally observed position,the distance specified in column 3 of Table 13.1 in theSchedule to this Code.
13.2 The clearance space horizontally from the outermostconductor of a transmission line must be—
(a) if the conductor is at the limit of sway, the distancespecified in column 2 of Table 13.1 in the Schedule tothis Code;
(b) if the conductor is in its normally observed position,
the distance specified in column 4 of Table 13.1 in theSchedule to this Code.
13.3 The space above the transmission line must be kept clear of
vegetation at all times.
__________________
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 19/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
18
SCHEDULE TO CODE OF PRACTICE
TABLE 9.3
Clauses 2.1 and 9.1
MINIMUM CLEARANCE SPACES SURROUNDING
A POWERLINE—ALL AREAS
Aerial Bundled Cable or Insulated Cable
Clearance Spaces2
Near pole Away from pole
1 2 3 4
Type of
Powerline
All Spans
near the pole
Spans up toand
including40 metres
Spansexceeding 40
up to andincluding
70 metres
Spansexceeding70 metres
In all directions
AerialBundledCable
300 mm 300 mm 600 mm 900 mm
InsulatedCable
600 mm 600 mm 1000 mm 1000 mm
Note: Table 9.3 is partially illustrated in Figures 9.3 and 9.4.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 20/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
19
Figure 9.3: ALL AREAS
Tables 9.3 and 10.1
PLAN VIEW OF AN OVERHEAD POWERLINE
NOT TO SCALE
Sch.
NEAR THE POLE
CENTRE 2/3 OF SPAN
AWAY FROM THE POLE POSITION
1/6 1/6
SPANSPAN
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 21/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
20
Figure 9.4: ALL AREAS3
Table 9.3
NOT TO SCALE
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 22/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
21
TABLE 10.1
Clauses 2.1 and 10
MINIMUM CLEARANCE SPACES SURROUNDING
A POWERLINE—LOW BUSHFIRE RISK AREAS
Other Than Aerial Bundled Cable or Insulated Cable
Clearance Spaces
Near Pole Away from pole
1 2 3
Type of
Powerline
Section of all spans near the
pole
Spans up to andincluding40 metres
Spans exceeding
40 metres
Nominal voltage In all directions
Bare andCovered LowVoltage
1000 mm 1000 mm 1500 mm
6⋅6 kV, 11 kV
and 22 kV
1500 mm 1500 mm 2000 mm
66 kV 2250 mm 2250 mm 3000 mm
For 66 kV—The space vertically above the powerline must be kept clear ofvegetation.
An additional distance must be added to the clearance space to allow for thesag and sway of the conductors and for vegetation regrowth during the period between pruning times.
Note: Table 10.1 is partially illustrated in Figure 9.3 and, except for66 kV powerlines, in Figure 10.4.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 23/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
22
TABLE 10.2
Clauses 2.1 and 10
MINIMUM CLEARANCE SPACES SURROUNDING
A POWERLINE—LOW BUSHFIRE RISK AREA
Other Than Aerial Bundled Cable or Insulated Cable
Clearance Spaces
1 2 3 4
Type of Powerline
Spans up toand
including30 metres
Spansexceeding
30 up to andincluding45 metres
Spansexceeding
45 up to andincluding70 metres
Spansexceeding70 metres
Nominal voltage In all directions
Bare lowvoltage
1000 mm 1000 mm 1500 mm 1500 mm
Bare lowvoltage and
additional safetymeasures
500 mm 600 mm 800 mm 1500 mm
Bare 6⋅6 kV,11 kV and 22kV
1000 mm 1500 mm 2000 mm 2000 mm
Covered 6⋅6 kV,11 kV and22 kV
1000 mm 1250 mm 1500 mm 2000 mm
An additional distance must be added to the clearance space to allow for thesag and sway of the conductors and for vegetation regrowth during the period between pruning times.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 24/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
23
TABLE 10.3
Clauses 2.1 and 10
CLEARANCE SPACES SURROUNDING A 66 KV POWERLINE—
LOW BUSHFIRE RISK AREA
Clearance Spaces
1 2 3 4
Type of Powerline
Spans up toand
including30 metres
Spans
exceeding30 up to and
including45 metres
Spans
exceeding45 up to and
including70 metres
Spans
exceeding70 metres
Nominal voltage In all directions except vertically above a 66 kV line
66 kV 2250 mm 2250 mm 3000 mm 3000 mm
Vertically above a 66 kV line
66 kV 3000 mm 3000 mm 3000 mm 3000 mm
An additional distance must be added to the clearance space to allow for thesag and sway of the conductors and for vegetation regrowth during the period
between pruning times.
Note: Table 10.3 is partially illustrated in Figure 10.4.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 25/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
24
Figure 10.4: LOW BUSHFIRE RISK AREAS
Tables 10.1 and 10.3
CLEARANCE SPACE
Free of vegetation
Trees should not beremoved without prior
consultation and agreement
Tominimize pruning
only specieswith suitablegrowth habits
should be plantedunder powerlines
LOW BUSHFIRE RISK AREAS
NOT TO SCALE
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 26/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
25
TABLE 11.1
Clauses 11.1 and 11.2
MINIMUM CLEARANCE SPACES SURROUNDING
A POWERLINE—HAZARDOUS BUSHFIRE RISK AREAS
Other Than Aerial Bundled Cable or Insulated Cable
Clearance Spaces
1 2 3 4 5
Type of Powerline
Spans up toand
including30 metres
Section of
all spansnear the
pole
Spansexceeding30 up to
andincluding45 metres
Spansexceeding45 up to
andincluding70 metres
Spansexceeding70 up to
andincluding
350 metres
Spansexceeding350 metres
Nominal
voltage In all directions (except vertically above the line)
Bare andcoveredlow voltage
1500 mm 1500 mm 2000 mm 2000 mm 2250 mm
6⋅6 kV,11 kV and22 kV
1500 mm 1500 mm 2000 mm 2000 mm 2250 mm
66 kV 2250 mm 2250 mm 3000 mm 3000 mm 3000 mm
For 66kV—The space vertically above the powerline must be kept clear ofvegetation.
An additional distance must be added to the clearance space to allow for the sag
and sway of the conductors and for vegetation regrowth during the period between pruning times.
Note: Clause 11.2 provides that the requirements of this table do not apply
to tree branches above a powerline of 22 000 volts or less if the branches are more than 3000 millimetres above the powerline and theresponsible person complies with the other conditions in clause 11.2.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 27/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
26
Figure 11.1: HAZARDOUS BUSHFIRE RISK AREAS
Table 11.1
CLEARANCE SPACE
Free of vegetation
Trees should not beremoved without prior
consultation and agreement
Only specieswith suitable
growth habitsshall be planted near or under powerlines orbe allowed to remain
NOT TO SCALE
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 28/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
27
TABLE 13.1
Clauses 2.2(b), 13.1 and 13.2
MINIMUM CLEARANCE SPACES SURROUNDING
A TRANSMISSION LINE
Minimum clearance space atthe limits of sag and sway of
the conductor
Minimum clearance space from the normally observed
position of the conductor
1 2 3 4
NominalVoltage
DimensionVertical
Dimension Horizontal
DimensionVertical
Dimension Horizontal
66 kV 3000 mm 3000 mm 7000 mm 12 000 mm
220 kV 3700 mm 4600 mm 8000 mm 13 000 mm
275 kV 4200 mm 5000 mm 8000 mm 13 000 mm
330 kV 4700 mm 5500 mm 9000 mm 14 000 mm
500 kV 6400 mm 6400 mm 11 000 mm 15 000 mm
For all voltages—The space vertically above the transmission line must be
kept clear of vegetation at all times.An additional distance must be added to the clearance space to allow for thesag and sway of the conductors and for vegetation regrowth during the period between clearing times if the distance between conductors exceeds 400metres.
Columns 1 and 2 set out the clearance spaces that must be kept clear ofvegetation under all conditions of sag and sway.
Columns 3 and 4 set out the distances that must be kept clear of vegetation tomaintain the clearance space from the normally observed position of theconductor
Note: Table 13.1 is partially illustrated in Figures 13.1 and 13.2.
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 29/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
28
Figure 13.1: END VIEW OF THE TRANSMISSION LINE
Table 13.1
Figure 13.2: SIDE VIEW OF THE TRANSMISSION LINE
Table 13.1
═══════════════
Sch.
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 30/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
29
ENDNOTES
1. General Information
The Electricity Safety (Electric Line Clearance) Regulations 2005,S.R. No. 74/2005 were made on 28 June 2005 by the Governor in Councilunder sections 89, 151 and 157 of the Electricity Safety Act 1998, No. 25/1998 and came into operation on 30 June 2005: regulation 3.
The Electricity Safety (Electric Line Clearance) Regulations 2005 will sunseton 30 June 2010: regulation 11.
Endnotes
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 31/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
30
2. Table of Amendments
There are no amendments made to the Electricity Safety (Electric Line
Clearance) Regulations 2005 by statutory rules, subordinate instruments andActs.
Endnotes
7/25/2019 05-74sr001
http://slidepdf.com/reader/full/05-74sr001 32/32
S.R. No. 74/2005
Electricity Safety (Electric Line Clearance) Regulations 2005
31
3. Explanatory Details
1 Reg. 4: S.R. No. 182/2004.
2 Sch. (Table 9.3): Clause 9.2 provides that small branches and leaves may be
allowed to grow within the dimensions in Table 9.3 for aerial bundled cable
and insulated cable if they are cut annually to create a clearance space inaccordance with the Table. However, branches and leaves are not required to
be annually removed if they are not likely to abrade the cable before they arenext removed in accordance with the Code.
3 Sch. (Figure 9.4): Clause 9.2 provides that small branches and leaves may
be allowed to grow within the clearance space surrounding an aerial bundledcable and insulated cable if they are cut annually to create a clearance spacein accordance with Table 9.3. However, branches and leaves are not requiredto be annually removed if they are not likely to abrade the cable before they
are next removed in accordance with the Code.
Endnotes