BÁO CÁO SỰ CỐ - INCIDENT ALERT (NEAR MISS, FIRST AID, RECORDABLE INCIDENT, SPILL …) Report date: Oct-24-2013 Report by: Tran Minh Phong Department: HSE NHÀ MÁY PLANT: SSTVN LOẠI SỰ CỐ INCIDENT TYPE: - Near miss: 02 furnace were in situation alert – can be exploded Furnace Explosion - Sự cố suýt xảy ra SỐ THỨ TỰ SỰ CỐ INCIDENT NUMBER: KHI NÀO? WHEN? - 12:16 MÔ TẢ SỰ CỐ WHAT? The back-up generator which powers the evaporative coolers and pumps did not engage. About ten minutes after the power failed he went down and killed the disconnect switch and immediately the generator kicked in and the pumps re-started. Although the shoe shorting out on the hot-track did not cause the power failure it did keep the generator from starting. NƠI XẢY RA? WHERE? - Furnaces – Monorail – cooling tower – generator MỨC ĐỘ THƯƠNG TẬT EMPLOYEE INJURY: - N/A NHÓM ĐIỀU TRA INCIDENT INVESTIGATION TEAM : - Joe, Manh, Thanh, Khang, Phong.Tran TỔN HẠI TÀI SẢN EQUIPMENT / FACILITY DAMAGE: - A carbon brush of the monorail was burnt. TÌNH TRẠNG ĐIỀU TRA INVESTIGATION STATUS: - Completed TẠI SAO? Why? Why was there here the a possibility of the impending danger of furnace explosion? Due to the power loss, the C c ooling towers were lost the power and could not supply the water to the furnaces TẠI SAO TẠI SAO ? Wh y Why ? Why did the power fail ? y was the power lost The main power CB & generator could not be on Why could not they be on? The po wer was leaked , but the CB used in the monorail system had no function to detect this whereas the main CB and generator could and automatically dropped Electric circuit of Monorail was leakage. . A carbon brush on one

Incident Alert - Leakage

Embed Size (px)

DESCRIPTION

Incident Alert - Leakage

Citation preview

BO CO S C - INCIDENT ALERT

BO CO S C - INCIDENT ALERT

(NEAR MISS, FIRST AID, RECORDABLE INCIDENT, SPILL )

Report date: Oct-24-2013Report by: Tran Minh PhongDepartment: HSE

NH MY

PLANT:SSTVN

LOI S C

INCIDENT TYPE:Near miss: Furnace Explosion

S c sut xy ra

S TH T S C

INCIDENT NUMBER:

KHI NO?

WHEN?12:16

M T S C

WHAT?The back-up generator which powers the evaporative coolers and pumps did not engage. About ten minutes after the power failed he went down and killed the disconnect switch and immediately the generator kicked in and the pumps re-started. Although the shoe shorting out on the hot-track did not cause the power failure it did keep the generator from starting.

NI XY RA?

WHERE?Furnaces Monorail cooling tower generator

MC THNG TT

EMPLOYEE INJURY:N/A

NHM IU TRA

INCIDENT INVESTIGATION TEAM :Joe, Manh, Thanh, Khang, Phong.Tran

TN HI TI SN

EQUIPMENT / FACILITY DAMAGE: A carbon brush of the monorail was burnt.

TNH TRNG IU TRA

INVESTIGATION STATUS:Completed

TI SAO?

Why?Why was there a possibility of the impending danger of furnace explosion?Due to the power loss, the cooling towers could not supply the water to the furnaces

TI SAO?

Why?Why did the power fail?The main CB & generator could not be on

Why could not they be on?

The power was leaked , but the CB used in the monorail system had no function to detect this whereas the main CB and generator could and automatically dropped . A carbon brush on one hoist was burned during running.

Why did the electrical leakage cause the power failure?

No ELCB used in the equipment.

NGUYN NHN GC

ROOT CAUSE Earth leakage occured in the monorail system

NGUYN NHN GP PHN

CONTRIBUTING CAUSESNo backup water for the furnaces when the power was lost.

HNH NG KHC PHC

CORRECTIVE ACTIONSinstall a disconnect panel between the generator and all systems except the evaporative coolers and the cooling pumps Thanh-MA

Due date: Oct-28-2013

install a "city water" or fresh water bypass that will cool the furnaces in the event of a catastrophic failureThanh-MA

Due date: Nov-04-2013