06672601

Embed Size (px)

Citation preview

  • 8/13/2019 06672601

    1/5

    Modelling and Simulation of Reverse Power Relay for

    Loss of Mains Protection of Distributed Generation in

    Microgrids

    C. Buque1, S. Chowdhury

    2, S.P. Chowdhury

    3

    Department of Electrical EngineeringUniversity of Cape Town

    Cape Town, South Africa

    [email protected], [email protected]

    2, [email protected]

    3

    Abstract Integration of distributed generation (DG) into theutility grid has led to a renewed emphasis on looking into novel

    power system control and protection issues pertaining to DG

    units. This paper focuses on loss of mains (LOM) detection and

    protection for DG. Commonly used methods of detection fail to

    effectively detect the loss of mains scenario when the local areanetwork load and generation are closely matched. The proposed

    method of detection and protection is highly efficient when the

    demand and supply are similar. For this reason it can be used

    together with the present methods to provide a complete

    solution to LOM protection.

    Index TermsReverse Power Relaying, Loss of Mains,

    Distributed Generation, Point of Common Coupling.

    I. INTRODUCTION

    Loss of mains occurs when the microgrid, formed by the

    distributed generator and local load, become disconnected to

    the utility source of electrical power but remain connected topart of the utility load [1][9]. Loss of mains is less apparent in

    terms of system stability when the DG is large enough to

    support the utility load to which it is connected, however it

    can become a big challenge to system operators if the DG

    does not have enough capacity to support the utility load.

    Consequences related to LOM include frequency instability

    and voltage dips.

    There is no industry standard method for LOM detection

    and protection, various literatures present different methods

    of detection ranging from active methods, passive methods

    and remote techniques. In this paper a passive method

    (reverse power relaying) is explored in order to provide a

    single and complete solution for loss of mains protection for

    microgrids. This relaying system demonstrates the benefits of

    active methods including speed of operation as well as

    avoiding the difficulty presented in passive methods when

    establishing detection thresholds.

    The developed relay is installed on the utility side of thepoint of common coupling (PCC). This enables it to detect theLOM occurrence and signal the static switch (SS), which is apower electronics device at the PCC. Once the SS is open themicrogrid can safely operate in isolated mode. In this mode

    the DG has enough capacity to support the local load withminimal negative effect on voltage levels and frequencystability.

    II. LOSS OF MAINS

    Loss of mains can occur due to faults in the utility grid,

    maintenance in the system or even circuit breaker nuisance

    trip. This event may have many negative effects on the

    distributed generator and microgrid.

    The real challenge faced by the system operators comes in

    when the microgrid has a small distributed generator. This

    can cause voltage dips and system instability. As a systems

    engineer it is important to determine at design stage whether

    the DG is suitable to support the utility load or not. In some

    areas for example, the UK, the DG is by no means allowed to

    support the utility load under a loss of mains scenario [2].

    This is due to the lack of the reliability of the grid when

    operating with a DG as its only source and the difficulties

    encountered when attempting to reconnect the system. Loss

    of mains, for whatever reason it may occur is a severe

    situation which design engineers must take into account,

    especially in terms of system control and protection during

    the occurrence.

    A. Loss of Mains Detection and ProtectionOver the years there have been many detection techniques

    developed, each of these have their own advantages anddisadvantages.

    Local detection means that long distance communication

    is not required. The detection device is located close to the

    The authors are grateful to the authority of the Electrical EngineeringDepartment, University of Cape Town for providing the support and

    infrastructure necessary for carrying out this research.

    978-1-4799-1303-9/13/$31.00 2013 IEEE

  • 8/13/2019 06672601

    2/5

    switch. There are two types of local detection methods:

    Active and Passive method.

    In the active method the detection device functions by

    directly interacting with the system under consideration.

    Perturbations are purposely injected to the system. The

    systems response to the perturbations determines whether

    loss of mains has occurred or not. Examples of active

    techniques are [3]: Reactive power export error detection

    Impedance measurement method

    Slip-mode frequency shift method

    Active Frequency Drift method

    Automatic phase-shift methodActive methods of detection have the disadvantage of

    directly affecting the system to which they are applied. If the

    injected signal is not adjusted correctly it may have a

    significant effect on the magnitude of the frequency of the

    voltage, current and power output of the DG, it can break the

    power balance between the DG and the local loads. However,

    it has a significant advantage in that it is cheaper than passive

    means of detection.In passive techniques there is no added signal to the

    system. This technique relies on the detection of certain

    distinct patterns at the DG output when islanding occurs. A

    difficulty faced when dealing with passive techniques is the

    proper selection of detection thresholds. This technique

    depends vastly on load condition. When there are local

    balanced loads LOM detection becomes difficult. Examples

    of these techniques are [3]:

    Rate of change of output power

    Rate of change of frequency (ROCOF)

    Rate of change of frequency over power

    Harmonics Detection

    Reverse Power RelayingLastly there are remote techniques for LOM detection.These are based on communication systems between the

    utility and the DG. These are expensive to implement,

    especially when small DGs are involved. Examples of remote

    detection include:

    Power Line carrier communications

    Supervisory Control and Data Acquisition systems

    When implementing Passive techniques of detection, the

    DG protection against LOM is provided for by the relays

    used to detect LOM. Once they detect an occurrence they

    send a signal to open the appropriate Circuit Breaker (CB)

    and from those pre-determined actions, the DG andMicrogrids are guaranteed protection.

    When implementing remote techniques, the

    communication links can be used to communicate with the

    PCC or the Static Switch to disconnect the microgrid from

    the utility grid when LOM occurs. The communications

    systems are usually reliable enough to provide effective

    signaling.

    However, when active detection techniques are

    implemented depending on the infrastructure, not always are

    appropriate protection mechanisms activated. Detectors will

    merely warn that LOM has occurred, they will not necessarily

    open any breakers or disconnect the microgrid at the point of

    common coupling. An effective way of making use of the

    information provided by the detector is to send it to relays

    located at the microgrid. Based on pre-determined settings,

    the relays can activate the SS at the PCC to open and leave

    the microgrid to operate in isolated mode.

    When the generation and load in a network area are closelymatched, it becomes difficult to detect a loss of grid supply at

    the generator [4].

    III. POWER SYSTEM MODEL

    The power system model, as shown in Fig. 1, consists of a

    utility source with impedance representing the estimated

    impedance for a utility grid of that capacity. There are two

    busbars with a reverse power relay between them. Once the

    relay detects an abnormality the Static Switch is opened and

    the microgrid becomes isolated. A normal installation would

    have different types of relays triggering the various circuit

    breakers due to certain events. For the purposes of this paper

    only 1 relay is used so that its capabilities can be clearlydemonstrated. The System characteristics are shown in Table

    1.

    Due to the configuration of the power system, the sizes of

    the generators and loads, it is expected that active power will

    only flow from busbar A to busbar B. If active power flows

    from busbar B to busbar A it is considered abnormal.

    Fig. 1. Power System Model

    TABLE 1

    POWER SYSTEM CHARACTERISTICSSystem Voltage (ph-ph) 132kV

    Nominal Frequency 50 Hz

    Utility Source Capacity 100 MVA

    DG Capacity 10MVA/ 10KVA

    Utility Load 100MVA

    Local Load 8MVA

    IV. REVERSE POWER RELAY

    Reverse power protection is generally applied to preventdamage to mechanical plant items in the event of failure of

    the prime mover. Common generator damage includes

    gearbox damage and mechanical damage to shafts.

    Power relays currently used in industry are capable of

    measuring system voltage and current. They also measure the

    angle between these two signals, the angle . With this

    information they can calculate real power which is as shown

    in Equation 1.

  • 8/13/2019 06672601

    3/5

    P = V I cos (1)

    Under normal operation, real power flow is in a determined

    forward direction and -90 < < 90, in the case of reverse

    power flow 90 < < 270. The relay allows for

    unidirectional flow of active power from A to B.

    V. REVERSE POWER RELAY MODELThe reverse element of the relay is the most important in

    identifying an abnormal condition, therefore it is the most

    important in modelling the relay. In this paper the directional

    component of the relay is adopted from [6], where a similar

    relay is used for generator protection.

    In this model, as depicted in Fig. 2, voltage and current

    signals are modified to square waves, with maximum and

    minimum values of 1 and -1. When the signal is positive, the

    value is 1 and when the signal is negative it is represented by

    -1. The two signals are then multiplied to give an output of 1

    when the signals overlap and -1 when they dont. The product

    is then integrated from 0 to L. The upper limit of the

    integrator is 0 so that under normal power flow conditions theintegral remains less than 0. However, under reversed power

    flow conditions the integral output tends to fall until it

    reaches a threshold value of L. The value of L varies

    according to the allowable reverse power, the higher the

    value of L, the higher the amount of reverse power. Once

    there is a reverse power flow in the location where the relay

    is situated the relay identifies the abnormal condition and can

    immediately react to it.

    A time delay component is incorporated in the relay. This

    ensures that the circuit breaker only trips if a prolonged fault

    or abnormal event occurs. The relays shouldnt trip for

    transient power swings.

    The last 4 elements in the model are used to ensure a logic0 is sent to the CB when an abnormality is detected so that

    the CB can open.

    A.Definition of Reverse Power LevelWhen reverse power relaying is used to protect a generator

    a relay setting is chosen based on the type of generator it is.

    An example of this is protection of a Diesel Engine the

    allowable motoring power is 5 to 25% of the rated generation

    capacity. The relay setting is chosen based on Equation 2 [8]:

    ratioratio VTxCT

    (MVA)CapacityGeneratingxPower(%)MotoringSetting = (2)

    For Loss of mains detection the method of determining

    allowable reverse power flow is different because it is not the

    generator that is primarily being protected. In this case -0.01

    was chosen as the lower limit because this is the lowest

    integral value during normal system operation. For other

    systems this value would have to be chosen based on

    modelling results as it depends on the size of the generation

    capacity and the system loads.

    B.Definition of Trip TimeReverse power relays with either built in timers or external

    timers must be used to avoid spurious isolation under

    transient reversal of power, which may arise following

    synchronisation or in the event of a power transmission

    system disturbance. The bigger the generating capacity, the

    lower the time delay should be.

    For loss of mains detection the delay time will essentially

    be defined by breaker reclosing times. When using high

    speed auto-reclosing, it is important to know the time for

    which the line must be de-energised in order to allow

    complete de-ionization of the arc, so that it will not strike

    when the voltage is re-applied. The de-ionization time

    depends on various factors, of these factors circuit voltage isthe most important. Utility reclosers usually reclose after

    0.17s for a 132kV system as shown in Table 2. For this

    reason loss of mains relays must activate before the circuit

    breakers attempt to reclose and reconnect the utility power

    source, this is to avoid reclosing on to unsynchronised

    systems.TABLE2

    ARC DE-ENERGISATION TIMES FOR DIFFERENT VOLTAGE LEVELS [8]

    Transmission

    Line Voltage (kV)

    Minimum de-

    energisation time

    66 0.1110 0.15132 0.17220 0.28275 0.3

    The trip signal time delay has to be long enough to not trip

    for transient cases but fast enough to open the circuit breaker

    before the recloser activates an unsynchronised circuit to be

    reconnected. It is assumed that [7], at medium level voltage

    it takes a relay 2 cycles to pick up the fault and the circuit

    breaker another 3 to 5 cycles to open. Therefore, in addition

    to the set trip time, it takes from 5 to 7 cycles (0.1s to 0.14s in

    a 50Hz system) from the time the fault occurs to the time the

    fault is cleared.

    Based on the preceding argument the trip time delay

    should be: 0.1s < t < 0.17s. The value chosen for t in this

    paper is 0.14s, which corresponds to 7 cycles in a 50Hzsystem.

    Trip1

    VariableTime Delay

    ToSwitch1

    Switch

    Product Integrator

    1s

    If ActionSubsystem

    if { }In1 Out1

    If

    u1if(u1 < -0.01)

    else

    Gain

    -1

    Constant6

    1

    Constant5

    0.06

    Constant4

    1

    Constant3

    -1

    Constant2

    1

    Constant1

    -1

    Constant

    1

    Add1V_in

    2

    I_in1

    Fig. 2. Reverse Power Relay Matlab Model

  • 8/13/2019 06672601

    4/5

    VI. TEST CASES

    A. Test Case 1: Loss of Mains due to open utility switch,large DG Capacity.

    In Test Case 1, CB1 is opened after 2 seconds. This

    represents a scenario where there is maloperation of a switch

    or nuisance tripping. It causes reverse power flow into the

    utility load from the 10MVA microgrid generator. It is

    important that the reverse power relay detects this scenario

    because it will prevent unsynchronized reconnection of the

    utility power source with the microgrid. In this case the

    reverse power relay is expected to cause the static switch at

    the point of common coupling to open.

    B. Test Case 2: Loss of Mains due to a 3-phase Fault,withlarge DG Capacity.

    3-phase faults are the most severe faults in terms of the

    levels of fault current. It is important to provide a protection

    system that can handle such high currents. In this case the

    Utility Source is lost due to a 3-phase fault between CB1 andbusbar A. After the fault has occurred, power will flow from

    the DG towards the fault. This power in the reverse direction

    should be detected by the reverse power relay and the fault is

    expected to be cleared by the relay and switch combination in

    between busbar A and busbar B.

    C. Test Case 3: Loss of Mains due to open utility switch, withSmall DG Capacity.

    This case is similar to test Case 1 but here it is expected

    that there will be the least active power flow which might

    make it more difficult for the reverse power relay to detect

    the abnormality. This test is included in order to test the

    sensitivity of the reverse power relay. Again the switch CB1will be opened at 2 seconds. This case will demonstrate the

    impact on the size of the DG with regards to reverse power

    relaying for loss of mains.

    D. Test Case 4: Loss of Mains due to a 3-phase Fault, withSmall DG Capacity.

    When it comes to reverse power flow with small DG,

    detection is the main issue and sensitivity of the relay model is

    of paramount importance. The reverse current is so small that

    it makes it difficult to detect the reverse active power. In this

    case the three phase fault will cause a relatively high reverse

    power flow and the relay is expected to detect it.

    In all of the test cases the relay setting is the same. The

    relay plays the vital role of detecting reverse active power. For

    all the tests the setting is as described in Section V.

    VII. RESULTS

    A. Test Case 1The results for this case indicate the relay detected the

    reverse power at 2 s. The SS was signalled to open at 2.14 s,

    after the 0.14 s time delay, as shown in Fig. 3. This was as

    expected. The reverse current was 10A which was detected

    by the relay, as shown in Fig. 4. The reverse active power can

    be equated using the values in Table I, Equation 1 and the

    measured reverse current.

    Fig. 3. Relay status during Test Case 1

    Fig. 4. Power System Current During Test Case 1

    B. Test Case 2The results for Test Case 2 indicate that the reverse current

    was 50A as shown by Fig. 6. This current was easily detected

    by the relay. The SS was opened at 2.14 s, as can be seen in

    Fig. 5.

    Fig. 5. Relay status during Test Case 2

    Fig. 6. Power System Current during Test Case 2

    C. Test Case 3The lowest active reverse power was experienced in test

    case as shown in Fig. 8. For this reason the relay did not

    detect the reverse active power and the SS did not open, as

    suggested by the Relay Status signal in Fig. 7. This result

    0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time (s)

    TripSignal

    0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 50

    50

    100

    150

    200

    250

    Time (s)

    Current(A)

    0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time (s)

    TripSignal

    0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 50

    50

    100

    150

    200

    250

    Time (s)

    Current(A)

  • 8/13/2019 06672601

    5/5

    shows that reverse power relaying is ineffective when the

    installed DG capacity is small. For this reason it cannot be

    used as the only means of protection for loss of mains.

    Fig. 7. Relay status during Test Case 3

    Fig. 8. Power System Current during Test Case 3

    D. Test Case 4In Test Case 4, where loss of mains occurs because of a

    fault, the reverse power flow is slightly higher than when loss

    of mains occurs due to a switch opening. The reverse current

    witnessed by the relay is 3A, this can be seen in Fig. 10. The

    relay detected this reverse in power flow and the SS was

    opened after a 0.14 s delay, as displayed in Fig. 9.

    Fig. 9. Relay Status during Test Case 4

    Fig. 10. Power System Current during Test Case 4

    VIII. CONCLUSIONS

    It can be concluded from the test cases and results that

    reverse power relaying is most effective in detecting loss of

    mains when the DG capacity is large. This is useful because

    most methods of loss of mains protection being used at the

    moment are least effective when the DG capacity is large.

    This reverse active power relaying method can be used to

    compliment or as back-up to more traditional loss of mains

    protection methods, such as ROCOF relaying, to provide a

    complete solution which will detect all of the abnormalities

    and protect the microgrid from all of the harms of Loss of

    Mains. This scheme is useful when other methods such asROCOF and frequency drop relays are not sensitive enough

    to detect an abnormal scenario. It is also better than active

    systems because it is not intrusive and better than most

    passive systems because it is reliable.

    REFERENCES

    [1] P. O'Kane and B. Fox, "Loss of mains detection for embeddedgeneration by system impedance monitoring," in Developments in

    Power System Protection, Sixth International Conference on (Conf.

    Publ. No. 434), 1997, pp. 95-98.

    [2] P.D. Hopewell, N. Jenkins, A.D.Cross, Loss-of-mains detection forsmall generators, IEE Proc. Electr. Power Appl., Vol. 143, No. 3,May 1996.

    [3] J. Yin, L.Chang and C. Diduch, Recent Developments in Islanding

    Detection for Distributed Power Generation, Power Engineering,2004. LESCOPE-04. 2004 Large Engineering systems Conference, July

    2004, pp.124 128.

    [4] P. Crolla, A.J. Roscoe, A Dysko and G.M. Burt, Methodology fortesting loss of mains detection algorithms for microgrids and

    distributed generation using real-time power hardware-in-the-loop

    based technique, 8thInternational Conference on Power Electronics ECCE Asia, May 2011.

    [5] Areva,Network Protection & Automation Guide, First Edition, July2001, pp.

    [6] M.M. Aman, G.B. Jasmon, Q.A. Khan, A.H.B. Abu Bakar, J.J. Jamian,Modeling and Simularion of Reverse Power Relay for Generator

    Protection, 2012 IEEE International Power Engineering and

    Optimization Conference (PEOCO2012),Malaysia, June 2012.[7] S.Chowdhury, S.P.Chowdhury and P.Crossley, Microgrids and Active

    Distribution Networks,UK: The IET(UK), 2009.[8] ABB,ABB Switchgear Manual, 10thEdition, 2001.[9] S.Chowdhury, S.P.Chowdhury and P.Crossley. Microgrids and Active

    Distribution Networks, The IET(UK), July 2009.

    IX. BIOGRAPHIES

    C. Buque received his BSc in Electrical Engineering in 2011 and is currentlypursuing his MSc in Electrical Engineering at the University of Cape Town,

    South Africa. Email: [email protected]

    S.Chowdhury is currently the Senior Lecturer in the Electrical Engineering

    Department of The University of Cape Town, South Africa. She became

    Member of IEEE in 2003 and Senior member of IEEE in 2011. She haspublished three books and over 150 papers in power systems modeling and

    simulation, power system protection, distributed generation and renewable

    energy systems. She is Member of SAIEE, Member of the IET (UK) andIE(India) and Senior Member of IEEE(USA). Email:

    [email protected]

    S.P. Chowdhury is currently Associate Professor in Electrical Engineering

    Department of the University of Cape Town, South Africa. He became

    Member of IEEE in 2003 and Senior Member of IEEE in 2011. He has

    published three books and over 200 papers in power systems, distributed

    generation and renewable energy systems. He is a Member of SAIEE, Fellow

    of the IET (UK) with C.Eng. IE (India) and the IETE (India) and SeniorMember of IEEE (USA). Email: [email protected]

    0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5-1

    -0.5

    0

    0.5

    1

    Time (s)

    T

    ripSignal

    0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 50

    50

    100

    150

    200

    250

    Time (s)

    Current(A)

    0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time (s)

    TripSignal

    0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 50

    50

    100

    150

    200

    250

    Time (s)

    C

    urrent(A)