Document Edition 1.0 Page 1 of 10 INSTALLATION & APPLICATION GUIDE Delta Application Controller (16-Input) DAC-1600 (Rev 1.0) Document Edition 1.0 Product Description The Delta 16-Input Controller  is a Native BACnet Application Controller that is fully programmable (via GCL+) and communicates on an RS-485 LAN using the MS/TP BACnet protocol. The controller includes an easy to mount enclosure and is designed for a wide range of monitoring applications requiring no more than 16 inputs. A secondary LINKnet network is also supported for up to 4 Delta BACstats or other Delta LINKnet devices. The 16 universal inputs are jumper configurable. Contents MODEL NUMBERS & ACCESSORIES............................................................................ 2 PACKAGE CONTENTS .......................... .............. .............. .......................................... ...... 2 OTHER RELEVANT DOCUMENTS................................................................................. 2 IMPORTANT INFORMATION.......................................................................................... 2 PRODUCT SPECIFICATIONS........................................................................................... 3 BOARD LAYOUT.. .............. ................................................................................................. 4 INDICATORS .................................................................... .............. ............................ ......... 5 JUMPERS ............ ............... ................................................................................................... 5 CONTROLLER ADDRESS DIP SWITCHES ............ ......................... ............. ................. 6 MOUNTI NG ............. ........................................................ .............. .............. .............. ........... 6 INPUT & OUTPUT WIRING.............................................................................................. 6 POWER............... .............. ...................................................................... .............. .............. ... 7 MS/TP NETWORK CABLING & REQUIREMENTS .......................... .............. ............. 7 MS/TP NETWORK TOPOLOGY................ ...................................................................... . 7 COMMUNICATIONS SETUP ...................................................... .............. .............. .......... 8 CAUTIONS & WARNINGS ................................................................................................ 9 COMPLIANCE DECLARATIONS .................................................................................... 9

DAC 1600 guia de instalación (1 0)

Embed Size (px)

Citation preview

Page 1: DAC 1600 guia de instalación (1 0)

7/26/2019 DAC 1600 guia de instalación (1 0)

http://slidepdf.com/reader/full/dac-1600-guia-de-instalacion-1-0 1/10

Document Edition 1.0 Page 1 of 10

INSTALLATION & APPLICATION GUIDE

Delta Application Controller (16-Input)DAC-1600 (Rev 1.0)

Document Edition 1.0

Product Description

The Delta 16-Input Controller is a Native BACnet

Application Controller that is fully programmable (via

GCL+) and communicates on an RS-485 LAN using the

MS/TP BACnet protocol. The controller includes an easy

to mount enclosure and is designed for a wide range of

monitoring applications requiring no more than 16 inputs.

A secondary LINKnet network is also supported for up to

4 Delta BACstats or other Delta LINKnet devices.

The 16 universal inputs are jumper configurable.

Contents

MODEL NUMBERS & ACCESSORIES............................................................................ 2

PACKAGE CONTENTS...................................................................................................... 2

OTHER RELEVANT DOCUMENTS................................................................................. 2

IMPORTANT INFORMATION.......................................................................................... 2

PRODUCT SPECIFICATIONS........................................................................................... 3

BOARD LAYOUT................................................................................................................. 4

INDICATORS ....................................................................................................................... 5

JUMPERS .............................................................................................................................. 5

CONTROLLER ADDRESS DIP SWITCHES ................................................................... 6

MOUNTING .......................................................................................................................... 6

INPUT & OUTPUT WIRING.............................................................................................. 6

POWER.................................................................................................................................. 7

MS/TP NETWORK CABLING & REQUIREMENTS..................................................... 7

MS/TP NETWORK TOPOLOGY....................................................................................... 7

COMMUNICATIONS SETUP ............................................................................................ 8

CAUTIONS & WARNINGS ................................................................................................ 9

COMPLIANCE DECLARATIONS .................................................................................... 9

Page 2: DAC 1600 guia de instalación (1 0)

7/26/2019 DAC 1600 guia de instalación (1 0)

http://slidepdf.com/reader/full/dac-1600-guia-de-instalacion-1-0 2/10

Delta Application Controll er DAC-1600 (Rev 0.0) I nstall ation & Application Guide

Page 2 of 10 Document Edition 1.0

Model Numbers

The 16-Input Controller has the following product number: DAC-1600

Accessories

• TRM-768 Delta Network Terminator for MS/TP

• RPT-768 Delta Network Repeater for MS/TP

Package Contents

• Delta Application Controller (16-Input) Board, DAC-1600 (Rev 1.0)

• Stylized Enclosure for quick mounting

• Delta Application Controller (16-Input) DAC-1600 (Rev 1.0) Installation Guide

Other Relevant Documents

• RS-485 Network Installation Guide (DOC818-11)

• ORCAview Operator Guide

• ORCAview Technical Reference Manual (particularly Appendix G in the V3.22 Manual)

• Release Notes for V3.22 Firmware/Software

Important Information

The capabilities of the DAC-1600 Controller is dependent on the firmware version that is loaded. The

following is not intended to be comprehensive, but should provide a quick overview.

1. V3.22 Firmware & Software or Higher

CONTROLLER CAPABILITIES & CHARACTERISTICS

• Unlike DSC products, the DAC-1600 is only configurable as a Subnet device

• A DCU is no longer necessary (as long as one System device exists on the MS/TP network)

• Data exchange may be done in GCL programming in any DCU/DSC or Application Controller on the

MS/TP network

• Now Supported: Peer Data Exchange, Alarms, Service Port, Routing, Slave Devices, AdditionalObjects

Refer to V3.22 DAC Firmware Release Notes for further information.

Page 3: DAC 1600 guia de instalación (1 0)

7/26/2019 DAC 1600 guia de instalación (1 0)

http://slidepdf.com/reader/full/dac-1600-guia-de-instalacion-1-0 3/10

Delta Controls

Document Edition 1.0 Page 3 of 10

Product Specifications

Power Requirements

24 VAC or 24 VDC• 8VA

• Class II

Ambient Ratings

• 32º to 131º F (0º to 55º C)

• 10 to 90% RH (non-condensing)

Communication Ports

NET1 - Main LAN (BACnet MS/TP)

• Communications Speed @ 9,600 or 19,200 or 38,400 or 76,800 bps (the default)

• Maximum of 99 nodes per MS/TP segment (50 without a repeater)

NET2 - SubLAN (LINKnet)• Communications Speed @ 76,800 bps

• Maximum 4 BACstats and other LINKnet devices per controller (as per Tech. Manual, App. G)

Inputs

• 16 Universal Inputs (10 bit) c/w LED status indication

• Jumper configurable for the following input types:

! 0-5 VDC

! 0-10 VDC

! 10 K Ω Thermistor

! Dry Contact (using 10 K Ω Thermistor jumper setting)

! 4-20mA

Technology

• 16-bit Processor

• 512 KB (4 Mb) Flash Memory (Network Loadable Firmware)

• 128 KB SRAM memory (for Database)

• Database backup via non-volatile Flash memory

• Visual LED status indication of the CPU

Device Addressing

• Set via DIP switch and jumpers, or Software Setup

• DIP switch MAC Address Range: 0 to 99 per network segment

• Software Address Range: As per the BACnet standard• Supports DNA – Delta’s intuitive addressing scheme

Size (c/w Plastic Enclosure)

• 5.9” x 5.75”x 2.05” (15 cm x 14.6 cm x 5.2 cm)

Weight (c/w Plastic Enclosure)

• 0.71 lb. (324 g.) with housing

Page 4: DAC 1600 guia de instalación (1 0)

7/26/2019 DAC 1600 guia de instalación (1 0)

http://slidepdf.com/reader/full/dac-1600-guia-de-instalacion-1-0 4/10

Delta Application Controll er DAC-1600 (Rev 0.0) I nstall ation & Application Guide

Page 4 of 10 Document Edition 1.0

Board Layout

I n p u t C o n n e c t i o n s 1 - 4 I n p u t C o n n e c t i o n s 5 - 8

I n p u t C o n n e c t i o n s 9 - 1 2 I n p u t C o n n e c t i o n s 1 3 - 1 6

2 4 V A C

P o w e r I n

D e v i c e

A d d r

e s s i n g

D I P S w i t c h e s

N e t w o r k

C o n n

e c t i o n

J u m p

e r

L E D

S t a t u s

I n d

i c a t o r s M

S / T P

L A N

P o r t

2 4 V A C

P o w e r O u t

S u b L A N

P o r t

S e r v i c e P o r t

I n p u t T y p e

S e l e c t o r

B l o c k s

D A C

C o n t r o l l e r

E n g i n e

D N A J u m

p e r

Page 5: DAC 1600 guia de instalación (1 0)

7/26/2019 DAC 1600 guia de instalación (1 0)

http://slidepdf.com/reader/full/dac-1600-guia-de-instalacion-1-0 5/10

Delta Controls

Document Edition 1.0 Page 5 of 10

Indicators

LED Function Description

Power Device Power Indicator. This amber LED is lit when Control Power is

present on the device. If no Control Power

transformer is connected or the fuse (F1) is blown,

the LED will be off.

Scan CPU Scan Indicator This red LED flashes at a rate relative to the CPU

scan rate of the database within the controller.

Network RS-485 Communication Status

Indicators for NET1 and NET2.

Green LEDs flash to indicate when the device is

transmitting out the associated port, and red LEDs

flash to indicate when the device is receiving data

through the port.

Jumpers

5V 10V4-20mA 10K INPUT SIGNAL TYPE

The input type is selected by placing the jumper in the correct location on

the Input Type Selector Block. The diagram to the left shows the factory

default selection of 10 K Ω.

4-20mA ! For sensors that use a 4 to 20 mA signal.

10K ! For 10 K Ω Thermistor temperature sensors, as well as Dry

Contact binary inputs.

5V ! For sensors that use a 0 to 5 VDC signal.

10V ! For sensors that use a 0 to 10 VDC signal.

Page 6: DAC 1600 guia de instalación (1 0)

7/26/2019 DAC 1600 guia de instalación (1 0)

http://slidepdf.com/reader/full/dac-1600-guia-de-instalacion-1-0 6/10

Delta Application Controll er DAC-1600 (Rev 0.0) I nstall ation & Application Guide

Page 6 of 10 Document Edition 1.0

DNA DERIVED NETWORK ADDRESSING (DNA)

Derived Network Addressing (DNA), which works in conjunction with

the Device Type setting and refers to the ability of inheriting portions of its

address from higher-up devices on an MS/TP network, may be enabled or

disabled via jumper setting.

Enabled ! With the jumper in place, the controller automatically obtains

portions of its overall BACnet device address (as related to Area

and possibly System) from higher-up devices on the network.

This is the preferred method of addressing the controller in a

system of Delta devices.

Disabled ! With the jumper removed, the device does not obtain any

portions of its address from higher-up devices. Instead, default

numbers are assumed (for Area and System), which may be

modified via software. This method of addressing is most useful

in OEM or multi-vendor installations where Delta products do

not exist higher-up in the network architecture, or where device

address ranges are pre-assigned for the installation.

NOTE: Whether or not Derived Network Addressing is enabled, the

Addressing DIP switches are always used to set the device MAC address.

Controller Address DIP Switches

Each individual DIP switch represents a pre-defined value, which added together forms the device address.

Mounting

The 1600 Controller is designed for mounting quickly and easily in a number of locations, usually within

packaged equipment or within another enclosure (to meet code requirements). Ensure the controller itself is a

safe distance away or in some other way protected from relief valves and other water sources.

Input Wiring

Inputs on the Delta 1600 Controllers follow the same general wiring connection diagrams as other Delta products. Refer to separate documentation for additional details.

Page 7: DAC 1600 guia de instalación (1 0)

7/26/2019 DAC 1600 guia de instalación (1 0)

http://slidepdf.com/reader/full/dac-1600-guia-de-instalacion-1-0 7/10

Delta Controls

Document Edition 1.0 Page 7 of 10

Power

The 1600 Controller requires a 24 VAC (or 15 to 35 VDC) power supply. With an isolated Class II 24 VAC

transformer you need not ground one leg. Several controllers (not including DCUs or V2 products) may be

connected to the same transformer, providing the transformer is properly sized for all the controllers and line

losses without drawing too much current, and polarity is observed between controllers (in regards to Hot and

Neutral). Also, the transformer must ONLY be used to provide power to other MS/TP or LINKnet devices,

and no other auxiliary purposes.

MS/TP Network & Cabling Requirements

To ensure network stability and reliable communications, particularly at high speeds on the MS/TP network for a

number of devices, it is imperative that you adhere to the following network and cabling requirements:

Item Description

Cabling For MS/TP and LINKnet networks it is recommended that you use network cabling that

matches the following specifications:

• Balanced 100 to 120 ohm nominal impedance Twisted Shielded Pair (TSP) Cable

• Nominal capacitance of 16 PF/FT or lower

• Nominal velocity of propagation of 66% or higher

Topology Ensure the MS/TP network cable is installed as adaisy-chain from one device to the next.

Max. Nodes The maximum number of devices per MS/TP network without any repeaters is 50 .

Termination

Boards

A termination board (TRM-768) must be installed at each end of each MS/TP network segment

– or two per MS/TP or LINKnet network. Ensure you do not overlook this in laying out your

network architecture and ordering product.

Repeater A repeater (RPT-768) is not necessary unless more than 50 nodes will be installed on a network

or you need to extend the MS/TP network beyond 4000 ft (1220 m).

For more detailed information, including wiring, refer to the RS-485 Network Installation Guide (DOC818-11).

MS/TP Network Topology

With V3.21 firmware MS/TP devices are all configured as Subnet devices, and you also need at least one

DCU. With V3.22 firmware DSC-606 Controllers are much more capable as peer-to-peer controllers on an

MS/TP network with one System device (DCU or otherwise).

Page 8: DAC 1600 guia de instalación (1 0)

7/26/2019 DAC 1600 guia de instalación (1 0)

http://slidepdf.com/reader/full/dac-1600-guia-de-instalacion-1-0 8/10

Delta Application Controll er DAC-1600 (Rev 0.0) I nstall ation & Application Guide

Page 8 of 10 Document Edition 1.0

Communications Setup

The 1600 Controller communicates on an MS/TP network at a default speed of 76,800 bps. Refer to theORCAview Technical Reference Manual for further detail on configuring the MS/TP network or changing

baud rates, etc.

DCU/DSC

(System Device)

BACnet (MS/TP) - Level 3 Network (Subnet)

DAC

(Subnet

Device)

TRM

DAC

(Subnet

Device)

TRM

Level 4

Network

(LINKnet)

! 16x16 Controller

! 12x12 Controller

! 12x8 Controller

! 6x6 Controller ! Room Controller

! VAV/VVT Controller

! Lighting Controller

! BACstat I

! BACstat II

(with or without I/O)

! Input Field Modules

Products

! DSC-1616EX [DCU]

! DSC-1616(H/E)

! DSC-1212(H/E)

! DSC-1280(H/E)

! DSC-T305

Products RS-485

NET1 NET2 NET1 NET2

RS-232

! BACstat I

! BACstat II

(with No I/O)! BACstat II

(with muxed I/O)

! I/O Field Modules

Products

TRM

Level 4

Network

(LINKnet)

DFMDFM

TRM

LINKnet Notes:

1. Ensure you use the recommended balanced cable.2. Ensure the cable is installed as a daisy-chain from one device to the

next. (1000' or 300m maximum).

3. Ensure you install MS/TP terminator boards when you have more than 1 or 2 devices.

4. Depending on the controller, up to 12 devices are supported on a LINKnet network, with limitations on how many of these may have I/O. (Refer to

the Technical Reference Manual.)

ORCAview

OWS

DFM

Ethernet Note:

If the DCU or DSC has Ethernet capability, it may exist on anEthernet network with other controllers in the same building, on whichthe ORCAview OWS could reside as well (instead of PTP).PTP

MS/TP Notes:

1. Ensure you use the recommended balanced cable.

2. Ensure the cable is installed as a daisy-chain from one device to the next (4,000' or 1220m maximum).3. Ensure you install an MS/TP terminator board (TRM-768) on each end of each MS/TP network.4. The maximum nodes per MS/TP network is 50 without a repeater, or up to 99 with at least one repeater (RPT-768).

Network Diagram (with V3.22 Firmware)

Page 9: DAC 1600 guia de instalación (1 0)

7/26/2019 DAC 1600 guia de instalación (1 0)

http://slidepdf.com/reader/full/dac-1600-guia-de-instalacion-1-0 9/10

Delta Controls

Document Edition 1.0 Page 9 of 10

Cautions and Warnings

WARNING

The 1600 Controller is an Electro-statically sensitive device. Proper ESD protection (ground

strap) should be used when installing this product so that damage to the product does not occur.

Compliance Declarations

FCC Compliance Information

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to

part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful

interference when the equipment is operated in a commercial environment. This equipment generates, uses,

and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,

may cause harmful interference to radio communications. Operation of this equipment in a residential area is

likely to cause harmful interference in which case the user will be required to correct the interference at hisown expense.

Industry Canada Compliance Statement

ICES-003 This Class A digital apparatus meets all requirements of the Canadian Interference-CausingEquipment Regulations

Cet appareil numérique de la Classe A Respecte toutes les exigences du Règlement sur le matérial

brouiller du Canada.

UL Compliance Information

This product conforms to the following UL requirements:

• UL916: Energy Management Equipment

Page 10: DAC 1600 guia de instalación (1 0)

7/26/2019 DAC 1600 guia de instalación (1 0)

http://slidepdf.com/reader/full/dac-1600-guia-de-instalacion-1-0 10/10

Delta Application Controll er DAC-1600 (Rev 0.0) I nstall ation & Application Guide

Page 10 of 10 Document Edition 1.0

CE - DECLARATION OF CONFORMITY

according to ISO/IEC Guide 22 and EN 45014

Manufacturer's Name: Delta Controls

Manufacturer's Address: 17850 56th

Avenue

Surrey, British ColumbiaCanada

V3S 1C7

declares that the product (s):

Product Name: 16-Input Controllers

Model Numbers: DAC-1600

Product Options: All

conforms to the following Product Specifications:

EMC:

EN 55022:1998 Radiated and Conducted Emissions Class A

EN 50082-1:1997 Generic Immunity Standard

EN 61000-3-2:1999 Harmonic Current Emissions Class A

EN 61000-3-3:1998 Voltage Fluctuations and Flicker

EN 61000-4-2:1995 + A1:1998 ESD Immunity Level B

EN 61000-4-3:1996 RF Electromagnetic Field Immunity Level A

ENV 50204:1995 RF Electromagnetic Field Immunity (Keyed) Level A

EN 61000-4-4:1995 EFT/Burst Immunity Level B

EN 61000-4-5:1995 Surge Immunity Level B

EN 61000-4-6:1996 Conducted RF Disturbances Immunity Level A

EN 61000-4-11:1994 Voltage Dips / Interruptions Level B/C

Supplementary Information:

The product(s) herewith comply with the requirements of the EMC Directive

89/336/EEC. The product(s) were tested in a typical configuration.

Lee DicksonQuality Assurance Manager