Medium Voltage Distribution
WIup to 52 kV
Gas-Insulated Switchgear with Vacuum Circuit-Breaker 1, 2 or 3-phase
System configuration
7/30/2019 GIS Sieens Wi en 100709
2/52
Conditions of Delivery
The General Conditions of Delivery as amended shall apply.
Illustrations
The illustrations are not binding
7/30/2019 GIS Sieens Wi en 100709
3/523WI EN
WI Contents
Overview ..............................................................................................................4
Features .........................................................................................................4
Product description ............................................................................................ 5
Technical description ......................................................................................5
Components of the switching unit ..................................................................6
Modular design ............................................................................................... 7
Single busbar WIA up to 36 kV .....................................................................7
Double busbar WIB up to 36 kV ...................................................................7
Single busbar WIA 52 kV, 250 kV BIL ..........................................................8
Double busbar WIB 52 kV, 250 kV BILL ....................................................... 8
Operator interfaces ........................................................................................9
Switchgear panels ........................................................................................ 10
Current/voltage transformers ....................................................................... 11
Busbar modules ...........................................................................................13
Modules ........................................................................................................15
Interlocks ......................................................................................................16
Gas compartment monitoring WIA, WIB ...................................................... 17
Gas-filled compartments of the WIA/ WIB ................................................... 18
Standards, regulations, provisions and standards.......................................19
Type designation ..........................................................................................20
Applied norms .............................................................................................. 21
Selection tables ................................................................................................22
WIA/WIB 12 kV ............................................................................................22 WIA/WIB 17 kV ............................................................................................24
WIA/WIB 24 kV ............................................................................................26
WIA/WIB 36 kV ............................................................................................28
WIA/WIB 38 kV ............................................................................................30
WIA/WIB 40.5 up to 52 kV ........................................................................... 32
WIA/WIB 1 and 2-pole, for stationary railway traction power supply 50/60 hz......34
Range of products ............................................................................................ 36
Single busbar panels WIA ............................................................................ 36
Double busar panels WIB ............................................................................37
Disconnector panel ......................................................................................38
Bus section coupler / riser panel ..................................................................38
Bus section coupler, Bus coupler, metering panel ....................................... 39
Cable connections ............................................................................................ 40
Ecological considerations ...............................................................................43
Design data .......................................................................................................44
Space requirements - dimensions and weights ...........................................44
Busbar connection with fully insulated conductor bars ................................48
Shipping instructions ....................................................................................... 50
Delievery, packaging .................................................................................... 50
7/30/2019 GIS Sieens Wi en 100709
4/524 WI EN
WI
FeaturesThe gas-insulated and metal-enclosed switchgear WI has been designed
for operation in power plants, transformer substations and industrialnetworks.
The WI switchgear with vacuum circuit-breaker features maximum
availability, optimum operator safety and clear design using SF6gas as
insulating medium. The switchgear units are insensitive to environmental
inuences,suchashumidity,dustandaggressivegases,andoffer
complete operator safety. Their clear design facilitates operation.
Essential features
Parts under medium voltage in SF6atmosphere
insensitive to air humidity, air pollution and foreign matter
High degree of operator safety
complete metal enclosure for all system components under mediumvoltage
Compact and clear design
No mechanically moved parts in the busbar section
No problems with SF6decomposition products
currents are switched in the vacuum interrupter chamber
Inert insulating gas SF6protectstheswitchgearagainstre
Three-pole enclosure of the functional compartments negligible sheath currents
small number of static and dynamic seals
few gas compartments, pressure relief devices and gas monitoring
devices
easy access
moderate pressure increase in case of internal arcs
straightforward kinematics between drive and circuit-breaker or
three-position switch
Steel used as enclosure material
high pressure proofness
good screening effect against X rays
Optimum security of operation
complete interlocking system
separate actuators for isolation and earthing
automatic circuit-breaker ON or OFF operation in case of earthing at
the outgoing feeder
High capacity current and voltage transformer
Delivery of prefabricated switchgear panels to the construction site Fully shrouded terminals
pluggable, fully insulated cable end boxes
Switchgear extension possible on both sides
from single to double busbar system.
Overview
Single busbar WIA up to 36 kV
7/30/2019 GIS Sieens Wi en 100709
5/525WI EN
WI Product description
Technical description
WIpanelsaresuitableforconguringsingleordoublebusbarswitchgearin
conjunction with indoor installation.
WI switchgear units are completely metal-enclosed. The busbar
compartmentwhichaccommodatesxedpartsonlyissegregatedgas-tight
fromtheange-mountedswitchingunit.Theswitchingunitcomprisesthe
three-position switch with isolating and earthing functions and the vacuum
circuitbreaker; in case of double busbar systems, there are two three-
position switches with isolating and earthing functions and the vacuumcircuit-breaker.
The busbar compartment and the switching unit feature three-pole
enclosure. Single-pole enclosure is provided in the area of the toroidalcore
current transformers which are located in an easily accessible position
outside of the SF6atmosphere. The compact design results in a very clear
switchgear arrangement with low space requirement; it has the advantagethat a switching unit can be mounted or removed very quickly without the
busbar requiring isolation from the power supply.
The panels are equipped with a low-voltage cabinet for the required
measuring and protection relays or the terminal strips. The high
performance of the instrument transformers installed means that not onlyelectronic but also conventional protection relays can be deployed.
Thanks to its design, this panel series permits straightforward extension of
an existing switchgear on both sides, and extension from single to double
busbar models.
Gas-insulated double busbar switchgear WIBRated voltage up to 36 kV; rated peak withstand
current up to 100 kA; rated current up to 2500 A
7/30/2019 GIS Sieens Wi en 100709
6/526 WI EN
WI Product description (contd.)
Components of the switching unit
The circuit-breaker in question is a vacuum circuit-breaker. The switching
unit has been equipped, for its isolating and earthing functions, with athree-position switch featuring the positions:
Earthing
The metal-enclosed WI series switchgear is equipped with a separate
earthing line running along the length of the switchgear.
Wiring
Wiringiseffectedwithexiblecables(HO7V-K)inthetechnicallyrequiredcross-sections.
Corrosion protection
If desired, the indoor panels WIA and WIB can be provided optionally with
enhanced corrosion protection. To ensure optimum switchgear protection,
the environmental installation conditions, such as wind-borne sand,
aggressivedust(tobedenedassaltdust,cokedust,cementdustetc.),
vermin(termites),increasedhumiditylevels,aggressiveatmosphere(typeofchemicalsandtheirconcentrationtobedened)mustbespecied.
Installation locations
The switchgear has been designed for installation in closed electrical
operating facilities.
Connection of cables and bars
The cables are connected by means of metal-enclosed connectors.
Switchgear units equipped with multiple connection tanks enable
connectionofuptove300mm2 cables or two 1250 mm2 cables perphase, depending on the insulation rating.
Alternatively, fully insulated busbar systems or SF6-insulated conductor
bars can be used.
Low voltage cabinet
The secondary devices for protection relay, control, measurement, billing
metering and other systems are installed in the low-voltage cabinet. Thelow-voltage cabinet is separated systematically from the primary part, is
shock-proof and arc-resistant. It is an independent, closed low-voltage
compartment with mechanical and electrical interfaces to the vertical
section(screw-fastenedplug-and-socketconnector).
The clear separation between the rack and the low-voltage cabinet is a
particularadvantageforthecompanyoperatingtheswitchgear.Retrotting
spare panels and conversion or replacement of complete low-voltage
cabinets(e.g.duetoprocesschanges)atalaterdateisalso
straightforward. The panel remains completely enclosed even if thelow-voltage cabinet is not attached.
Optional inspection ports can be integrated in the torsion-resistant door ofthe low-voltage cabinet, the door also being able to accommodate
measuring instruments, control elements and protection relays.
Disconnector ON(CLOSE)
Disconnector earthing switch OFF(TRIP)
Earthing switch ON(CLOSE)
7/30/2019 GIS Sieens Wi en 100709
7/527WI EN
WI Product description (contd.)
Modular design
Single busbar WIA up to 36 kVTank with vacuum circuit-breaker and disconnector / earthing switch
Drive with control panel and pressure gauge for gas monitoring
Tank with busbar
Supporting structure with cable connection area
Low voltage cabinet
Double busbar WIB up to 36 kV
Tank with vacuum circuit-breaker and disconnector / earthing switch
Drive with control panel and pressure gauge for gas monitoring
Tank with busbar 1
Tank with busbar 2
Supporting structure with cable connection area
Low voltage cabinet
A
B
C
D
E
A
B
C2
C1
D
E
A
B
D
E
C1
C2
A
B
E
C
D
7/30/2019 GIS Sieens Wi en 100709
8/528 WI EN
WI Product description (contd.)
Single busbar WIA 52 kV, 250 kV BIL
Tank with vacuum circuit-breaker and disconnector / earthing switch
Drive with control panel and pressure gauge for gas monitoring
Tank with busbar
Supporting structure with cable connection area
Low voltage cabinet
Double busbar WIB 52 kV, 250 kV BILL
Tank with vacuum circuit-breaker and disconnector / earthing switch
Drive with control panel and pressure gauge for gas monitoring
Tank with busbar 1
Tank with busbar 2
Supporting structure with cable connection area
Low voltage cabinet
A
B
C
D
E
A
B
C2
C1
D
E
A
B
E
C
D
A
B
D
E
C1
C2
7/30/2019 GIS Sieens Wi en 100709
9/529WI EN
WI Product description (contd.)
i , l I
1
21
2
3
18
4
5
16
17
6
SS2
7
8
9
10
11
12
SS1
13
14
15
Operator interface, double busbar WIB
i , i l I
1
2
3
18
4
5
16
17
9
10
11
12
SS1
13
14
Operator interface, single busbar WIA
Operator interfaces for WIA (single busbar)
and WIB (double busbar)1 Button circuit-breaker ON
2 Button circuit-breaker OFF
3 Opening for charging the energy- storing device by means of a slide
4 PositionindicatorEnergy-storingdevice(charged/released)5 Circuit-breaker position indicator
6 Switchpositionindicator,disconnector(SS2)
7 Openingforoperationofthedisconnector(SS2)
8 Interrogating lever, disconnector
9 Earthing switch position indicator
10 Opening for operation of the earthing switch11 Interrogating lever earthing switch
12 Switchpositionindicator,disconnector(SS1)
13 Openingforoperationofthedisconnector(SS1)
14 Interrogating lever, disconnector15 Mechanical lock-out with cylinder lock
16 Rating plate17 Insulating gas monitoring device
18 Operations counter
SS1:busbar1(correspondstothelowerbusbartank)
SS2:busbar2(correspondstotheupperbusbartank)
7/30/2019 GIS Sieens Wi en 100709
10/5210 WI EN
WI Product description (contd.)
6
8
7
5
4
2
1
3
8
7
9 10
10
6
5
4
2
1
3
8
1
3
2
7
6
5
4
10
10
9
8
7
6
5
4
1
2
3
Switchgear panels
Single busbarSwitchgear panel WIA up to 36 kV
Double busbar
Switchgear panel WIB up to 36 kV
1 Drive mechanism
2 Vacuum circuit-breaker
3 Low voltage cabinet
4 Cable end boxes
5 Current transformers
6 Busbar
7 Disconnector /earthing switch8 Pressure relief device
1 Drive mechanism
2 Vacuum circuit-breaker
3 Low voltage cabinet
4 Cable end boxes
5 Current transformers
6 Busbar I
7 Disconnector /earthing switch SSI8 Busbar II
9 Disconnector /earthing switch SSII
10 Pressure relief device
Switchgear panel WIA up to 52 kV Switchgear panel WIB up to 52 kV
1 Drive mechanism
2 Vacuum circuit-breaker
3 Low voltage cabinet4 Cable end boxes
5 Current transformers
6 Busbar
7 Disconnector /earthing switch
8 Pressure relief device
1 Drive mechanism
2 Vacuum circuit-breaker
3 Low voltage cabinet
4 Cable end boxes
5 Current transformers
6 Busbar I
7 Disconnector /earthing switch SSI
8 Busbar II
9 Disconnector /earthing switch SSII
10 Pressure relief device
7/30/2019 GIS Sieens Wi en 100709
11/5211WI EN
WI Product description (contd.)
Current/voltage transformers
Current transformersThe current transformers are designed as toroidal-core transformers and
are put onto the cable outgoing feeder areas with single-pole enclosure.
The current transformers in line with the busbar consist of identical units.
There, they are slipped onto the busbar areas which also feature singlepole
enclosure. The capacity of the current transformers is designed in such a
way that supply of conventional protective devices is also possible.
Upto3transformers(3cores)canbeaccommodatedperphaseand
outgoing feeder. The transformers can also be exchanged subsequently.
Threecurrenttransformers(3cores)perphasecanalsobeinstalledinline
with the busbar, in order to measure its currents.
A special current transformer arrangement is the bus coupler panel withinone panel width. In the double busbar top attachment tank, one core of
max.80mmheightwithanIDof135mmandanODof195mmcanbe
installed for each phase. The low voltage is led out via a max. 7-pole line
which is SF6proof.
Dimensions
Outgoing feeder:
Transformer ID 185 mm
Transformer OD 275 mm
Max. stacking height 160 mm
In line with busbar:
Minimum ID 185 mm
Maximum OD 250 mm
Maximum stacking height for all
cores incl. intermediate layer225 mm
Measurement Protection
/dyn
(kA) 100
Ith(3sec) (kA) 40
Class 0.5 M 5 10 P 40 10 P 10
Corerating(VA) (VA) up to 15 up to 5 up to 30
Primary rated current (A) 150 up to 2500
Secondary rated current (A) 1 or 5
Current transformer in line
with the busbar
7/30/2019 GIS Sieens Wi en 100709
12/5212 WI EN
WI Product description (contd.)
on the busbar
A separate metering panel with a set of inductive voltage transformers isprovided to this effect. Taking account of the high priority of the busbar, a
disconnector enables isolation of the transformer section. Both
disconnector and transformer are located in separate compartments.
Thus, any damage which might occur in the vicinity of the transformer
does not affect the isolating area or the busbar.
Performance characteristic
1
2
Ratings: up to 50 VA
Class: 0.5
1 Multi-tank
2 Test cable connector
Voltage transformer in outgoing feeder cable
(connectionviamulti-tank)
Voltage transformer on busbar
Voltage transformer
The conventional solution for the inductive voltage transformer is a
separate single-phase metalenclosed module which can be connected viacable connectors almost anywhere in the busbar area and on the outgoing
feeder cable, and thus arranged in practically any location as required.
in the outgoing feeder areaAnother design comprises metal-enclosed inductive voltage transformers
directlyangemountedtotheoutgoingfeederblock,withtheisolating/
earthing device mounted upstream. An externally operated isolating
feature prevents the voltage transformer from being endangered/ put at
risk during DC tests on the cable.
7/30/2019 GIS Sieens Wi en 100709
13/5213WI EN
WI Product description (contd.)
Busbar modules Gas tank incl. installation parts
Busbar Coverattachmentonmountingangewithorwithoutpressurerelief.
Allvebusbarcompartmentsrequireonepressurereliefdevice.Ifitisnot
possible to mount the device to the ends of the busbar tanks, e.g. if a tankfor voltage transformer connection or a busbar earthing switch is located
on the busbar end, or if the switchgear consists of over 10 panels, every
fthpanelisequippedwithapressurereliefdeviceonthemountingange
Coverattachmentonthestopangeoftheleft-handandright-handend
panel, with or without pressure relief, to connect metalenclosed voltage
transformers with cable connection to the front.
Gas lines incl. pressure gauges; preferably attached to the end panel.
(Onlyonceforeachgascompartment.)
Desiccantfor4busbartankseach,orforeachgascompartment.(Cannot
bemountedonswitchgearpanelsequippedwithpressurereliefdevice.) Compensation element for busbar tanks. Required after 20 single busbarpanels, and after 10 double busbar panels.
Disconnector for bus sectionalizer
Earthing switch for bus sectionalizer to the left and right of the
disconnector
7/30/2019 GIS Sieens Wi en 100709
14/5214 WI EN
WI Product description (contd.)
Accessories (for overall system)
SF6gas for on-site assembly of the busbar sections
Special paint Corrosion protection in case of extreme environmental conditions
Panellabelingaccordingtospecication
Operating elements, operating crank for vacuum circuit-breaker,
disconnector, earthing switch; for the busbar sections movable
segregating cover.
Star handle spanner
Hex. spanner
Castors
Transportcoverforthebusbartanks(canbereturned)
Jack rings
Integrated Voltage Detection System IVIS
Earthing and short-circuit device, 3-phase incl. operating rod Cable dummy plug
Cable test socket on cable connector for cable measurement
Blanking caps for live cable connectors which have been withdrawn
always required
optional
Auxiliary equipment for transport only
Possible arrangement of the castors
Castors to be used
for movements in longitudinal direction
for transverse movements
1
2
3
12
3
7/30/2019 GIS Sieens Wi en 100709
15/5215WI EN
WI Product description (contd.)
ModulesThe modules and attachments shown on this page apply to
outgoing feeder panels
incoming feeder panels
panels with circuit-breaker in case of coupler panels and bus
sectionalizers.
Switching device module Gas tank incl. pressure relief device, gas lines and pressure gauge
Switching devices with three-position switch and vacuum circuit-breaker,
desiccant
Drive section module
Drive casing with drive mechanisms incl. interlocks
Attachment of drive casing on switching device module incl. connecting
parts
Attachments for the vacuum circuit-breaker Motor drive mechanism to charge the energy-storing device
Auxiliary switch, 8, 12 or 16 contacts; 8 contact elements are required for
thebasiccircuitry(material:silver[normal],gold,silver-palladium)
Passingcontactforpulsecontacttimestretching(contactsnormalor
gold-plated)
Pushswitchactuatedbyenergystoringdevice.(Pushswitchesforbasiccircuitryincludedinbasicdesign)
Pushswitch,actuatedbyON-OFFpushbutton.(Thebasicdesign
includes1pushswitchforeach)
Shunt closing release, 1 ea.
Shunt opening release, 1 or 2 ea. with or without auxiliary spring energy
store Secondary release, 1 or 2 ea., or in case of design without undervoltage
release: 3 ea.
Undervoltage release, with or without time delay
Blocking coil on ON pushbutton. Always required on coupler switch in
case of bus section coupler and bus coupler, consisting of 2 panels(switchgearpanel+busriserpanel)
Blocking coil on OFF pushbutton. Always required on coupler switch in
caseofbussectioncouplerandbuscoupler,consistingof1or2panel(s)
(switchgearpanel+busriserpanel)
Mechanicallock-outwithlock(forvacuumcircuit-breakerandthree-
positionswitch) Counter
Attachments for three-position switch Motor-drive mechanism. In case of single busbar: 1 motor-drive
mechanism each for isolating and earthing movements. In case of doublebusbar: 1 motor-drive mechanism for the isolating movement of busbar 1,
busbar2andearthingmovementofbusbars1+2.Thevacuum
circuitbreaker s ON button features a mechanical lock-out.
An auxiliary switch, 2-20 contact elements each, for disconnecting and
earthingmovement.(Material:silver(normal),gold,silverpalladium)
Interlocking solenoid. Single busbar: only in circuit-breaker panel ofcoupler and in bus riser panel of bus sectionalizer. Generally required in
case of double busbar. If the interlocking solenoids are not installed in
caseofremotecontrol(motor-drivemechanism)ofthethree-position
switch, the local actuation is not locked. In this case, mechanical lock-
outs(locks)arerequiredontheONbuttonofthevacuumircuit-breakerand on the threeposition switch.
always required
optional
7/30/2019 GIS Sieens Wi en 100709
16/5216 WI EN
WI Product description (contd.)
InterlocksActuation of the three-position switch and the continuous mechanical
interlock between circuitbreaker and three-position switch are designed insuch a way that the operator can proceed as usual. This means separate,
completely interlocked actuation for the switching procedures Establishing
isolating distance and Earthing. For the earthing procedure, which is onlypossible with the three-position switch in isolated position, the circuit-breaker
switched off and the circuit-breaker energy-storing device pre-charged, the
circuitbreaker is connected positively after the contact blades have
beeninserted into the earthing contacts, and protected against immediate
mechanical or electrical switching OFF. Vice versa, on de-earthing, the
circuit-breakerisrstswitchedoffpositivelybeforetheisolatingdistancetothe earthing contacts established. The interlocks ensure that each
switching operation is always performed completely. Thus, once the
switching operation has commenced, the motion cannot be reversed, if
applicable, and the operating lever cannot be removed before it reaches its
end position.
The description only refers to the single busbar. In the case of double
busbars, some of the internal interlocking functions of the panel, as well as
all inter-panel interlocking functions are performed by electro-mechanical
interlocks(blockingcoil).
The following interlocking functions are provided:
Disconnector does not switch ON while the circuit-breaker or the earthing
switch are ON
None of the disconnectors switches OFF while the circuit-breaker or the
earthing switch are ON Circuit-breaker only switches ON with the disconnector in its end position
No earthing with disconnector engaged
No earthing with circuit-breaker ON No earthing without circuit-breaker being in ready-to-operate condition
Automatic connection of circuitbreaker during earthingAutomatic disconnection of circuit- breaker during de-earthing
The following has been ensured:
The operating crank cannot be removed from the disconnector or
earthing switch before it has reached its end positions completely
The circuit-breaker cannot be actuated while a switching operation is
being performed on the disconnector or earthing switch The circuit-breaker cannot be switched off with the three-position switch
in earthing position
All interlocks act partly mechanically and partly electrically
An operating crank can only be inserted on the disconnector or earthing
switch once the insertion opening has been released via a manualinterrogation system.
All interlocks also effective when the three-position switch is
motor-actuated.
7/30/2019 GIS Sieens Wi en 100709
17/5217WI EN
WI Product description (contd.)
Gas compartment monitoring
Single busbar WIA with bus section coupler
Gas compartment monitoring
Double busbar WIB with bus coupler
Gas connector socket (disposal valve)
Pressure gauge
Gas-tight electricalbushing
Check valve
1
2
1 Gas-filled busbar compartments
2 Gas-filled circuit-br eaker compartments
Gas connector socket (disposal valve)
Pressure gauge
Gas-tight electricalbushing
Double check valve
1
2
3
1 Gas-filled busbar2 compartments
2 Gas-filled busbar1 compartments
3 Gas-filled circuit-br eaker compartments
7/30/2019 GIS Sieens Wi en 100709
18/5218 WI EN
WI Product description (contd.)
Gas-lled compartments of the WIA/B series panels
WIA up to 40.5 kV,
single busbar
WIB up to 40.5 kV,
double busbar
WIA up to 52 kV,
single busbar
WIB up to 52 kV,
double busbar
WIA up to 36 kV,
single busbar
WIB up to 36 kV,
double busbar
Gas-lledcircuit-breaker compartment
busbar 1 compartment
busbar 2 compartment
7/30/2019 GIS Sieens Wi en 100709
19/5219WI EN
WI
WI series switchgear units are
metal enclosed
SF6 insulated prefabricated and type-tested
tested for internal faults
Ambient and operating conditionsWI switchgear units are to be operated under normal operating conditions
accordingtothespecicationsEN60694ortheIECpublication60694
(new:IEC62271-1).
Operation under conditions other than these is only admissible upon
consultation with and with the consent of the manufacturer.
Degrees of protection against foreign
objects and accidental contact
Other ambient temperatures
Therated(normal)currentsIN
speciedintheselectiontablesrefertoa
maximum ambient switchgear temperature of 40 C.In case of different maximum ambient temperatures T of the switchgear,
between+25Cand+55C,theappropriatenormalcurrentINT
can be
determined from the following formula:
1) Optional: minus 25 indoors2) Optional up to 55 C in case of reduction of normal currents
3) Optional up to 40 C in case of reduction of normal currents4) Higher installation altitudes possible on request
Main electric circuits IP 65
Drives IP 2X, IP 5X1)
Low-voltage cabinets and cable connectioncompartments(operatorssidewithcable
compartmentcoverandsidepanels)
IP 3X, IP 5X1)
1) Optional
105 - T
65At 25 0C T < 40 0C INT = IN
At 40 0C < T 55 0C INT = IN105 - T
650.7
Ambient conditions
Temperature class "Minus 25 indoors 1)
Min./max. ambient temperature C -51) / 40 2)
Averagevalueover24hours(max.) C 353)
Maximum installation altitude above sea
level
m 1000 4)
Insulating gas
Type Sulphurhexauoride(SF6)
Design pressurepre
at 20 C MPa 0.03 - 0.05
StandardsRegulations, provisions and standards
7/30/2019 GIS Sieens Wi en 100709
20/5220 WI EN
WI
Type designationThe type designation of the type-tested, prefabricated panels contains information about their design, rated voltage, insulation
level, panel width and panel height.
Example:
Prefabricated, type-tested WI
series panel with single busbar, for indoor installation, version A
Rated peak withstand current 100 kA
Rated voltage 12 kV; insulation level acc. to list 2
Panel width: 600 mm, panel height: 2100 mm
Type designation: WI A 10 / 12-2 / 621
Type designation
Series
Version
WI . . .
A
/ . . - .
Explanation
Fully insulated (SF6) switchgear panels, primarily for distribution
substations, for very stringent requirements
Single busbar, indoorsB
8
10
Double busbar, indoors
Rated peak withstand current 80
100
kA
kA
Rated voltage
Dimension code WI A
/ 12-2
/ 17-2
/ 24-2
/ 36-2
/ 38-2
/ 40.5-2
/ 52-2
up to 40.5 kV/ 621
upper rated voltage 12
17.5
kV
kV
24
36
kV
kV
Panel width
38
40.5
kV
kV
52
600
kV
mm Panel height 2100 mm
WI
WI
A
B
WI B
up to 52
up to 40.5
up to 52
kV
kV
/ 626
/ 627
kV/ 633
600
600
mm
mm
600 mm
2664
2750
3314
mm
mm
mm
StandardsRegulations, provisions and standards(contd.)
7/30/2019 GIS Sieens Wi en 100709
21/5221WI EN
WI
Designation IEC standard IEC classes EN standard
Switchgear IEC 62271-200
IEC 60694
(new IEC 62271-1)
Category for operating
availability:
LSC 2A
Partition class
(compartmentalization class): PM
EN 62271-200
EN 60694
(new EN 62271-1)
Behaviour in case of internal faults IEC 60298 EN 60298
Circuit-breaker IEC 62271-100 M2, E1, C1 EN 62271-100
Earthing switch IEC 62271-102 E2 EN 62271-102
Three position disconnector IEC 62271-102 M1 EN 62271-102
Current transformers IEC 60044-1 EN 60044-1Inductive voltage transformers IEC 60044-2 EN 60044-2
Voltage detection systems IEC 61243-5
Protection against accidental contact,foreign objects and water
IEC 60529 EN 60529
Erection HD 637 S1
Operation of electrical equipment EN 50110
Applied normsWI switchgear units meet the following standards and regulations:
StandardsRegulations, provisions and standards(contd.)
7/30/2019 GIS Sieens Wi en 100709
22/5222 WI EN
WI
Type
WIA
Panelwidth
8/12-2/621
mm
Rated insulation level
Ratedvoltage
Ratedlightningimpulse
withstandvoltage
kV kV
Ratedpowerfrequency
withstandvoltage
Ratingsofisolatingdistance
kV kV/kV
Designpressure
Pr
at20
0C
5)
Ratedfrequency
bar
0.8
Hz
Rated(normal)current3)
Ratedpeakwithstandcurrent
equaltoratedshort-circuit
makingcurrent
A
630
kA
80
Ratedshort-timecurrent
1s 3s
kA
31.5
kA
20
Ratedshort-circuitbreaking
current
PercentagevalueoftheDC
component
kA
31.5
%
WIA
WIA
WIA
WIA
8/12-2/621
8/12-2/621 600
8/12-2/621
8/12-2/621
WIB
WIB
WIB
WIB
8/12-2/627
8/12-2/627
8/12-2/627
8/12-2/627
600
12 75 28 85/32
12 75 28 85/32
0.8
0.8 50/60
1.3
1.3
1250
1600
80
80
2000
25001)
80
80
0.8
0.8
0.8
1.3
50/60
630
1250
80
80
1600
2000
80
80
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5 38
31.5
31.5
31.5
31.5
20
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
38
WIBWIA
WIA
WIA
8/12-2/62710/12-2/621
60010/12-2/621
10/12-2/621
WIA
WIB
WIB
WIB
10/12-2/621
10/12-2/627
60010/12-2/627
10/12-2/627
12 75 28 85/32
12 75 28 85/32
WIB 10/12-2/627
1.30.8
50/600.8
1.3
25002)
125080100
1600
2000
100
100
1.3
0.8
50/600.8
1.3
25001)
1250
100
100
1600
2000
100
100
31.540
31.540
40
40
40
40
31.540
3840
40
40
40
40
40
40
40
40
40
40
40
3840
40
1.3 25002) 100 40 40 40
Selection tables
WIA/WIB 12 kV
LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O
1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentstted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressure0.3baratallingpressureof0.8bar;0.7baratallingpressureof1.3bar
7/30/2019 GIS Sieens Wi en 100709
23/5223WI EN
WI Selection tables (contd.)
Rated operating
sequence
O-3min-CO-3min-CO
O-0.3s-CO-3min-CO
CO-15s-CO
O-0.3s-CO-15s-CO
Cablebreakingcurrent
A
Smallindirectcurrents
Ratedbreakingcurrent
underout-of-phaseconditions
A kA
8
Number of operating
cycles withoutoverhaul
mecha-
nical
electrical
Operating times
with release
25 W
LS,TS,E w
ithrated(normal)current
10000
withratedshort-circuit
breakingcurrent
Openingtime
4)
ms
160 W 160 W
Command times
with release
25 W
Openingtime
4)
Closingtime
4)
ms ms
Arcduration(max.)
Off
ms ms
160 W 160 W
Off
On
On
Off
ms ms
Chargingtimeformotordrive
mechanism
Operatingtimefordisconnector
andearthingswitchwithmotordrive
mechanism,160W
s s
25 10
8
25
8
8
10
1000
1000 10000 100 45-65
10000
1000
1000 10000 100 45-65
33-50 40-70 12 50
33-50 40-70 12 50
20 20 12 18
20 20 12 18
25 10
10
10
10
25 10
10
10
10
10
10
10000
100001000
1000100 45-65
10000
100001000
1000100 45-65
33-50 40-70 12 50
33-50 40-70 12 50
20 20 12 18
20 20 12 18
7/30/2019 GIS Sieens Wi en 100709
24/5224 WI EN
WI
Type
WIA
Panelwidth
8/17-2/621
mm
Rated insulation level
Ratedvoltage
Ratedlightningimpulse
withstandvoltage
kV kV
Ratedpowerfrequency
withstandvoltage
Ratingsofisolatingdistance
kV kV/kV
Designpressure
Prat200
C5)
Ratedfrequency
bar
0.8
Hz
Rated(normal)current3)
Ratedpeakwithstandcurrent
equaltoratedshort-circuit
makingcurrent
A
630
kA
80
Ratedshort-timecurrent
1s 3s
kA
31.5
kA
20
Ratedshort-circuitbreaking
current
PercentagevalueoftheDC
component
kA
31.5
%
WIA
WIA
WIA
WIA
8/17-2/621
8/17-2/621 600
8/17-2/621
8/17-2/621
WIB
WIB
WIB
WIB
8/17-2/627
8/17-2/627
8/17-2/627
8/17-2/627
600
17.5 95 38 110/45
17.5 95 38 110/45
0.8
0.8 50/60
1.3
1.3
1250
1600
80
80
2000
25001)
80
80
0.8
0.8
0.8
1.3
50/60
630
1250
80
80
1600
2000
80
80
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5 38
31.5
31.5
31.5
31.5
20
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
38
WIB
WIA
WIA
WIA
8/17-2/627
10/17-2/621
60010/17-2/621
10/17-2/621
WIA
WIB
WIB
WIB
10/17-2/621
10/17-2/627
60010/17-2/627
10/17-2/627
17.5 95 38 110/45
17.5 95 38 110/45
WIB 10/17-2/627
1.3
0.8
50/600.8
1.3
25002)
1250
80
100
1600
2000
100
100
1.3
0.8
50/600.8
1.3
25001)
1250
100
100
1600
2000
100
100
31.5
40
31.5
40
40
40
40
40
31.5
40
3840
40
40
40
40
40
40
40
40
40
40
40
3840
40
1.3 25002) 100 40 40 40
Selection tables (contd.)
WIA/WIB 17 kV
LS = Circuit-breakerTS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O
1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentstted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressure0.3baratallingpressureof0.8bar;0.7baratallingpressureof1.3bar
7/30/2019 GIS Sieens Wi en 100709
25/5225WI EN
WI Selection tables (contd.)
Rated operating
sequence
O-3min-CO-3min-CO
O-0.3s-CO-3min-CO
CO-15s-CO
O-0.3s-CO-15s-CO
Cablebreakingcurrent
A
Smallindirectcurrents
Ratedbreakingcurrent
underout-of-phaseconditions
A kA
8
Number of operating
cycles withoutoverhaul
mech. electrical
Operating times
with release
25 W
LS,TS,
Ewithrated(normal)current
10000
withratedshort-circuit
breakingcurrent
Openingtime
4)
ms
160 W 160 W
Command times
with release
25 W
Openingtime
4)
Closingtime
4)
ms ms
Arcduration(max.)
Off
ms ms
160 W 160 W
Off
On
On
Off
ms ms
Chargingtimeformotordrive
mechanism
Operatingtimefordisconnector
andearthingswitchwithmotor-
drivemechanism,160W
s s
25 10
8
8
8
8
25
8
8
10 8
8
1000
1000 10000 100 45-65
10000
1000
1000 10000 100 45-65
33-50 40-70 14 50
33-50 40-70 14 50
20 20 12 18
20 20 12 18
25 10
8
10
10
10
25 10
10
10
10
10
10
10000
100001000
1000100 45-65
10000
100001000
1000100 45-65
33-50 40-70 14 50
33-50 40-70 14 50
20 20 12 18
20 20 12 18
7/30/2019 GIS Sieens Wi en 100709
26/5226 WI EN
WI
Type
WIA
Panelwidth
8/24-2/621
mm
Rated insulation level
Ratedvoltage
Ratedlightningimpulse
withstandvoltage
kV kV
Ratedpowerfrequency
withstandvoltage
Ratingsofisolatingdistance
kV kV/kV
Designpressure
Prat200C
5)
Ratedfrequency
bar
0.8
Hz
Rated(normal)current3)
Ratedpeakwithstandcurrent
equaltoratedshort-circuit
makingcurrent
A
630
kA
80
Ratedshort-timecurrent
1s 3s
kA
31.5
kA
20
Ratedshort-circuitbreaking
current
PercentagevalueoftheDC
component
kA
31.5
%
WIA
WIA
WIA
WIA
8/24-2/621
8/24-2/621 600
8/24-2/621
8/24-2/621
WIB
WIB
WIB
WIB
8/24-2/627
8/24-2/627
8/24-2/627
8/24-2/627
600
24 125 50 145/60
24 125 50 145/60
0.8
0.8 50/60
1.3
1.3
1250
1600
80
80
2000
25001)
80
80
0.8
0.8
0.8
1.3
50/60
630
1250
80
80
1600
2000
80
80
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5 38
31.5
31.5
31.5
31.5
20
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
38
WIB
WIA
WIA
WIA
8/24-2/627
10/24-2/621
60010/24-2/621
10/24-2/621
WIA
WIB
WIB
WIB
10/24-2/621
10/24-2/627
60010/24-2/627
10/24-2/627
24 125 50 145/60
24 125 50 145/60
WIB 10/24-2/627
1.3
0.8
50/600.8
1.3
25002)
1250
80
100
1600
2000
100
100
1.3
0.8
50/600.8
1.3
25001)
1250
100
100
1600
2000
100
100
31.5
40
31.5
40
40
40
40
40
31.5
40
3840
40
40
40
40
40
40
40
40
40
40
40
3840
40
1.3 25002) 100 40 40 40
Selection tables (contd.)
WIA/WIB 24 kV
LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O
1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentstted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressure0.3baratallingpressureof0.8bar;0.7baratallingpressureof1.3bar
7/30/2019 GIS Sieens Wi en 100709
27/5227WI EN
WI Selection tables (contd.)
Rated operatingsequence
O-3min-CO-3min-CO
O-0.3s-CO-3min-CO
CO-15s-CO
O-0.3s-CO-15s-CO
Cablebreakingcurrent
A
Smallindirectcurrents
Ratedbreakingcurrent
underout-of-phaseconditions
A kA
8
Number of operatingcycles without
overhaul
mech. electrical
Operating times
with release
25 W
LS,TS,
Ewithrated(normal)current
10000
withratedshort-circuit
breakingcurrent
Openingtime
4)
ms
160 W 160 W
Command times
with release
25 W
Openingtime
4)
Closingtime
4)
ms ms
Arcduration(max.)
Off
ms ms
160 W 160 W
Off
On
On
Off
ms ms
Chargingtimeformotordrive
mechanism
Operatingtimefordisconnector
andearthingswitchwithmotor-
drivemechanism,160W
s s
31.5 10
8
8
8
8
31.5
8
8
10 8
8
1000
1000 10000 100 45-65
10000
1000
1000 10000 100 45-65
33-50 40-70 14 50
33-50 40-70 14 50
20 20 12 18
20 20 12 18
31.5 10
8
31.5 10
-
10000
100001000
1000100 45-65
10000
100001000
1000100 45-65
33-50 40-70 14 50
33-50 40-70 14 50
20 20 12 18
20 20 12 18
7/30/2019 GIS Sieens Wi en 100709
28/5228 WI EN
WI
Type
WIA
Panelwidth
6/36-2/621
mm
Rated insulation level
Ratedvoltage
Ratedlightningimpulse
withstandvoltage
kV kV
Ratedpowerfrequency
withstandvoltage
Ratingsofisolatingdistance
kV kV/kV
Designpressure
Pr
at200C
5)
Ratedfrequency
bar
1.3
Hz
Rated(normal)current3)
Ratedpeakwithstandcurrent
equaltoratedshort-circuit
makingcurrent
A
630
kA
63
Ratedshort-timecurrent
1s 3s
kA
25
kA
20
Ratedshort-circuitbreaking
current
PercentagevalueoftheDC
component
kA
25
%
42
WIA
WIA
WIA
WIA
6/36-2/621
6/36-2/621 600
6/36-2/621
6/36-2/621
WIB
WIB
WIB
WIB
6/36-2/627
6/36-2/627
6/36-2/627
6/36-2/627
600
36 170 70 195/80
36 170 70 195/80
1.3
1.3 50
1.3
1.3
1250
1600
63
63
2000
25001)
63
63
1.3
1.3
1.3
1.3
50
630
1250
63
63
1600
2000
63
63
25
25
25
25
25
25
25
25
25
25
42
42
25
25
42
42
25
25
20
25
25
25
25
25
25
25
42
42
25
25
42
42
WIB
WIA
WIA
WIA
6/36-2/627
10/36-2/621
60010/36-2/621
10/36-2/621
WIA
WIB
WIB
WIB
10/36-2/621
10/36-2/627
60010/36-2/627
10/36-2/627
36 170 70 195/80
36 170 70 195/80
WIB 10/36-2/627
1.3
1.3
50/601.3
1.3
25002)
1250
63
100
1600
2000
100
100
1.3
1.3
50/601.3
1.3
25001)
1250
100
100
1600
2000
100
100
25
40
25
40
40
40
40
40
25
40
42
31
40
40
31
31
40
40
40
40
40
40
40
40
40
40
31
31
40
40
31
31
1.3 25002) 100 40 40 40 31
Selection tables (contd.)
WIA/WIB 36 kV
LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O
1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentstted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimum service pressure 0.7 bar
7/30/2019 GIS Sieens Wi en 100709
29/5229WI EN
WI Selection tables (contd.)
Rated operating
sequence
O-3min-CO-3min-CO
O-0.3s-CO-3min-CO
CO-15s-CO
O-0.3s-CO-15s-CO
Cablebreakingcurrent
A
Smallindirectcurrents
Ratedbreakingcurrent
underout-of-phaseconditions
A kA
6.3
Number of operating
cycles withoutoverhaul
mech. electrical
Operating times
with release
25 W
LS,TS,
Ewithrated(normal)current
10000
withratedshort-circuit
breakingcurrent
Openingtime
4)
ms
160 W 160 W
Command times
with release
25 W
Openingtime
4)
Closingtime
4)
ms ms
Arcduration(max.)
Off
ms ms
160 W 160 W
Off
On
On
Off
ms ms
Chargingtimeformotordrive
mechanism
Operatingtimefordisconnector
andearthingswitchwithmotor-
drivemechanism,160W
s s
50 10
6.3
6.3
6.3
6.3
50
6.3
6.3
10 6.3
6.3
1000
1000 10000 100 43-65
10000
1000
1000 10000 100 43-65
29-50 40-65 14 50
29-50 40-65 14 50
20 20 12 18
20 20 12 18
50 10
6.3
6.3
6.3
6.3
50 10
6.3
6.3
6.3
6.3
6.3
10000
100001000
1000100 43-65
10000
100001000
1000100 43-65
40-65 14 50
40-65 14 50
1220
20
18
12 18
7/30/2019 GIS Sieens Wi en 100709
30/5230 WI EN
WI
Type
WIA
P
anelwidth
8/38-2/621
mm
Rated insulation level
R
atedvoltage
R
atedlightningimpulse
w
ithstandvoltage
kV kV
R
atedpowerfrequency
w
ithstandvoltage
R
atingsofisolatingdistance
kV kV/kV
D
esignpressure
P
rat200C
5)
R
atedfrequency
bar
1.45
Hz
R
ated(normal)current3)
R
atedpeakwithstandcurrent
equaltoratedshort-circuit
m
akingcurrent
A
630
kA
80
R
atedshort-timecurrent
1s 3s
kA
31.5
kA
20
R
atedshort-circuitbreaking
current
P
ercentagevalueoftheDC
component
kA
31.5
%
31
WIA
WIA
WIA
WIA
8/38-2/621
8/38-2/621 600
8/38-2/621
8/38-2/621
WIB
WIB
WIB
WIB
8/38-2/627
8/38-2/627
8/38-2/627
8/38-2/627
600
38 200 80 220/90
38 200 80 220/90
1.45
1.45 50/60
1.45
1.45
1250
1600
80
80
2000
25001)
80
80
1.45
1.45
1.45
1.45
50/60
630
1250
80
80
1600
2000
80
80
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31
31
31.5
31.5
31
31
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31
31
31.5
31.5
31
31
WIB
WIA
WIA
WIA
8/38-2/627
8/40.5-2/621
6008/40.5-2/621
8/40.5-2/621
WIA
WIB
WIB
WIB
8/40.5-2/621
8/40.5-2/627
6008/40.5-2/627
8/40.5-2/627
40.5185(200)
85215/90(220/90)
40.5185(200)
85215/90(220/90)
WIB 8/40.5-2/627
1.45
1.45
501.45
1.45
25002)
1250
80
80
1600
2000
80
80
1.45
1.45
501.45
1.45
25001)
1250
80
80
1600
2000
80
80
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31
31
31.5
31.5
31
31
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31
31
31.5
31.5
31
31
1.45 25002) 80 31.5 31.5 31.5 31
Selection tables (contd.)
WIA/WIB 38 kV
LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O
1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) forpossiblelimitvaluesandcomponentstted,refertotheprojectplanningdocumentsWIno.495424) adm. tolerance range, is not a manufacturing tolerance, for the current value of a specimen, refer to the routine test report5) minimumservicepressureat20C=1.0bar(overpressure)
7/30/2019 GIS Sieens Wi en 100709
31/5231WI EN
WI Selection tables (contd.)
Rated operatingsequence
O
-3min-CO-
3min-CO
O
-0.3s-CO-
3min-CO
C
O-
15s-CO
O
-0.3s-CO-
15s-CO
C
ablebreakingcurrent
A
S
mallindirectcurrents
R
atedbreakingcurrent
underout-of-phaseconditions
A kA
Number of operatingcycles withoutoverhaul
mech. electrical
Operating times
with release
25 W
LS,TS,
E withrated(normal)current
10000
w
ithratedshort-circuit
breakingcurrent
O
peningtime
4)
ms
160 W160 W
Command times
with release
25 W
O
peningtime
4)
C
losingtime
4)
ms ms
A
rcduration(max.)
O
ff
ms ms
160 W160 W
O
ff
OnO
n
Off
ms ms
C
hargingtimeformotordrive
m
echanism
O
peratingtimefordisconnector
andearthingswitchwithmotor-
drivemechanism,
160W
s s
50 10
50
10
1000
1000 10000 100 43-65
10000
1000
1000 10000 100 43-65
40-65 14 50
40-65 14 50
20 12 18
20 12 18
50 10
50 10
10000
100001000
1000100 43-65
10000
100001000
1000100 43-65
40-65 14 50
40-65 14 50
20 12 18
20 12 18
7/30/2019 GIS Sieens Wi en 100709
32/5232 WI EN
WI Selection tables (contd.)
WIA/WIB 40.5 up to 52 kV
2 vacuum interrupter chambers per conductor
LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O
1) with cooling gas tank, panel height 3314 mm and with motor-actuated fans2) with motor-actuated fan3) possiblelimitsandcomponentstted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressureat20C:0.1baratallingpressureof1.45bar;1.8baratallingpressureof2.2bar
Type
WIA
Panelw
idth
10/40.5-2/626
mm
600
Rated insulation level
Ratedv
oltage
Ratedlightningimpulse
withstan
dvoltage
kV
40.5
kV
200
Ratedp
owerfrequency
withstan
dvoltage
Ratings
ofisolatingdistance
kV
80
kV/kV
220/90
Design
pressure
Prat20
0C
5)
Ratedfrequency
bar
1.45
Hz
50
Rated(normal)current3)
Ratedp
eakwithstandcurrent
equalto
ratedshort-circuit
making
current
A
1250
kA
100
Rateds
hort-timecurrent
1s 3s
kA
40
kA
40
Rateds
hort-circuitbreaking
current
PercentagevalueoftheDC
compon
ent
kA
40
%
26WIA
WIB
WIB
10/40.5-2/626
10/40.5-2/633
10/40.5-2/633600
WIA
WIA
8/52-2/626600
8/52-2/626
40.5 200 80220/90
52
(60)
250
(110)95
290/110
1.45
1.45
1.4550
25001) 100
1250
25002)
100
100
2.250/60
2.2
1250 82
25001) 82
40 40
40
40
40
40
40
40
4026
31.5 31.5
31.5 31.5
31.526
31.5
WIB
WIB
8/52-2/633
8/52-2/633600
52(60)
250(110)
95290/110 2.2
2.250/60
1250
25002)
82
82
31.5
31.5
31.5
31.5
31.5
31.526
7/30/2019 GIS Sieens Wi en 100709
33/5233WI EN
WI Selection tables (contd.)
Rated operatingsequence
O-3min-CO-3min-CO
O-0.3s-CO-3min-CO
CO-15
s-CO
O-0.3s-CO-15s-CO
Cableb
reakingcurrent
A
50
Smallin
directcurrents
Ratedb
reakingcurrent
underout-of-phaseconditions
A kA
Number of operatingcycles without
overhaul
mech. electrical
Operating times
with release
25 W
LS,TS,E w
ithrated(normal)current
1000010000
withratedshort-circuit
breakingcurrent
Openingtime
4)
100
ms
50-80
160 W 160 W
Command times
with release
25 W
Openingtime
4)
Closing
time
4)
ms
ms
40-65
Arcduration(max.)
Off
ms
14
ms
50
160 W 160 W
Off
On
On
Off
ms
ms
20
Chargin
gtimeformotordrive
mechan
ism
Operatingtimefordisconnector
andearthingswitchwithmotor-
drivemechanism,160
W
s
12
s
18
50
50
1000
1000
10000
100010000 100 50-80
1000
1000010000
1000
1000
100 50-80
40-65 14 50
40-65 14 50
20 12 18
20 12 18
5010000
100010000
1000
100 50-80 40-65 14 12 18
50 20
7/30/2019 GIS Sieens Wi en 100709
34/5234 WI EN
WI Selection tables (contd.)
WIA/WIB 1 and 2-POLE, for stationary railway traction power supply 50/60 Hz
with 2 vacuum interrupter chambers per conductor
LS = Circuit-breaker
TS = Three-position switch, disconnector I/O
ES = Three-position switch, earthing switch I/O
S = 1-pole
T = 2-pole
3) without cooling gas tank and heat sink4) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimum service pressure at 20 C 1.8 bar
Type
WIA
Pane
lwi
dth
6/55-S/626
mm
600
Rated insulation level
Ra
tedvo
ltage
UNM
acc.
to
EN
5012
4
Ra
tedvo
ltage
U
acc.
to
EN
6069
4
kV
27.5
kV
52
Ra
tedlig
htning
impu
lse
withs
tand
vo
ltage
Ra
tedpo
wer
frequency
withs
tand
vo
ltage
kV
250
kV
95
Ra
tingso
fiso
lating
distance
Des
ignp
ressure
Pr
be
i20
0C
5)
kV/kV
290/110
bar
2.2
Ra
tedfre
quency
Ra
ted(norma
l)curren
3)
Hz
50/60
A
1250
Ra
tedpe
akw
iths
tan
dcurren
t
equa
ltora
teds
hort-c
ircu
itma-
kingcurren
t
Ra
tedsh
ort-t
imecurren
t
1s
kA
65
kA
25
3s
Ra
tedsh
ort-c
ircu
itbrea
king
curren
t
kA kA
25
Percenta
geva
lueo
fthe
DC
compone
nt
%
26WIA
WIA
WIA
6/55-S/626
6/55-T/626
6/55-T/626600
WIA-Z 600
27.5 52 250 95
17.5 36 170 70
290/110 2.2
2000
50/601250
2000
195/110 2.2 16 2/3 1250
65 25
65
65
25
25
25
25
25
80 31.5 31.5
26
46
7/30/2019 GIS Sieens Wi en 100709
35/5235WI EN
WI Selection tables (contd.)
Rated operatingsequence
O-
3min
-CO-
3min-CO
O-
0.3s
-CO-
3min-CO
CO-
15s-CO
O-
0.3s
-CO-
15s-CO
Cablebreakingcurrent
A
50
Smallind
irectcurrents
Ratedbreakingcurrent
underou
t-of-phaseconditions
A kA
12.5
Number of operatingcycles without over -
haul
mech. electrical
Operating times
with release
25 W
LS,TS,E w
ithrated(normal)current
1000010000
withratedshort-circuit
breaking
current
Opening
time
4)
100
ms
50-80
160 W 160 W
Command time
with release
25 W
Opening
time
4)
Closingtime
4)
ms
ms
40-50
Arcduration(max.)
Off
ms
14
ms
50
160 W 160 W
Off
On
On
Off
ms
ms
20
Charging
timeformotordrive
mechanism
Operatingtimefordisconnector
andearth
ingswitchwithmotor-
drivemechanism,
160
W
s
12
s
18
50 12.5
50
1000
1000
10000
100010000 100 50-80
1000
10000 10000
1000
1000
100
40-50 14 50
25-35 40-50 6-68
12 18
20 20
20
12 18
7/30/2019 GIS Sieens Wi en 100709
36/5236 WI EN
WI Range of products
Single busbar panels
Circuit-breaker panel
With inner cone-type cable connection for
rated voltage up to 52 kV
rated short-circuit breaking current up to 40 kA
ratedbusbarandoutgoingfeeder(normal)currentsupto2500A
Disconnector panel
With inner cone-type cable connection for
rated voltage up to 52 kV
rated short-time current up to 40 kA
ratedbusbarandoutgoingfeeder(normal)currentsupto2500A
Bus section couplerfor
rated voltage up to 52 kV
rated short-circuit breaking current up to 40 kA
ratedbusbar(normal)currentsupto2500A
connection
Panel connection
or
or
or
and Busbarcurrenttransformer
Surgearrester,pluggable
Voltagetransformer,pluggable
Plug-in cablesingle,
Terminal type3
or
or
or
or Busbarwith solidinsulation
Panel
variants
Surgearrester,
pluggable
Currenttransformer
Voltagetransformer,
pluggable
Busbar attachments
attachment
Currenttransformer
Plug-in cablequadruple
Plug-in cabletriple
Plug-in cabledouble
Plug-in cablesingle
1)
1)
1)
1)if a surge arrester is used,the number of cables isreduced by one
1)
1)
Circuit-breaker panel
(Innercone-typecableconnection)
Bus section coupler
1) not possible in case of 52 kV
7/30/2019 GIS Sieens Wi en 100709
37/5237WI EN
WI Range of products (contd.)
Double busar panels
Circuit-breaker panel With inner cone-type cable connection for
rated voltage up to 52 kV
rated short-circuit breaking current up to 40 kA
ratedbusbarandoutgoingfeeder(normal)currentsupto2500A
Bus section coupler(Circuit-breakerpanelandbusriserpanel)
With inner cone-type cable connection for rated voltage up to 52 kV
rated short-circuit breaking current up to 40 kA
ratedbusbarandoutgoingfeeder(normal)currentupto2500A
Bus section couplerfor
rated voltage up to 52 kV rated short-circuit breaking current up to 40 kA
ratedbusbar(normal)currentupto2500A
Bus coupler (transverse)for
rated voltage up to 52 kV
rated short-circuit breaking current up to 40 kA
ratedbusbar(normal)currentupto2500A
Metering panelfor
rated voltage up to 36 kV
ratedbusbar(normal)currentupto2500A
Circuit-breaker panel(Innercone-typecableconnection)
or
or
or
and Busbarcurrenttransformer
Surgearrester,pluggable
Voltagetransformer,pluggable
Plug-in cablesingle,Terminal type3
or
or
or
or Busbarwith solidinsulation
variants
Surgearrester,
pluggable
Currenttransformer
Busbar attachments
Panel connectionattachment
Plug-in cablequadruple
Plug-in cabletriple
Plug-in cabledouble
Plug-in cablesingle
1)
1)
1)
1) if a surge arrester is used,the number of cables isreduced by one
Voltagetransformer,
pluggable
1)
1)
SS2SS1
1) not possible in case of 52 kV
7/30/2019 GIS Sieens Wi en 100709
38/5238 WI EN
WI Range of products (contd.)
1) not possible in case of 52 kV
SS2
SS1
Panelconnection
variants
or
or
or
or Busbar
with solidinsulation
Surgearrester,
pluggable
Plug-in cablequadruple
Plug-in cabletriple
Plug-in cabledouble
Plug-in cablesingle
Panelconnectionattachment
SS2
SS1
Panelconnection
variants
or
or
or
or Busbar
with solidinsulation
Surge
arrester,pluggable
Panel connectionattachment
Currenttransformer
1)
1)
1)
1) if a surge arrester is used,the number of cables isreduced by one
Voltagetransformer,
pluggable
1)
1)
1)
1) if a surge arrester is used,the number of cables isreduced by one
Voltagetransformer,
pluggable
Plug-in cablequadruple
Plug-in cabletriple
Plug-in cabledouble
Plug-in cablesingle
1) 1)
Disconnector panel
(Innercone-typecableconnection)
Bus section coupler / riser panel
7/30/2019 GIS Sieens Wi en 100709
39/5239WI EN
WI Range of products (contd.)
1) only up to 40.5 kV
Abbreviations
SS1 = Busbar 1
SS2 = Busbar 2
SS2
SS1
Current
transformer
SS2
SS1
Currenttransformer
SS2
SS1
Bus coupler
up to 2000 A
(1 panel width) 1)
SS2
SS1
Currenttransformer
Bus section coupler Bus coupler up to 2500 A 1) Disconnector/earthing
switch in line with busbar
7/30/2019 GIS Sieens Wi en 100709
40/5240 WI EN
WI Cable connections
Cable connections in outgoing feeder blockThe medium-voltage cables are connected to the switchgear panels via
metal-enclosed inner cone-type plug-in terminations. The panels areequipped with inner cone-type appliance couplers according to EN 50 181.
Themanufacturersspecicationsoftheregardingselectionandassembly
of the plug-in terminations must be adhered to. This does not only apply to
the selection of size, but also to all electrical rated data, in line with the
switchgears data.
It is essential that all appliance couplers which are not equipped withplug-in terminations are terminated correctly using voltage-proof and fully
shrouded insulating terminals/ dummy plugs.
To this effect, the inner cone-type cable plug-in terminations for attachment
to WI require capacitive decoupling. The coupling electrodes for the
capacitive voltage detection system are an integral part of the appliance
couplers installed in the switchgear panel.
Cable connections in outgoing feeder
3 phase switchgear
panels
1 phase switchgear
panels
2 phase switchgear
panels
Inner cone acc. to EN 50181
Terminal types:
size 1 630 A
size 2 800 A
size3(upto40.5kV) 1250 A
size3(>40.5upto52kV) 1250 A
size 4 2500 A
Single / double busbar Single cable, 3-phase, withoutoutgoing voltage transformer
12-36 kV 38-40.5 kV
1x size 1
1x size 2
1x size 3
1x size 4
Size 4 with supporting structure increased in height
Single busbar Railway traction power supply with 2 vacuuminterrupter chambers per phase
1-pole L1 2-pole L1, L3
1x size 3/S Single cable connection
7/30/2019 GIS Sieens Wi en 100709
41/5241WI EN
WI Cable connections (contd.)
Single / double busbar with 1 vacuum interrupter chamberper conductor/phase
Multi-cable, 3-phase, without outgoingvoltage transformer
12 kV - 36 kV 38 kV - 40.5 kV
2 x size 1
3 x size 1
2 x size 2
3 x size 2
4 x size 2
2 x size 3
3 x size 3
4 x size 3
1xsize1+2xsize3
1xsize2+2xsize3
Single / double busbar with 2 vacuum interrupter chambersper conductor/phase
Single- and multi-cable, 3-phase, without outgoing voltage transformer
40.5 kV
BIL 200 kV
52 kV
BIL 250 kV
1 x size 3
1 x size 3/S
2 x size 3
2 x size 3/S
3 x size 3
3 x size 3/S
Single busbar for stationary railway traction power supplywith 2 vacuum interrupter chambers per conductor/phase
Multiple cable without voltage transformer
1-phase L1 2-phase L1 + L3
2 x size 3/S
3 x size 3/S
4 x size 3/S
5 x size 3/S
Multi-cable connection
7/30/2019 GIS Sieens Wi en 100709
42/5242 WI EN
WI Cable connections (contd.)
Single / double busbar with 1 vacuum interrupter chamberper conductor/phase
Multi-cable, 3-phase with 3 outgoingvoltage transformers
12 kV - 36 kV 38 kV - 40.5 kV
1 x size 2
3 x size 2
4 x size 2
1 x size 3
2 x size 3
3 x size 3
4 x size 3
1xsize2+1xsize3
1xsize2+2xsize3
1xsize2+3xsize3
1xsize2+4xsize3
1xsize1+3xsize3
Single / double busbar with 2 vacuum interrupter chambersper conductor/phase
Multi-cable, 3-phase, with 1 outgoing voltage transformer (1-phase in L2)
40.5 kV
BIL 200 kV
52 kV
BIL 250 kV
1 x size 3
1 x size 3/S
2 x size 3
3 x size 3/S
possibleuptorated(normal)currentinoutgoingfeederofmax.1600A
Single busbar for stationary railway traction power supplywith 2 vacuum interrupter chambers per conductor/phase
Multi-cable with 1 or 2 voltage transformers
1-phaseL1
2-phase L1 + L3
Voltagetransformers
L3
Voltage transformers
L1 + L3
1 x size 3/S
2 x size 3/S
3 x size 3/S
4 x size 3/S
Multi-cable connection with voltage
transformer in outgoing feeder
7/30/2019 GIS Sieens Wi en 100709
43/5243WI EN
WI Ecological considerations
A WI switchgearsatisestoahighdegreeecologicalrequirementsinviewof environmental protection thanks to
optimization of material and energy consumption during manufacture compliance with all ecological requirements during its service life theuseofrecyclablematerialsforefcientdisposalattheendofitsservice life.
Our design directives regarding environmentally compatible design specifythe use of materials which are easily recyclable and can be disassembled.The metals which make up approx. 90 % of the switchgear are easilyrecyclable. At the end of their service life, they are recycled 100 % in theform of homogenous materials.
Plastics can also be recycled. Thermosetting i.e. non-melting plasticscanbecomminutedandreusedasllersinotherplasticcomponents;thermoplastic - i.e. melting - materials can be recycled in the form ofhomogenous material. This means that the material is conserved, melteddown and used for the construction of new durable parts.
Toensureefcientandenvironmentallycompatibledisassemblyandassignment of materials by the responsible disposal experts, the
switchgearsplasticcomponentshavebeenidentiedaccordingly.Moreover, material and utilization data sheets are available to provide thecustomer with an over- view about the materials used. Equally, the disposalcompany is provided with important information regarding the recycling process.
Thus, the materials used for our products can be reused 100 %.
This represents a major contribution towards saving primary energy andmaterial resources.
Allmaterialswereselectedanddevelopedsothate.g.incaseofrewithinbuildings,affectedswitchgearonlyhaveaminorinuenceonthereload(heatdevelopment,pollutantsintheemissions) .
Anotherimportantecologicalaspectisthelongevityofourproducts(min.30to40years),whichisanextremelylongservicelifecomparedtoothercapital goods. Furthermore, the switchgear units have been designed so asto require little maintenance which would in turn use up energy and material,
and so as to enable straightforward replacement of part components, e.g. ifnewcontrollershavebeendevelopedonthemarket(upgrading).
In our gas-insulated switchgear WI, the majority of the switchgear panelhasbeensealedhermeticallyinaninsulatinginertgas(sulphurhexauorideSF
6whichisneitherreactivenortoxic).Thus,all
environmentalinuencesreducingtheservicelifeareshutout.Thespecialcharacteristics of the insulating gas also enable an overall size reduction byapprox. 50 percent versus switchgear designed without insulating gas withcomparable technical properties. This again saves a lot of material andenergy required for material production. The portion of insulating gas usedfor WI switchgear amounts to approx. 0.5 percent by weight. Once theswitchgears service life has elapsed, the gas is extracted completely viathedisposalvalveprovidedseriallyineachgas-lled,claddedcompartment, and then recycled. The gas suppliers have developed anefcientrecyclingconcepttothiseffect.
During normal operation, the gas need not be replenished during the entireservice life of the switchgear. The switchgear is a hermetically sealedpressuresystemacc.toIEC60694(IEC62271-1).
Average material distribution in gas-insulatedswitchgear units
Materials Wt. %
Metals Steel 7
Copper 6.5
Aluminium, brass 2
Plastics Thermosetting plastics 7
Thermo-plastics 2
Elastomers 0.5
Electronics Plastics 0.5
Metals 1
Insulating gas Sulphurhexauoride 0.5
7/30/2019 GIS Sieens Wi en 100709
44/5244 WI EN
WI Design dataSpace requirements - dimensions andweights
>500
>500
>1000 >1500 1)
2400
WIA up to 40.5 kV
>500
>500
>500 >1500
1)
>500
>500
>1500 1)
>1000
WIA up to 52 kV
2964
1) smaller gap on request
Weights:
WIA up to 40.5 kV approx. 1000 kg
WIA 52 kV approx. 1350 kg
280
673
1692
600
460
70
70
Spacer bars7070
Flooring ducts
Top view
view
7/30/2019 GIS Sieens Wi en 100709
45/5245WI EN
WI Design dataSpace requirements - dimensions andweights(contd.)
WIA up to 52 kV
>50
0
>500 >500
>10
00 >1500 1)
2400
WIA up to 40.5 kV
>500
>500
>500 >1500
1) >500
280
673
1692
600
460
70
70
Spacer bars7070
>5
00
>500
>15001)
>10
00
2964
WIA up to 52 kV
1) smaller gap on request
Weights:
WIA up to 40.5 kV max. 1000 kg
WIA 52 kV approx. 1350 kg
Flooring ducts
Top view
view
7/30/2019 GIS Sieens Wi en 100709
46/5246 WI EN
WI
WIB up to 40.5 kV
>500
>500
>500 >1500
1)>500
280673
1692
600
460
70
70Spacer bars
70
70
>500
>500 >500
>1000 >1500 1)
3050
WIB bis 40,5 kV>50
0
>500
>1500 1)
>1000
3614
WIB bis 52 kV
1) smaller gap on request
Weights:
WIB up to 40.5 kV approx. 1300 kg
WIB 52 kV approx. 1700 kg
Flooring ducts
Top view
view
Design dataSpace requirements - dimensions andweights(contd.)
7/30/2019 GIS Sieens Wi en 100709
47/5247WI EN
WI
WIB up to 52 kV
>500
>500
>1000 >1500 1)
3050
WIB up to 40.5 kV
>500
>500
>500 >1500
1)
280673
1692
600
460
70
7070
70
Spacer bars
>500
>500
>1500 1)
>1000
3614
WIB up to 52 kV
1) smaller gap on request
Weights:
WIB up to 40.5 kV approx. 900 - 1000 kg
WIB 52 kV approx. 1100-1500Kg
Flooring ducts
Top view
view
Design dataSpace requirements - dimensions andweights(contd.)
7/30/2019 GIS Sieens Wi en 100709
48/5248 WI EN
WI
Busbar connection with fully insulated conductor bars
Direct transfer line. Phase exchange in terminal tank
Design dataSpace requirements - dimensions andweights(contd.)
7/30/2019 GIS Sieens Wi en 100709
49/5249WI EN
WI
Direct transfer line. Phase exchange in terminal tank
Transfer line top and bottom by means of supplementary gas tank
Transfer line at the bottom. Phase exchange required in transfer line
Design dataSpace requirements - dimensions andweights(contd.)
7/30/2019 GIS Sieens Wi en 100709
50/5250 WI EN
WI Shipping instructions
Transporting the switchgear unitWhen transporting the switchgear unit, it is important to ensure that the
transportunitsdonotsliportilt(ifnecessary,nailtransportpalletdowntotheloadingsurface).Reusetheoriginalpackagingtostorepartswhich
have been unpacked for inspection.
Packaging of the switchgear
If packed for truck transport, the switchgear unit is delivered on a pallet
withPEprotectivelm.
Forsea-worthytransport,theunitsarepackedinsealedaluminiumlm
with desiccant and in a closed case with tightly closed wooden base. In case of air transport, the switchgear unit is packed in a wooden crate
withclosedwoodenbaseandwithablisterIPElmasdustprotectionor
in a wooden case, also with closed wooden base.
Transport to the site of installationStore under conditions admissible for switchgear operation. Avoid
condensation.
During transport to the site of installation, remember that the main weight islocated in the top area of the switchgear top-heavy.
Transport using a forklift truck: Only transport the switchgear on a pallet.
Attention top-heavy!
Transport without pallet: The crane mounting harness must be hooked into
the jack rings of the switchgear.