TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application <Indoor unit> 2004 Models Ceiling Concealed Series PEFY PEFY-P40VMH-E,PEFY-P50VMH-E PEFY-P63VMH-E,PEFY-P71VMH-E PEFY-P80VMH-E,PEFY-P100VMH-E PEFY-P125VMH-E,PEFY-P140VMH-E PEFY-P200VMH-E,PEFY-P250VMH-E INDOOR UNIT CONTENTS SAFETY PRECAUTIONS ························· 1 1. FEATURES ··········································· 3 2. PART NAMES AND FUNCTIONS········ 4 3. SPECIFICATION··································· 6 4. OUTLINES AND DIMENSIONS············ 9 5. WIRING DIAGRAM····························· 11 6. REFRIGERANT SYSTEM DIAGRAM 13 ···· 7. TROUBLE SHOOTING······················· 14 8. DISASSEMBLY PROCEDURE··········· 17 For use with the R410A & R407C & R22

Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application 2004 ... installation by the

  • Upload
    ngonhan

  • View
    244

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

TECHNICAL & SERVICE MANUAL

Air-Conditioners For Building Application

<Indoor unit>

2004

Models

Ceiling ConcealedSeries PEFY

PEFY-P40VMH-E,PEFY-P50VMH-EPEFY-P63VMH-E,PEFY-P71VMH-EPEFY-P80VMH-E,PEFY-P100VMH-EPEFY-P125VMH-E,PEFY-P140VMH-EPEFY-P200VMH-E,PEFY-P250VMH-E

INDOOR UNIT

CONTENTSSAFETY PRECAUTIONS ·························11. FEATURES ···········································32. PART NAMES AND FUNCTIONS ········43. SPECIFICATION···································64. OUTLINES AND DIMENSIONS············95. WIRING DIAGRAM ·····························116. REFRIGERANT SYSTEM DIAGRAM 13····7. TROUBLE SHOOTING·······················148. DISASSEMBLY PROCEDURE···········17

For use with the R410A & R407C & R22

Page 2: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

1

SAFETY PRECAUTIONS

and install the unit at the specified place.- Improper installation may cause the unit to topple and result in

injury.• Always use an air cleaner, humidifier, electric heater, and other

accessories specified by Mitsubishi Electric.- Ask an authorized technician to install the accessories. Improper

installation by the user may result in water leakage, electric shock,or fire.

• Never repair the unit. If the air conditioner must be repaired,consult the dealer.- If the unit is repaired improperly, water leakage, electric shock, or

fire may result.• Do not touch the heat exchanger fins.

- Improper handling may result in injury.• If refrigerant gas leaks during installation work, ventilate the

room.- If the refrigerant gas comes into contact with a flame, poisonous

gases will be released.• Install the air conditioner according to this Installation Manual.

- If the unit is installed improperly, water leakage, electric shock, orfire may result.

• Have all electric work done by a licensed electrician accordingto “Electric Facility Engineering Standard” and “Interior WireRegulations”and the instructions given in this manual and al-ways use a special circuit.- If the power source capacity is inadequate or electric work is per-

formed improperly, electric shock and fire may result.

• Securely install the cover of control box and the panel.- If the cover and panel are not installed properly,dust or water may

enter the outdoor unit and fire or electric shock may result.• When installing and moving the air conditioner to another site,

do not charge the it with a refrigerant different from the refrig-erant specified on the unit.- If a different refrigerant or air is mixed with the original refrigerant,

the refrigerant cycle may malfunction and the unit may be dam-aged.

• If the air conditioner is installed in a small room, measuresmust be taken to prevent the refrigerant concentration fromexceeding the safety limit even if the refrigerant should leak.- Consult the dealer regarding the appropriate measures to pre-

vent the safety limit from being exceeded. Should the refrigerantleak and cause the safety limit to be exceeded, hazards due tolack of oxygen in the room could result.

• When moving and reinstalling the air conditioner, consult thedealer or an authorized technician.- If the air conditioner is installed improperly, water leakage, elec-

tric shock, or fire may result.• After completing installation work, make sure that refrigerant

gas is not leaking.- If the refrigerant gas leaks and is exposed to a fan heater, stove,

oven, or other heat source, it may generate noxious gases.• Do not reconstruct or change the settings of the protection

devices.- If the pressure switch, thermal switch, or other protection device

is shorted and operated forcibly, or parts other than those specifiedby Mitsubishi Electric are used, fire or explosion may result.

1. Before installation and electric work

s Before installing the unit, make sure you read all the“Safety precautions”.

s The “Safety precautions” provide very importantpoints regarding safety. Make sure you follow them.

s This equipment may cause the adverse effect on thesame supply system.

s Please report to or take consent by the supply au-thority before connection to the system.

Symbols used in the textWarning:

Describes precautions that should be observed to prevent dangerof injury or death to the user.

Caution:Describes precautions that should be observed to prevent damageto the unit.

Symbols used in the illustrations: Indicates an action that must be avoided.

: Indicates that important instructions must be followed.

: Indicates a part which must be grounded.

: Indicates that caution should be taken with rotating parts. (Thissymbol is displayed on the main unit label.) <Color: Yellow>

: Beware of electric shock (This symbol is displayed on the mainunit label.) <Color: Yellow>

Warning:Carefully read the labels affixed to the main unit.

Warning:• Ask the dealer or an authorized technician to install the air con-

ditioner.- Improper installation by the user may result in water leakage, elec-

tric shock, or fire.• Install the air unit at a place that can withstand its weight.

- Inadequate strength may cause the unit to fall down, resulting ininjuries.

• Use the specified cables for wiring. Make the connections se-curely so that the outside force of the cable is not applied to theterminals.- Inadequate connection and fastening may generate heat and cause

a fire.• Prepare for typhoons and other strong winds and earthquakes

• Keep the electric parts away from water (washing water etc.).- It might result in electric shock, catching fire or smoke.

• To dispose of this product, consult your dealer.• Do not use a leak detection additive.

Page 3: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

2

2. Precautions for devices that use

Caution:• Do not use the existing refrigerant piping.

- The old refrigerant and refrigerator oil in the existing piping con-tains a large amount of chlorine which may cause the refrigeratoroil of the new unit to deteriorate.

• Use refrigerant piping made of C1220 (Cu-DHP) phosphorusdeoxidized copper as specified in the *JIS H3300 “Copper andcopper alloy seamless pipes and tubes”. In addition, be surethat the inner and outer surfaces of the pipes are clean andfree of hazardous sulphur, oxides, dust/dirt, shaving particles,oils, moisture, or any other contaminant.- Contaminants on the inside of the refrigerant piping may cause

the refrigerant residual oil to deteriorate.*JIS: Japanese Industrial Standard

• Store the piping to be used during installation indoors and keepboth ends of the piping sealed until just before brazing. (Storeelbows and other joints in a plastic bag.)- If dust, dirt, or water enters the refrigerant cycle, deterioration of

the oil and compressor trouble may result.• Use ester oil, ether oil or alkylbenzene (small amount) as the

refrigerator oil to coat flares and flange connections.- The refrigerator oil will degrade if it is mixed with a large amount of

mineral oil.• Use liquid refrigerant to fill the system.

- If gas refrigerant is used to seal the system, the composition ofthe refrigerant in the cylinder will change and performance maydrop.

• Do not use a refrig- If another refrigerant (R22, etc.) is used, the chlorine in the refrig-

erant may cause the refrigerator oil to deteriorate.• Use a vacuum pump with a reverse flow check valve..

- The vacuum pump oil may flow back into the refrigerant cycle andcause the refrigerator oil to deteriorate.

• Do not use the following tools that are used with conventionalrefrigerants.(Gauge manifold, charge hose, gas leak detector, reverse flowcheck valve, refrigerant charge base, vacuum gauge, refriger-ant recovery equipment)- If the conventional refrigerant and refrigerator oil are mixed in the

• Do not use a charging cylinder.- Using a charging cylinder may cause the refrigerant to deteriorate.

• Be especially careful when managing the tools.- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant

may deteriorate.

R410A or R407C refrigerant

erant other than R410A or R407C.

R410A or R407C, the refrigerant may deteriorated.- If

deteriorate.water is mixed in the R410A or R407C, the refrigerator oil may

- Since R410A or R407C does not contain any chlorine, gas leak detectors for conventional refrigerants will not react to it.

Page 4: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

3

PEFY-P40VMH-EPEFY-P50VMH-EPEFY-P63VMH-EPEFY-P71VMH-EPEFY-P80VMH-EPEFY-P100VMH-EPEFY-P125VMH-EPEFY-P140VMH-EPEFY-P200VMH-EPEFY-P250VMH-E

4.5 / 5.05.6 / 6.37.1 / 8.08.0 / 9.09.0 / 10.0

11.2 / 12.514.0 / 16.016.0 / 18.022.4 / 25.028.0 / 31.5

FEATURES1

Indoor unit

Ceiling ConcealedSeries PEFY

ModelsCooling capacity/Heating capacity

kW

Page 5: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

4

PART NAMES AND FUNCTIONS2

Indoor (Main) Unit

Remote controller

[Operation buttons]

[PAR-20MAA] Once the controls are set, the same operation mode can

be repeated by simply pressing the ON/OFF button.

Air inlet

Air outlet

PAR-20MAA

ON/OFF

CENTRALLY CONTROLLED

ERROR CODE

CLOCK

ON OFF

°C

CHECK

CHECK MODEFILTER

TEST RUNFUNCTION

°C1Hr.

NOT AVAILABLESTAND BY DEFROST

FILTER

CHECK TEST

TEMP.

TIMER SET

1

2

3

4 5 6 8 7 9

0

C

A

B

1 [Room temperature adjustment] Button2 [Timer/continuous] Button3 [Selecting operation] Button4 [Time selection] Button

[Time-setting] Button5 [Louver] Button6 [Fan speed adjustment] Button

7 [Up/down airflow direction] Button8 [Ventilation] Button9 [Checking/built-in] Button0 [Test run] ButtonA [Filter] ButtonB [ON/OFF] ButtonC Position of built-in room temperature

•Never expose the remote controller to direct sunlight. Doing so can result in the erroneous measure-ment of room temperature.

•Never place any obstacle around the lower right-hand section of the remote controller. Doing so canresult in the erroneous measurement of room temperature.

Page 6: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

5

[Display]

ON/OFF

CENTRALLY CONTROLLED

ERROR CODE

CLOCK

ON OFF

°C

CHECK

CHECK MODEFILTER

TEST RUNFUNCTION

°C1Hr.

NOT AVAILABLESTAND BY DEFROST

TEMP.

ABCD

E

F

H I KLJ

M

P

N

O

R

SQTU

G

Current time/TimerCentralized controlTimer ONAbnormality occursOperation mode: COOL, DRY, AUTO, FAN, HEATPreparing for Heating modeDefrost modeSet temperaturePower ONLouverNot available functionVentilationFunction setting modeTest run modeError check modeFilter signSet effective for 1 hr.Sensor positionRoom temperatureAirflowFan speed

ABCDEFGHIJKLMNOPQRSTU

Page 7: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

3 SPECIFICATION

3-1. Specification

Power sourceModel

kWCooling capacity 1kWkWCooling

HeatingCoolingHeating

kWAA

mmmmmmkg

m3/min

PaPa

50/100/200100/150/200

220V230, 240V

kW

mm

mm

dB(A)dB(A)

27-3431-37

32-3836-41

32-3935-41

Heating capacity 1Power consumption(50/60Hz)

Current

External finish

DimensionHeightWidthDepth

Net weightHeat exchanger

Fan

TypeAirflow rate(Lo-Hi)External staticpressure 2

Motor Output 3Type

Air filter (option)

Refrigerant pipe dimension

Gas(Flare)Liquid(Flare)

Drain pipe dimensionNoise level (Lo-Hi) 220V

230, 240V

~

750 1000

44Cross fin (Aluminum plate fin and copper tube)

Sirocco fan

Single phase induction motor

Synthethic fiber unwoven cloth filter(long life)

10.0-14.0

220-240V 50Hz /60HzPEFY-P40VMH-E PEFY-P50VMH-E

5.64.56.35.0

Galvanizing380

900

1

12.7

6.35

32 (1-1/4 inch)

0.08

0.19/0.230.19/0.230.88/1.060.88/1.06

0.24/0.300.24/0.301.12/1.381.12/1.38

0.26/0.330.26/0.331.20/1.511.20/1.51

45 50

ø

ø 9.52ø

PEFY-P63VMH-E

7.18.0

ø 15.88ø 12.7(R410A)ø 15.88(R22,R407C)ø 6.35(R410A)ø 9.52(R22,R407C)

13.5-19.0

0.12 0.14

PEFY-P71VMH-E

8.09.0

15.5-22.0

Note: 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27°CDB/19 °CWB,Outdoor 35°CDB (WR2: water 30°C)Heating : Indoor 20°CDB,Outdoor 7°CDB/6°CWB (WR2: water 20°C)

2 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment. 3 The value are that at 240V.

6

Page 8: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

7

Power sourcekWCooling capacity 1kWkWCooling

HeatingCoolingHeating

kWAA

mmmmmmkg

m3/min

PaPa

50/100/200100/150/200

220V230, 240V

kW

mm

mm

dB(A)dB(A)

35-4138-43

34-4238-44

Heating capacity 1Power consumption(50/60Hz)

Current

External finish

DimensionHeightWidthDepth

Net weightHeat exchanger

Fan

TypeAirflow rate(Lo-Hi)External staticpressure 2

Motor Output 3Type

Air filter (option)

Refrigerant pipe dimension

Gas(Flare)Liquid

(Flare)Drain pipe dimensionNoise level (Lo-Hi) 220V

230, 240V

~

1000 1200

50Cross fin (Aluminum plate fin and copper tube)

Sirocco fan

Single phase induction motor

Synthethic fiber unwoven cloth filter(long life)

18.0-25.0

220-240V 50Hz /60HzPEFY-P80VMH-E PEFY-P100VMH-E

11.29.012.510.0

Galvanizing380

900

1 Sirocco fan 2

15.88

32 (1-1/4 inch)

0.18

0.48/0.580.48/0.582.34/2.662.34/2.66

0.48/0.590.48/0.592.35/2.702.35/2.70

0.32/0.400.32/0.401.47/1.831.47/1.83

70

ø

9.52ø

PEFY-P125VMH-E

14.016.0

26.5-38.0

0.26

PEFY-P140VMH-E

16.018.0

28.0-40.0

PEFY-P200VMH-E~ 380-415V 50Hz / 60Hz

PEFY-P250VMH-E

22.4 28.025.0 31.5

Power sourcekWCooling capacity 1kWkWCooling

HeatingCoolingHeating

kWAA

mmmmmmkg

m3/minPaPa

kW

mm

mm

dB(A)dB(A)

Heating capacity 1Power consumption(50/60Hz)

Current

External finish

DimensionHeightWidthDepth

380V400, 415V

380V400, 415V

Net weightHeat exchanger

FanTypeAirflow rateExternal staticpressure 4

Motor Output 5Type

Air filter (option)

Refrigerant pipe dimension

Gas(Brazing)Liquid

(Brazing)Drain pipe dimension

Noise level

Galvanizing47012501120100

Cross fin (Aluminum plate fin and copper tube)Sirocco fan 2

phase induction motor

Synthethic fiber unwoven cloth filter(long life)

32 (1-1/4 inch)

58.0 72.0110/220130/260

0.76 1.08

52(130Pa)/54(260Pa)50(110Pa)/52(220Pa)

44(130Pa)/47(260Pa)42(110Pa)/45(220Pa)

0.99/1.140.99/1.141.62/1.861.62/1.86

1.23/1.411.23/1.41

2.0/2.32.0/2.3

Note: 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27°CDB/19 °CWB,Outdoor 35°CDB (WR2: water 30°C)Heating : Indoor 20°CDB,Outdoor 7°CDB/6°CWB (WR2: water 20°C)

2 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment. 3 The value are that at 240V. 4 The external static pressure is set to 110Pa (at 380V) /130Pa (at 400, 415V) at factory shipment. 5 The value are that at 415V.

3N

Model

Model

ø 15.88 (R410A)ø 19.05 (R22,R407C)

ø 9.52 (R410A)ø 12.7 (R22,R407C)

ø 22.2 (R410A)ø 28.58 (R22,R407C)

ø 19.05 (R410A)ø 25.4 (R22,R407C)

Page 9: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

8

LEV

C1

MF1,2

PEFY-P40VMH-E

3-2. Electrical parts specifications

Model

Partsname

Tranrsformer T (Primary) 50/60Hz 220-240V (Secondry) (23.5V 0.9A)

TH21 Resistance 0°C/15kΩ,10°C/9.6kΩ,20°C/6.3kΩ,25°C/5.4kΩ,30°C/4.3kΩ,40°C/3.0kΩ

TH22 Resistance 0°C/15kΩ,10°C/9.6kΩ,20°C/6.3kΩ,25°C/5.4kΩ,30°C/4.3kΩ,40°C/3.0kΩ

Gas pipethermistor

FUSE 250V 6.3A

TB2 (L,N, ) 330V 30A

TB5TB15

(1,2),(M1,M2,S) 300V 10A

Fuse(Indoor con-

troller board)

Power supplyterminal bed

Transmissionterminal bed

PEFY-P50VMH-E

PEFY-P63VMH-E

PEFY-P71VMH-E

PEFY-P80VMH-E

PEFY-P100VMH-E

PEFY-P125VMH-E

PEFY-P140VMH-E

PEFY-P200VMH-E

PEFY-P250VMH-E

OFF 135°C±5°CON 95°C±20°C

Roomtemperaturethermistor

Fan motor(with Inner-

thermostat)

4-pole OUTPUT130W

NC-45VMH

4-poleOutput180W

NC-71VMH

Symbol

(L1,L2,L3,N, )660V 40A

TH23 Resistance 0°C/15kΩ,10°C/9.6kΩ,20°C/6.3kΩ,25°C/5.4kΩ,30°C/4.3kΩ,40°C/3.0kΩ

Inner-thermostat

(Fan motor)

Liquid pipethermistor

Fan motorcapacitor

Linear expansion valve

4-poleOutput220W

NC-80VMH

4-poleOutput230W

NC-90VMH

4-poleOutput550W

NS-200VMH

4-poleOutput800W

NS-250VMH

4-pole OUTPUT 400WNS-112VMH

3.0µF440V 4.0µF440V 5.0µF440V -7.0µF440V

DC12V Stepping motor driveport dimension ø 3.2

0~1800pulse<at R410A outdoor unit>0~2000pulse<at the other outdoor unit>

0~1800pulse<at R410A outdoor unit>0~2000pulse<at the other outdoor unit>

0~1800pulse<at R410A outdoor unit>0~2000pulse<at the other outdoor unit>

0~1800pulse<at R410A outdoor unit>0~2000pulse<at the other outdoor unit>

DC12V Stepping motor driveport dimension ø 5.2

DC12V Stepping motor driveport dimension ø 5.2

DC12V Steppingmotor drive portdimension ø 6.4

Page 10: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

9

4 OUTLINES AND DIMENSIONS

Unit : mmPEFY-P40·50·63·71·80·100·125·140VMH-E

Ter

min

al b

ed(T

rans

miss

ion)

Ter

min

al b

ed(P

ower

sour

ce)

150~

200

700

5050

L

Acc

ess

door

625

Not

e 2

Reg

uire

d sp

ace

for s

ervi

ce a

nd m

aint

enan

ce

450

100~

200

450

Mak

e th

e ac

cess

doo

r at t

he a

ppoi

nted

pos

ition

prop

erly

for s

ervi

ce m

aint

enan

ce.

Acc

ess

door

Cei

ling

surfa

ce

Higher than 20mmHigher than 20mm

Dra

in h

ole

(opt

ion)

Con

trol b

ox2

1

30

Dra

in h

ole

Term

inal

box

340

D

814

(Lift

ing

bolt

pitc

h)

B (Lifting bolt pitch)A

904

Lifti

ng b

olt

383

60

23

15

80

3

50

10

F

G-ø

3J-

ø3

5050x(J-1)=K

250

E

24

50x(G-1)=H

5050x5=250 45

10

340 17

900

847

1529

380

50 50 50 50

250

25

32894

4113077

38734

320

092

C41

70

Mod

el:4

0-80

(Not

e 3)

Air

outle

tA

ir in

let

Kee

p du

ct-w

ork

leng

th 8

50m

m o

r mor

e.N

ote1

.Use

M10

scr

ew fo

r the

lifti

ng b

olt (

field

sup

ply)

.

2.K

eep

the

serv

ice

spac

e fo

r the

mai

nten

ance

from

the

botto

m w

hen

the

heat

exc

hang

er is

cle

aned

.

3.T

his

char

t ind

icat

es fo

r PE

FY-P

100·

125·

140

mod

els,

whi

ch h

as 2

fans

.

P

EFY

-P40

·50·

63·7

1·80

mod

els

have

1 fa

n.

4.M

ake

sure

to in

stal

l the

air

filte

r(fie

ld s

uppl

y) o

n th

e ai

r int

ake

side

.

In

cas

e fie

ld s

uppl

ied

air f

ilter

is u

sed,

atta

ch it

whe

re th

e fil

ter s

ervi

ce is

eas

ily d

one.

5

.On

Mod

el :5

0, 1

00, 1

25, 1

40, y

ou w

ould

use

flar

e nu

t pac

ked

with

the

Indo

or U

nit,

whe

n co

nnne

ctin

g th

e O

utdo

or U

nit f

or R

407C

, R22

.

6.In

ord

er to

incr

ease

the

stre

ngth

of t

he fl

are

nut,

the

size

of s

ome

of th

em h

as b

een

incr

ease

d.

Ref

riger

ant p

ipin

g fla

re c

onne

ctio

n(ga

s M

cop

per t

ube)

:HP

····

····

····

··R

efrig

eran

t pip

ing

flare

con

nect

ion(

liqui

d N

cop

per t

ube)

:LP

····

····

····

Dra

in h

ose

32m

m(1

-1/4

inch

) <fle

xibl

e jo

int 2

00m

m>

(acc

esso

ry)·

····

1 2 3P

1

2ø1

2.7

ø15.

88

1

2ø1

5.88

ø19.

05

1

2ø6

.35

ø9.5

2

1

2ø9

.52

ø9.5

2

1

2

22 22

1

2

22 22

1

2

29 29

1

2

36 36

Mod

elA 80

0

800

800

1050

1250

B 754

754

754

1004

1204

C 680

680

680

930

1130

D 600

600

600

850

1050

E 550

550

550

800

1000

H 500

500

500

800

1000

F 50 50 50 25 25

G 11 11 11 17 21

J 10 10 10 15 19

K 450

450

450

700

900

L 780

780

780

1030

1230

Mø1

2.7

ø15.

88ø1

5.88

Nø6

.35

ø9.5

2ø9

.52

P(Liq

uid)

17 22 22

P(Ga

s)27 29 29

P40

VM

H-E

P50

VM

H-E

P63

VM

H-E

P71·

80VM

H-E

P100

·125

·140

VMH-

E

1:

R41

0A o

utdo

or u

nit

2:

The

othe

r out

door

uni

t

Lower than 550mm

Low

er th

an 3

00m

m 170m

m±5

mm

(Act

ual l

engt

h)

3

Whe

n in

stal

ling

the

drai

n w

ater

lifti

ng-u

p m

ech(

optio

n).

Page 11: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

10

PEFY-P200·250VMH-EUnit : mm

21

3N

ote1

.Use

M10

scr

ew fo

r the

lifti

ng b

olt (

field

sup

ply)

.

2.K

eep

the

serv

ice

spac

e fo

r the

mai

nten

ance

from

the

botto

m

w

hen

the

heat

exc

hang

er is

cle

aned

.

3.M

ake

sure

to in

stal

l the

air

filte

r(fie

ld s

uppl

y)

on

the

air i

ntak

e si

de.

In c

ase

field

sup

plie

d ai

r filt

er is

use

d, a

ttach

it w

here

the

filte

r ser

vice

is e

asily

don

e.

Ter

min

al b

ed(P

ower

sou

rce)

Ter

min

al b

ed(T

rans

miss

ion)

Lifti

ng b

olt

2410

50x6=300

50x7=350

327

30

21-ø

322

-ø3

125050x21=1050 25 102

50x20=1000 50

15

100

42035

20

1120

1010

6715

29

470340 105

44 164

20

41

48942

295

249

231326(Lifting bolt pitch)1372

1100

420

1124

1034

(Lift

ing

bolt

pitc

h)60

340

1100D

rain

hol

e

Con

trol b

ox

Dra

in h

ole

(opt

ion)

Kee

p du

ct-w

ork

leng

th 8

50m

m o

r mor

e.

Air

outle

tA

ir in

let

Lower than 550mmLo

wer

than

300

mm

3

Whe

n in

stal

ling

the

drai

n w

ater

lifti

ng-u

p m

ech(

optio

n).

Ref

riger

ant p

ipin

g fla

re c

onne

ctio

n(ga

s M

cop

per t

ube)

:HP

····

····

····

··R

efrig

eran

t pip

ing

flare

con

nect

ion(

liqui

d N

cop

per t

ube)

:LP

····

····

····

Dra

in h

ose

32m

m(1

-1/4

inch

) <fle

xibl

e jo

int 2

00m

m>

(acc

esso

ry)··

···1 2 3

Mak

e th

e ac

cess

doo

r at t

he a

ppoi

nted

pos

ition

prop

erly

for s

ervi

ce m

aint

enan

ce.

Acc

ess

door

Cei

ling

surfa

ce

Higher than 20mmHigher than 20mm

150~

200

700

5050

1359

Acc

ess

door

625

Not

e 2

Reg

uire

d sp

ace

for s

ervi

ce a

nd m

aint

enan

ce

450

100~

200

450

170m

m±5

mm

(Act

ual L

engt

h)

Mod

elA

B

P20

0VM

H-E

ø19.

05ø2

5.4

ø22.

2ø2

8.58

ø9.5

2ø1

2.7

ø9.5

2ø1

2.7

P25

0VM

H-E

1

2

1

2

1

2

1

2

1:

R41

0A o

utdo

or u

nit

2:

The

othe

r out

door

uni

t

Page 12: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

11

5 WIRING DIAGRAM

PEFY-P40·50·63·71·80·100·125·140VMH-E

Sw

itch(

for v

olta

ge s

elec

tion)

atta

chm

ent t

o al

ter t

he e

xter

nal s

tatic

pre

ssur

e on

the

fan

PE

*NO

TE 1

,2

*NO

TE 1

*NO

TE 1

*A c

onne

ctor

is a

ttach

ed to

the

dra

in li

ft up

mec

hani

sm,

whi

ch is

an

opt

iona

l par

t.

TO O

UTD

OO

R U

NIT

TO M

A R

EM

OTE

CO

NTR

OLL

ER

B

C C

ON

TRO

LLE

R

RE

MO

TE C

ON

TRO

LLE

R

BR

EA

KE

R(1

6A)

FUS

E(1

6A)

PU

LL B

OX

TO N

EX

T IN

DO

OR

UN

IT

TO D

UC

T

PO

WE

R S

UP

PLY

~ 2

20,2

30,2

40V

5

0,60

Hz

Sw

itch(

for m

odel

sel

ectio

n) S

witc

h(fo

r mod

e se

lect

ion)

Sw

itch

(con

nect

ion

No.

set)

Sw

itch

(2nd

dig

it ad

dres

s se

t)

Sw

itch(

for c

apac

ity c

ode)

Sw

itch(

for m

ode

sele

ctio

n)*B

Cap

acito

r M

OD

ELS

40/

50

3

.0µF

MO

DE

L 6

3

4

.0µF

MO

DE

LS 7

1/80

5.0

µF M

OD

ELS

100

/125

/140

7.0

µF

The

rmist

or (p

iping

tem

p.de

tecti

on/g

as)

The

rmist

or (p

iping

temp

.detec

tion/l

iquid)

Aux

.rela

y

*inse

rt

SW

5(A.

B)

NO

TE;1

.The

par

t of t

he b

roke

n lin

e in

dica

tes

the

circ

uit

for o

ptio

nal p

arts

.

2.*

A in

the

char

t is

the

conn

ecto

r for

a d

rain

pum

p

te

st ru

n op

erat

ion.

(The

Dra

in P

ump

oper

ates

con

tinuo

usly

if th

e

c

onne

ctor

is in

serte

d an

d th

e po

wer

is s

uppl

ied.

)

A

fter t

he te

st ru

n, m

ake

sure

to re

mov

e th

e

*

A co

nnec

tor.

3

.The

wiri

ngs

to T

B2,

TB5

(sho

wn

in d

otte

d lin

e) a

re

fi

eld

wor

k.

4.M

ark

i

ndic

ates

term

inal

bed

,

con

nect

or,

b

oard

inse

rtion

con

nect

or o

r fas

teni

ng c

onne

ctor

of c

ontro

l

b

oard

.in

side

< >

is th

e op

tiona

l par

ts.

N

AM

ES

YM

BO

L E

XP

LAN

ATIO

N

Pow

er s

ourc

e te

rmin

al b

ed T

rans

mis

sion

term

inal

bed

TB

5Tr

ansm

issi

on te

rmin

al b

edTB

15

TB

2

SW

4(I.B

)

SW

1(A.

B) S

W14

(A.B

) S

W12

(A.B

) S

W11

(A.B

)

SW

3(I.B

) S

W2(

I.B)

Sw

itch

(1st

dig

it ad

dres

s se

t)

Tra

nsfo

rmer

Add

ress

boa

rd I

ndoo

r con

trolle

r boa

rd

Ele

ctro

nic

linea

r exp

an. v

alve

*B

Cap

acito

r (fo

r MF)

F

an m

otor

LE

V

T

A

.B

I.B

C M

F S

YMBO

L

<D

S>

<D

P>

SYM

BOL

N

AM

E

TH

22

TH23

The

rmis

tor (

inle

t tem

p.de

tect

ion)

TH

21

X04~

X06

<F

2>

F1

Fus

e A

C25

0V 6

.3A

F F

use

AC

250V

5A

F

S

.B S

urge

abs

orbe

r boa

rd

Dra

in s

enso

r

Dra

in P

ump

Col

or/E

xter

nal S

tatic

Pre

ssur

eR

ed/2

00P

a (a

t 220

,230

,240

V)

Blu

e/50

Pa

(at 2

20V

),100

Pa(

at 2

30,2

40V

)W

hite

/100

Pa

(at 2

20V

),150

Pa(

at 2

30,2

40V

)

C

TB2

1 23 4 5 6 7 80

8 76

54321

09

9ABCDEF1

90

2 3 46

578

TB5(

TRA

NS

MIS

SIO

N T

ER

MIN

AL

BE

D)

TB15

(TR

AN

SM

ISS

ION

TE

RM

INA

L B

ED

)

56

SW

5

T

ZNR

CN

82C

N62

(Blu

e)

SW

4C

N42

4321

43

21

7 8

TH2321

CN

29

8 7 123456

A.B

CN

3T

31

M1

M2

SW

1

SW

2S

W3

TH22

TH21

DS

MF

LEV

NL

62

51

7

88 9

4

CN

31D

rain

sen

sor

31

33

11

32

22

4433

11

13

31

11

1

654321

CN

81

CN

20C

N21

CN

31C

N60

CN

TC

ND

CN

PFA

N3

X01

X05

X06

X04

CN

2MI.B

12

12C

N3A

13

*B

(Red

)

39

81

98

631

9(W

hite

)56

44

8 8

9 95

31 31

DP

1 2

*A

S.B

DS

A1

CN

11 3

ZNR

1

S

W14

(Con

nect

ion

No.

)

SW

11(1

st d

igit)

S

W12

(2nd

dig

it)

AC

250V

5A

F

AC25

0V6.

3A F

F1

F221

1 2

INS

IDE

SE

CTI

ON

OF

CO

NTR

OL

BO

X

S(S

HIE

LD)

PE

Page 13: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

12

PEFY-P200·250VMH-E

conn

ecto

r to

alte

r the

ext

erna

l sta

tic p

ress

ure

on th

e fa

n

BR

EA

KE

R

*NO

TE 1

*NO

TE 1

,2

*A c

onne

ctor

is a

ttach

ed to

the

drai

n lif

t up

mec

hani

sm,

whi

ch is

an

optio

nal p

art.

* NO

TE 1

Sw

itch(

for m

odel

sel

ectio

n) S

witc

h(fo

r vol

tage

sel

ectio

n)

Sw

itch(

for m

ode

sele

ctio

n)

Sw

itch

(con

nect

ion

No.

set)

Sw

itch

(2nd

dig

it ad

dres

s se

t)

Sw

itch(

for c

apac

ity c

ode)

Sw

itch(

for m

ode

sele

ctio

n)

The

rmist

or (p

iping

tem

p.de

tecti

on/g

as)

The

rmist

or (p

iping

temp

.detec

tion/l

iquid)

Aux

.rela

y

PO

WE

R S

UP

PLY

3N~

380/

400/

415V

50/

60H

z

TO D

UC

T

TO O

UTD

OO

R U

NIT

B

C C

ON

TRO

LLE

R

RE

MO

TE C

ON

TRO

LLE

R

CA

UTI

ON

;1.T

o pr

otec

t Fan

mot

or fr

om a

bnor

mal

cur

rent

, Ove

r cur

rent

rela

ys<5

1F>

is

inst

alle

d. T

here

fore

, do

not c

hang

e fa

ctor

y se

t val

ue o

f Ove

r

cur

rent

rela

ys.

52

F C

onta

ctor

(fan

mot

or)

Ove

r cur

rent

rela

y (fa

n m

otor

)

49

F I

nner

ther

mos

tat

51

F

<F

2>

insi

de <

> is

the

optio

nal p

arts

.

N

AM

ES

YM

BO

L E

XP

LAN

ATIO

N

Pow

er s

ourc

e te

rmin

al b

ed T

rans

mis

sion

term

inal

bed

TB

5Tr

ansm

issi

on te

rmin

al b

edTB

15

TB

2

Tra

nsfo

rmer

Add

ress

boa

rd I

ndoo

r con

trolle

r boa

rd

Ele

ctro

nic

linea

r exp

an. v

alve

Fan

mot

or

LEV

1,LEV

2

T

A

.B

I.B M

F S

YMBO

L

<D

S>

<D

P>

F

1 F

use

AC

250V

6.3

A F

Fus

e A

C25

0V 5

A F

S

.B S

urge

abs

orbe

r boa

rd D

rain

sen

sor

Dra

in P

ump

SW

4(I.B

) S

W5(

A.B)

SW

1(A.

B) SW

14(A

.B) SW

12(A

.B) SW

11(A

.B)

SW

3(I.B

) S

W2(

I.B) S

witc

h (1

st d

igit

addr

ess

set)

SYM

BOL

N

AM

E

TH

22

TH23

The

rmis

tor (

inle

t tem

p.de

tect

ion)

TH

21

X04~

X06

NO

TE;1

.The

par

t of t

he b

roke

n lin

e in

dica

tes

the

circ

uit f

or o

ptio

nal p

arts

.

2. *

A in

the

char

t is

the

conn

ecto

r for

a d

rain

pum

p te

st ru

n op

erat

ion.

(The

Dra

in P

ump

oper

ates

con

tinuo

usly

if th

e co

nnec

tor i

s in

serte

d

a

nd th

e po

wer

is s

uppl

ied.

)

A

fter t

he te

st ru

n, m

ake

sure

to re

mov

e th

e *A

con

nect

or.

3

.The

wiri

ngs

to T

B2,

TB5

show

n in

dot

ted

line

are

field

wor

k.

4.M

ark

i

ndic

ates

term

inal

bed

,

con

nect

or,

b

oard

inse

rtion

con

nect

or o

r fas

teni

ng c

onne

ctor

of c

ontro

l boa

rd.

( 5A

)

Col

our/E

xter

nal S

tatic

Pre

ssur

e B

lue/

110P

a(at

380

V),1

30P

a(at

400

,415

V)

Whi

te/2

20P

a(at

380

V),2

60P

a(at

400

,415

V)

TB2

TB5(

TRA

NS

MIS

SIO

N T

ER

MIN

AL

BE

D)

TO M

A R

EM

OTE

CO

NTR

OLL

ER

TB15

(TR

AN

SM

ISS

ION

TE

RM

INA

L B

ED

)

8 75

6432

09

1F E D C B A 9

90

1 2 3 45

6780 87

65432151

F

Dra

in s

enso

r

56

52F

PE

NL3L2

PE

CR

SW

5

2 1

I.B

CN

2MFA

N3

CN

PC

ND

CN

TC

N60

CN

31C

N21

CN

20

CN

81

1 2 3 4 5 6

11

11

13

15 8

22

23

31

33

CN

31

4

6

15

26

L1

DP

MF

DS

TH22

SW

3S

W2

13

CN

3T

A.B

6 5 4 3 2 178

CN

29 12

TH23

87

12

34

1 2 3 4C

N42SW

4

31

TH21

7 95

94

(Blu

e)

CN

62C

N82

ZNR

82

3

49F

1 12

34

56

89

52F

*AT

12

34

56

LEV

1

12

34

56

65

43

21

65

43

21

LEV

2

65

43

21

F1

F2

S

W12

(2nd

dig

it)

SW

11(1

st d

igit)

S

W14

(Con

nect

ion

No.

)

ZNR1

31CN

1

DSA1

S.B

(Whi

te)

SW

1

M2

M1

3 1C

N3A

2 1

1 221

1 2

INS

IDE

SE

CTI

ON

OF

CO

NTR

OL

BO

X

LEV

ada

pter

boa

rd

S(S

HIE

LD)

X01

X05

X06

X04

AC25

0V6.

3A F

AC

250V

5A

F

Page 14: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

13

REFRIGERANT SYSTEM DIAGRAM6

Strainer (#100mesh)

Strainer (#100mesh)

Heat exchanger

Room temperature thermistor TH21

Gas pipe thermistor TH23

Liquid pipe thermistor TH22

Linear expansion valve

Gas pipe

Flared joints(Type 40~140)Brazed joints(Type 200·250)

Gas pipe

PEFY-P40VMH-E PEFY-P50VMH-E

Liquid pipe

CapacityItem

ø 12.7 <1/2F> (R410A)ø 12.7 <1/2F>

ø 6.35 <1/4F>

ø 15.88 <5/8F>

ø 9.52 <3/8F>

ø 15.88 <5/8F> (R22,R407C)

ø 6.35 <1/4F> (R410A)ø 9.52 <3/8F> (R22,R407C)

PEFY-P63,71,80VMH-E

Gas pipe

PEFY-P100,125,140VMH-E PEFY-P200VMH-E

Liquid pipe

CapacityItem

ø 19.05 <3/4> (R410A)

ø 9.52 <3/8F>

ø 25.4 <1> (R22,R407C)ø 15.88 <5/8F> (R410A)ø 19.05 <3/4F> (R22,R407C)

ø 9.52 <3/8> (R410A)ø 12.7 <1/2> (R22,R407C)

ø 22.2 <7/8> (R410A)ø 28.58 <1-1/8> (R22,R407C)

ø 9.52 <3/8> (R410A)ø 12.7 <1/2> (R22,R407C)

PEFY-P250VMH-E

Page 15: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

14

7 TROUBLE SHOOTING

7-1. How to check the parts

Room temperaturethermistor (TH21)Liquid pipe thermistor

(TH22)Gas pipe thermistor

(TH23)

Trans

Fan motor

Fan motor

Linear expansionvalve

Disconnect the connector, then measure the resistance using a tester.(Sorrounding temperature 10°C~30°C)

Disconnect the connector and measure the resistance using a tester.

Measure the resistance between the terminals using a tester. (at 20°C)

Measure the resistance between the terminals usinga tester.

Disconnect the connector then measure the resistance valve using a tester.

Drain Pump(Drain water lift up kit)

Drain sensor(Drain water lift up kit)

Disconnect the connector then measure the resistancevalve using a tester.(Sorrounding temperature 20°C~30°C)

(Refer to the thermistor characteristic graph)Normal

4.3kΩ~9.6kΩAbnormal

Open or short

CNT(1)-(3)Normal

App.15ΩCN3T(1)-(3) App.4Ω

Abnormal

Open or short

Motor terminalor

Relay connectorNormal

P40·50 P63Abnormal

Gray-Orange 68.8Ω

Open or shortGray-BlackGray-BrownGray-Blue

53.73Ω59.92Ω74.17Ω

47Ω37.29Ω39.81Ω49.8Ω

P7132.9Ω27.56Ω30.64Ω38.31Ω

P8033.3Ω27.1Ω

28.56Ω36.82Ω

P100·125·14014.05Ω9.11Ω9.87Ω12.89Ω

Motor terminalor

Relay connectorNormal Abnormal

Red-White 5Ω

Open or short

White-BlackRed-Black

Brown-Gray

5Ω5Ω

6.08ΩGray-Yellow

Brown-Yellow6.08Ω6.08Ω

Normal(1)-(5)

White-Red150Ω ±10%

Abnormal

Open or short(2)-(6)

Yellow-Brown(3)-(5)

Orange-Red(4)-(6)

Blue-Brown

CNT3T

13

CN3T

123456789

Gray

BlueBlackOrangeBlown

RedRed

Protector Relay connector

Protector

Relay connector

4

189

2

536

Brown

RedOrangeOrange

White

GrayBlack

Yellow

1

3

Red

Red

123456

LEV

White

YellowOrange

BlueRed

Brown

CN60

Parts name Check points

PEFY-P40~140

PEFY-P200·250 Measure the resistance between the terminals using a tester. (at 20°C)

Normal399Ω

AbnormalOpen or short

(Refer to the thermistor characteristic graph)

<Thermistor characteristic graph>Room temperature thermistor(TH21)Liquid pipe thermistor(TH22)Gas pipe temperature thermistor(TH23)Drain sensor(DS)Thermistor R0=15kΩ ± 3%Fixed number of B=3480kΩ ± 2%Rt=15exp 3480( ) 0°C 15kΩ10°C 9.6kΩ20°C 6.3kΩ25°C 5.2kΩ30°C 4.3kΩ40°C 3.0kΩ

0

10

20

30

40

50

-20 -10 0 10 20 30 40 50Temperature (°C)

Res

ista

nce

(KΩ

)

1273+t

1273

0°C/6.0kΩ, 10°C/3.9kΩ20°C/2.6kΩ, 25°C/2.2kΩ30°C/1.8kΩ, 40°C/1.3kΩ1

3

Page 16: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

15

7-2. Setting of address switch Make sure that power source is turning off.

ONOFF

1 2 3 4 5 6 7 8 9 10

SW1

Indoor unit control board

< At delivery (All models)>

Refer to the next page for SW2,SW3 setting.

SW2 SW3

1)In case using network remote controller, address is set by rotary switches.(SW11,SW12)* It is not necessary setting address in case of using unit remote controller.

2) Indoor unit address setting rule is different by each field work.Refer to install manual of outdoor unit , operate the address setting.

3)Setting the address is combination of SW11(1st digit address setting) and SW12(2nd digit address setting).Address " 3 " setting is composed SW11 " 3 " and SW12 " 0 " .Address " 25 " setting is composed SW11 " 5 " and SW12 " 2 " .

Indoor unit do not run without address setting in field.

CN62

SW1

SW7

ON

ONON

W254665G06JP2

SW14

FP-AD-R

CN82 68 1 1

240V

220V

1

1

0 1 12

AS

SY

2

3 4 5 6 7 8 9 1021

3 4 5 6 7 8 9

G 2 3

1

1O F F

2 3

3

A B C D E F

10JP1

SW5SWCSWA

1

32

SW12 SW110123456789ABC

DEF 0 1 2

3

45678

9 0 1 23

45678

9

ONOFF

1 2 543

SW 4< At delivery (All models)>

SW4

Page 17: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

16

7-3. Setting of Dip-switch (at delivery)

7-4. Attention for test run

1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 910 1 2 31 2 3 4 5 6

SW1 SW2ONOFF

ONOFF

ONOFF

ONOFF

SW3 SW4

5

ONOFF

220V240V

SW5

1 2 3

SW4

5

1 2 3

SW4

5

1 2 3

SW4

5

1 2 3

SW4

5

1 2 3

SW4

5

1 2 3

SW4

5

1 2 3

SW4

5

PEFY-P40VMH-E

1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 9101 2 3 4 5 6

ONOFF

220V240V

SW5PEFY-P50VMH-E

SW1 SW2ONOFF

ONOFF

ONOFF

ONOFF

SW3

SWA1

SWCStandardIndicate

Models Dip-SW

ONOFF

220V240V

SW5PEFY-P71VMH-E

SW1 SW2ONOFF

ONOFF

ONOFF

ONOFF

SW3

1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 9101 2 3 4 5 6

1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 9101 2 3 4 5 6ONOFF

220V240V

SW5PEFY-P63VMH-E

SW1 SW2ONOFF

ONOFF

ONOFF

ONOFF

SW3

ONOFF

220V240V

SW5PEFY-P100VMH-E

SW1 SW2ONOFF

ONOFF

ONOFF

ONOFF

SW3

1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 9101 2 3 4 5 6

ONOFF

220V240V

SW5PEFY-P125VMH-E

SW1 SW2ONOFF

ONOFF

ONOFF

ONOFF

SW3

1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 9101 2 3 4 5 6

ONOFF

220V240V

SW5PEFY-P140VMH-E

SW1ONOFF

SW2ONOFF

ONOFF

SW3ONOFF

1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 9101 2 3 4 5 6

ONOFF

220V240V

SW5PEFY-P200VMH-E

SW1ONOFF

SW2ONOFF

ONOFF

SW3ONOFF

SW4

51 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 910 1 2 3

SW4

5

4

4

4

4

4

4

4

4

4

41 2 3

1 2 3 4 5 6

ONOFF

220V240V

SW5PEFY-P250VMH-E

SW1ONOFF

SW2ONOFF

ONOFF

SW3ONOFF

1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 9101 2 3 4 5 6

1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 9101 2 3 4 5 6

ONOFF

220V240V

SW5PEFY-P80VMH-E

SW1 SW2ONOFF

ONOFF

ONOFF

ONOFF

SW3

Equipment which is attached drain water lift up kit can be testedpump out test when power supplied.(connect the connector(A))

< Drain-up machine >Test run Connector (red)(A)

After pump out test, remove the connector and put in the dummy connector.

After test run,remove the connector (A)(Fig .1)

7-4. Function the

Symbol Silk display LED operation under normal stateLightingLED1 Main power source At applying main power source (indoor unit 200V)

At receiving M-NET transmission power sourceLED2 Transmission power source Lighting

7-5. Function the unit of the indoorLED service board

Page 18: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

17

8 DISASSEMBLY PROCEDURE

OPERATING PROCEDURE PHOTOSModels 40~1401.Removing the control box cover

(1) Remove the fixing screws (two) of the control box (A), andremove the cover. (Fig. 1)

*At this stage, the following servicing is possible.

1 Operation and check of the switches (listed below) whichare on the control board.• Dip switch SW2 · · · · · · · · · · ·Capacity code setting• Dip switch SW3 · · · · · · · · · · ·Function change• Dip switch SW4 · · · · · · · · · · ·Model code setting

2 Connection check of the lead wires (listed below) which areconnected to the controller board.• Power supply lead wire.• Network remote contoller transmission lead wire.• Fan motor lead wire.• LEV lead wire• Intake air sensor lead wire• Liquid piping sensor lead wire• Gas piping sensor lead wire• Power supply transformer lead wireAddress board lead wire(• Drain pump lead wire)(• Drain sensor lead wire)

3 Control board exchange4 Condenser exchange5 Power supply transformer exchange6 Arrest exchange7 Intake air sensor exchange

( ):Optional parts

2.Removing the terminal bed cover (1) Remove the fixing screws (two) of the terminal bed cover

(B), and remove the cover. (Fig. 2)

*At this stage, the following servicing is possible.(Fig. 3)

1 Operation and check of the switches (listed below) whichare on the adress board.• Rotary switches SW11, 12 · · · Address setting• Rotary switch SW14 · · · · · · · · ·Branch port setting• Dip switch SW1 · · · · · · · · · · · · ·Function change (main)

2 Address board exchange3 Power supply terminal bed exchange4 Transmission terminal bed exchange

8-1. CONTROL BOX Be careful on removing heavy parts.

Fig.1

Fig.2

Fig.3

(A)

(B)

Page 19: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

18

OPERATING PROCEDURE PHOTOS

Be careful on removing heavy parts.

Fig.4

Fig.5

Models 200·2501.Removing the control box cover

(1) Remove the fixing screws (four) of the control box cover (C),and remove the cover. (Fig. 4)

*At this stage, the following servicing is possible.(Fig. 5)

1 Operation and check of the switches (listed below) whichare on the control board.• Dip switch SW2 · · · · · · · · · · ·Capacity code setting• Dip switch SW3 · · · · · · · · · · ·Function change• Dip switch SW4 · · · · · · · · · · ·Model code setting

2 Connection check of the lead wires (listed below) which areconnected to the controller board.• Power supply lead wire.• Network remote contoller transmission lead wire.• Fan motor lead wire.• LEV lead wire• Intake air sensor lead wire• Liquid piping sensor lead wire• Gas piping sensor lead wire• Power supply transformer lead wire• Address board lead wire(• Drain pump lead wire)(• Drain sensor lead wire)

3 Control board exchange4 Power supply transformer exchange5 Arrest exchange6 Intake air sensor exchange7 Operation and check of the switches (listed below) which

are on the address board• Rotary switches SW11, 12 · · · ·Address setting• Rotary switch SW14 · · · · · · · · · ·Branch port setting• Dip switch SW1· · · · · · · · · · · · · ·Function change (main)

8 Address board exchange9 Power supply terminal bed exchange10 Transmission terminal bed exchange

( ):Optional parts

(C)

Page 20: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

19

Fig.1

Fig.2

Fig.3

Fig.4

8-2. FAN and FAN MOTOR

OPERATING PROCEDURE PHOTOSModels 40~1401.Removing the control box.

(1) Remove the control box cover and terminal bed cover withprocedure 8-1.

(2) Remove the fan motor connectors.(3) Remove the fixing screws (two) of the control box and slide

the control box to remove.(Fig. 1)(4) Move the control box to place that is not block operation.

(Fig. 2)

2.Removing the fan motorModels 40~80

*After motor base (D) and bell mouse (C) attached the fancase (B) removed,motor (A) can be pull with motor baseand fan along rail.

(1) Remove the fan motor connector (E).(2) Loosen the fixing screws (F) (three) of the bell mouse (C),

and removed the bell mouse (D) turning screws in directionarrow (counterclockwise).(Fig. 3)

(3) Remove the fixing screws (four) of the motor base(D).

Notice: It's necessary using the driver over 30cm length toremove the fixing screws (a) .(Fixing screws are placed back)

Be careful on removing heavy parts.

Fixing screws

Motor base (D)Fixing screws (a)

Control box

Control box

(A)

(E)

(B)

(C)

(D)

Fixing screws (F)Loosen fixing screws (not remove)

Models 40~63

Page 21: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

20

(A)

(D)

Arrow 1

Motor (A)

OPERATING PROCEDURE PHOTOS(4) Slide the motor (A) with motor base (D) in direction of allow

1. (Fig. 5)

Models 100~140

*Motor maintenance procedure is almost 40~80 modelsprocedure.Models 100~140 have twin shaft motor.After removing thefan and fan case which are in front of motor,remove themotor.

(1) Remove the bell mouse of the front fan motor with proceduremodels 40~140.

(2) Loosen the setting screws of the front fan , removed the fan.(3) Remove the front fan case.(4) Operate with procedure models 40~80.

Notice: Fixing screws of the fan case are shown Fig. 7.Remove the fixing screws (H) ,fan case can be removed.

Fig.5

Fig.6

Fan case

Service

side

Fan case fixing screws (H)

Fig.7

Be careful on removing heavy parts.

Page 22: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

21

Fig.7

Fig.8

Fig.9

Fig.10

OPERATING PROCEDURE PHOTOSModels 200·2501.Removing the control box.

(1) Remove the control box cover1 with procedure 8-1.(2) Remove the fixing screws (four) of the control cover 2, and

remove the control cover2. (Fig. 7)(3) Remove the fan motor connectors.(4) Remove the fixing screws (three) of the control box and

remove the control box (Fig. 8)(5) Move the control box to place that is not block operation.

(Fig. 9)

2.Removing the fan motor

*After the fan (A) ,the fan case (B) and the bell mouse (C)removed, motor can be pull with motor base and inner fanalong rail.

(1) Remove the fixing screws (three) of the bell mouse (C), andremove the bell mouse (C). (Fig. 3)

(2) Loosen the setting screws (G) of the front fan , removed thefan.(Fig. 10)

Be careful on removing heavy parts.

Control box cover 2

Control box

Control box

(A)

(E)

(B)

(C)

(D)

Fixing screws (F)

(G)

Page 23: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

22

OPERATING PROCEDURE PHOTOS(3) After removing the fixing screws (H)(as shown models

100~140) of the front fan case(B) and remove the fan.Pull the fan case (B).

(4) Remove the fixing screws (K)(three) of the bell mouse (J)attached fan case (L), and remove the bell mouse (J).(Fig.12)

(5) Remove the fixing screws (four) of the motor base(D).

Notice: It's necessary using the driver over 30cm length toremove the fixing screws (a) .(Fixing screws are placed back)(Fig. 13)

(6) Slide the motor (M) with motor base (D) in direction of arrow2 . (Fig. 14)

Notice: It's not necessary removing the fan case (L).

Fig.11

Fig.12

Fig.14

Be careful on removing heavy parts.

Fig.13

Fig.15

(B)

Fixing screws (H)

(J)

Fixing screws (K)(L)

(D)

Fixing screws

Motor base(D)Fixing screws (a)

Motor (M)

(M)

(D)

Arrow 2

Page 24: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

23

8-3. LEV,THERMISTOR (Liquid/Gas piping temperature detection)

OPERATING PROCEDURE PHOTOSModels 40~1401.Removing the LEV.

(1) Remove the control box cover with procedure 8-1.(2) Remove the fixing screws (four) of the heat exchanger cover

(A), and remove the cover (A).(Fig. 1)(3) Remove the LEV driving motor with a double spanner.(Fig. 2)

2.Removing the thermistors.(1) Remove the thermistors from the thermistor holders which

are installed on the piping.(Fig. 2)(liquid piping : fine piping , gas piping : thick piping)

Models 200·2501.Removing the LEV. (These models have 2 LEV)

(1) Remove the fixing screws (three) of the heat exchanger cover(A), and remove the cover (A).

(2) Remove the fixing screws (four) of the maintenance cover(B), and remove the cover (B).(Fig. 3)

(3) Remove the LEV driving motor with a double spanner.(Fig. 4)

2.Removing the thermistors.(1) Remove the thermistors from the thermistor holders which

are installed on the piping.(Fig. 4)(liquid piping : fine piping , gas piping : thick piping)

Fig.1

Fig.2

Fig.3

LEV Thermistor

Fig.4

Be careful on removing heavy parts.

(A)

Fixing screws

LEV Thermistor

(A)

(B)

Fixing screws

Fixing screws

Page 25: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

24

8-4. HEAT EXCHANGER

OPERATING PROCEDURE PHOTOSModels 40~1401.Removing the heat exchanger.

(1) Remove the heat exchanger cover with procedure 8-3-1.(2) Remove the bottom plate which is air outlet side.(fixing

screws : ten) (Fig. 1)(3) Remove the drainpan.(Fig. 2)

Fig.1

Fig.2

Fig.3

Be careful on removing heavy parts.

Bottom plate

Drainpan

Fixing screws

Page 26: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

25

OPERATING PROCEDURE PHOTOS(4) Remove the maintenance cover.(fixing screws : two) (Fig. 4)(5) Remove the heat exchanger.(fixing screws : four) (Fig. 3,5)

*Removerd heat exchanger is as shown Fig .6

Fig.4

Fig.5

Fig.6

Be careful on removing heavy parts.

Fixing screwsMaintenance cover

Fixing screws

Page 27: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

26

Bottom plate

Drainpan

Fixing screws

OPERATING PROCEDURE PHOTOSModels 200·2501.Removing the heat exchanger.

(1) Remove the refrigerant piping and drain hose from mainunit.(Be care that water is not leaking from drain hose. )

(2) Remove the power supply wire and the transmission line.(Make sure that power source is turning off. )

(3) Pull down the main unit.(4) Turn over the main unit upside the bottom plate (5) Remove the bottom plate which is air outlet side.(fixing

screws : fifteen) (Fig. 7)(6) Remove the drainpan.(Fig. 8)

Fig.7

Fig.8

Fig.9

Be careful on removing heavy parts.

Page 28: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

27

OPERATING PROCEDURE PHOTOS(7) Remove the fixing screws (three) of the heat exchanger

cover, and remove the cover. Remove the fixing screws(four) of the maintenance cover, and remove the cover. (Fig.10)

(7) Remove the heat exchanger.Fixing screws(non-piping side) : two (Fig. 9)Fixing screws(piping side) : two (Fig. 11)

*Removerd heat exchanger is as shown Fig.12

Fig.10

Fig.11

Fig.12

Be careful on removing heavy parts.

Fixing screws

Fixing screws (A)

Maintenance cover

Fixing screws

Page 29: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

28

8-5. CONTROL BOX INSIDE LAYOUT

Models 40~140

Models 200·250

X06 X05 X04

CN42

CN81

FAN2

FAN3

CNP CNT CND CN3T

CN2M

CN20

CN60

LEV1

SW4SW3SW2CN60 CN27CN52

CN25

CN

51

CN

41

CN

50CN

20

CN3R

CN29

CN21

CN2M

CN3TCNDCNTCNP

FAN3

FAN2

CN81

CN

42

CN23

CN26

CN24

X04X05X06

DSA board

Magnet contactor

Trans

Trans

DSA board

Condenser(for motor)

Power sourse terminal bed

Power sourse terminal bed

Address board

Address board

LEV adapter board

Transmission terminal bed

Transmission terminal bed

Indoor unitcontoller board

Indoor unitcontoller board

CN62CN82

SW12 SW11

SW1

SW14

SWA SWC

STR2012

SW5

SW5

STR2012

SW11SW12SW14

SWCSWA

SW1 CN82 CN62

L N 21

Page 30: Mitsubishi Electric PEFY-P VMH-E Technical & Service Manual · TECHNICAL & SERVICE MANUAL Air-Conditioners For Building Application  2004 ... installation by the

29

8-6. SENSOR POSITION

PEFY-P40VMH-E PEFY-P50·63VMH-E

PEFY-P71·80VMH-E PEFY-P100·125VMH-E

PEFY-P140VMH-E PEFY-P200·250VMH-E

Liquid sensor

Liquid sensor(200·250)

Liquid sensor

Liquid sensor

Liquid sensor

Liquid sensorGas sensor Gas sensor

Gas sensor

Gas sensor

Gas sensor(125)

Gas sensor(250)Gas sensor(200)

Gas sensor(100)