    A New Differential Protection Scheme for BusbarConsidering CT Saturation Effect

    This work is funded by Gujarat Council on science

    and Technology, Government of Gujarat, India, under

    Project no. GUJCOST/MRP/201409/2009-10.

    Nilesh Chothani, Lecturer

    Department of Electrical Engineering,

    ADIT, New Vidyanagar, Anand, Gujarat 388121, India.

    e-mail: [email protected]

    Bhavesh Bhalja, Senior Member IEEE

    Department of Electrical Engineering,

    ADIT, New Vidyanagar, Anand, Gujarat 388121, India.

    e-mail: [email protected]

    Abstract-- The protection of busbar demands high integrity and

    high speed relaying scheme. This paper presents a new

    differential relaying scheme for the protection of busbar. The

    proposed scheme depends on the difference of the value of

    incoming and outgoing line currents of the respective phase at a

    particular bus. The proposed scheme has been tested extensively

    using the PSCAD/EMTDC software package with fault data

    generated, by modeling the existing 230 kV Indian power

    transmission systems. The proposed scheme provides stability

    against external faults, more sensitivity towards high resistance

    faults and better reliability in discriminating in-zone and out of

    zone faults. Moreover, the proposed scheme avoids the effect ofearly & severe CT saturation during heavy through faults.

    Index Terms--Busbar fault, differential protection, protective

    relay simulation, CT saturation detection.

    I. INTRODUCTION

    Igh speed bus protection is required not only to limit the

    damaging effects on equipment and system stability but

    also to maintain service to as much load as possible [1]. In

    practice, busbar is protected by various differential protection

    schemes such as biased percentage differential protection

    scheme, low impedance protection scheme and high

    impedance voltage scheme. Percentage differential relayscreate a restraining signal in addition to the differential signal

    and apply a percentage (biased) characteristic. The low-

    impedanceapproach does not require dedicated CTs. Further,

    this approach tolerates substantial CT saturation and provides

    high-speed tripping. High impedance voltage scheme is used

    in order to overcome the problem of spill current due to CT

    saturation in case of heavy through fault. However, this

    requires dedicated CTs (a significant cost associated) and

    cannot be easily applied to re-configurable buses.

    For better security, directional protection principle used to

    dynamically supervise the main current differential function.

    The main theme of this scheme is that if the power flow in one

    or more circuits is away from the bus, an external fault existswhereas for the power flow in all of the circuits into the bus,

    an internal bus fault exists [2]. The principal disadvantage of

    this scheme is that it requires greater maintenance and there is

    a probability of failure of the scheme due to large numbers of

    contacts connected in series with the trip circuit. Further, the

    operation of relays depends on bus voltage for polarization;

    they might not operate for a metallic short circuit that reduced

    the voltage practically to zero.

    The common practice in busbar protection is to use numerical

    busbar protection scheme which provides complete protection

    for all types of extra/ultra high voltage busbar configurations.

    The digital relays use innovative techniques such as CT

    saturation detection and processing algorithms which provides

    a unique combination of security, speed and sensitivity [3].

    Many digital busbar relaying schemes have been developed bythe designers and researchers using microprocessors,

    microcontrollers, digital signal processors, Artificial Neural

    Network (ANN), traveling waves, Wavelet Transform and

    employing various Artificial Intelligence techniques [4]-[7].

    Protection of substation busbars is almost universally

    accomplished by differential relaying scheme. The

    conventional busbar differential relaying scheme may

    maloperate in case of CT saturation during an external fault

    [8]. Hence, in order to avoid maloperation of the conventional

    differential protection scheme due to CT saturation during

    heavy through fault, authors have proposed a new differential

    relaying scheme. Verification of the proposed scheme has been

    done on simulated data of an existing part of the Indian power

    system network using PSCAD /EMTDC software package.

    The proposed scheme is highly sensitive and provides fast

    protection in case of internal fault. Moreover, it remains stable

    in case of external fault. Furthermore, it avoids early and

    severe CT saturation problem during heavy external fault. The

    proposed scheme has shown satisfactory performance under

    various fault conditions, especially for high resistance fault.

    II. SIMULATION AND MODELING

    Fig. 1 shows single line diagram of a portion of Indian power

    system network consisting of four sources represented by

    Thevenins equivalent. These sources are connected to the bus

    under consideration through different lines Line-1, Line-2

    Line-3 & Line-4 respectively. The system and line parameters

    are given in Appendix. A sampling frequency of 4 kHz for a

    system operating at a frequency of 50 Hz is used in this study.

    The components of power system such as generators,

    H

    IEEE CCECE 2011 - 000007

  • 7/29/2019 06030398

    2/4

    2

    generator transformers (GT) and transmission lines (TL) etc.

    are designed according to the collected data and specifications.

    The transmission line is represented using the Bergeron line

    model. The said developed model uses some of the main

    library components available in PSCAD. Also, own

    components have been developed by authors using

    programming in Fortran 77 compiler. The current signals

    measured from each line for all three phases are delivered to

    Current Transformers (CTs). The CT ratio has been decidedon the basis of loading condition of the system (in this case

    respective change in load angle of the source). The difference

    between the current quantities of each incoming and outgoing

    lines at the bus of the respective phase has been given as an

    input to the relay. Test data for verifying the said scheme have

    been generated by modeling the complete system using the

    PSCAD/EMTDC software package [9]. The performance of

    the proposed scheme has been evaluated for different types of

    in-zone and out of zone faults. Relay responses for some

    special case such as high resistance fault was also investigated.

    Fig. 2 shows the tripping logic for differential relay connected

    at the bus. In this logic, the differential principle isaccomplished by comparing the value of CT secondary

    currents of the respective phase of all four lines connected to

    the main bus. As shown in Fig. 2, the summing block generates

    three differential current signals namely Isa, Isb and Isc as per

    the direction and magnitude of fault current. Thereafter, these

    differential signals are given to the respective phase relay unit.

    If the values ofIsa, Isband Iscexceed the pick-up setting (0.5 pu

    which is decided on the basis of loading condition of system),

    the differential relay generates a spike, which will be made

    constant by Hysteresis-Buffer. Thereafter, the output of each

    phase relay is given to OR gate. Depending upon the output

    (logic 1) of the relay of the respective phase, OR gate

    generates a final tripping signal (BRK) which will be given toall the circuit breakers connected to the main bus.

    Fig. 1 Busbar relaying scheme modeled in PSCAD software

    III. SIMULATION RESULTS

    The system shown in Fig. 1 was subjected to various types of

    fault. The performance of the proposed technique was

    evaluated for different types of internal and external faults.

    The effect of high resistance fault and CT saturation has been

    also investigated. The output of all branch currents, along with

    the differential current of CT secondaries and the status of

    circuit breakers are represented graphically in this paper.

    Fig. 2 Tripping logic of differential relay connected at bus

    A. Internal Fault

    Fig. 3 shows the behavior of the proposed scheme in terms ofdifferential currents and breaker status for single-line to

    ground fault (a-g) which is applied at 0.06 second on the main

    bus (Fig. 1) with fault resistance Rf = 0.01. It has been

    observed from Fig. 3 that the differential current exceeds the

    predetermine threshold value depending upon the types of

    faults. Accordingly, the respective relay generates a tripping

    signal which will be given to all the line circuit breakers

    connected to the main bus. It is to be noted from Fig. 3 that the

    differential relay operates successfully and clears a-g fault

    within 13ms. A wide variation of in-zone faults such as single-

    line to ground fault, double line fault, double line to ground

    fault and triple line fault have been investigated. However, due

    to space limitations, the results are not shown in the paper.

    Fig. 3 Relay response during L-g (a-g) internal fault on bus

    with Rf= 0.01

    B. External Fault

    Fig. 4 shows the response of the proposed differential scheme

    for a single line-to-ground external fault (a-g) on line-4 at 10

    km from the main bus (Fig. 1) which is applied at 0.07 second

    with fault resistance Rf = 0.01. It has been observed from

    IEEE CCECE 2011 - 000008

  • 7/29/2019 06030398

    3/4

    3

    Fig. 4 that the differential current remains well below the

    predetermine threshold value and hence, the relay dost not

    operate. In this condition, no trip signal is generated by the

    relay. A wide variation of external faults such as single-line to

    ground fault, double line fault, double line to ground fault and

    triple line fault at different locations have been investigated. It

    is to be noted that for all types of external faults, the proposed

    differential scheme remains stable and hence, gives better

    stability.

    Fig. 4 Relay response during external fault on line-4 with

    Rf= 0.01

    C. High Resistance Fault

    Many algorithms related to bus protection fail to detect fault

    with a considerable value of fault resistance. Although, high

    resistance fault reduces the magnitude of the fault current, the

    proposed scheme is capable to detect these faults. To analyze

    the said situation, a single line-to-ground fault with fault

    resistance of 75 has been simulated inside the zone of the

    main bus. Although, there is a delay in the action of crossing

    the threshold boundary of the relay, as shown in Fig. 5, the

    proposed differential relaying scheme operates within 18ms.

    The proposed scheme has been tested for different types of

    high resistance faults such as single line to ground fault and

    double line to ground faults up to RF=200 (not shown in the

    paper). In these situations, it has been observed by the authors

    that the operating time of relay was within 20ms after the

    inception of fault.

    D. Effect of CT Saturation

    The effect of CT saturation for any busbar protection scheme

    is of crucial importance particularly during heavy through

    fault. The protection scheme must remain stable during

    external fault and must not delay or prevent operation in case

    of an internal fault. The CT saturation is obtained by CT

    model block available in PSCAD/EMTDC. By changing the

    CT secondary burden resistance, different degrees of CT

    saturation can be obtained [10].

    Fig. 5 Relay response during internal fault at F on phase A

    with Rf= 75

    The performance of the proposed scheme during CT saturationis carried out by simulating different faults on line-4 at 10 km

    from the main bus with varying fault resistances. When a

    heavy through fault occurs, the secondary current of CT is

    reduced sharply due to saturation of CT. Therefore, the time

    between two successive zero crossings of the secondary

    current becomes smaller than half a cycle. This phenomenon is

    used to detect the CT saturation by comparing the zero

    crossing interval of the secondary current of saturated CT to

    the zero crossing interval of the secondary current of

    unsaturated CT for half a cycle time interval. The zero

    crossing time of CT secondary during fault can be considered

    as 8 ms9 ms instead of 10 ms (half a cycle for a rated

    frequency of 50 Hz) because of noise and transient frequencypenetration [11]. Fig. 6 shows simulated module of zero

    crossing detector developed by authors in PSCAD which uses

    zero detectors, monostable multivibrators and logical circuits.

    Fig. 6 The simulated module of zero crossing detector

    IEEE CCECE 2011 - 000009

  • 7/29/2019 06030398

    4/4

    4

    Fig. 7 Simulation results of unsaturated signal, saturated signal

    and the difference of zero crossing of two signals.

    In this module, zero detector measures the zero crossing

    interval of the secondary current of saturated CT. A standard

    estimated 50 Hz signal is given to another zero detector which

    measures the zero crossing interval of the secondary current of

    unsaturated CT (estimated signal) at every 10 ms. The

    computation is repeated for every half a cycle and the

    difference between the zero crossing interval of the estimated

    signal and the saturated CT secondary signal are calculated.

    Fig. 7 shows the simulation results for estimated signal

    (unsaturated signal), saturated CT secondary current and the

    difference of the zero crossing interval for phase-a during

    single line to ground external fault on line-4 at 0.04 second

    with Rf = 0.01 . The middle section shows the closer view of

    signals shown in the first section (Fig. 7) for one cycle

    interval. If this difference exceeds a predetermined threshold

    value, a phase comparator circuit (not shown in the paper) is

    activated and the blocking command is given to the bus

    differential relay. With wide range of variations in fault

    conditions and transient frequency penetration, it has been

    found by the authors that the appropriate value of threshold is

    1.5 ms. It is to be noted that the proposed scheme is able to

    detect heavy and low saturation of CT during external faults.

    IV. CONCLUSION

    A new differential relaying scheme for busbar protection is

    proposed in this paper. The proposed scheme was tested

    extensively by using data that was generated by modeling an

    existing 230 kV Indian power transmission system network

    using PSCAD/EMTDC software package. The proposed

    scheme has the ability to detect all types of in-zone faults and

    remains stable during out of zone faults. An average tripping

    time for most of the internal faults is within 20ms. The

    proposed zero crossing technique is able to detect severe CT

    saturation during all types of external faults with different

    system parameters to achieve better security. Further, the

    proposed scheme is highly sensitive in case of high resistance

    in-zone faults.

    APPENDIX

    Source Data

    Positive-sequence impedance of sources G1, G2 = 5 850

    Zero-sequence impedance of sources G1, G2= 10 850

    Positive-sequence impedance of sources G3, G4 = 10 85

    0

    Zero-sequence impedance of sources G3, G4= 20 850

    Frequency = 50 Hz

    Load angle of G1, G2 and G4 = 00

    Load angle of G3 = 200

    Transmission-line Data

    Length:

    Line-1 and Line-2 = 50 km

    Line-3 = 100 km

    Line-4 = 80 km

    Voltage = 230 kV

    Positive-sequence impedance = 0.0297 + j0.332 /km

    Zero-sequence impedance = 0.162 + j1.24 /km

    Positive-sequence capacitance = 9.23 nF/kmZero-sequence capacitance = 6.72 nF/km

    V. REFERENCES

    [1] N. G. Chothani, B.R. Bhalja and R.P.Maheshwari, A new digitaldifferential relaying scheme for the protection of busbar, 4th

    International Conference on CERA-09,February 19-21, 2010.IIT

    Roorkee.

    [2] M. M. Eissa, A novel digital directional technique for bus-barsprotection, IEEE Transactions on Power Delivery, Vol. 19, No. 4,

    pp. 1636-1641, October 2004.

    [3] P740 Numerical Busbar Protection, Technical Data Sheet,Publication No. P740/EN TD/G22, AREVA T&D, pp. 1-22.

    [4] T. S. Sidhu, L. Mital and M. S. Sachdev, A ComprehensiveAnalysis of an Artificial Neural-Network-Based Fault DirectionDiscriminator, IEEE Transactions on Power Delivery, Vol. 19,

    No. 3, pp. 1042-1048, July 2004.

    [5] Gang Wang, Heifeng Li and Xiaohua Li, A New NumericalDistributed Busbar Protection, In Proceedings of 8 th IEE

    International Conference on Developments in Power System

    Protection, Vol. 1, 5-8 April 2004, pp. 387-390.

    [6] M. M. Eissa, A novel wavelet approach to busbar protectionduring CT saturation and ratio-mismatch, Electric Power System

    Research, Vol. 72, 2004, pp. 41-48.

    [7] S. P. Valsan and K. S. Swarup, Computationally EfficientWavelet-Transform Based Digital Directional Protection for

    Busbars, IEEE Transactions on Power Delivery, Vol. 22, No. 3,

    July 2007, pp. 1342-1350.

    [8] M. E. Mohammed, High speed differential busbar protectionusing wavelet packet transform, Proceeding IET Generation,

    Transmission & Distribution, Vol. 152, No. 6, November 2005,pp. 927-933.

    [9] PSCAD/EMTDC Manual, Getting Started, Manitoba HVDCResearch Centre Inc., January 2001.

    [10] Annakkage, U.D. McLaren, P.G., Dirks, E., Jayasinghe, R.P., andParker, A.D.: A current transformer model based on the Jiles

    Atherton theory of ferromagnetic hysteresis, IEEE Trans. On

    Power Delivery, Vol. 15 No. 1, 2000, pp. 57 61

    [11] Hamed Dashti, Majid Sanaye Pasand, Senior Member, IEEE, andMahdi Davarpanah, Fast and Reliable CT Saturation Detection

    Using a Combined Method, IEEE Transactions On Power

    Delivery, Vol. 24, No. 3, July 2009,Pp. 1037-1044.

    IEEE CCECE 2011 - 000010