Complete IP Alison

Embed Size (px)

Citation preview

  • 8/3/2019 Complete IP Alison

    1/26

    A STUDY ON THE FEASIBILITY OF USING

    GEOTHERMAL COOLING AS AN ALTERNATIVE

    TO CONVENTIONAL AIR CONDITIONING

    An Investigatory and Exploratory Project

    Presented to the Faculty of

    Westfield Science-Oriented School and Colleges

    Las Pias City

    In Partial Fulfilment of the

    Requirements in General Science

    Danielle Alison B. Black

    HS1- Consunji

    December 2011

  • 8/3/2019 Complete IP Alison

    2/26

    Chapter I. INTRODUCTION

    Background of the Study

    The world is currently experiencing problems involving our energy resources.

    The problem is the rate that the worlds energy demands are increasing is faster than

    the rate at which renewable sources are being developed.

    So until the time that both renewable and fossil fuelled energy resources can be

    stabilized to meet demand, the only real solution is to look for ways to reduce our

    energy consumption.

    Looking at how much electricity we use, you will see that air conditioning

    contributes the largest share of our total energy consumption. This is particularly true in

    summer, where the use of air conditioning can contribute to more than 50% of

    household electrical consumption. Of course we can just stop using our aircons, but that

    would only work on cool days, like around Christmas time, but it would also make our

    homes very uncomfortable during summer. So the better solution would be to look at

    how to make an aircons use less electricity.

    The reason why aircons use so much electricity is because of the compressor.

    This is the most important part of the aircon because it compresses the heat that is

    taken from inside the room and transfers that heat outside where the heat is radiated

    into the atmosphere. The compressor makes sure that the temperature of the aircons

    condenser is always hotter than the outside ambient air temperature, so that the heat

    will transfer from the condenser to the outside air. When the heat is transferred (or

    exchanged) to the outside air, the now cool air is brought back into the room. That is

  • 8/3/2019 Complete IP Alison

    3/26

    why aircons are also called heat exchangers. If there was a way to construct a heat

    exchanger that does not use a compressor, then it would be possible to have a very

    energy efficient air conditioner.

    For a compressor-less heat exchanger to work, it has to be able to radiate its

    heat into a place that is cooler than the room being cooled. One possible place is the

    earth itself. In the Philippines, the ground temperature beyond 5m below the surface is

    constant at 25C, regardless of what the outside temperature is. This can be as low as

    20 C if ground water is present, usually around 30m below the surface.

    This project aims to explore the feasibility of building a compressor-less heat

    exchanger as an alternative to conventional aircons. The heat exchanger will take the

    heat from a room (the same way as a regular aircon) and then use the earth as a heat

    sink to absorb that heat. Since the ground temperature will always be lower than the

    temperature of the room being cooled, then there is no need for a compressor. It should

    be possible to get the room to cool down to the same temperature as the ground.

    Because this type of heat exchanger will only use a radiator, a blower fan and a

    small water pump, its energy consumption can be much lower than what an aircon uses

    but it will still be able to provide the same cooling as a regular aircon.

    The researcher chose to conduct this study because the world needs to find a

    way to prevent the abatement of our non-renewable resources by making use of our

    renewable energy resources for a better future.

    If this experiment is successful, it will prove that it is possible to make an energy

    efficient air conditioner.

  • 8/3/2019 Complete IP Alison

    4/26

    Objectives of the Study

    The researcher considers the following objective of the study:

    1. The study aims to determine if ground source geothermal cooling can be

    used as an alternative for conventional air-conditioning

    2. The study also aims to determine if a ground source geothermal cooling

    system will use less electricity than a conventional air conditioner.

    Statement of the Problem

    This study seeks to answer the following questions:

    1. Can ground source geothermal cooling be an alternative of air-conditioning?

    2. Will a ground source geothermal cooling system use less electricity than a

    conventional air conditioner?

    Hypothesis

    1. The ground source geothermal cooling is a possible alternative for

    conventional air-conditioning.

    2. The ground source geothermal cooling system will be more energy efficient

    than a conventional air conditioner.

  • 8/3/2019 Complete IP Alison

    5/26

    Scope and Delimitation

    This study will focus on proving the concept of ground source geothermal

    cooling. The output of this project will be a scaled down ground source geothermal

    cooling system using a miniature room mock up with a heat exchanger and a heat sink

    in a simulated ground cooling system.

    As a proof of concept, this project will not be done in full scale, but it will identify

    possible issues to be considered for building a full-scale version.

    Significance of the Study

    To the students, this study shows that they can help the environment at a young

    age. And in the future, they can use this study as a guide for a better living.

    To the researchers, this study will provide the basis for further study on how to

    build a full-scale ground source geothermal cooling system that can potentially replace

    the use of conventional aircons.

    To the businessmen, this study will help them in finding new ways in saving

    money because this study promotes less use of electricity. Therefore, less money is

    spent.

    To the country, this study is significant because of the amount of electricity that

    can be saved by this system can result in not only lower electricity bills, but also lessen

    our countrys use of fossil fuels and reduce our CO2 emissions.

  • 8/3/2019 Complete IP Alison

    6/26

    Definition of Terms

    Fossil fuels. Fuels that are formed by natural processes such as anaerobic

    decomposition of buried dead organisms. The age of the organisms and their resulting

    fossil fuels is typically millions of years, and sometimes exceeds 650 million years.

    Ground source geothermal cooling. A central cooling system that pumps heat to or

    from the ground. It uses the earth as a heat sink. This design takes advantage of the

    moderate temperatures in the ground to boost efficiency and reduce the operational

    costs of heating and cooling systems

    Heat Exchanger. A device for transferring heat from one medium to another.

    Heat Sink.A device or substance for absorbing excessive or unwanted heat

    Renewable energy.Renewable energy is energy which comes from natural resources

    such as sunlight, wind, rain, tides, and geothermal heat, which are renewable (naturally

    replenished).

  • 8/3/2019 Complete IP Alison

    7/26

    Chapter II. REVIEW OF RELATED LITERATURE

    Throughout the history of man, people have been taking advantage of the

    insulating properties of the earth as protection from the weather. From the time that

    Stone Age man started moving out of caves and into man-made dwellings during the

    Middle Paleolithic Age 50,000 years ago, fully or semi-underground man-made shelters

    were the primary means used by man to protect himself from extreme heat or cold.

    (Clark, J. Desmond, 1982. The Culture of the Middle Paleolithic/Middle Stone Age)

    This use of underground shelters as well as above ground earthen structures

    continued throughout the ancient and modern times, because earthen structures

    provide constant year-round indoor temperatures, regardless of the outdoor

    temperature. (Roy, Robert, 2006. Earth Sheltered Houses).

    Modern geologists have since determined that underground temperature for any

    specific location on the planet remains constant throughout the year and is equal to the

    average annual temperature for that specific region (California Energy Commission,

    2009. Geothermal or Ground Source Heat Pumps). In the Philippines, the underground

    temperature has been determined to be 25.8 degC above the water table or when there

    is no ground water present, and 20.3 degC when ground water is present (Philippine

    Atmospheric, Geophysical and Astronomical Services Administration, 2001. Climate of

    the Philippines).

    In the United States and Europe, the use of coolant piped into the ground is

    called ground source geothermal cooling. This is primarily used to reduce energy

    consumption during the winter months where the ground temperatures are higher than

  • 8/3/2019 Complete IP Alison

    8/26

    the ambient air temperature. It has also been used secondarily for cooling in summer,

    when the ground is cooler than the ambient air. However, the low average humidity

    makes evaporative coolers cheaper and more efficient, therefore, the use of ground

    source geothermal as a replacement for conventional airconditioning is limited. Several

    non-commercial and experimental ground source geothermal air conditioning systems

    are being used and tested in some southern US states where the high summer humidity

    prevents the efficient use of evaporative coolers (Gannon, Robert, 1978, Ground-Water

    Heat Pumps - Home Heating and Cooling from Your Own Well).

    In the Philippines, there is a potential to use ground source cooling because the

    ground temperature can be as much as 15 degC cooler than the ambient air

    temperature at the peak of summer. Air conditioning manufacturers recommend that for

    maximum comfort and efficiency, conventional airconditioners should be set to a

    temperature exactly 10 degC lower than the outside temperature (Jan F. Kreider. 1996.

    Handbook of heating, ventilation, and air conditioning). Since the ground temperature

    can be as much as 15 degC cooler than the outside air, then a compressor-less ground

    source cooling air conditioner can potentially provide the same cooling as a standard air

    conditioner.

    Also, with a 15 degC temperature difference between the ground and the inside

    of a house or building will allow the use of a simple heat exchanger using water pump

    and a heat sink buried underground below the water table to take the hot indoor air from

    a house or building and transfer that heat into the ground (Winnick, J,1996. Chemical

    engineering thermodynamics).

  • 8/3/2019 Complete IP Alison

    9/26

    Chapter III. Methodology

    Materials

    This study used a small scale mock-up of a ground source cooling system. The

    following materials were used to construct the mock-up:

    1. Cardboard box (1m x 1m x 1m)

    2. Foam roofing insulation

    3. Heat sink / radiator

    4. Electric blower fan (computer fan)

    5. Aquarium water pump

    6. Ducting (3" diameter)

    7. Rubber hoses

    8. Ice cooler

    9. Coiled aluminium tubing

    10. Digital thermometers

    11. Timer

    To construct the mock-up of a house, the cardboard box was first lined with foam

    insulation. Then Two 3-inch holes were cut into the box, one on each side and ducting

    was attached to each hole. A digital thermometer was put inside the house to observe

    the changes in air temperature during the experiment.

    To simulate the ground, the ice cooler was filled with water and ice added to

    attain a temperature of 20.3 degC measured with a thermometer. Ice was then added

    as needed during the experiment to keep the temperature constant.

  • 8/3/2019 Complete IP Alison

    10/26

    For the heat exchanger, the tubing from the box was connected to an electric

    blower fan. The radiator was them attached to the other end of the fan. The other end of

    the duct was then attached to the opposite side of the radiator.

    To simulate the underground heat sink, coiled aluminium tubing was put into the

    ice cooler. Rubber hoses were then attached to both ends of the aluminium tubing. To

    circulate the water between the radiator and the heat sink, an aquarium water pump

    was used and connected to both the radiator and the heat sink so that water could

    circulate between the heat sink and the radiator.

    Procedures

    Before starting the experiment, the temperature of the box was measured and

    noted. Then the blower fan and water pump were turned on to circulate the coolant and

    the timer was started.

    With the fan and the pump running, the temperature of the box was constantly

    monitored and any changes in temperature over time were noted. Simultaneously, the

    temperature of the ice box was also monitored to make sure that the temperature

    remained constant. If the temperature of the ice box increased, then additional ice was

    added as needed to maintain a constant 20.3 degC temperature.

    The heat exchanger was kept running until the time that the temperature of the

    box became constant. The ending temperature and the elapsed time were then noted.

  • 8/3/2019 Complete IP Alison

    11/26

    Chapter IV. RESULTS AND DISCUSSIONS

    A. Presentation of Data

    Four tests were conducted using the mock-up in order to examine how the mock

    up performs under daytime and night time temperature conditions. A description of

    each test and the results are discussed below.

    As this is a test of a cooling system, the temperatures both inside and outside of

    the test box were measured before and during the test. Likewise the temperature of the

    coolant box was measured and maintained at 21C to simulate the constant ground

    temperature.

    In the following discussions, "outdoor temperature" shall refer to the ambient

    temperature outside the box, "indoor temperature" shall refer to the measured

    temperatures inside the box, while "ground temperature" shall refer to the temperature

    of the coolant box.

  • 8/3/2019 Complete IP Alison

    12/26

    Test No. 1 : Daytime test. Starting indoor temperature SAME as outdoor

    temperature

    This test was conducted in the daytime with the mock-up set outdoors in a

    shaded location. The indoor temperature inside the mock-up was equalized with the

    outdoor temperature prior to the test. At the time of the test, the outdoor temperature

    was measured to be 32C with the ground temperature kept constant at 21C.

    The results are shown in Table 1 below.

    Table 1 : Test No. 1 Measured Temperature Over Time

    Time

    (Minutes)

    Outdoor

    Temperature (C)

    Ground

    Temperature (C)

    Indoor

    Temperature (C)

    Temp DifferenceIndoor vs

    Outdoor (C)

    Temp DifferenceIndoor vs

    Ground (C)

    0 32 21 32 0 +11

    1 32 21 32 0 +11

    2 32 21 32 0 +11

    3 32 21 31 -1 +10

    4 32 21 29 -3 +8

    5 32 21 28 -4 +7

    6 32 21 28 -4 +7

    7 32 21 27 -5 +6

    8 32 21 27 -5 +6

    9 32 21 27 -5 +6

    10 32 21 26 -6 +5

    11 32 21 26 -6 +5

    12 32 21 26 -6 +5

    13 32 21 25 -7 +4

    14 32 21 25 -7 +4

    15 32 21 25 -7 +4

    16 32 21 25 -7 +4

    17 32 21 24 -8 +3

    18 32 21 24 -8 +3

    19 32 21 24 -8 +3

    20 32 21 24 -8 +3

  • 8/3/2019 Complete IP Alison

    13/26

    As seen in Table 1 (above), for the first two minutes of the test, there was no

    recorded change in the indoor temperature. Beginning the 3rd minute, the indoor

    temperatures began to fall at a relatively constant rate until 17 minutes into the test,

    where the indoor temperature remained constant until the end of the test.

    By the end of the test period, the mock-up was able to achieve a constant indoor

    temperature of 24C, which was 8C cooler than the outside temperature, and only 3C

    warmer than the ground temperature. This is illustrated in Graph 1 (below).

    Graph 1: Results of Test No. 1 (Daytime, Indoor and Outdoor Temperature Sameat Start)

    19

    21

    23

    25

    27

    29

    31

    33

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

    Temperature(C)

    Time (Minutes)

    Outdoor Temp

    Indoor Temp

    Ground Temp

  • 8/3/2019 Complete IP Alison

    14/26

    Test No. 2 : Daytime test. Starting indoor temperature HIGHER than outdoor

    temperature

    This test was done in the daytime with the mock-up set outdoors in the shade.

    The indoor temperature was raised by 5C above the outdoor temperature. This was

    done to simulate a real world scenario where the inside of a house may be warmer than

    the outside temperature because of internal heat sources such as stoves, appliances,

    and body heat from people. At the time of the test, the outdoor temperature was

    measured to be 32C with the ground temperature kept constant at 21C and the indoor

    temperature was raised to 37C. The results are shown in Table 2 below.

    Table 2 : Test No. 2 Measured Temperature Over Time

    Time

    (Minutes)

    Outdoor

    Temperature (C)

    Ground

    Temperature (C)

    Indoor

    Temperature (C)

    Temp Difference

    Indoor vs

    Outdoor (C)

    Temp Difference

    Indoor vs

    Ground (C)

    0 32 21 37 +5 +16

    1 32 21 35 +5 +16

    2 32 21 34 +4 +15

    3 32 21 33 +3 +144 32 21 32 +2 +13

    5 32 21 32 +1 +12

    6 32 21 32 0 +11

    7 32 21 31 0 +11

    8 32 21 30 -2 +9

    9 32 21 30 -3 +8

    10 32 21 28 -4 +7

    11 32 21 28 -4 +7

    12 32 21 27 -5 +6

    13 32 21 26 -5 +6

    14 32 21 26 -6 +5

    15 32 21 25 -7 +4

    16 32 21 25 -7 +4

    17 32 21 25 -7 +4

    18 32 21 24 -8 +3

    19 32 21 24 -8 +3

    20 32 21 24 -8 +3

  • 8/3/2019 Complete IP Alison

    15/26

    As seen in Table 2 (above), the temperature immediately began to drop from the

    very beginning of the test until the indoor temperature reached the same as the outdoor

    temperature of 32C after four minutes. and then the temperature remained steady for

    three minutes before continuing to drop until it reached a minimum of 24C after 18

    minutes.

    Although the starting indoor temperature was higher by 5C than on Test No.1,

    then ending temperature was of 24C was the same for both Test No.1 and Test No.2.

    This is illustrated in Graph 2 (below).

    Graph 2: Results of Test No. 2 (Daytime, Indoor and Outdoor TemperatureHigher at Start)

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

    Temperature(C)

    Time (Minutes)

    Outdoor Temp

    Indoor Temp

    Ground Temp

  • 8/3/2019 Complete IP Alison

    16/26

    Test No. 3 : Night time test. Starting indoor temperature SAME as outdoor

    temperature

    This test was done at night time with the mock-up set outdoors in the shade. Just

    as with Test No.1, the indoor temperature was first equalized with the outdoor

    temperature before starting the test. At the time of the test, the outdoor temperature

    was measured to be 28C with the ground temperature kept constant at 21C. The

    results are shown in Table 3 below.

    Table 3 : Test No. 3 Measured Temperature Over Time

    Time

    (Minutes)

    Outdoor

    Temperature (C)

    Ground

    Temperature (C)

    Indoor

    Temperature (C)

    Temp Difference

    Indoor vsOutdoor (C)

    Temp Difference

    Indoor vsGround (C)

    0 28 21 28 0 +7

    1 28 21 27 -1 +6

    2 28 21 27 -1 +6

    3 28 21 26 -2 +5

    4 28 21 26 -2 +5

    5 28 21 25 -3 +4

    6 28 21 25 -3 +4

    7 28 21 24 -4 +3

    8 28 21 24 -4 +3

    9 28 21 23 -5 +2

    10 28 21 23 -5 +2

    11 28 21 23 -5 +2

    12 28 21 23 -5 +2

    13 28 21 22 -6 +1

    14 28 21 22 -6 +1

    15 28 21 22 -6 +1

    16 28 21 22 -6 +1

    17 28 21 22 -6 +1

    18 28 21 22 -6 +1

    19 28 21 22 -6 +1

    20 28 21 22 -6 +1

  • 8/3/2019 Complete IP Alison

    17/26

    As seen in Table 3 (above), after one minute, the indoor temperature began to

    fall at a constant rate until 13 minutes into the test, afterwhich the indoor temperature

    stayed constant until the end of the test.

    By the end of the test period, the mock-up was able to achieve a constant indoor

    temperature of 22C, which was 6C cooler than the outside temperature, and only 1C

    warmer than the ground temperature. This is illustrated in Graph 3 (below).

    Graph 3: Results of Test No. 3 (Night time, Indoor and Outdoor TemperatureSame at Start)

    19

    20

    21

    22

    23

    24

    25

    26

    27

    28

    29

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

    Temperature

    (C)

    Time (Minutes)

    Outdoor Temp

    Indoor Temp

    Ground Temp

  • 8/3/2019 Complete IP Alison

    18/26

    Test No. 4 : Night time test. Starting indoor temperature HIGHER than outdoor

    temperature

    This test was done at night time with the mock-up set outdoors in the shade. Just

    as with Test No.2, the indoor temperature was raised by 5C above the outdoor

    temperature to simulate indoor heat sources. At the time of the test, the outdoor

    temperature was measured at 28C with the ground temperature kept constant at 21C

    and the indoor temperature was raised to 33C. The results are shown in Table 4 below.

    Table 4 : Test No. 4 Measured Temperature Over Time

    Time

    (Minutes)

    Outdoor

    Temperature (C)

    Ground

    Temperature (C)

    Indoor

    Temperature (C)

    Temp Difference

    Indoor vsOutdoor (C)

    Temp Difference

    Indoor vsGround (C)

    0 28 21 33 +5 +12

    1 28 21 32 +4 +11

    2 28 21 32 +4 +11

    3 28 21 31 +3 +10

    4 28 21 30 +2 +9

    5 28 21 29 +1 +8

    6 28 21 28 0 +7

    7 28 21 28 0 +7

    8 28 21 28 0 +7

    9 28 21 27 -1 +6

    10 28 21 26 -2 +5

    11 28 21 25 -3 +4

    12 28 21 25 -3 +4

    13 28 21 24 -4 +3

    14 28 21 24 -4 +3

    15 28 21 23 -5 +2

    16 28 21 23 -5 +2

    17 28 21 22 -6 +1

    18 28 21 22 -6 +1

    19 28 21 22 -6 +1

    20 28 21 22 -6 +1

  • 8/3/2019 Complete IP Alison

    19/26

    As seen in Table 4 (above), the temperature immediately began to drop from the

    very beginning of the test until the indoor temperature reached the same as the outdoor

    temperature of 28C after six minutes. and then the temperature remained steady for

    three minutes before continuing to drop until it reached a minimum of 22C after 17

    minutes.

    This drop in temperature over time is illustrated in Graph 4 (below).

    Graph 4: Results of Test No. 4 (Daytime, Indoor and Outdoor TemperatureHigher at Start)

    19

    21

    23

    25

    27

    29

    31

    33

    35

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

    Temperature

    (C)

    Time (Minutes)

    Outdoor Temp

    Indoor Temp

    Ground Temp

  • 8/3/2019 Complete IP Alison

    20/26

    B. Analysis of Data

    Based on the data collected, the experiment was able to achieve a decrease in

    the indoor temperatures in all of the four tests. This can clearly be seen in Graph 5

    below.

    These results show that it is possible for a simple heat exchanger using the earth

    as a heat sink to cool an enclosed space.

    Graph 5: Comparative Temperature Drop for Tests 1,2,3 & 4

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

    Tem

    perature(C)

    Time (Minutes)

    Test No.1

    Test No.2

    Test No.3

    TestNo.4

    DayOutdoor Tem

    NightOutdoor Te

    Ground Temp

  • 8/3/2019 Complete IP Alison

    21/26

    It was also noted that in both the daytime and nigh time tests, the coolest

    temperatures attained were the same, even when the beginning temperatures were

    increased above that of the outside temperature.

    For the daytime tests (Tests No.1 and No.2), even if they had different starting

    indoor temperatures, 32C for Test No.1 and 37C for Test No.2, both were able to

    reach the same ending temperature of 24C. The only difference was the length of time

    it took for the tests to reach their minimum temperature, 17 minutes for Test No.1, and

    18 minutes for Test No.2. This can be seen in Graph 6 below.

    Graph 6: Comparative Temperature Drop for Daytime Test No.1 and No.2

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

    Temperature(C)

    Time (Minutes)

    Test No.1

    Test No.2

    Outdoor Temp

    Ground Temp

  • 8/3/2019 Complete IP Alison

    22/26

    Similarly, for the night time tests (Tests No.3 and No.4), even if they had

    different starting indoor temperatures, 28C for Test No.1 and 33C for Test No.2, both

    were able to reach the same ending temperature of 22C. The only difference was the

    length of time it took for the tests to reach their minimum temperature, 15 minutes for

    Test No.3, and 17 minutes for Test No.2. This can be seen in Graph 7 below.

    Graph 7: Comparative Temperature Drop for Night Time Test No.3 and No.4

    It was also observed that both the daytime and night time tests were able to

    achieve significant cooling compared to the outside temperature, with the daytime tests

    achieving indoor temperatures that were 8C cooler than the outside air. Likewise, the

    night time tests achieved temperatures -8C cooler than the outside air. However,

    19

    21

    23

    25

    27

    29

    31

    33

    35

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

    Temperature(C)

    Time (Minutes)

    Test No.3

    Test No.4

    Outdoor Temp

    Ground Temp

  • 8/3/2019 Complete IP Alison

    23/26

    the neither the daytime nor the night time tests were able to achieve the same

    temperatures as the ground, with the lowest daytime test temperatures ending at +3C

    warmer than the ground temperature. Likewise, the night time test temperatures ended

    at +1C warmer than the ground temperature. These results be seen in Table 1 below.

    Table 1: Comparative Temperature Difference for Day and Night Tests

    Maximum Temp Difference

    vs Outdoor Temperature

    Minimum Temp Difference

    vs Ground Temperature

    Day Time Test No.1 & 2 -8C +3C

    Night Time Test No. 3 & 4 -6C +1C

    Since the process of heat exchange slows down as the temperature difference

    becomes smaller, this may explain why the night time temperature difference is not as

    large as the day time temperature difference.

    Also, it was noted that the minimum temperature difference vs the ground

    temperature was lower for the night test at +1C compared to the day test at +2C.This

    may be because heat was still entering the mock-up box and the coolant hoses, thus

    preventing the system from achieving equal temperature with the ground.

    However, even with external heat entering the system, the indoor temperatures

    of 24C in the daytime and 21C at night attained by the geothermal cooling system

    were still comparable to that of a conventional air conditioner.

  • 8/3/2019 Complete IP Alison

    24/26

    Chapter V. CONCLUSIONS AND RECOMMENDATIONS

    Conclusions

    Based on the study investigated, the following conclusions were drawn:

    1. It was possible to use a ground-source geothermal cooling system as an alternative

    to conventional air-conditioning. Therefore, hypothesis Number 1 is accepted.

    2. Since the ground source geothermal system only used a water pump and a fan and

    no air compressor, then the system uses less electricity and is more energy efficient

    than an air-conditioner. Therefore, hypothesis Number 2 is accepted.

    Recommendations

    Based on the study done, the following recommendations were made:

    1. Try to use better insulation on the system to see if it is possible to attain indoor

    temperatures equal to the ground temperature.

    2. Try to test on a larger scale and with higher heat loads (ie test in direct sunlight) to

    further explore the system's efficiency.

    3. Repeat the tests and measure humidity along with temperature to test if the system

    can also control humidity similar to an air-conditioner.

  • 8/3/2019 Complete IP Alison

    25/26

    BIBLIOGRAPHY

    I. Books

    Clark, J. Desmond, 1982. The Culture of the Middle Paleolithic/Middle Stone Age

    Cambridge University Press

    Roy, Robert, 2006. Earth Sheltered Houses

    New Society Publishers

    Winnick, Jack, 1996. Chemical engineering thermodynamics

    Wiley

    Jan F. Kreider. 1996. Handbook of heating, ventilation and air conditioning

    CRC Press

    Gannon, Robert. 1978. Ground-Water Heat Pumps Home Heating and Cooling

    from Your Own Well

    Times Mirror Magazines, Inc.

    II. Internet

    Climate of the Philippines.Retrieved 2001 from

    http://kidlat.pagasa.dost.gov.ph/cab/statfram.htm

  • 8/3/2019 Complete IP Alison

    26/26