  • HP BladeSystem Onboard Administrator User Guide Version 2.10

    Part Number 416216-006 November 2007 (Sixth Edition)

  • Copyright 2006, 2007 Hewlett-Packard Development Company, L.P.

    The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.

    Confidential computer software. Valid license from HP required for possession, use or copying. Consistent with FAR 12.211 and 12.212, Commercial Computer Software, Computer Software Documentation, and Technical Data for Commercial Items are licensed to the U.S. Government under vendors standard commercial license.

    Microsoft, Windows, and Windows NT are U.S. registered trademarks of Microsoft Corporation. Windows Server 2003 is a U.S. trademark of Microsoft Corporation. Java is a trademark of Sun Microsystems.

    Audience assumptions This document is for the person who installs, administers, and troubleshoots servers and storage systems. HP assumes you are qualified in the servicing of computer equipment and trained in recognizing hazards in products with hazardous energy levels.

  • Contents 3

    Contents

    Introduction.................................................................................................................................. 7 Overview ................................................................................................................................................. 7 Access requirements .................................................................................................................................. 7 Running Onboard Administrator for the first time ........................................................................................... 8 Signing in to the Onboard Administrator GUI ............................................................................................... 9 Running the setup wizard ......................................................................................................................... 10 Using online help .................................................................................................................................... 11 Changing enclosure and device configurations ........................................................................................... 11 Recovering the administrator password ...................................................................................................... 11 Flash disaster recovery............................................................................................................................. 12

    HP BladeSystem c7000 Enclosure hardware installation.................................................................. 13 Installing Onboard Administrator modules .................................................................................................. 13 Onboard Administrator cabling ................................................................................................................ 14

    HP BladeSystem Insight Display .................................................................................................... 16 HP BladeSystem c7000 Insight Display components..................................................................................... 16 HP BladeSystem c3000 Insight Display components..................................................................................... 17 Insight Display overview........................................................................................................................... 17 Accessing the HP BladeSystem c3000 Insight Display .................................................................................. 18 Running the Insight Display installation steps ............................................................................................... 19 Navigating the Insight Display .................................................................................................................. 24

    Health Summary screen.................................................................................................................. 25 Enclosure Settings screen................................................................................................................ 26 Enclosure Info screen ..................................................................................................................... 27 Blade or Port Info screen ................................................................................................................ 28 Turn Enclosure UID On/Off screen................................................................................................... 29 View User Note screen................................................................................................................... 31 Chat Mode screen ......................................................................................................................... 31

    Insight Display errors ............................................................................................................................... 32 Power errors ................................................................................................................................. 32 Cooling errors............................................................................................................................... 32 Location errors .............................................................................................................................. 32 Configuration errors....................................................................................................................... 33 Device failure errors....................................................................................................................... 33

    First Time Setup Wizard .............................................................................................................. 34 Before you begin..................................................................................................................................... 34 Enclosure Selection screen........................................................................................................................ 35 Configuration Management screen ............................................................................................................ 37 Rack and Enclosure Settings screen............................................................................................................ 39 Administrator Account Setup screen........................................................................................................... 41 Local User Accounts screen....................................................................................................................... 42 Enclosure Bay IP Addressing ..................................................................................................................... 43 Directory Services Configuration screen ..................................................................................................... 46 Onboard Administrator Network Settings screen ......................................................................................... 48 Enclosure SNMP Settings screen................................................................................................................ 50

  • Contents 4

    Power Management screen ...................................................................................................................... 51 Finish..................................................................................................................................................... 53

    Navigating Onboard Administrator .............................................................................................. 54 Navigation overview ............................................................................................................................... 54 Tree view ............................................................................................................................................... 54 Graphical view navigation ....................................................................................................................... 57

    Rack View.................................................................................................................................. 60 Rack View screen .................................................................................................................................... 60 Topology modes ..................................................................................................................................... 61 Rack Topology tab .................................................................................................................................. 62 Rack Power and Thermal tab .................................................................................................................... 64 Rack Firmware Summary tab .................................................................................................................... 65

    Configuring the HP BladeSystem c7000 enclosure and enclosure devices ......................................... 66 Viewing the status screens ........................................................................................................................ 66 Enclosure settings .................................................................................................................................... 67

    Selecting enclosures....................................................................................................................... 67 Enclosure Settings screen................................................................................................................ 67 AlertMail ...................................................................................................................................... 70 Date and Time .............................................................................................................................. 72 Network Access ............................................................................................................................ 74 SNMP Settings .............................................................................................................................. 75 Enclosure Virtual Buttons tab ........................................................................................................... 77 Configuration Scripts ..................................................................................................................... 77 FRU Summary ............................................................................................................................... 78 Active to Standby .......................................................................................................................... 80 DVD Drive .................................................................................................................................... 81 Device Summary ........................................................................................................................... 82 Reset Factory Defaults .................................................................................................................... 82

    Managing enclosures .............................................................................................................................. 83 Powering off the enclosure.............................................................................................................. 83 Linking enclosures.......................................................................................................................... 83 Managing multiple enclosures ......................................................................................................... 83

    Onboard Administrator Module ................................................................................................................ 85 Active Onboard Administrator screen............................................................................................... 85 Active Onboard Administrator Virtual Buttons tab .............................................................................. 86 TCP/IP Settings screen ................................................................................................................... 87 Information tab.............................................................................................................................. 89 Certificate Request tab ................................................................................................................... 90 Certificate Upload tab.................................................................................................................... 92 Firmware update ........................................................................................................................... 93 System log.................................................................................................................................... 94 Standby Onboard Administrator module .......................................................................................... 97 Standby Onboard Administrator Virtual Buttons tab ........................................................................... 98 Standby Certificate Request tab....................................................................................................... 98 Standby Certificate Upload tab ..................................................................................................... 100

    Device bays.......................................................................................................................................... 100 Device Bay Overview screen......................................................................................................... 100 Device Bay Status tab .................................................................................................................. 102 Server blade information tab......................................................................................................... 107 Boot Options tab ......................................................................................................................... 109 Device Bay Status screen .............................................................................................................. 110

  • Contents 5

    IML Log tab................................................................................................................................. 110 Storage blades............................................................................................................................ 111

    Interconnect bays .................................................................................................................................. 115 Interconnect Bay Summary screen.................................................................................................. 115 Interconnect Bay screen................................................................................................................ 116 Interconnect Bay Virtual Buttons ..................................................................................................... 117 Interconnect Bay Port Mapping screen............................................................................................ 118

    Enclosure power management ................................................................................................................ 119 Power Supplies ........................................................................................................................... 119 Power Management settings ......................................................................................................... 119 Setting power management options ............................................................................................... 121 Power management planning........................................................................................................ 123 Enclosure Power Meter................................................................................................................. 124 Enclosure Power Meter Table view................................................................................................. 126

    Enclosure DVD/CD-ROM Drive ............................................................................................................... 127 DVD/CD-ROM Drives .................................................................................................................. 127 Interactive installation and configuration of DVD/CD-ROM drive ....................................................... 128 Unattended OS deployment .......................................................................................................... 135 Ad-hoc access to DVD-based media for application installation or data import .................................... 140 Updating blade firmware with HP Smart Update Manager ............................................................... 140

    Fans and cooling management ............................................................................................................... 141 Fan management and settings ....................................................................................................... 141 Fan Zones .................................................................................................................................. 145 Thermal monitoring...................................................................................................................... 146 c7000 Fan location rules.............................................................................................................. 151 c3000 Fan location rules.............................................................................................................. 153

    Managing users .................................................................................................................................... 153 Users/Authentication ................................................................................................................... 153 Signed-in users............................................................................................................................ 153 User roles and privilege levels....................................................................................................... 154 User accounts ............................................................................................................................. 155 Directory Settings screen .............................................................................................................. 157 Directory Groups screen............................................................................................................... 158 Uploading a Certificate ................................................................................................................ 159 SSH Administration...................................................................................................................... 160 HP SIM integration ...................................................................................................................... 160 Edit Local User Certificate Information tab....................................................................................... 161

    c3000 Fan location rules ....................................................................................................................... 162 Two-Factor Authentication....................................................................................................................... 162

    Two-Factor Authentication Certificate Information tab ....................................................................... 163 Two-Factor Authentication Certificate Upload tab............................................................................. 163

    Virtual Connect Manager ....................................................................................................................... 163 iLO 2 Integration................................................................................................................................... 164

    Port mapping ........................................................................................................................... 165 Port mapping explained ......................................................................................................................... 165 Mapping half-height c3000 enclosures .................................................................................................... 167 Mapping full-height c3000 enclosures ..................................................................................................... 169

    Using the command line interface ............................................................................................... 171 Command line overview......................................................................................................................... 171

    Using the serial connection ........................................................................................................ 172 Setting up Onboard Administrator using serial connection .......................................................................... 172

  • Contents 6

    Using configuration scripts ......................................................................................................... 173 Configuration scripts.............................................................................................................................. 173

    Troubleshooting ........................................................................................................................ 175 Onboard Administrator error messages.................................................................................................... 175 Onboard Administrator factory default settings.......................................................................................... 181

    Enabling LDAP Directory Services Authentication to Microsoft Active Directory................................. 182 Certificate Services ................................................................................................................................ 182 Preparing the directory........................................................................................................................... 182 Uploading the DC Certificate (optional).................................................................................................... 183 Creating directory groups....................................................................................................................... 185 Testing the directory login solution........................................................................................................... 187 Troubleshooting LDAP on Onboard Administrator ...................................................................................... 188

    Technical support...................................................................................................................... 190 Before you contact HP............................................................................................................................ 190 HP contact information........................................................................................................................... 190

    Acronyms and abbreviations...................................................................................................... 191

    Index....................................................................................................................................... 194

  • Introduction 7

    Introduction

    Overview HP BladeSystem Onboard Administrator is the enclosure management processor, subsystem, and firmware base used to support the HP BladeSystem c7000 and all the managed devices contained within the enclosure.

    Onboard Administrator provides a single point from which to perform basic management tasks on server blades or switches within the enclosure. Utilizing this hardwired knowledge, Onboard Administrator performs initial configuration steps for the enclosure, allow for run-time management and configuration of the enclosure components, and informs you of problems within the enclosure through email, SNMP, or the Insight Display.

    HP recommends that you read the HP BladeSystem c7000 Enclosure User Guide before moving on to HP BladeSystem Onboard Administrator setup. Reading this guide in order ensures that you will obtain an overall understanding of the HP BladeSystem Onboard Administrator and that you properly complete the initial setup to facilitate proper functioning of the Onboard Administrator.

    Access requirements To access HP BladeSystem Onboard Administrator, you need the Onboard Administrator IP address and a compatible web browser. Access to the application must be through HTTPS (HTTP exchanged over an SSL-encrypted session).

    The HP BladeSystem Onboard Administrator web interface requires an XSLT enabled browser with support for JavaScript 1.3 or the equivalent.

    The following browsers are officially supported. Other browsers can run the application, but are not supported.

    Microsoft Internet Explorer 6.0. Mozilla Firefox 1.5. The following browser settings must be enabled before running the application:

    ActiveX (for Microsoft Internet Explorer) Cookies JavaScript If you receive a notice that your browser does not have the required functionality, be sure that your browser settings meet the preceding requirements and see the "Recovering Lost Administrator Password" section in this guide.

  • Introduction 8

    Running Onboard Administrator for the first time It is considered best practice to power up the enclosure and Onboard Administrator first and then add blades to the enclosure incrementally. Powering up the enclosure with server blades and storage blades already in the device bays can result in an increased startup time of 5 to 7 minutes.

    In setting up an HP BladeSystem enclosure for the first time, ensure that you have done the following:

    1. Power up the enclosure. The Enclosure Settings screen appears on the Insight Display. Use the Insight Display to configure the c7000 enclosure ("Configuring the HP BladeSystem c7000 enclosure and enclosure devices" on page 66).

    2. On this Enclosure Settings screen, you can configure several settings. However, at a minimum, an IP address for the active Onboard Administrator Ethernet port can be obtained automatically by using a DHCP service on your network or alternately by configuring a static IP address using the Insight Display keys.

    If you are not using DHCP, you must configure each Onboard Administrator IP address and then all the individual device and interconnect module management IP addresses.

    Preferred Method: Configure each Onboard Administrator static IP address using the Insight Display. Then Enable Enclosure Bay IP addresses for the Device Bays and Interconnect Bays using Onboard Administrator GUI First Time Setup Wizard.

    Alternate method: If you do not want to use Enclosure Bay IP addressing, you must connect to each server blades front SUV port (using the SUV cable shipped with every enclosure) and configure the iLO IP address manually during BIOS POST. For the Interconnect Modules that contain management processors (typically switches), use a serial interface (through the Onboard Administrator CLI or external connection, depending on the individual switch design). After changing IP addresses and settings, all switches in the interconnect bay must be restarted using the Onboard Administrator GUI virtual power buttons. See the EBIPA section later in this guide for more information.

    a. Complete Insight Display enclosure settings.

    b. Record the user name and password from the tag attached to each HP Onboard Administrator, and note which Onboard Administrator bay contains the active Onboard Administrator.

    3. Using the IP address for active Onboard Administrator that you configured in step 2, sign in to the active HP Onboard Administrator using a PC on your network with a browser.

    4. Run the First Time Setup Wizard (on page 34).

    An alternate method to setting up HP BladeSystem Onboard Administrator for the first time is to use a serial connection ("Setting up Onboard Administrator using serial connection" on page 172).

  • Introduction 9

    Signing in to the Onboard Administrator GUI

    Signing in to Onboard Administrator

    Enter the user name and initial administration password for your HP BladeSystem Onboard Administrator account found on the tag attached to the Onboard Administrator.

    If you have problems signing in, it could be for one of the following reasons:

    You are not entering the information correctly. Passwords are case sensitive. The account information you are entering has not been set up for HP BladeSystem Onboard

    Administrator.

    The user name you are entering has been deleted, disabled, or locked out. The password for the account must be changed. You are attempting to sign in from an IP address that is not valid for the specified account. The password for the Administrator account has been forgotten or lost. To reset the Administrator

    password, see Recovering the administrator password section later in this guide.

    If you continue to have problems signing in, contact your administrator.

  • Introduction 10

    Running the setup wizard To run the setup wizard, sign in to Onboard Administrator. The First Time Setup Wizard starts automatically when you sign into Onboard Administrator for the first time. This wizard assists you in setting up all of the functions of the Onboard Administrator. You can access the setup wizard at any time after initial setup by clicking the Wizards link on the top left of the center screen.

    See First Time Setup wizard (on page 34) later in this guide for detailed information.

  • Introduction 11

    Using online help To access online help, click the blue box with the white question mark located on the top right of the screen under the header bar. Online help displays information related to the section of HP BladeSystem Onboard Administrator in which you are navigating.

    Changing enclosure and device configurations After you have completed the First Time Setup Wizard, you can return to the Onboard Administrator GUI to make configuration changes at any time. See Configuring the HP BladeSystem c7000 enclosure and enclosure devices (on page 66) for information that will help you make changes to enclosure and device configuration, user setup, and LDAP server settings and LDAP groups.

    See Enclosure Power Management (on page 119) for information about enclosure power settings.

    Recovering the administrator password In the event that the administrator password has been lost, misplaced, or forgotten, the following procedure allows for resetting the administrator password to the factory default that shipped on the tag with the Onboard Administrator module. The Onboard Administrator resets a lost password to Lost Password/Flash Disaster Recovery (LP/FDR) mode. To recover the password and reset the administrator password to the factory default:

    Connect a computer to the serial port of the Active Onboard Administrator using a null-modem cable.

    1. Open HyperTerminal (in Microsoft Windows) or a suitable terminal window (in Linux) and connect to the Active Onboard Administrator.

    2. Press and hold in the Onboard Administrator reset button for 5 seconds.

    3. Select LP from the serial console prompt.

  • Introduction 12

    4. Press L to boot the system into Lost Password mode. The password appears on the screen as it reboots.

    Flash disaster recovery If your Onboard Administrator encountered an error during a firmware update, you can use the following process to recover from such an error.

    1. Connect locally to the Onboard Administrator with a null-modem cable (9600 N, 8, 1, VT100).

    2. Press and hold both the Reset and the Onboard Administrator UID buttons for 5 seconds.

    3. On the serial console, when you are prompted for Flash Recovery or Reset Password, select Flash Recovery. The Onboard Administrator obtains an IP address through DHCP.

    4. At the prompt for the FTP server's IP address (where the Onboard Administrator image files are stored), enter the appropriate IP address.

    You are prompted for the path to the Onboard Administrator firmware image. The Onboard Administrator downloads the image and flashes itself.

    Upon successful completion of this process, the Onboard Administrator firmware is up to date and any error condition is repaired.

  • HP BladeSystem c7000 Enclosure hardware installation 13

    HP BladeSystem c7000 Enclosure hardware installation

    Installing Onboard Administrator modules The HP BladeSystem c7000 Enclosure is shipped with one HP BladeSystem Onboard Administrator module installed and can support up to two Onboard Administrator modules. Install Onboard Administrator modules based on the total number ordered:

    One Onboard Administrator module: Bay 1 Two Onboard Administrator modules: Bays 1 and 2 Install an Onboard Administrator blank in an unused Onboard Administrator bay.

    NOTE: When two Onboard Administrator modules are installed, the module installed in Bay 1 is active and the module installed in Bay 2 is redundant.

    To install an Onboard Administrator module:

    1. Remove the Onboard Administrator blank, if present.

    a. Press the button on the front of the blank to release the handle.

    b. Pull the handle, and slide the Onboard Administrator blank out of the Onboard Administrator tray.

  • HP BladeSystem c7000 Enclosure hardware installation 14

    2. Slide the Onboard Administrator module into the Onboard Administrator tray, and close the handle. When the Onboard Administrator module is fully inserted, it locks into place.

    Onboard Administrator cabling

    Item Connector Description

    1 OA/iLO Onboard Administrator Ethernet connection. Use a CAT5 patch cable to connect to the management network. This is the connector for the IP address of the Onboard Administrator and for the iLO ports on each server blade.

    2 USB For future USB connections. Not currently supported.

    3 Serial connector Used for command line interface (CLI). Connects to a laptop or computer with a null-modem serial cable (RS232).

    4 Enclosure link-down port

    Connects to the enclosure link-up port on the enclosure below with a CAT5 patch cable.

  • HP BladeSystem c7000 Enclosure hardware installation 15

    Item Connector Description

    5 Enclosure link-up port and service port

    Connects to the enclosure link-down port on the enclosure above with a CAT5 patch cable. On a stand-alone enclosure or the top enclosure in a series of linked enclosures, the top enclosure link-up port functions as a service port.

  • HP BladeSystem Insight Display 16

    HP BladeSystem Insight Display

    HP BladeSystem c7000 Insight Display components

    Item Description Function

    1 Up arrow button Moves the menu selection up one position

    2 Down arrow button Moves the menu selection down one position

    3 OK button Accepts the highlighted selection and navigates to the selected menu

    4 Left arrow button Moves the menu or navigation bar selection left one position

    5 Right arrow button Moves the menu or navigation bar selection right one position

    6 Insight Display screen Displays Main Menu error messages and instructions

  • HP BladeSystem Insight Display 17

    HP BladeSystem c3000 Insight Display components

    Item Description Function

    1 Insight Display screen Displays Main Menu error messages and instructions

    2 Left arrow button Moves the menu or navigation bar selection left one position

    3 Right arrow button Moves the menu or navigation bar selection right one position

    4 OK button Accepts the highlighted selection and navigates to the selected menu

    5 Down arrow button Moves the menu selection down one position

    6 Up arrow button Moves the menu selection up one position

    Insight Display overview The Insight Display enables the rack technician to initially configure the enclosure. It also provides information about the health and operation of the enclosure. The color of the Insight Display varies with the condition of the enclosure health:

    BlueThe Insight Display illuminates blue when the enclosure UID is active. The enclosure UID is automatically turned on when the enclosure is powered up for the first time, and can be turned by selecting Turn Enclosure UID On from the Main Menu or by pressing the enclosure UID button on the management interposer.

    When the enclosure UID is on, the Insight Display flashes after two minutes of inactivity. Pressing any button on the Insight Display stops the blinking and reactivates the screen.

    GreenThe Insight Display illuminates green when no error or alert conditions exist, and the enclosure is operating normally. After two minutes of inactivity, the Insight Display light turns off. Pressing any button on the Insight Display reactivates the screen.

    AmberThe Insight Display illuminates amber when the Onboard Administrator detects an error or alert condition. The details of the condition display on the screen.

  • HP BladeSystem Insight Display 18

    After two minutes of inactivity, the Insight Display flashes amber indicating an error or alert condition exists. If the enclosure UID is on and an error or alert condition exists, the Insight Display illuminates blue as the enclosure UID takes priority over the alert. Pressing any button on the Insight Display reactivates the screen.

    Dark (no power)The Insight Display has a two-minute inactivity period. If no action is taken and no alert condition exists, the screen light turns off after two minutes. Hitting any button on the Insight Display will reactivate the screen.

    The Enclosure Health icon is located on the bottom left corner of every screen, indicating the condition of the enclosure health. Navigate the cursor to the Enclosure Health icon and pressing OK to access the Health Summary screen from any Insight Display screen.

    Accessing the HP BladeSystem c3000 Insight Display

    1. Push on the exposed end of the Insight Display for display access.

  • HP BladeSystem Insight Display 19

    2. Pull the Insight Display out of the chassis to lock it into place, then tilt it for viewing.

    Running the Insight Display installation steps When the enclosure is powered up for the first time, the Insight Display launches an installation wizard to guide you through the configuration process. After configuring the enclosure, the Insight Display verifies that there are no installation or configuration errors.

    To identify the enclosure, the rear enclosure UID light and the background of the Insight Display are illuminated blue when the enclosure is powered on initially.

    The Installation Wizard automatically turns on the enclosure UID at the beginning of the installation and turns it off after the installation is complete.

    The Enclosure Settings screen is the first screen to display. The background color is blue because the enclosure UID is active when this screen displays.

    1. Review each setting on the Enclosure Settings screen for accuracy.

    2. To change any value, navigate the cursor to the menu option to be edited, and press the OK button.

  • HP BladeSystem Insight Display 20

    3. Change the setting to the appropriate value, navigate the cursor to Accept, and press the OK button to return to the Enclosure Settings menu. Repeat this step until all options on the Enclosure Settings menu are accurate.

    TIP: Select the ? icon to access detailed help information about each setting or topic.

    TIP: Within any menu option, navigate the cursor to What is This, and press the OK button to view additional information about each setting, option, or alert.

    4. When all settings on the Enclosure Settings menu are accurate, navigate the cursor to Accept All, and press the OK button to accept the current settings.

    You can change the following options in the Enclosure Settings screen:

    Power ModeThe default setting is AC Redundant. The following selections are valid:

    o AC Redundant

    o Power Supply Redundant

    o None

    Power LimitThe default setting is Not Set. The Power Limit Watts AC setting can be changed in increments of 50 Watts.

    IMPORTANT: When calculating the Power Limit Watts AC value, derate the circuit to 80% of the maximum to prevent tripping the circuit breaker (United States only).

    IMPORTANT: If your facility cannot support the calculated peak Watts AC, set the Power Watts AC value to match the capability of your facility.

    Dynamic PowerThe default setting is Enabled. The following selections are valid:

    o EnabledSome of the power supplies can be automatically placed on standby to increase overall enclosure power subsystem efficiency.

    o DisabledAll power supplies share the load; the power subsystem efficiency will vary based on load.

    OA1 IP AddrThe default setting is DHCP; if no IP address is received, the IP address is 0.0.0.0. The IP address, mask, and gateway are set within this option.

  • HP BladeSystem Insight Display 21

    OA2 IP AddrIf this module is present, the default setting is DHCP; if no IP address is received, the IP address is 0.0.0.0. If only one Onboard Administrator module is installed, the screen will display "Not Present."

    Enclosure NameThe default setting is a unique factory-assigned name. The accepted character values are 09, AZ, az, -, _ and . is used to signal the end of the name.

    NOTE: Do not use the symbol in the middle of a text field. Entries in text fields will be truncated to the last character before the symbol.

    TIP: Select Clear from the navigation bar to quickly clear entries in text fields up to the symbol.

    Rack NameThe default setting is UnnamedRack The accepted character values are 09, AZ, az, -, _ and . is used to signal the end of the name.

    DVD DriveThe default setting is Detached on all server blades. To connect any server blade to a CD or DVD disk inserted into the enclosure DVD that is plugged into the Onboard Administrator or included in the enclosure, navigate to Connect and press OK. The following selections are valid on the DVD Connection Settings menu:

    o Detach/AttachEach server can be individually attached to or detached from the enclosure DVD

    drive by navigating to that bay and pressing the OK button.

  • HP BladeSystem Insight Display 22

    o ChangeNavigates to the Attach:Enclosure DVD menu where you can attach, attach and reboot, or detach all bays from the DVD drive.

    o AttachAttaches the enclosure DVD to all server blades.

    o Attach and Reboot SvrAttaches the enclosure DVD to all server blades, then reboots all server blades.

    o DetachDetaches the enclosure DVD from all server blades.

    Insight Display PIN#The default setting is Not Set. HP recommends that you set a PIN to protect the enclosure configuration from unauthorized changes. You must enter the PIN after each inactivity period to change options in the Enclosure Settings menu. The accepted character values are 09, AZ, az, -, _ and . is used to signal the end of the name.

    5. Navigate to the Accept All button at the bottom of the Enclosure Settings screen, and press the OK button to accept all the settings and continue.

    6. In the Check: Linked Enclosures screen, the message "Linked enclosures detected" displays if the Onboard Administrator module detects other enclosures. Use the up and down arrow buttons to change Push Settings = to one of the following values:

    o YesCopy the configured power settings, rack name, and LCD Lockout PIN (if set) from the Enclosure Settings screen to the detected enclosures.

    o NoContinue configuring the current enclosure only. The Insight Display installation wizard must be run on each of the other detected enclosures. Select this option if each enclosure requires different power settings.

    IMPORTANT: If your facility uses Static IP addressing for the Onboard Administrator modules, you must manually enter those IP addresses into the Insight Display for each Insight Display separately. You can enter those Onboard Administrator module IP addresses before you send the settings to adjacent enclosures. You can return to the Enclosure Settings menu after the Installation Wizard completes to change the Onboard Administrator module IP addresses, if necessary.

  • HP BladeSystem Insight Display 23

    7. Navigate the cursor to Accept, and press the OK button.

    The installation wizard displays the Check: Installation and Cables screen.

    8. Verify all components are installed and cabled before continuing. Select Continue, and press the OK

    button to begin checking for configuration and installation errors. When Continue is selected, the enclosure UID automatically turns off. If Push Settings = Yes:

    o The enclosure settings are pushed to adjacent enclosures

    o The installation wizards run on each adjacent enclosure

    o The enclosure UID turns off on the adjacent enclosures

  • HP BladeSystem Insight Display 24

    9. If no errors are detected, the rear enclosure UID turns off, and the Insight Display screen illuminates green. Press the OK button to return to the Main Menu. Enclosure and blade hardware setup and configuration is complete.

    If errors are detected, the Insight Display screen illuminates amber, and the Health Summary screen displays. See Insight Display errors (on page 32) for more information on troubleshooting configuration and installation errors.

    IMPORTANT: All configuration errors prevent the operation of the enclosure and should be corrected immediately.

    10. Open a browser and connect to the active Onboard Administrator module using the Onboard Administrator IP address that was configured during the Insight Display installation wizard process.

    11. Enter the user name and password from the tag supplied with the Onboard Administrator module to access the remote Onboard Administrator web interface and complete the Onboard Administrator first time installation wizard.

    Navigating the Insight Display Navigate through the menus and selections by using the arrow buttons on the Insight Display panel.

    The first menu seen is the Main Menu:

  • HP BladeSystem Insight Display 25

    The Main Menu of the Insight Display has the following menu options:

    Health Summary Enclosure Settings Enclosure Info Blade or Port Info Turn Enclosure UID On/Off View User Note Chat Mode For detailed information regarding the Main Menu of the Insight Display, see the HP BladeSystem Insight Display User Guide.

    TIP: Within any menu option, navigate the cursor to What is This, and press the OK button to view additional information about each setting, option, or alert.

    The navigation bar contains options to:

    Navigate forward and backward through alert screens Return to the main menu Accept changes to current settings Cancel changes to current settings Access the Health Summary screen from any screen by selecting the Health Summary icon on the

    navigation bar

    Health Summary screen The Health Summary screen displays the current condition of the enclosure. The Health Summary screen can be accessed by:

    Selecting Health Summary from the main menu Selecting the Health Summary icon from any Insight Display screen When an error or alert condition is detected, the Health Summary screen displays the total number of error conditions and the error locations.

    Select Next Alert from the navigation bar, and press the OK button to view each individual error condition. The Insight Display displays each error condition in the order of severity. Critical alerts display first (if one exists), followed by caution alerts.

    When the enclosure is operating normally, the Health Summary screen displays green. The bright green rectangles are components that are installed and on. A light green rectangle represents a component that is installed but powered off with no errors.

    The Health Summary screen displays the current condition of the enclosure. The Health Summary screen can be accessed by:

    Selecting Health Summary from the main menu Selecting the Health Summary icon from any Insight Display screen

  • HP BladeSystem Insight Display 26

    When an error or alert condition is detected, the Health Summary screen displays the total number of error conditions and the error locations.

    Select Next Alert from the navigation bar, and press the OK button to view each individual error condition. The Insight Display displays each error condition in the order of severity. Critical alerts display first (if one exists), followed by caution alerts.

    When the enclosure is operating normally, the Health Summary screen displays green. The bright green rectangles are components that are installed and on. A dark green rectangle represents a component that is installed but powered off with no errors. A black rectangle represents an empty bay.

    Note: For the c-Class Enclosure DVD feature, a black DVD rectangle indicates no DVD drive is connected to the Onboard Administrator while a dark gray rectangle indicates the DVD drive is present but that no media is present. A dark green rectangle indicates media is present but not actively connected to any server or all connected servers have issued a disk eject command, so the disk can be removed from the drive. A bright green rectangle indicates the media is present in the drive and actively connected to at least one server in the enclosure, and the drive tray is locked.

    If there is an error, the Health Summary screen background color changes from green to amber and the error is highlighted with yellow rectangles for caution and red rectangles for failures. Overall enclosure health icons in the bottom left corner of all Insight Display screens indicate the overall enclosure health.

    Select View Alert and press the OK button to display the errors.

    Select Details to view the details of the error.

    Enclosure Settings screen The Enclosure Settings screen displays the following setting information about the enclosure:

    Power Mode setting Power Limit setting Power Savings mode setting Active and Standby OA IP addresses Enclosure Name Rack Name DVD Drive

  • HP BladeSystem Insight Display 27

    Insight Display PIN#

    NOTE: The DVD Drive setting can attach or detach a CD or DVD loaded in the optional c3000 enclosure DVD drive to any or all server blades in the enclosure. This feature can be used to install an operating system or software on the server blade(s). If the optional DVD drive is not present, an external HP USB DVD drive can be used with this feature instead.

    TIP: Set a PIN to protect the enclosure settings from changes.

    Navigate the cursor to a setting or to the ?, and press OK to change the setting or get help on that setting.

    Enclosure Info screen The Enclosure Info screen displays information about the enclosure, including:

    Active OA IP address Active OA Service IP address Current health status of the enclosure Current enclosure ambient temperature Current AC input power to the enclosure Enclosure name

  • HP BladeSystem Insight Display 28

    Rack name

    Blade or Port Info screen The Blade or Port Info screen displays information about a specific server blade. On the first screen, select the server blade number, then press the OK button. Select Blade Info or Port Info, and press the OK button.

  • HP BladeSystem Insight Display 29

    To view information about the server blade, select Blade Info and press the OK button.

    To view the ports used by a specific server blade, select Port Info and press the OK button.

    On the full-height server blade shown below, there are two embedded NICs. The other interconnect bays are empty. The two embedded NICs are connected to particular port numbers on the interconnect modules.

    Turn Enclosure UID On/Off screen The main menu option displays "Turn Enclosure UID Off" when the enclosure UID is active, and displays "Turn Enclosure UID on" when the enclosure UID is off.

  • HP BladeSystem Insight Display 30

    Selecting Turn Enclosure UID On from the main menu turns on the rear enclosure UID LED and changes the color of the Insight Display screen to blue.

    Selecting Turn Enclosure UID Off from the main menu turns off the rear enclosure UID LED and changes the color of the Insight Display screen to the current condition.

  • HP BladeSystem Insight Display 31

    View User Note screen The View User Note screen displays six lines of text, each containing a maximum of 16 characters. Use this screen to display helpful information such as contact phone numbers or other important information. Change this screen using the remote Onboard Administrator user web interface. Both the background bitmap and the text can be changed.

    Chat Mode screen The Chat Mode screen is used by the remote administrator who uses the web interface to send a message to an enclosure Insight Display. The technician uses the Insight Display buttons to select from a set of prepared responses, or dials in a custom response message on the ? line. To send a response back to the Administrator, navigate the cursor to Send, then press the OK button.

    The Chat Mode screen has top priority in the Insight Display and will remain on the screen until Send is selected. The technician can leave this chat screen temporarily and use the other Insight Display screens, then return to the Chat Mode screen from the Main Menu to send a response. After the response, the Chat Mode screen is cleared. Both the A and ? responses are then displayed to the remote Administrator on the web interface for LCD Chat.

  • HP BladeSystem Insight Display 32

    Insight Display errors The enclosure installation is successful when all errors are corrected. The errors in the following sections are specific to installation and initial configuration of the enclosure. To clear errors that occur after initial powerup and configuration, see the HP BladeSystem Onboard Administrator User Guide for information.

    The following types of errors can occur when installing and configuring the enclosure:

    Power errors Cooling errors Location errors Configuration errors Device failure errors When the enclosure UID LED is off, the Insight Display is illuminated amber when any error condition exists. The navigation bar displays the following selections when an error condition exists:

    Health summary iconDisplays the Health Summary screen. Fix THISSuggests corrective action to clear the current error. Next AlertDisplays the next alert, or if none exist, displays the Health Summary screen. Previous AlertDisplays the previous alert.

    Power errors Power errors can occur because of insufficient power to bring up an enclosure. Power errors can occur on server blades, storage blades, or interconnect modules.

    To correct a power error:

    1. Use the arrow buttons to navigate to Fix This, and press OK.

    2. Review and complete the corrective action suggested by the Insight Display. In most cases, you must either add power supplies to the enclosure or remove the indicated components.

    Cooling errors Cooling errors occur when too few fans are installed in the enclosure or when the existing fans are not installed in an effective configuration. Cooling errors can occur on server blades, storage blades, or interconnect modules.

    To correct a cooling error:

    1. Use the arrow buttons to navigate to Fix This, and press OK.

    2. Review and complete the corrective action suggested by the Insight Display. In most cases, you must either add fans to the enclosure, correct the fan configuration, or remove the indicated components.

    Location errors Location (installation) errors occur when the component is not installed in the appropriate bay. Location errors can occur on server blades, storage blades, power supplies, and fans.

    To correct a location error:

  • HP BladeSystem Insight Display 33

    1. Use the arrow buttons to navigate to Fix This, and press OK.

    2. Review and complete the corrective action suggested by the Insight Display. Remove the indicated component, and install it into the correct bay. The Insight Display will indicate the correct bay number.

    Configuration errors Configuration errors can occur if the interconnect modules are installed in the wrong bays or if mezzanine cards are installed in the wrong connectors in the server blade. Configuration errors can occur on server blades and interconnect modules.

    To correct a configuration error:

    1. Use the arrow buttons to navigate to Fix This, and press OK.

    2. Review and complete the corrective action suggested by the Insight Display. Depending on the error received, do one of the following:

    o Remove the indicated interconnect module and install it into the correct bay (the Insight Display indicates the correct bay).

    o Remove the server blade to correct the mezzanine card installation (the Insight Display will indicate the correct bay). For information on installing the mezzanine card, see the server-specific user guide on the Documentation CD.

    Device failure errors Device failure errors occur when a component has failed. Device failure errors can occur on all components, including:

    Server blades Storage blades Power supplies Interconnect modules Onboard Administrator modules Fans AC power inputs To correct a device failure error:

    1. Use the arrow buttons to navigate to Fix This, and press OK.

    2. Review and complete the corrective action suggested by the Insight Display. In most cases, you must remove the failed component to clear the error.

    3. Replace the failed component with a spare, if applicable.

    NOTE: If the device failure error is an AC power input failure error, you must have the failed AC input repaired to clear the error.

  • First Time Setup Wizard 34

    First Time Setup Wizard

    Before you begin Before running the First Time Setup Wizard, complete the following tasks:

    Install the Onboard Administrator modules. Connect the Onboard Administrator modules to the network. Run the Insight Display installation.

    Signing in to Onboard Administrator 1. Open a browser and connect to the active HP BladeSystem Onboard Administrator using the IP

    address that was configured during the Insight Display installation wizard process.

    2. Enter the user name and initial administration password for your HP BladeSystem Onboard Administrator account found on the tag attached to the Onboard Administrator.

    If you have problems signing in, it could be for one of the following reasons. Contact the administrator if you continue to have problems.

    You are not entering the information correctly. Passwords are case sensitive. The account information you are entering has not been set up for HP BladeSystem Onboard

    Administrator.

    The user name you are entering has been deleted, disabled, or locked out. The password for the account must be changed. You are attempting to sign in from an IP address that is not valid for the specified account. If you continue to have problems signing in, contact your administrator. The first time you sign in, the Onboard Administrator automatically runs the First Time Setup Wizard.

    To navigate through the setup wizard, click Next to save your changes and go to the next step. Click Skip if you want to leave the step without saving changes.

    You can return to previous wizard steps by selecting them in the left tree view. You can also run the wizard again at any time by selecting it from the Wizards menu.

  • First Time Setup Wizard 35

    The following sections describe each step of the First Time Setup Wizard and provide you with detailed information about each step in the process.

    Enclosure Selection screen The Enclosure Selection screen displays all discovered enclosures. The active enclosure is selected by default. The selected status for each enclosure can be toggled by selecting its corresponding checkbox, or all enclosures can be toggled automatically by selecting the topmost checkbox in the header row.

  • First Time Setup Wizard 36

    If there are too many enclosures to fit in the display window, a vertical scrollbar appears, enabling access to all enclosures and the navigation buttons.

    If more than one enclosure is listed on the Enclosure Selection screen, select the enclosure you want to set up and select Next.

    See Enclosure Settings screen for possible values and descriptions of each field.

  • First Time Setup Wizard 37

    Configuration Management screen The Configuration Management screen enables you to set up the selected enclosures using a configuration file saved from a previous setup. You can run scripts for multiple Onboard Administrators before leaving the current screen.

    To set up selected enclosures using a configuration file:

    On the Configuration Management screen, select one of the following options:

    Local fileBrowse for the configuration file, or enter the path of the script file into the textbox. The maximum number of characters in the file path is 256. Click Upload after entering the script file path.

    URLEnter an http:// path to the configuration file if it is located on a web server. The maximum number of characters in the file path is 256. Click Upload after entering the URL. After clicking the Upload button, a window appears and displays the results.

  • First Time Setup Wizard 38

    If more than one enclosure was selected during the enclosure selection, select the enclosure to upload or apply the configuration file to use from the dropdown menu that appears. If multiple enclosures were selected, repeat this process for each additional enclosure. You cannot select more than one enclosure at a time for configuration management.

  • First Time Setup Wizard 39

    Rack and Enclosure Settings screen Use this form to assign a common name and time settings to your rack and assign unique names and asset tags to your enclosures.

    Field Possible value Description

    Rack Name 1 to 32 characters including all alphanumeric characters, the dash (-), and the underscore (_)

    The name of the rack in which the enclosure is installed

    Date yyyy-mm-dd, where:

    mm is an integer from 1 to 12

    dd is an integer from 1 to 31

    The current date assigned to the enclosure

    Time hh:mm:ss (24-hour time)

    hh is an integer from 0 to 23

    mm is an integer from 0 to 59

    ss is an integer from 0 to 59

    The current time assigned to the enclosure

  • First Time Setup Wizard 40

    Field Possible value Description

    Time Zone Time zone settings

    Africa time zone settings Americas time zone

    settings

    Asia time zone settings Universal time zone

    settings

    Oceanic time zone settings

    Europe time zone settings Polar time zone settings

    The time zone assigned to the enclosure

    Enclosure Name 1 to 32 characters including all alphanumeric characters, the dash (-), and the underscore (_)

    The name of the selected enclosure

    Asset Tag 0 to 32 characters including all alphanumeric characters, the dash (-), and the underscore (_)

    The asset tag is used for inventory control

    The default asset tag is blank

    See the HP BladeSystem c7000 User Guide for more information on connecting enclosures.

  • First Time Setup Wizard 41

    Administrator Account Setup screen The Administrator Account Setup screen initially displays the name of the active enclosure and its current settings. If multiple enclosures were selected on the Enclosure Selection screen, a button is activated, enabling you to expose separate inputs for each selected Onboard Administrator.

    Field Possible value Description

    Full Name 0 to 20 characters including all alphanumeric characters, the dash (-), the underscore (_), and the space

    The full name of the user

    Contact 0 to 20 characters including all alphanumeric characters, the dash (-), the underscore (_), and the space

    Contact information for the user account. The contact information can be the name of an individual, a telephone number, or other useful information.

    Administrator Password 3 to 8 characters including all printable characters

    The password for the user account

    Administrator Password Confirm

    3 to 8 characters including all printable characters

    Must match the Administrator Password value

    PIN Code 1 to 6 characters from the character sets 0 to 9, a to z, and A to Z

    The PIN code for the enclosure Insight Display

  • First Time Setup Wizard 42

    Field Possible value Description

    PIN Code Confirm 1 to 6 characters from the character sets 0 to 9, a to z, and A to Z

    Must match the Insight Display PIN value

    Local User Accounts screen The Local User Accounts screen displays the user accounts assigned to the Active Onboard Administrator and provides choices for adding, editing and deleting accounts.

    NewClick New to add a new user to the selected enclosure. A maximum of 30 user accounts can be added including the reserved accounts. The Add Local User screen appears.

    EditSelect a user (only one can be selected) by selecting the checkbox next to the name of the user. Click Edit to change the settings on the Edit Local User screen.

    DeleteSelect a user or users to be deleted by selecting the checkbox next to the name of the user. Click Delete to remove the accounts. If an attempt is made to delete the last remaining Administrator account, you will receive an alert warning that one Administrator account must remain and the delete action will be canceled.

    User Settings screen

  • First Time Setup Wizard 43

    The User Settings screen displays configurable user information. Enter user information in the User Information and User Permissions sections. When you are finished, click Add User or Update User to save the information. To return to the Local User Accounts screen, click Cancel.

    For each user added, select the appropriate boxes to grant access to servers and interconnect bays.

    See User accounts in this guide for possible values and descriptions of each field.

    Enclosure Bay IP Addressing The server blade iLO 2 ports and interconnect module management ports can obtain IP addresses on the management network in three ways: DHCP address, static IP address or EBIPA. If your network has an external DHCP service or if you want to manually assign static IP addresses one by one to the server blades and interconnect modules, click Skip to bypass this step.

    DHCP addressesThe server blade iLO 2 defaults to DHCP addressing, obtained through the network connector of the active Onboard Administrator. Interconnect modules that have an internal management network connection to the Onboard Administrator may also default to DHCP address.

    The Onboard Administrator GUI lists the IP address for the server blade iLO 2 port and interconnect module management port

    Static IP o ManualIf your facility prefers static IP address assignment, you can individually change each

    of the server blade iLO 2 ports and interconnect module management ports to unique static addresses or use EBIPA to assign a range of static IP addresses to individual server blade and interconnect module bays.

    o EBIPAWhen a server blade or interconnect module is inserted into a bay that has EBIPA enabled, that management port will get the specific static IP address from the Onboard Administrator if that device is configured for DHCP.

    The administrator sets an independent range for server blade bays and interconnect module bays using the Onboard Administrator EBIPA setup wizard. The first address in a range is assigned to the first bay and then consecutive bays through the range.

  • First Time Setup Wizard 44

    For example, if you set the server bay EBIPA range to 16.100.226.21 to 16.100.226.36, the iLO 2 in device bay #1 will be assigned 16.100.226.21 and the iLO 2 in device bay #12 is assigned 16.100.226.32. If you set the interconnect bay EBIPA range to 16.200.139.51 to 16.209.139.58, the interconnect module management port in interconnect bay #1 will be assigned 16.200.139.51 and the interconnect module management port in interconnect bay #7 will be assigned 16.200.139.57.

  • First Time Setup Wizard 45

    Knowing your network configuration before setting up EBIPA ensures an easy setup and enables you to install your HP BladeSystem Onboard Administrator on your network quickly. Record the information requested in the fields on the EBIPA screen, and verify before entering the data. Use only the values discussed in the following table.

    Field Possible value Description

    Beginning Address ###.###.###.### where ### ranges from 0 to 255

    Beginning IP address for the device or interconnect bays. Click the arrow next to the Beginning Address field, and click Update List to update the Device List or Interconnect List.

  • First Time Setup Wizard 46

    Field Possible value Description

    Subnet Mask ###.###.###.### where ### ranges from 0 to 255

    Subnet mask for the device or interconnect bays

    Gateway ###.###.###.### where ### ranges from 0 to 255

    Gateway address for the device or interconnect bays

    Domain A character string, including all alphanumeric characters and the dash (-)

    The domain name for the device or interconnect bays

    DNS Server 1 ###.###.###.### where ### ranges from 0 to 255

    The IP address for the primary DNS server

    DNS Server 2 ###.###.###.### where ### ranges from 0 to 255

    The IP address for the secondary DNS server

    DNS Server 3 ###.###.###.### where ### ranges from 0 to 255

    The IP address for the tertiary DNS server

    NTP Server 1 ###.###.###.### where ### ranges from 0 to 255

    The IP address of the primary server used to synchronize time and date using the NTP protocol

    NTP Server 2 ###.###.###.### where ### ranges from 0 to 255

    The IP address of the secondary server used to synchronize time and date using the NTP protocol

    Enable Enclosure Bay IP Addressing for Server Bay iLO ProcessorsSelect this checkbox to enable EBIPA settings for the server bays in this enclosure.

    Directory Services Configuration screen LDAP is an open protocol for accessing information directories. While LDAP is based on the X.500 standard, it is significantly simpler. LDAP supports TCP/I which enables applications to work independently of the server hosting the directory.

  • First Time Setup Wizard 47

    Use the LDAP Configuration screen to set directory access for the currently selected enclosures.

    On this screen, you can configure the following settings:

    Enable LDAP AuthenticationEnables a directory server to authenticate a user login. Enable Local UsersEnables a user to sign in using a local user account instead of a directory

    account.

    Field Possible value Description

    Directory Server Address ###.###.###.### where ### ranges from 0 to 255 or DNS name of the directory server or the name of the domain

    The IP address or the DNS name or the name of the domain of the directory service.

    Directory Server SSL Port 0 to xxxx The port used for LDAP communications. The default port is port 636.

    Search Context 1 All characters except " (quotes), not to exceed 128 characters

    First searchable path used to locate the user when the user is trying to authenticate using directory services.

    Search Context 2 All characters except " (quotes), not to exceed 128 characters

    Second searchable path used to locate the user when the user is trying to authenticate using directory services.

    Search Context 3 All characters except " (quotes), not to exceed 128 characters

    Third searchable path used to locate the user when the user is trying to authenticate using directory services.

  • First Time Setup Wizard 48

    Use NT Account Name Mapping (DOMAIN\username)Enables NT name mapping so that you can enter the NT domain and user name.

    Onboard Administrator Network Settings screen Use the Onboard Administrator Network Settings screen to modify network settings for all the Onboard Administrator modules in the selected enclosures. Settings for Standby Onboard Administrator modules appear only if the modules are present. Options for DHCP and static IP are supported.

    Use DHCP for all Active (or Standby) Onboard AdministratorGet the IP address for the Onboard Administrator from a DHCP server. The Standby checkbox is only shown if there is a Standby Onboard Administrator in the enclosure.

    Enable Dynamic DNSEnable using a DNS server to translate host names into IP addresses when using DHCP.

  • First Time Setup Wizard 49

    Use static IP settings for each Active (or Standby) Onboard AdministratorManually set up static IP settings for the Onboard Administrator. The Standby checkbox is only shown if there is a Standby Onboard Administrator in the enclosure.

    See TCP/IP Settings for possible values and descriptions of each field.

  • First Time Setup Wizard 50

    Enclosure SNMP Settings screen Use the Enclosure SNMP Settings screen to configure or modify the SNMP settings for the active HP BladeSystem Onboard Administrator.

    See "SNMP Settings" later in this guide for possible values and descriptions of each field.

  • First Time Setup Wizard 51

    Power Management screen

    The HP BladeSystem c7000 Enclosure power management system allows for a variety of configurations to best suit your needs. You can choose from the different modes on the Onboard Administrator Power Management screen. The power modes are explained in the following table.

  • First Time Setup Wizard 52

    Mode Insight Display name

    Description

    AC Redundant AC Redundant In this configuration, N power supplies are used to provide power, and N are used to provide redundancy (where N can equal 1, 2, or 3). Up to three power supplies can fail without causing the enclosure to fail. When correctly wired with redundant AC line feeds, this configuration also ensures that an AC line feed failure will not cause the enclosure to power off.

    Power Supply Redundant

    Power Supply Redundant

    Up to six power supplies can be installed with one power supply always reserved to provide redundancy. In the event of a single power supply failure, the redundant power supply takes over the load. An AC line feed failure of more than one power supply causes the system to power off.

    Not Redundant Power None There is no power redundancy. Any power supply or AC line failure causes the system to power off.

    Dynamic Power Savings Mode

    Power Saving Mode If enabled, Dynamic Power Savings Mode automatically places unused power supplies in standby mode to increase enclosure power supply efficiency, thereby minimizing enclosure power consumption during lower power demand. Increased power demands automatically return standby power supplies to full performance.

    Enable AC Input Watts Limit An optional setting intended for two situations:

    If the facility power is limited to the enclosure, you can enter a fixed limit into each enclosure so the enclosure will not exceed that power consumption. Example: The hosted location limits the enclosure to 5,000 W. Enter 5000 in the Limit Enclosure AC Input Watts field. The Onboard Administrator will limit total power allocation to 5,000 W which might result in denying power to some of the server blades.

    If the facility limits cooling capacity to the enclosure, divide the facility's limit of BTU/hr available to the enclosure by 3.41 to determine the watts limit for that enclosure. Enter that watts limit to restrict the heat load of the enclosures. Example: The facility limits individual enclosure to 27,280 BTU/hr. Dividing 27,280 by 3.41 yields 8,000 W. Enter the watts limit to restrict that enclosure to 27,280 BTU/hr. This limit might result in denying power to some of the server blades.

    Dynamic Power SavingsThe default setting is Enabled. The following selections are valid:

    EnabledSome of the power supplies can be automatically placed on standby to increase overall enclosure power subsystem efficiency.

    DisabledAll power supplies share the load. The power subsystem efficiency varies based on load.

  • First Time Setup Wizard 53

    Finish You can clear the Do not automatically start this wizard again checkbox to force the First Time Setup Wizard to run again the next time a user signs into the Onboard Administrator.

    To save the configuration, click Click here to save the setup script to your local machine.

    Click Finish to save and exit the First Time Setup Wizard. The First Time Setup Wizard screen closes and you are returned to the default main screen of HP BladeSystem Onboard Administrator.

  • Navigating Onboard Administrator 54

    Navigating Onboard Administrator

    Navigation overview The main HP BladeSystem Onboard Administrator navigation system consists of a tree view, which lists all of the system devices on the left side of the main page and remains visible at all times and a graphical view, which displays a physical picture of the enclosure. You can navigate through an enclosure's devices and functions through either of these views.

    Tree view The tree view aids in navigating through enclosure devices and functions for multiple enclosures in a hierarchal manner. The way in which the tree view is rendered depends on several factors including user permissions, device availability, and device status. If a user is configured to be an operator or user, some options might not be visible in the tree view.

  • Navigating Onboard Administrator 55

    The physical appearance of the tree view for the c3000 and c7000 are analogous. Differences between the two enclosures are evident in the graphical view navigation.

    One of the main purposes of the tree view is to allow navigation using categories based on the major systems within the enclosure. When a category is expanded (by clicking the white plus sign in the blue box to the left of the category), an icon next to the category name can indicate a degraded status of the affected system. In the case of multiple components reporting status, the status icon indicates a cumulative worst-case status of all the devices in the same category.

    Individual device pages

  • Navigating Onboard Administrator 56

    Clicking the link for an individual device selects the device, opens the device detail page, and selects the device in the graphical view in the right frame of the GUI. Individual device pages contain detailed information about the selected device and any other functions related to that device.

    Category summary pages

    Category summary pages contain summary information for each of the devices in that category. For example, clicking the Device Bays link opens a bay summary page. Each parent element in the tree works in this manner. When you click a category summary link, no devices are selected in the graphical view navigation.

  • Navigating Onboard Administrator 57

    System forms pages

    Some devices, particularly HP Onboard Administrator, can have links to various system forms pages listed beneath their main links in the left tree navigation view. Form pages contain input text boxes, radio buttons, and other HTML input element and are used to administer settings related to the device to which they belong. For example, you can use the HP Onboard Administrator system forms page to change IP address settings or update firmware. These forms are all linked under the HP Onboard Administrator parent element. When you click a system forms link, the device to which the form page belongs is selected in the graphical view. For example, clicking the Firmware Update link for the Active HP Onboard Administrator selects the Active HP Onboard Administrator device in the graphical view. Links to system forms do not display status icons.

    Graphical view navigation The second component of the HP BladeSystem Onboard Administrator GUI navigation system is a graphical representation of the physical enclosure, called the graphical view. The graphical view consists of two subcomponents: a front view and a rear view.

    The following image shows the graphical view of a typical c7000 enclosure.

  • Navigating Onboard Administrator 58

    The following image shows the graphical view of a typical c3000 enclosure.

    All functions and features for the graphical view navigation are the same for both the c3000 and the c7000 except where noted.

    Selecting a device

    To select a device, click the graphical representation of the device in the front or rear graphical view. When you select a device, its surrounding border changes from gray to light blue to indicate it is the currently selected device. Selecting a device in the graphical view selects the corresponding device in the left navigation tree view. Every time you select a device from any part of the navigation system, the rest of the navigation reflects that device selection event and updates accordingly.

    Status reporting

    The graphical view reports the status of every device in the enclosure. The status of each device is indicated on the device by a small status icon. No status icon appears for a device that is working properly and has an OK status. However, any other status codes appear as status icons on the device.

    The graphical view does not report the presence or absence of hard drives in the server blade or storage blade.

    Device security

    Although the front and rear graphical views are both affected by user permissions, security on the graphical view is handled differently from the left tree view. If the user does not have permission to access a device, a blank bay appears regardless of whether a device is present in that bay, and a padlock icon in the bay table cell appears, indicating that the bay is locked to the current user.

    The user cannot select a locked bay. When the user's mouse hovers over the locked bay, a message appears, indicating that the user does not have permission to access the device in that bay.

    Minimizing the graphical view

  • Navigating Onboard Administrator 59

    To minimize the graphical view from the main display, click the small box that contains an arrow and is located directly to the left of the name of the enclosure in the Graphical View box. This will minimize the Graphical View and give more room for the main section of the display. This is useful when viewing the Onboard Administrator on a small monitor or on a monitor using low resolution.

  • Rack View 60

    Rack View

    Rack View screen The Rack Topology tab shows a graphical representation of the physical enclosure, called the graphical view. The graphical view consists of a front view and a rear view. When you mouse over a device in the graphical view, a window appears with information on that device. The graphical view provides status on each device in the enclosure and gives you the option of selecting an individual device for more detailed information.

    If there are multiple enclosures, some enclosures appear in the Rack Overview as all gray. To view the enclosure's contents and information, click Load Enclosure Information.

  • Rack View 61

    After selecting Load Enclosure Information, the enclosure contents become available.

    Rack Information

    Row Description

    Enclosure Name The DNS name of the enclosure and the name of the enclosure in the rack.

    Serial Number The unique serial number for the enclosure.

    Part Number The part number of the enclosure used when obtaining a new or replacement enclosure.

    Asset Tag The asset tag is used for inventory control.

    UID State Displays On or Off, depending on whether the UID is active.

    Linked Enclosures

    The Rack Topology tab displays all linked enclosures, which will have one of the following states:

    LinkedNot Logged In: Enter a user name and password in the text boxes and click Sign In. A graphical view of the enclosure will display.

    LinkedLogged In with a Load Enclosure Information button: Click Load Enclosure Information to display the graphical view of the enclosure.

    LinkedLogged In with a graphical view of the enclosure displayed.

    Topology modes Onboard Administrator supports three topology modes which are determined by the selection made on the sign in screen prior to signing in. The three topology modes are:

  • Rack View 62

    Local ModeUsed to manage a single enclosure when more than one enclosure can be selected. Onboard Administrator ignores all topology changes. This mode is useful when you do not want to change topology by adding linked enclosures.

    Linked ModeUsed to manage a single enclosure when no other enclosures are attached. You can use Linked Mode to allow the addition of new enclosures as they are added to the interlink. As long as no new enclosures are connected, Onboard Administrator appears to be in Local Mode. All topology changes that occur while signed in are displayed by Onboard Administrator. This mode provides an unrestricted view of enclosures connected to the interlink.

    Fixed ModeUsed to manage more than one, but not all enclosures. Only the topology changes affecting the current topology are displayed by Onboard Administrator. This mode is useful when monitoring a subset of the total enclosures connected to the interlink.

    If the active mode is set for a single enclosure and one or more enclosures are connected,if you want to ensure that the additional enclosures are not visible in the enclosure topology, you must sign out and back in without selecting a linked enclosure.

    Rack Topology tab The Rack Topology tab shows a graphical representation of the physical enclosure, called the graphical view. The graphical view consists of a front view and a rear view. When you mouse over a device in the graphical view, a window appears with information on that device. The graphical view provides status on each device in the enclosure and gives you the option of selecting an individual device for more detailed information.

    Selecting a device