06162716

  • Upload
    alaaa3

  • View
    216

  • Download
    0

Embed Size (px)

Citation preview

  • 8/13/2019 06162716

    1/5

    1

    AbstractWith high penetrations of wind energy, differenttypes of wind farm generators do not have the same fault

    transient characteristics that can complicate the selection and

    configuration of wind farm grid protection equipment. Incorrect

    selection of protection equipment will affect the stability and of

    the power systems. This paper investigates and analyzes the

    transient characteristics of doubly-fed induction generator

    (DFIG) under various short-circuit fault conditions for a typical

    distribution network. Firstly a detailed model of the DFIG and

    its principles is descried. A realistic of a 99 MW wind farm with

    66 units of 1.5 MW DFIG is modeled using RTDS/RSCAD. The

    transient characteristic of the wind farm with the DFIG units

    have been analyzed under different short-circuit fault

    conditions. Results from the fault performance study on the

    distribution network are presented and discussed.

    Index TermsDoubly-Fed induction generator, Wind farm,Fault transient analysis.

    I. INTRODUCTIONHE technique advance and wide applications of power

    electronic devices make it possible for manufactures to

    develop large Variable-Speed Constant-Frequency

    (VSCF) wind turbine generators. It is expected that the VSCF

    wind power generators will gradually replace constant

    frequency wind components [1]. Since most VSCF windturbine generators are induction machines which can't provide

    a longer enough stable short-circuit current to operate the

    relays for the networks. One of solutions is that relay can use

    the fault transient characters by the relay to protect the

    network against the fault [2,3]. In order to allow relays to use

    correct fault transient information, it is thus necessary to study

    the fault characteristics, the security and stability of system

    under the network fault conditions.

    There are many studies on modeling and simulation of

    VSCF wind turbine generators which often consists of a

    wound-rotor generator, a brushless exciter and a low-rating

    controlled power converter. Mainly from three aspects[4]: (i)

    Generator model: VSCF wind turbine generators alwayschoose DFIG which can connect wind turbines and power

    system flexibly[5]. Reference [6] takes the mechanism of a

    DIFG as a starting point and derives the DFIGs dynamic

    mathematical model according to the relationship among the

    flux, electric potential and current. The only drawback is the

    need to add the relationship between the control variables

    Yang Beige and XueHui are with Shanxi Electric Power Co., Ltd., Datong

    037008, China.Bai Dandan, Hu Wei and He Jinghan are with the School of Electrical

    Engineering of Beijing Jiaotong University, Beijing 100044, China. (Prof. He'semail: 11121572@bjtu. edu.cn).

    characteristics of rotor winding excitation voltage and electric

    controlled variables of generator; (ii) Converter and control

    implementation [7-10]: In [10] a dual PWM converter control

    strategy is proposed in order to achieve stability of the DC

    voltage and adjust the power factor; and (iii) Pitch control:

    There are a variety of improved programs at present so as to

    solve that a fixed set of PID parameters in different wind

    speed is difficult to get good control results. Reference [11]

    puts forward a control pitch on a fuzzy combination of

    feed-forward and a new fuzzy PID control to ensure good

    control effect at different wind speed levels.

    This paper investigates and analyzes the fault transient

    characteristics of doubly-fed induction generator (DFIG)

    under various short-circuit fault conditions for a typical

    distribution network. Results can be used to provide a

    reference to improve the effectiveness of the protection

    devices for the network with wind farms.

    II. MODELING OF DFIGSAND DISTRIBUTIONNETWORKSA. Analysis and Modeling of DFIGs

    A DFIG model [13] as shown in Fig.1 consists of a wind

    turbine model, a gearbox, a double-fed induction generator

    model, an AC/DC and a DC/AC inverters, the controller and

    pitch control.

    DFIGransmission

    Control ofrotor sideconverter

    Master controllerPitchcontrol

    Control ofstator sideconverter

    grid

    dcV

    mT

    sV

    Fig.1 Structure of a DFIG and its control system

    1) Basic equations of DFIG at two-phase rotated coordinate

    system: The control strategy of the DFIG is the vector control

    which can achieve a decoupling control of the reactive and

    reactive power. The voltage equation of the DFIG at

    synchronous rotating coordinate system can be expressed as:

    Fault Analysis of Distribution Network with

    Wind Turbines of DFIG

    Yang Beige, Xue Hui, Bai Dandan, Hu Wei, and He Jinghan

    T

  • 8/13/2019 06162716

    2/5

    2

    s

    s s s 1 s

    rr r r 1 r r

    dV R I j

    dt

    dV R I j( )

    dt

    = + +

    = + +

    (1)

    Corresponding flux equation is :

    s s s m r

    r m s r r

    L I L I

    L I L I

    = +

    = +

    (2)

    Where,sVand

    rV are the stator and rotor voltage vectors;

    sI and rI are the stator and rotor current vectors ; s and r are

    the stator and rotor flux linkage vectors;sR and rR are the

    stator and rotor resistance ;sLand

    rL are the stator and rotor

    winding total self-inductance;m

    L ,

    L andrL are the mutual

    inductance between stator and rotor, the leakage inductance of

    stator and rotor; 1 is the synchronous angular speed; r is

    the rotor angular speed.

    If turning the stator flux linkage to coincide with the d-axis

    at synchronous rotating system, the q-axis component of fluxlinkage will be zero. According to the output expression of theDFIG, the stator active and reactive output power can be

    described as :

    ms s s rq

    s

    2

    s s s s ms rd

    s s

    L3P i

    2 L

    L3Q ( i )

    2 L L

    =

    =

    (3)

    2) The control of the rotor-side inverter: According toequation (3), the d-axis component of rotor current can control

    thesP and the rdi can control the sQ .Because the rqi and rdi are

    orthogonal to each other, thesP and sQ can achieve

    decoupling control. The rotor-side inverter takes the stator

    flux-oriented rotor current control methods. Rotor current is

    indirectly controlled by controlling the applied voltage on therotor. The equation of rotor current control at the stator flux

    oriented coordinates can be derived as:

    rdrd r rd r sl r rq

    2rq m

    rq r rq r sl ms r rd

    s

    diu R i L L i

    dt

    di Lu R i L + ( i L i )

    dt L

    +

    +

    =

    = +

    (4)

    Where the 2m s r L L/1 L= represents leakage factor.

    From equation(4), the rotor active and reactive current are

    completed decoupled, but the voltage vector which controls

    the current isnt decoupled. Choose the feed-forwardcompensation to solve this question:

    rdc sl r rq

    2

    mrqc sl ms r rd

    s

    u L i

    Lu ( i L i )

    L

    =

    = +

    (5)

    So, after rdu substracting rdcu and rqu subtracting rqcu

    the control to rqi and rdi will be decoupling.

    3) The control of the grid-side inverter: Similarly, grid-side

    converter selects the grid voltage oriented vector control

    method to maintain the DC link capacitor voltage at a

    predetermined constant value independent of the direction and

    size of the rotor power. And control the reactive power at areference value according to the wind turbine reactive power

    requirements. The control voltage of grid-side converter can

    be derived as:

    gd

    gcd g gd g gd e g gq

    gq

    gcq g gq g e g gd

    diu (R i L ) (u L i )

    dt

    diu (R i L ) L i

    dt

    = + + +

    = +

    (6)

    The feed-forward compensation is:

    gcdD gd e g gq

    gcqD e g gd

    u u L i

    u L i

    = +

    =

    (7)

    Where, gR and gL are the resistance and inductance of the

    grid-side converter; gdu and gqu are the d- and q-axis

    component of three-phase voltage; gdi and gqi are the d- and

    q-axis component of three-phase current.

    According to equation (1)-(7), the VSCF wind turbine withDFIG model can be established and the control structure and

    the control blocks are shown in Fig.2.

    Fig.2 Control of DFIG

    B. Distribution Network ModelUsing the established DFIG model and a actual wind farm

    in Shanxi province, the studied distribution network wasestablished as shown in Fig.3. The number of wind turbines is

    66 units and the total installed capacity is 99MVA. Each unit

    in wind farm uses the two boost program. Each wind turbine

  • 8/13/2019 06162716

    3/5

    3

    export voltage is 0.69kV, and then boosts to 35kV. All the

    units pool together through collection line, then access intopower grid. The second boost voltage will be 110kV. Take the

    actual operating data of a DFIG in the wind farm and the

    variable values are shown in table 1.The substation and

    transmission line parameters in the distribution network areshown in table 2 and table 3.

    220KV

    35KV

    110KV

    110KV

    T3

    T5

    T6

    35KV

    110KV

    T2

    T1

    110KV

    35KV

    G

    F1

    load4

    F2

    F3

    10KV

    load3

    load1

    TRF1 TRF2

    TRF3 TRF4

    110KV

    load2

    TRF5

    T4

    Fig.3 The studied distribution network based on Shanxi Province

    TABLEI

    PARAMETERS OF DFIGMODEL

    Power Rating 1.5MW Stator resistance 0.0244pu

    Stator voltage 690V Rotor resistance 0.01316pu

    No. of pole pairs 1 Stator leakage

    inductance

    0.26619pu

    Maximum rotorspeed

    1.2pu Rotor leakageinductance

    0.45471pu

    DC-link voltage 1.5kV Stator and rotor

    mutual inductance

    16.7495pu

    Frequency 50HZ Rated wind speed 15m/s

    Cut-in speed 3m/s Cut-out speed 21m/s

    TABLEIIPARAMETERS OF THE SUBSTATION NEAR THE WIND FARM

    Name X1 X2 X3 Ratio Total

    Capacity

    (MVA)

    Load

    Loss

    (MW)

    TRF1 0.118 0.0074 0.0772 22081.5%/121/385 120 0.132

    TRF2 0.119 0.00585 0.0675 22081.5%/121/385 120 0.132

    TRF3 0.341 0.0023 0.249 11081.25%/36.7/10.5 31.5 0.026

    TRF4 0.549 0.0075 0.3325 11081.25%/36.7/10.5 20 0.025

    TRF5 0.210 0.1136 11081.25%/36.7 100 0.1

    TABLEIIITRANSMISSION LINE PARAMETERS NEAR THE WIND F ARM

    Lines Voltage SB

    (MVA)

    UB (kV) X0 (p.u) R0 (p.u) X1 (p.u) R1 (p.u.)

    T1 110 100 110 0.1608 0.0471 0.0520 0.0124

    T2 110 100 110 0.1668 0.0847 0.0477 0.0247

    T3 110 100 110 0.1982 0.0911 0.0566 0.0242

    T4 110 100 110 0.2747 0.1132 0.0785 0.0265

    T5 110 100 110 0.0861 0.0396 0.0246 0.0105

    T6 35 20 35 0.0895 0.0545 0.0256 0.0175

    III. FAULT ANALYSISWhen the wind farm connects to the power system, the

    power flow and the fault contribution in the network will

    change. Protections now used must be adjusted and changed to

    ensure correct fault clearing with right method, and maintain

    the safe and stable operation of the system.

    If the power system goes wrong, the short-circuit current issupplied by not only conventional power but also the wind

    farm. The change of the short-circuit current will influence the

    operation of the relay protection, such as making the

    protection devices miss-trip or miss-operate. We need tooptimize the protection devices by analyzing the fault

    characteristics of the power system connected with DFIG.

    This makes simulation analysis of the fault characteristics by

    setting different fault position, different wind speed anddifferent reactive power state.

    A. At different fault positionBased on the network in Fig.3, we carried out various fault

    simulation and analysis. In this paper only results of the faultson lines T1, T2 and T3 are presented and discussed. The total

    installed wind farm capacity is 99MVA, and this wind farm

    has 66 units, and rated capacity of every unit is 1.5MVA, the

    annual average wind speed is 7.5m/s. Take the three-phaseshort-circuit as the fault type, the operation wind speed is15m/s, fault initial angle is 90 degrees. Monitoring the voltage

    and current situation of the bus bar 6, and the results are as

    Fig.4 and Fig.5.

    From the results we can get that the degree of the voltage

    drop and the short current characteristics in the wind farm are

    (a)fault on T1 (b) fault on T2 (c) fault on T3

    Fig.5 The current waveform at bus 6 with different fault position

    (a)fault on T1 (b) fault on T2 (c) fault on T3

    Fig.4 The voltage waveform at bus 6 with different fault position

  • 8/13/2019 06162716

    4/5

    4

    different when the fault position is different. If the fault is on

    T1, the voltage drop is large, and then finally decreases tozero. At the same time, the short circuit current increases at

    first and then decreases to zero fast, that causes the generator

    unstable. If the faults on T2 or T3, the voltage drop is less than

    the voltage drop when the fault is on T1, and then decreases toa stable value larger than zero. The generator is unstable

    because of serious voltage dip, and the wind farm could only

    supply transitory short circuit current and the amplitude islow.

    B. At different wind speedThe output of the wind farm changes with the wind

    conditions because of the random, volatile and

    non-controllable of the wind power. So it is necessary to studythe characteristics of wind power short circuit failure in

    different wind speed. If there is a three-phase short circuit on

    T1, make a research on the voltage and current characteristics

    at the point where the wind farm access into the power grid.The simulation results are shown in Fig.6 and Fig.7.

    When the wind speed is 15m/s, the voltage drops seriouslyduring the fault and the wind farm can only provideinstantaneous short-circuit current. When the wind speed is

    9m/s, the voltage during the fault is larger, but the current is

    smaller. The reason is that the stator and rotors flux linkage

    will increase as wind speed increases.

    C. At different reactive stateAs all the wind generators are DFIGs, we can use

    converters to control the size and frequency of the excitation

    current added in the rotor windings, so as to achieve thepurpose of power control. Thus the reactive power of the wind

    farm can be controlled as absorption or output state. In this

    article, by controlling the reactive power of the wind farm onabsorption or output state, we can observe the fault voltage

    and fault current in the point connected to the power grid. As

    the waveforms shown in Fig.8 and Fig.9, the fault location is

    still set in the T1 line and the fault type is still the most seriousthree-phase short-circuit.

    It can be seen from the waveforms in Fig. 8 and Fig.9,whether the DFIG is absorbing or output the reactive power,

    the change trend of voltage and current is basically the same,but the short circuit current during the fault when absorbing

    the reactive power is larger than that when output reactivepower. This is mainly because when stator output reactive

    power, the generator armature reaction is demagnetizing thesynthesis of flux. After the three-phase short-circuit fault

    occurred in the power grid, the rotor flux will increase, inorder to guarantee the stator flux won't mutate, so the short

    circuit currents of the stator and the rotor will increase, and

    vice versa.

    IV. CONCLUSIONBased on theoretical analysis of double-fed wind turbine

    working principle, this paper builds a double-fed inductiongenerator model on the RTDS software and a distributionnetwork simulation model based on t a wind farm in Shanxi

    Province. Also the fault characteristics of distribution network

    connected with DFIG wind turbine generators were studiedwhen simulated with different fault location, different wind

    speed and different reactive state. The results show that the

    greater the wind speed is, the greater short-circuit current

    DFIG provides. By adjusting and controlling converter, theDFIG output or absorb reactive power according to the

    network needs, and the short-circuit current is large when

    (a) Current waveform (b)voltage waveform

    Fig.9 the voltage and current waveform in the point (bus 6) connected to the

    power grid when output the reactive power

    (a) Current waveform (b)voltage waveformFig.8. the voltage and current waveform in the point (bus 6) connected to the

    ower rid when Absorbin the reactive ower

    (a)current waveform (b)voltage waveform

    Fig.7voltage and current waveform at bus 6 when the wind speed is 9m/s

    (a)current waveform (b)voltage waveform

    Fig.6voltage and current waveform at bus 6 when the wind speed is 15m/

  • 8/13/2019 06162716

    5/5

    5

    DFIG output reactive power. The wind power station will

    provide short-circuit current to the point of failure after thewind power is merged into the grid, Therefore, the protection

    system designing need to consider the characteristics of the

    wind turbine, and regarding its short-circuit characteristics as

    a protection device configuration reference.

    ACKNOWLEDGMENT

    Thanks to the support of Datong Electric Company ,China.

    REFERENCE

    [1] YUAN guo-fengCAI jian-yunLI yong-dongStudy onexcitation converter of variable speed constant frequency wind

    generation systemProceeding of the CSEE200525(8)

    90-94

    [2] LING yu-zhiCUI shu-pingWANG dong-mei.; Discussion ofconfiguration for relay protection after wind farm integration

    into power system. North china electric power200909

    1-4.

    [3] WEN yu-lingCHAO qinTUERXUN.yibulayin. Study onadaptive protection of wind farm. Power system protection and

    controlProceeding of the CSEE, 20090547-51.[4] YING mingLI gen-yinZHOU ming ,et alAnalysis and

    comparison of dynamic models for the doubly fed induction

    generator wind turbin Automation of electric power

    systems2006(13)22-27.

    [5] Ekanayake J BHoldworth LWu X G. Dynamic modeling ofdoubly fed induction generator wind turbines Power

    Systems20032(18)803-809

    [6] Feijo F, Cidrs JCarrillo C, et alA third order model for thedoubly-fed induction machine[J]Electric Power Systems

    Research200050(2)121-127

    [7] Pena RClare J Cand Asher G MDoubly fed inductiongenerator using back-to-back PWM converters and its

    application to variable speed wind-energy generationIEE

    ProcB1996143(3)231-241

    [8] Datta R and Ranganathan V TVariable-speed wind powergeneration using doubly fed wound rotor induction machine-a

    companson with alternative schemesIEEE TransEnergy

    Conversion200217(3)414-421

    [9] Zhang L and Watthanasam CA matrix converter exciteddoubly-fed induction machine a wind power generator. InSeventh International Conference on Power Electronics and

    Variable Speed Drives199832-537

    [10] CHEN wei CHEN cheng SONG zhan-feng , etal.Proportional-resonant control for dual PWMconverter in

    doubly fed wind generation system. Proceeding of the CSEE

    200929151-7.

    [11] GUO peng.Varibale pitch control of wind turbine generatorcombined with fuzzy feed forward and fuzzy PID controller.Proceeding of the CSEE2010308123-128.

    [12] Holdworth LWu X GEkanayake J BComparison of fixedspeed and doubly-fed induction wind turbines during power

    system disturbances Generation Transmission and

    Distribution20033(150)343-352.

    [13] LI jingSONG jia-yeWANG wei-sheng.Modeling anddynamic simulation of variable speed wind turbine with large

    capacity. Proceeding of the CSEE200424 (6)100 -105

    [14] HE qingZHONG zhi-mingCHEN wen-fu. Simulation andanalysis for pitch control of doubly-fed induction wind turbine

    with PSCAD/EMTDC software. Journal of electric power

    science and technology200924340-44.

    [15] ZHANG jian-huaCHENG xing-yin LIU hao-ming, etal.Three-phase short-circuit analysis for double-fedwind-driven generator and short-circuiter maximal resistance

    calculation. Electric power automation equipment2009

    46-10.

    [16] GUO jia-huZHANG lu-huaCAI xu.Response and protectionof DFIG system under three-phase short circuit fault of grid.

    Power system protection and control2010640-44.

    BIOGRAPHY

    YANG Bei-ge is now a senior engineer engaged in Power Supply

    Company of Datong. He recently is focused on the application of thepower grid operation mode intelligent core platform and research onthe intelligent communication devices monitoring system of standaccused of layer and software design of infrared thermal imagingwireless video surveillance system client.

    Xue Hui is now a professional Engineer in Branch Marsh Center ofPower Supply Company in Datong . His interest is the power system.

    HE Jing-han received her master degree from the TianjingUniversity in 1994 and got the PHD degree in Beijing JiaotongUniversity in China. She is now a professor in Beijing Jiaotong

    University. Her interests include online power system monitoring

    protection and control, power quality and rail electrification.

    Bai Dan-dan received her BSc degree from the Beijing JiaotongUniversity in 2011. She is currently working toward the MSc degreein the School of Electrical Engineering, Beijing Jiaotong University,Beijing, China. Her research interest is power system protection and

    control.

    Hu Wei received his BSc degree from the Henan University of

    Technology in 2009. He received the MSc degree in the School ofElectrical Engineering, Beijing Jiaotong University, Beijing, China.

    His research interest is power system protection and control.