Upload
alaaa3
View
216
Download
0
Embed Size (px)
Citation preview
8/13/2019 06162716
1/5
1
AbstractWith high penetrations of wind energy, differenttypes of wind farm generators do not have the same fault
transient characteristics that can complicate the selection and
configuration of wind farm grid protection equipment. Incorrect
selection of protection equipment will affect the stability and of
the power systems. This paper investigates and analyzes the
transient characteristics of doubly-fed induction generator
(DFIG) under various short-circuit fault conditions for a typical
distribution network. Firstly a detailed model of the DFIG and
its principles is descried. A realistic of a 99 MW wind farm with
66 units of 1.5 MW DFIG is modeled using RTDS/RSCAD. The
transient characteristic of the wind farm with the DFIG units
have been analyzed under different short-circuit fault
conditions. Results from the fault performance study on the
distribution network are presented and discussed.
Index TermsDoubly-Fed induction generator, Wind farm,Fault transient analysis.
I. INTRODUCTIONHE technique advance and wide applications of power
electronic devices make it possible for manufactures to
develop large Variable-Speed Constant-Frequency
(VSCF) wind turbine generators. It is expected that the VSCF
wind power generators will gradually replace constant
frequency wind components [1]. Since most VSCF windturbine generators are induction machines which can't provide
a longer enough stable short-circuit current to operate the
relays for the networks. One of solutions is that relay can use
the fault transient characters by the relay to protect the
network against the fault [2,3]. In order to allow relays to use
correct fault transient information, it is thus necessary to study
the fault characteristics, the security and stability of system
under the network fault conditions.
There are many studies on modeling and simulation of
VSCF wind turbine generators which often consists of a
wound-rotor generator, a brushless exciter and a low-rating
controlled power converter. Mainly from three aspects[4]: (i)
Generator model: VSCF wind turbine generators alwayschoose DFIG which can connect wind turbines and power
system flexibly[5]. Reference [6] takes the mechanism of a
DIFG as a starting point and derives the DFIGs dynamic
mathematical model according to the relationship among the
flux, electric potential and current. The only drawback is the
need to add the relationship between the control variables
Yang Beige and XueHui are with Shanxi Electric Power Co., Ltd., Datong
037008, China.Bai Dandan, Hu Wei and He Jinghan are with the School of Electrical
Engineering of Beijing Jiaotong University, Beijing 100044, China. (Prof. He'semail: 11121572@bjtu. edu.cn).
characteristics of rotor winding excitation voltage and electric
controlled variables of generator; (ii) Converter and control
implementation [7-10]: In [10] a dual PWM converter control
strategy is proposed in order to achieve stability of the DC
voltage and adjust the power factor; and (iii) Pitch control:
There are a variety of improved programs at present so as to
solve that a fixed set of PID parameters in different wind
speed is difficult to get good control results. Reference [11]
puts forward a control pitch on a fuzzy combination of
feed-forward and a new fuzzy PID control to ensure good
control effect at different wind speed levels.
This paper investigates and analyzes the fault transient
characteristics of doubly-fed induction generator (DFIG)
under various short-circuit fault conditions for a typical
distribution network. Results can be used to provide a
reference to improve the effectiveness of the protection
devices for the network with wind farms.
II. MODELING OF DFIGSAND DISTRIBUTIONNETWORKSA. Analysis and Modeling of DFIGs
A DFIG model [13] as shown in Fig.1 consists of a wind
turbine model, a gearbox, a double-fed induction generator
model, an AC/DC and a DC/AC inverters, the controller and
pitch control.
DFIGransmission
Control ofrotor sideconverter
Master controllerPitchcontrol
Control ofstator sideconverter
grid
dcV
mT
sV
Fig.1 Structure of a DFIG and its control system
1) Basic equations of DFIG at two-phase rotated coordinate
system: The control strategy of the DFIG is the vector control
which can achieve a decoupling control of the reactive and
reactive power. The voltage equation of the DFIG at
synchronous rotating coordinate system can be expressed as:
Fault Analysis of Distribution Network with
Wind Turbines of DFIG
Yang Beige, Xue Hui, Bai Dandan, Hu Wei, and He Jinghan
T
8/13/2019 06162716
2/5
2
s
s s s 1 s
rr r r 1 r r
dV R I j
dt
dV R I j( )
dt
= + +
= + +
(1)
Corresponding flux equation is :
s s s m r
r m s r r
L I L I
L I L I
= +
= +
(2)
Where,sVand
rV are the stator and rotor voltage vectors;
sI and rI are the stator and rotor current vectors ; s and r are
the stator and rotor flux linkage vectors;sR and rR are the
stator and rotor resistance ;sLand
rL are the stator and rotor
winding total self-inductance;m
L ,
L andrL are the mutual
inductance between stator and rotor, the leakage inductance of
stator and rotor; 1 is the synchronous angular speed; r is
the rotor angular speed.
If turning the stator flux linkage to coincide with the d-axis
at synchronous rotating system, the q-axis component of fluxlinkage will be zero. According to the output expression of theDFIG, the stator active and reactive output power can be
described as :
ms s s rq
s
2
s s s s ms rd
s s
L3P i
2 L
L3Q ( i )
2 L L
=
=
(3)
2) The control of the rotor-side inverter: According toequation (3), the d-axis component of rotor current can control
thesP and the rdi can control the sQ .Because the rqi and rdi are
orthogonal to each other, thesP and sQ can achieve
decoupling control. The rotor-side inverter takes the stator
flux-oriented rotor current control methods. Rotor current is
indirectly controlled by controlling the applied voltage on therotor. The equation of rotor current control at the stator flux
oriented coordinates can be derived as:
rdrd r rd r sl r rq
2rq m
rq r rq r sl ms r rd
s
diu R i L L i
dt
di Lu R i L + ( i L i )
dt L
+
+
=
= +
(4)
Where the 2m s r L L/1 L= represents leakage factor.
From equation(4), the rotor active and reactive current are
completed decoupled, but the voltage vector which controls
the current isnt decoupled. Choose the feed-forwardcompensation to solve this question:
rdc sl r rq
2
mrqc sl ms r rd
s
u L i
Lu ( i L i )
L
=
= +
(5)
So, after rdu substracting rdcu and rqu subtracting rqcu
the control to rqi and rdi will be decoupling.
3) The control of the grid-side inverter: Similarly, grid-side
converter selects the grid voltage oriented vector control
method to maintain the DC link capacitor voltage at a
predetermined constant value independent of the direction and
size of the rotor power. And control the reactive power at areference value according to the wind turbine reactive power
requirements. The control voltage of grid-side converter can
be derived as:
gd
gcd g gd g gd e g gq
gq
gcq g gq g e g gd
diu (R i L ) (u L i )
dt
diu (R i L ) L i
dt
= + + +
= +
(6)
The feed-forward compensation is:
gcdD gd e g gq
gcqD e g gd
u u L i
u L i
= +
=
(7)
Where, gR and gL are the resistance and inductance of the
grid-side converter; gdu and gqu are the d- and q-axis
component of three-phase voltage; gdi and gqi are the d- and
q-axis component of three-phase current.
According to equation (1)-(7), the VSCF wind turbine withDFIG model can be established and the control structure and
the control blocks are shown in Fig.2.
Fig.2 Control of DFIG
B. Distribution Network ModelUsing the established DFIG model and a actual wind farm
in Shanxi province, the studied distribution network wasestablished as shown in Fig.3. The number of wind turbines is
66 units and the total installed capacity is 99MVA. Each unit
in wind farm uses the two boost program. Each wind turbine
8/13/2019 06162716
3/5
3
export voltage is 0.69kV, and then boosts to 35kV. All the
units pool together through collection line, then access intopower grid. The second boost voltage will be 110kV. Take the
actual operating data of a DFIG in the wind farm and the
variable values are shown in table 1.The substation and
transmission line parameters in the distribution network areshown in table 2 and table 3.
220KV
35KV
110KV
110KV
T3
T5
T6
35KV
110KV
T2
T1
110KV
35KV
G
F1
load4
F2
F3
10KV
load3
load1
TRF1 TRF2
TRF3 TRF4
110KV
load2
TRF5
T4
Fig.3 The studied distribution network based on Shanxi Province
TABLEI
PARAMETERS OF DFIGMODEL
Power Rating 1.5MW Stator resistance 0.0244pu
Stator voltage 690V Rotor resistance 0.01316pu
No. of pole pairs 1 Stator leakage
inductance
0.26619pu
Maximum rotorspeed
1.2pu Rotor leakageinductance
0.45471pu
DC-link voltage 1.5kV Stator and rotor
mutual inductance
16.7495pu
Frequency 50HZ Rated wind speed 15m/s
Cut-in speed 3m/s Cut-out speed 21m/s
TABLEIIPARAMETERS OF THE SUBSTATION NEAR THE WIND FARM
Name X1 X2 X3 Ratio Total
Capacity
(MVA)
Load
Loss
(MW)
TRF1 0.118 0.0074 0.0772 22081.5%/121/385 120 0.132
TRF2 0.119 0.00585 0.0675 22081.5%/121/385 120 0.132
TRF3 0.341 0.0023 0.249 11081.25%/36.7/10.5 31.5 0.026
TRF4 0.549 0.0075 0.3325 11081.25%/36.7/10.5 20 0.025
TRF5 0.210 0.1136 11081.25%/36.7 100 0.1
TABLEIIITRANSMISSION LINE PARAMETERS NEAR THE WIND F ARM
Lines Voltage SB
(MVA)
UB (kV) X0 (p.u) R0 (p.u) X1 (p.u) R1 (p.u.)
T1 110 100 110 0.1608 0.0471 0.0520 0.0124
T2 110 100 110 0.1668 0.0847 0.0477 0.0247
T3 110 100 110 0.1982 0.0911 0.0566 0.0242
T4 110 100 110 0.2747 0.1132 0.0785 0.0265
T5 110 100 110 0.0861 0.0396 0.0246 0.0105
T6 35 20 35 0.0895 0.0545 0.0256 0.0175
III. FAULT ANALYSISWhen the wind farm connects to the power system, the
power flow and the fault contribution in the network will
change. Protections now used must be adjusted and changed to
ensure correct fault clearing with right method, and maintain
the safe and stable operation of the system.
If the power system goes wrong, the short-circuit current issupplied by not only conventional power but also the wind
farm. The change of the short-circuit current will influence the
operation of the relay protection, such as making the
protection devices miss-trip or miss-operate. We need tooptimize the protection devices by analyzing the fault
characteristics of the power system connected with DFIG.
This makes simulation analysis of the fault characteristics by
setting different fault position, different wind speed anddifferent reactive power state.
A. At different fault positionBased on the network in Fig.3, we carried out various fault
simulation and analysis. In this paper only results of the faultson lines T1, T2 and T3 are presented and discussed. The total
installed wind farm capacity is 99MVA, and this wind farm
has 66 units, and rated capacity of every unit is 1.5MVA, the
annual average wind speed is 7.5m/s. Take the three-phaseshort-circuit as the fault type, the operation wind speed is15m/s, fault initial angle is 90 degrees. Monitoring the voltage
and current situation of the bus bar 6, and the results are as
Fig.4 and Fig.5.
From the results we can get that the degree of the voltage
drop and the short current characteristics in the wind farm are
(a)fault on T1 (b) fault on T2 (c) fault on T3
Fig.5 The current waveform at bus 6 with different fault position
(a)fault on T1 (b) fault on T2 (c) fault on T3
Fig.4 The voltage waveform at bus 6 with different fault position
8/13/2019 06162716
4/5
4
different when the fault position is different. If the fault is on
T1, the voltage drop is large, and then finally decreases tozero. At the same time, the short circuit current increases at
first and then decreases to zero fast, that causes the generator
unstable. If the faults on T2 or T3, the voltage drop is less than
the voltage drop when the fault is on T1, and then decreases toa stable value larger than zero. The generator is unstable
because of serious voltage dip, and the wind farm could only
supply transitory short circuit current and the amplitude islow.
B. At different wind speedThe output of the wind farm changes with the wind
conditions because of the random, volatile and
non-controllable of the wind power. So it is necessary to studythe characteristics of wind power short circuit failure in
different wind speed. If there is a three-phase short circuit on
T1, make a research on the voltage and current characteristics
at the point where the wind farm access into the power grid.The simulation results are shown in Fig.6 and Fig.7.
When the wind speed is 15m/s, the voltage drops seriouslyduring the fault and the wind farm can only provideinstantaneous short-circuit current. When the wind speed is
9m/s, the voltage during the fault is larger, but the current is
smaller. The reason is that the stator and rotors flux linkage
will increase as wind speed increases.
C. At different reactive stateAs all the wind generators are DFIGs, we can use
converters to control the size and frequency of the excitation
current added in the rotor windings, so as to achieve thepurpose of power control. Thus the reactive power of the wind
farm can be controlled as absorption or output state. In this
article, by controlling the reactive power of the wind farm onabsorption or output state, we can observe the fault voltage
and fault current in the point connected to the power grid. As
the waveforms shown in Fig.8 and Fig.9, the fault location is
still set in the T1 line and the fault type is still the most seriousthree-phase short-circuit.
It can be seen from the waveforms in Fig. 8 and Fig.9,whether the DFIG is absorbing or output the reactive power,
the change trend of voltage and current is basically the same,but the short circuit current during the fault when absorbing
the reactive power is larger than that when output reactivepower. This is mainly because when stator output reactive
power, the generator armature reaction is demagnetizing thesynthesis of flux. After the three-phase short-circuit fault
occurred in the power grid, the rotor flux will increase, inorder to guarantee the stator flux won't mutate, so the short
circuit currents of the stator and the rotor will increase, and
vice versa.
IV. CONCLUSIONBased on theoretical analysis of double-fed wind turbine
working principle, this paper builds a double-fed inductiongenerator model on the RTDS software and a distributionnetwork simulation model based on t a wind farm in Shanxi
Province. Also the fault characteristics of distribution network
connected with DFIG wind turbine generators were studiedwhen simulated with different fault location, different wind
speed and different reactive state. The results show that the
greater the wind speed is, the greater short-circuit current
DFIG provides. By adjusting and controlling converter, theDFIG output or absorb reactive power according to the
network needs, and the short-circuit current is large when
(a) Current waveform (b)voltage waveform
Fig.9 the voltage and current waveform in the point (bus 6) connected to the
power grid when output the reactive power
(a) Current waveform (b)voltage waveformFig.8. the voltage and current waveform in the point (bus 6) connected to the
ower rid when Absorbin the reactive ower
(a)current waveform (b)voltage waveform
Fig.7voltage and current waveform at bus 6 when the wind speed is 9m/s
(a)current waveform (b)voltage waveform
Fig.6voltage and current waveform at bus 6 when the wind speed is 15m/
8/13/2019 06162716
5/5
5
DFIG output reactive power. The wind power station will
provide short-circuit current to the point of failure after thewind power is merged into the grid, Therefore, the protection
system designing need to consider the characteristics of the
wind turbine, and regarding its short-circuit characteristics as
a protection device configuration reference.
ACKNOWLEDGMENT
Thanks to the support of Datong Electric Company ,China.
REFERENCE
[1] YUAN guo-fengCAI jian-yunLI yong-dongStudy onexcitation converter of variable speed constant frequency wind
generation systemProceeding of the CSEE200525(8)
90-94
[2] LING yu-zhiCUI shu-pingWANG dong-mei.; Discussion ofconfiguration for relay protection after wind farm integration
into power system. North china electric power200909
1-4.
[3] WEN yu-lingCHAO qinTUERXUN.yibulayin. Study onadaptive protection of wind farm. Power system protection and
controlProceeding of the CSEE, 20090547-51.[4] YING mingLI gen-yinZHOU ming ,et alAnalysis and
comparison of dynamic models for the doubly fed induction
generator wind turbin Automation of electric power
systems2006(13)22-27.
[5] Ekanayake J BHoldworth LWu X G. Dynamic modeling ofdoubly fed induction generator wind turbines Power
Systems20032(18)803-809
[6] Feijo F, Cidrs JCarrillo C, et alA third order model for thedoubly-fed induction machine[J]Electric Power Systems
Research200050(2)121-127
[7] Pena RClare J Cand Asher G MDoubly fed inductiongenerator using back-to-back PWM converters and its
application to variable speed wind-energy generationIEE
ProcB1996143(3)231-241
[8] Datta R and Ranganathan V TVariable-speed wind powergeneration using doubly fed wound rotor induction machine-a
companson with alternative schemesIEEE TransEnergy
Conversion200217(3)414-421
[9] Zhang L and Watthanasam CA matrix converter exciteddoubly-fed induction machine a wind power generator. InSeventh International Conference on Power Electronics and
Variable Speed Drives199832-537
[10] CHEN wei CHEN cheng SONG zhan-feng , etal.Proportional-resonant control for dual PWMconverter in
doubly fed wind generation system. Proceeding of the CSEE
200929151-7.
[11] GUO peng.Varibale pitch control of wind turbine generatorcombined with fuzzy feed forward and fuzzy PID controller.Proceeding of the CSEE2010308123-128.
[12] Holdworth LWu X GEkanayake J BComparison of fixedspeed and doubly-fed induction wind turbines during power
system disturbances Generation Transmission and
Distribution20033(150)343-352.
[13] LI jingSONG jia-yeWANG wei-sheng.Modeling anddynamic simulation of variable speed wind turbine with large
capacity. Proceeding of the CSEE200424 (6)100 -105
[14] HE qingZHONG zhi-mingCHEN wen-fu. Simulation andanalysis for pitch control of doubly-fed induction wind turbine
with PSCAD/EMTDC software. Journal of electric power
science and technology200924340-44.
[15] ZHANG jian-huaCHENG xing-yin LIU hao-ming, etal.Three-phase short-circuit analysis for double-fedwind-driven generator and short-circuiter maximal resistance
calculation. Electric power automation equipment2009
46-10.
[16] GUO jia-huZHANG lu-huaCAI xu.Response and protectionof DFIG system under three-phase short circuit fault of grid.
Power system protection and control2010640-44.
BIOGRAPHY
YANG Bei-ge is now a senior engineer engaged in Power Supply
Company of Datong. He recently is focused on the application of thepower grid operation mode intelligent core platform and research onthe intelligent communication devices monitoring system of standaccused of layer and software design of infrared thermal imagingwireless video surveillance system client.
Xue Hui is now a professional Engineer in Branch Marsh Center ofPower Supply Company in Datong . His interest is the power system.
HE Jing-han received her master degree from the TianjingUniversity in 1994 and got the PHD degree in Beijing JiaotongUniversity in China. She is now a professor in Beijing Jiaotong
University. Her interests include online power system monitoring
protection and control, power quality and rail electrification.
Bai Dan-dan received her BSc degree from the Beijing JiaotongUniversity in 2011. She is currently working toward the MSc degreein the School of Electrical Engineering, Beijing Jiaotong University,Beijing, China. Her research interest is power system protection and
control.
Hu Wei received his BSc degree from the Henan University of
Technology in 2009. He received the MSc degree in the School ofElectrical Engineering, Beijing Jiaotong University, Beijing, China.
His research interest is power system protection and control.