138625544 Ch 5 Control Valves Ppt

Embed Size (px)

Citation preview

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    1/42

    Control Valves

    Ted HuddlestonDept of Chemical EngineeringUniversity of South Alabama

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    2/42

    Fig C-7.2 page 747

    Reciprocating StemSliding Stem

    vp

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    3/42

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    4/42

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    5/42

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    6/42

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    7/42

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    8/42

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    9/42

    Control Valve ActionPage 201 - see Figure C-7.2 on page 747, In this figuresupply air enters the case above the diaphragm. For anair pressure of 3 psig, the diaphragm and valve stem

    are at their topmost position and the valve is wide open.When the air pressure is 9 psig, the diaphragm andvalve stem are at their mid point and the valve is half open. When the air pressure is 15 psig, the diaphragmand valve stem are at their bottom position and the valveis closed.

    This is an air-to-close (ATC) valve. If control air pressure were to fail, the spring would push the stem upand open the valve - called a fail-open (FO valve.

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    10/42

    ATO and ATC Actuators

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    11/42

    ATO and ATC Actuators

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    12/42

    Control Valve Actions

    Which to select? ATC or ATO ?Ask Which is safer if there is a malfunctionwhich includes loss of control air? On fuel and steam valves, use FC.On cooling water, and inert gas blanket linesuse FO.On all valves perform a safety audit.

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    13/42

    P&ID Example

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    14/42

    Control Valve Characteristics

    Describes how flow through valve varieswith stem position.Results from the shape of the valves seatand plug, which determines how valveresistance changes with stem position.Inherent valve characteristicInstalled valve characteristic

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    15/42

    Control Valve Action

    Actuators are built to either open a valve with increasingair pressure (ATO) or to close a valve with increasing air

    pressure (ATC).

    See Figure C-8.1 page 750.

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    16/42

    Plugs and Seats

    Parabolic Characteristic Quick-Opening Characteristic(Equal Percentage)

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    17/42

    Valve Equation

    f

    v

    v G

    p

    Cf

    f = liquid flow, U.S. gpm

    D pv = pressure drop, psiGf = specific gravity of liquidCv = valve coefficientCv = C v(vp)

    Eqn (5-2.1) page 203

    LIQUID SERVICE

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    18/42

    Inherent Characteristic

    constant)vp(Cf v

    Valve is mounted on a test stand such that vp can be

    changed, changing C v and f, but pressures areadjusted such that D pv is held constant.

    f

    vv G

    p)vp(Cf

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    19/42

    Inherent Valve Characteristic

    Curves

    % vp

    Cv,maxf max100

    vmax

    Cf 100f

    f

    0

    constant)vp(Cf v

    Page 211

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    20/42

    Inherent Valve Characteristic

    CurvesLinear Characteristic:

    Cv

    = Cv,max

    (vp) 0 < vp < 1

    Equal Percentage Characteristic

    Cv = C v,max a (vp-1) 0 < vp < 125 < a < 100

    Page 211

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    21/42

    Equal Percentage Valves

    Note the shape of the inherent characteristic.

    When the valve is at vp = 0.2, flow is small, and the slopeD f/D vp is small.

    When the valve is at vp = 0.8, flow is large, and theslope D f/D vp is large.

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    22/42

    Equal Percentage Valves

    The quantity

    100vp

    f f 100f vpf

    represents the percent change of flow per unitchange in valve position.

    The percentage change of flow per unit change

    in valve position is the same or equal for all vp.

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    23/42

    Equal Percentage Valves

    constantCf 1)(vp

    maxv,

    )1)(ln(constantC 1)(vpmaxv, a

    dvp

    df

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    24/42

    Equal Percentage Valves

    )ln(

    constantC)1)(ln(constantC1

    1)(vpmaxv,

    1)(vpmaxv,

    a

    a

    dvpdf

    f

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    25/42

    Installed Valve Characteristics

    Section starts on page 212. See diagram on page 213. Acontrol valve is installed in series with a heat exchanger.Water is supplied from the left at a constant pressure, andexhausts to the atmosphere at the right. Valve positioncan vary, flow through the process can vary, pressure dropthrough the exchanger, through the pipe and fittings, and

    through the valve can vary. But the total pressuredrop D p o is constant.

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    26/42

    Installed Valve Characteristics

    Assume flow is fully turbulent. Pressure drop throughline, fittings, and heat exchanger is

    2f LL f Gk p

    Pressure drop across valve is obtained from valve equation

    2

    v

    2

    f v Cf

    Gp

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    27/42

    Installed Valve Characteristics

    The total pressure drop is

    2f L2

    v

    o f Gk C1

    p

    Solving for the flow f yields

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    28/42

    Installed Valve Characteristics

    f

    o

    2vL

    v

    Gp

    Ck 1

    Cf(vp)

    Linear

    =%1)(vp

    maxv,v

    maxv,v

    CC(vp)CC

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    29/42

    Installed Valve Characteristics

    What installed valve characteristic isdesirable?Flow rate should change by the same amount

    per vp change throughout valve stroke.

    Gain (flow rate change/vp change) should beconstant for all values of vp.This is a linear installed valve characteristic.

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    30/42

    Inherent vs Installed Characteristics

    vp

    flow

    When a valve is installed in series with processequipment, the installed characteristic flow curve isshifted up and to the left of the inherent flow curve.

    See Figure 5-2.7 on page 217.

    Installed

    Inherent

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    31/42

    So which to choose ?

    When valve takes up most ( > 80 %) of the pressuredrop use a linear valve. (Ex: Valve on a fuel gasline between the header and the burner.)When valve is installed in series with other equipment and valve takes up 20 60% of the

    pressure drop use =% valve.When valve takes up 60-80% of pressure drop let

    boss decide.

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    32/42

    Valve Rangeability

    f(0.05)f(0.95)

    positionvalve5%atFlow

    positionvalve95%atFlowtyRangeabili

    Defined on page 212. Also known as the turn-downratio, it is the ratio of the maximum controllable flow tothe minimum controllable flow FOR THEINSTALLED VALVE. Flow f(vp) is computed usingEQN (5-2.14) on page 214.

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    33/42

    Control Valve C v

    The size of a control valve is described by its C v.

    f

    vmaxv, G

    pCf

    The valve is fully open.

    D pv = 1 psiG f = 1 (fluid is water)

    f = C v,max gpm

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    34/42

    Control Valve C v

    The C v of a control valve is the flow in gpm

    of water that would flow through the fullyopen valve caused by a pressure drop of 1

    psi.

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    35/42

    Control Valve Sizing

    Linear Installed Characteristic

    Small Pressure DropHigh RangeabilityOperates approximately half open at design

    flow

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    36/42

    Control Valve Sizing

    Method One: The Overcapacity M ethod in which the valve

    is specified so that when the valve is fully open with specifiedD pv, the flow is double the design flow.

    1) flow = 2 x Design Flow

    2p

    p4

    p)2 ov

    o

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    37/42

    Control Valve Sizing

    4) From the manufacturers literature select thesmallest C v that exceeds the value of C v,max found in

    part (3).

    f

    vmaxv,

    Gp

    FlowDesign2C)3

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    38/42

    Control Valve Sizing

    Method Two: The Design F low M ethod in which the valve

    will pass the design flow at valve position vp = 0.6 with thespecified D pv.

    1) flow = Design Flow

    2p

    p4

    p)2 ov

    o

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    39/42

    Control Valve Sizing

    f

    vmaxv,

    Gp

    vp

    FlowDesignC

    )3 Valve Linear

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    40/42

    Control Valve Sizing

    f

    v1vpmaxv,

    Gp

    FlowDesignC

    %)3 Valve

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    41/42

    Control Valve Sizing

    4) From the manufacturers literature select the

    smallest C v that exceeds the value of C v,max found in part (3).

  • 7/28/2019 138625544 Ch 5 Control Valves Ppt

    42/42

    Control Valve Sizing

    We have not considered cavitation, flashing, sonic flow, the pressure drop recovery factor, the Reynolds Number

    recovery factor, piping geometry factor, noise reduction,and other important items. The equation used here is for liquid service. Equations for gases and vapors are morecomplicated.

    When buying valves from a particular manufacturer use that manufacturers equationsand technical support.