52
Phone Topics Applying 19XRV Chillers in Variable Primary Systems Ron Beliveau Carrier Commercial Sales Middletown, CT

PRIMARY VFD AND CHILLER SYSTEM

Embed Size (px)

DESCRIPTION

PRIMARY VFD AND CHILLER SYSTEM

Citation preview

Page 1: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Applying 19XRV Chillers in Variable Primary Systems

Ron Beliveau

Carrier Commercial Sales

Middletown, CT

Page 2: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Outline

19XRV chillers in VPF systems.

19XRV Chillers in Variable Primary Systems

1. Review conventional Primary Secondary System.

2. Review Variable Primary Flow System.

3. Review the Benefits of “Max Cap” in both P/S and VPF systems.

4. Review the Benefits of VFD driven chillers in both P/S and VPF systems.

5. Review chiller selection guidelines for VPF applications.

.

WARNING:

55 slides in 45 minutes –

We will be moving very quickly!

Page 3: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Why VPF?

Why all the interest in VPF?19XRV Chillers in Variable Primary Systems

1. Unlike many items –this isn’t a “sell up” concept – it is actually a lower installed cost.

- VPF Reduces pumping and piping complexities and lowers installation costs.

- Less real estate in mechanical and electrical rooms.

2. Unlike many cost reductions, VPF can offer lower operational costs.

- VPF reduces low T, increasing eff.

- Fewer, but larger pumps have better efficiency.

.

Page 4: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Primary Secondary Systems.

Primary Secondary Systems use constant speed pumps to supply water to the chillers.

OFF = 0 gpm

ON = 1200 gpm

Page 5: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Primary Secondary Systems.

The chiller controls to a leaving chilled water set point.

OFF = 0 gpm

ON = 1200 gpm

44 F

Chiller cools 1200 gpm of water to 44F.

How much work is the chiller doing?

Page 6: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Primary Secondary Systems.

The amount of work the chiller does is related to the return water temperature.

GPM is fixed.

LCHWT is fixed.

Only variable is return temp.

OFF = 0 gpm

ON = 1200 gpm

Tons = GPM x T 24

500 = 1200 x (54-44) / 24

400 = 1200 x (52-44) / 24

300 = 1200 x (50-44) / 24

44 F??

Page 7: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Chiller (primary) pumps are constant speed (flow).

Secondary pumps are variable speed.

Secondary pump speed (gpm) controlled by DP switch at most hydraulically remote coil.

Primary Secondary Systems.

Page 8: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

If primary gpm equals secondary gpm, there is no flow through the hydraulic decoupler line.

Primary Secondary Systems.

0 gpm 3600 gpm3600 gpm

1200 gpm

1200 gpm

1200 gpm

Page 9: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

If primary gpm is greater than secondary gpm, chilled water flows through the decoupler line, bypassing the coils.

This cold water mixes with the return water, lowering the return temperature to the chillers.

Primary Secondary Systems.

600 gpm 3000 gpm3600 gpm

1200 gpm

1200 gpm

1200 gpm

Page 10: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

If primary gpm is less than secondary gpm, return water flows through decoupler line.

This warm water mixes with the chilled water, raising the entering chilled water temperature to the coils.

If return temp is too high, another chiller / pump set is started.

Primary Secondary Systems.

600 gpm 3000 gpm2400 gpm

0 gpm

1200 gpm

1200 gpm

Page 11: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Start up.

Coils call for load.

One chiller / pump started and a secondary pump started.

Secondary pump only needs 240 gpm to satisfy coil load.

0 gpm

0 gpm

1200 gpm

240 gpm

0 tons

0 tons

100 tons

960 gpm 240 gpm1200 gpm

46 F 44 F

EX: 100 ton building load

Primary Secondary Systems.

Page 12: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

At 500 tons of building load the secondary pumps require 1200 gpm.

Primary gpm equals secondary gpm and there is no flow through decoupler line.

0 gpm

0 gpm

1200 gpm

1200 gpm

0 tons

0 tons

500 tons

0 gpm 1200 gpm1200 gpm

54 F 44 F

EX: 500 ton building load

Primary Secondary Systems.

Page 13: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

At 550 tons of building load the secondary pumps require 1320 gpm.

For a brief time, primary gpm is less than secondary gpm warm water flows back through decoupler line.

0 gpm

0 gpm

1200 gpm

1320 gpm

0 tons

0 tons

500 tons

120 gpm 1320 gpm1200 gpm

54 F 44 F

EX: 550 ton building load

Primary Secondary Systems.

Page 14: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

To meet coil load, temp sensor turns on chiller and pump set.

Now primary gpm > secondary gpm and chilled water flows through decoupler line bypassing the load.

0 gpm

1200 gpm

1200 gpm

1320 gpm

0 tons

275 tons

275 tons

1080 gpm 1320 gpm2400 gpm

49. 5 F 44 F

EX: 550 ton building load

Primary Secondary Systems.

Page 15: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

When the building reaches 1000 tons, in theory, the chillers are fully utilized and there is no flow through the decoupler line.

0 gpm

0 gpm

1200 gpm

1200 gpm

2400 gpm

2400 gpm

0 tons

500 tons

500 tons

2400 gpm

54 F 44 F

EX: 1000 ton building load

Primary Secondary Systems.

Page 16: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

When building is at full load, there is 1500 tons required by coils and 1500 tons provided by chillers.

System is balanced and there is no flow through decoupler

1200 gpm

1200 gpm

1200 gpm

3600 gpm

500 tons

500 tons

500 tons

0 gpm 3600 gpm3600 gpm

54 F 44 F

EX: 1500 ton building load

Primary Secondary Systems.

Page 17: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

As we unload, the system can shut off the 3rd chiller only if the delta T is at design.

0 gpm

0 gpm

1200 gpm

1200 gpm

2400 gpm

2400 gpm

0 tons

500 tons

500 tons

2400 gpm

54 F 44 F

EX: 1000 ton building load

Primary Secondary Systems.

Page 18: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

If not controlled properly, 1000 ton load could look like this.

3 chillers running at 67% load!

Primary Secondary Systems.

1200 gpm

1200 gpm

1200 gpm

1200 gpm

2400 gpm

2400 gpm

334 tons

333 tons

333 tons

3600 gpm

50.7 F 44 F

EX: 1000 ton building load

Page 19: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

1029 gpm

1200 gpm

1200 gpm

1200 gpm

2571 gpm

2571 gpm3600 gpm

49 F 44 F

EX: 750 ton building load with Low Delta T syndromePrimary

Secondary Systems.

T across dirty coil = 7

Load is 750 Tons, GPM=?

44 F51 F

TONS = GPM x DT / 24

TONS = 1200 X 7 / 24

TONS = 350 ???

TONS = GPM x DT / 24

TONS = 1200 X 5 / 24

TONS = 250

Tons = GPM x T 24

GPM = Tons x 24 TIn perfect world (2)

chillers operate @ 375 tons each.

2@ .479 IKW/Ton

With low delta T (3) chillers operate @ 250 tons each.

3 @ .518 IKW/Ton

Extra pump power is also consumed. T across dirty coil = 7

Load is 750 Tons,

750 x 24 /7 = 2571 gpm

250 tons

250 tons

250 tons

Page 20: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Outline

19XRV chillers in VPF systems.

19XRV Chillers in Variable Primary Systems

1. Review conventional Primary Secondary System.

2. Review Variable Primary Flow System.

3. Review the Benefits of “Max Cap” in both P/S and VPF systems.

4. Review the Benefits of VFD driven chillers in both P/S and VPF systems.

5. Review chiller selection guidelines for VPF applications.

.

Page 21: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems use variable speed pumps to supply water to the chillers.

OFF = 0 gpm

ON = ??? gpm

(within min / max flow)

Variable Primary Systems

Page 22: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

The chiller controls to a leaving chilled water set point. 44 F

Chiller cools 54F water to 44F.

How much work is the chiller doing?

Variable Primary Systems

OFF = 0 gpm

ON = ??? gpm

54

Page 23: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

The amount of work the chiller does is related to the flow through the cooler.

ECHWT is fixed.

LCHWT is fixed.

Only variable is cooler gpm.

OFF = 0 gpm

ON = 1200 gpm

Tons = GPM x T 24

500 = 1200 x (54-44) / 24

400 = 960 x (54-44) / 24

300 = 720 x (54-44) / 24

44 F54

Variable Primary Systems

Page 24: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Tons = GPM x T

24

Variable Primary Systems

Primary Secondary

GPM = Constant, T changes as load changes

Variable Primary

T constant, GPM changes as load changes.

Pump only the chilled water necessary to serve the load.

Page 25: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

Only one set of pumps.

No decoupler line

All pumps are Variable speed.

Flow (gpm) is regulated to

maintain T.

Tons = GPM x T

24

Page 26: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

Start up.

Coils call for load.

One chiller / pump started.

Min. flow rate of chiller is 500 gpm.

Therefore, 260 gpm must bypass around coils

240 gpm

500 gpm

0 gpm

500 gpm

500 gpm

100 tons

0 tons

0 tons

48.8 F

44 F

260 gpm bypass

500 gpm

0 gpm

0 gpm

EX: 100 ton building load

44 F54 F

Page 27: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

At 208 tons, the design T (of 10F)

is achieved.

Flow is no longer required to bypass coils.

208 = 500 x 10 24

500 gpm

500 gpm

0 gpm

500 gpm

500 gpm

208 tons

0 tons

0 tons

54 F 44 F

500 gpm

0 gpm

0 gpm

0 gpm

EX: 208 ton building load

44 F54 F

Page 28: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

At 500 tons, the design T (of 10F)

is achieved with 1200 gpm of flow.

(1) chiller is now fully loaded.

500 = 1200 x 10 24

1200 gpm

1200 gpm

0 gpm

1200 gpm

1200 gpm

500 tons

0 tons

0 tons

54 F44 F

1200 gpm

0 gpm

0 gpm

0 gpm

EX: 500 ton building load

44 F54 F

Page 29: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

At 550 tons, the design T (of 10F)

is achieved with 1320 gpm of flow.

(2) Chillers are now part loaded.

Flow split equally.

550 = 1320 x 10 24

1320 gpm

1320 gpm

0 gpm

1320 gpm

1320 gpm

275 tons

275 tons

0 tons

54 F44 F

660 gpm

0 gpm

660 gpm

0 gpm

EX: 550 ton building load

44 F54 F

Page 30: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

At 750 tons, the design T (of 10F)

is achieved with 1800 gpm of flow.

The 2nd pump is turned on.

Flow split equally.

750 = 1800 x 10 24

1800 gpm

900 gpm

900 gpm

1800 gpm

1800 gpm

375 tons

375 tons

0 tons

54 F44 F

900 gpm

0 gpm

900 gpm

0 gpm

EX: 750 ton building load

44 F54 F

Page 31: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

At 1000 tons, the design T (of 10F)

is achieved with 2400 gpm of flow.

(2) Chillers are now fully loaded.

Flow split equally.

1000 = 2400 x 10 24

2400 gpm

1200 gpm

1200 gpm

2400 gpm

2400 gpm

500 tons

500 tons

0 tons

54 F44 F

1200 gpm

0 gpm

1200 gpm

0 gpm

EX: 1000 ton building load

44 F54 F

Page 32: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

At 1100 tons, the design T (of 10F)

is achieved with 2640 gpm of flow.

(3) Chillers are now part loaded.

Flow split equally.

1100 = 2640 x 10 24

2640 gpm

1320 gpm

1320 gpm

2640 gpm

2640 gpm

367 tons

367 tons

366 tons

54 F 44 F

880 gpm

0 gpm

880 gpm

880 gpm

EX: 1100 ton building load

44 F54 F

Page 33: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

At 1500 tons, the design T (of 10F)

is achieved with 3600 gpm of flow.

(3) Chillers are now fully loaded.

Flow split equally.

1500 = 3600 x 10 24

3600 gpm

1800 gpm

1800 gpm

3600 gpm

3600 gpm

500 tons

500 tons

500 tons

54 F44 F

1200 gpm

0 gpm

1200 gpm

1200 gpm

EX: 1500 ton building load

44 F54 F

Page 34: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Primary Secondary Pumping System Constant Speed

Variable Speed

Building Load GPM

Qty of Chillers

Chiller % Load ECWT

Chiller IKW/Ton

Chiller IKW/Ton

100 1200 1 20% 65 0.954 0.551208 1200 1 42% 65 0.619 0.36500 1200 1 100% 65 0.446 0.384550 2400 2 55% 65 0.537 0.332750 2400 2 75% 65 0.479 0.33

1000 2400 2 100.0% 71.8 0.485 0.4361100 3600 3 73.4% 74.2 0.527 0.4441500 3600 3 100% 85 0.59 0.589

Variable Primary Pumping SystemConstant Speed

Variable Speed

Building Load GPM

Qty of Chillers

Chiller % Load ECWT

Chiller IKW/Ton

Chiller IKW/Ton

100 500 1 20% 65 0.954 0.548208 500 1 42% 65 0.619 0.358500 1200 1 100% 65 0.446 0.384550 1320 2 55% 65 0.537 0.332750 1800 2 75% 65 0.479 0.328

1000 2400 2 100% 71.8 0.485 0.4361100 2640 3 73.4% 74.2 0.527 0.4421500 3600 3 100% 85 0.59 0.589

When comparing the two systems we find that chiller efficiency is basically equal

Variable Primary Systems

Page 35: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Compressor HP ~

Mass Flow X Lift

Load

Chiller

CoolingTower

Compressor/Cycle Efficiency

19XRV Chillers in Variable Primary Systems

Why is chiller performance identical for both systems?

KW = Tons x Lift

Page 36: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Lift is equivalent in both Primary / Secondary and VPF

systems.

Lift is SCT – SST.

SST – based on LCHWT

SCT – based on Tower Performance

Tons – Building load identical in VPF and P/S systems – just adjust flow and T .

19XRV Chillers in Variable Primary Systems

All of this is exactly the same regardless of chilled water system type!

The Efficiency Advantage of VFD Chillers is just as powerful on VPF systems!

Page 37: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Primary Secondary Pumping System Constant Speed

Variable Speed

Building Load GPM

Qty of Chillers

Chiller % Load ECWT

Chiller IKW/Ton

Chiller IKW/Ton

100 1200 1 20% 65 0.954 0.551208 1200 1 42% 65 0.619 0.36500 1200 1 100% 65 0.446 0.384550 2400 2 55% 65 0.537 0.332750 3600 2 75% 65 0.479 0.33

1000 3600 2 100.0% 71.8 0.485 0.4361100 3600 3 73.4% 74.2 0.527 0.4441500 3600 3 100% 85 0.59 0.589

Variable Primary Pumping SystemConstant Speed

Variable Speed

Building Load GPM

Qty of Chillers

Chiller % Load ECWT

Chiller IKW/Ton

Chiller IKW/Ton

100 500 1 20% 65 0.954 0.548208 500 1 42% 65 0.619 0.358500 1200 1 100% 65 0.446 0.384550 1320 2 55% 65 0.537 0.332750 1800 2 75% 65 0.479 0.328

1000 2400 2 100% 71.8 0.485 0.4361100 2640 3 73.4% 74.2 0.527 0.4421500 3600 3 100% 85 0.59 0.589

750 3600 3 50% 65 0.562 0.3391000 3600 3 66.7% 71.8 0.533 0.414

When comparing the two systems we find that chiller efficiency is basically equal

Variable Primary Systems

750 1800 2 75% 65 0.479 0.3281000 2400 2 100% 71.8 0.485 0.436

Except when the VPF chiller is able to operate fewer chillers than the Primary / Secondary system.

Page 38: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Outline

19XRV chillers in VPF systems.

19XRV Chillers in Variable Primary Systems

1. Review conventional Primary Secondary System.

2. Review Variable Primary Flow System.

3. Review the Benefits of “Max Cap” in both P/S and VPF systems.

4. Review the Benefits of VFD driven chillers in both P/S and VPF systems.

5. Review chiller selection guidelines for VPF applications.

.

Page 39: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Positive Pressure chillers typically can produce above rated tons as entering condenser water drops.

The “Max Cap” Advantage Applied in VPF Systems?

19XRV Chillers in Variable Primary Systems

570570

600600

630630

643643

630 630

Tons

8585ooFF 7575ooFF 7070ooFF <65<65ooFF8080ooFF

550550

Carrier

Others

Page 40: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

With MAX CAP feature,

At 550 tons, the design T (of 10F)

is achieved with 1320 gpm of flow.

(1) Chiller is fully loaded.

550 = 1320 x 10 24

1320 gpm

1320 gpm

0 gpm

1320 gpm

1320 gpm

550 tons

0 tons

0 tons

54 F44 F

1320 gpm

0 gpm

0 gpm

0 gpm

EX: 550 ton building load

44 F54 F

Page 41: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

With MAX CAP feature.

At 1100 tons, the design T (of 10F)

is achieved with 2640 gpm of flow.

(2) Chillers are now fully loaded.

1100 = 2640 x 10 24

2640 gpm

1320 gpm

1320 gpm

2640 gpm

2640 gpm

550 tons

550 tons

0 tons

54 F

44 F

1320 gpm

0 gpm

1320 gpm

0 gpm

EX: 1100 ton building load

44 F54 F

Page 42: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Variable Primary Systems

With MAX CAP feature.

At 1100 tons, the T can be increased from 10F to 11F by

lowering the LCHWT.

(2) Chillers are fully loaded.

1100 = 2400 x 11 24

2400 gpm

1200 gpm

1200 gpm

2400 gpm

2400 gpm

550 tons

550 tons

0 tons

54 F43 F

1200 gpm

0 gpm

1200 gpm

0 gpm

EX: 1100 ton building load

43 F54 F

Page 43: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Max Cap advantage – increasing evaporator flow.

Good idea on constant speed, not the way to control VFD chillers.

Variable Primary Systems

Primary Secondary Pumping System Constant Speed

Variable Speed

Building Load GPM

Qty of Chillers

Chiller % Load ECWT

Chiller IKW/Ton

Chiller IKW/Ton

100 1200 65208 1200 77500 1200 65550 2400 2 55% 65 0.537 0.332750 3600 65900 3600 69

1000 3600 71.81100 3600 3 73.4% 74.2 0.527 0.4441500 3600 85

MAX CAP ADVANTAGE - MORE EVAPORATOR FLOW.

Variable Primary Pumping SystemConstant Speed

Variable Speed

Building Load GPM

Qty of Chillers

Chiller % Load ECWT

Chiller IKW/Ton

Chiller IKW/Ton

100 500 65208 500 77500 1200 65550 1320 1 110% 65 0.453 0.433750 1800 65900 2160 69

1000 2400 71.81100 2640 2 110.0% 74.2 0.507 0.4971500 3600 85

Page 44: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Max Cap advantage holding evaporator flow constant and lowering LCHWT.

Increased lift on chiller – less efficient than increasing flow.

Variable Primary Systems

Primary Secondary Pumping System Constant Speed

Variable Speed

Building Load GPM

Qty of Chillers

Chiller % Load ECWT

Chiller IKW/Ton

Chiller IKW/Ton

100 1200 65208 1200 77500 1200 65550 2400 2 55% 65 0.537 0.332750 3600 65900 3600 69

1000 3600 71.81100 3600 3 73.4% 74.2 0.527 0.4441500 3600 85

MAX CAP ADVANTAGE - CONSTANT EVAP FLOW, LOWER LCHWT.

Variable Primary Pumping SystemConstant Speed

Variable Speed

Building Load GPM

Qty of Chillers

Chiller % Load ECWT

Chiller IKW/Ton

Chiller IKW/Ton

100 500 65208 500 77500 1200 65550 1320 1 110% 65 0.458 0.443750 1800 65900 2160 69

1000 2400 71.81100 2640 2 110.0% 74.2 0.517 0.5091500 3600 85

Page 45: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Outline

19XRV chillers in VPF systems.

19XRV Chillers in Variable Primary Systems

1. Review conventional Primary Secondary System.

2. Review Variable Primary Flow System.

3. Review the Benefits of “Max Cap” in both P/S and VPF systems.

4. Review the Benefits of VFD driven chillers in both P/S and VPF systems.

5. Review chiller selection guidelines for VPF applications.

.

Page 46: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Same reasons you would supply 19XRV on Primary Secondary Systems.

Why Provide Variable Speed Chillers in VPF?

19XRV Chillers in Variable Primary Systems

VFD driven chillers take advantage of reduced lift and/or reduced load hours offering annual power costs unmatched by any constant speed chiller.

.

Page 47: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Flow ~ V, ATo increase flow, increase flow area or rotor speed

Lift ~ V2

To increase lift, increase diameter or rotor speed

Power ~ Flow x Lift ~ V2

With constant flow and reduced lift, reduce speed to reduce power

Affinity laws for centrifugal fans, pumps and compressors.

V

Diameter

FlowArea

How 19XRV Chillers save kW in P/S & VPF Systems

Ideal Fan Laws Dictate the relationship between speed, flow and lift

19XRV Chillers in Variable Primary Systems

Page 48: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Methods to Improve Efficiency - Lift Reduction

- Aerodynamics

- Motor efficiency

- Transmission efficiency

- Metering devices

- Refrigerant

- Cycle enhancements

Compressor HP ~

Mass Flow X Lift

Load

Chiller

CoolingTower

Compressor/Cycle Efficiency

19XRV Chillers in Variable Primary Systems

How 19XRV Chillers save kW in P/S & VPF Systems

LiftECWT

Page 49: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Efficiency improves dramatically as ECWT drops.

19XRV Chillers in Variable Primary Systems

Reduced Lift at 100% tons(500 Tons)

0.30.35

0.40.45

0.50.55

0.6

85 80 75 70 65 60

Entering Condenser Water Temperature

IKW

/ Ton 19XRV

19XR

All points shown are 100% load (500 tons)

19XRV “unlifts” much better then constant speed machine.

Page 50: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Primary Secondary Pumping System Constant Speed

Variable Speed

Building Load GPM

Qty of Chillers

Chiller % Load ECWT

Chiller IKW/Ton

Chiller IKW/Ton

100 1200 1 20% 65 0.954 0.551208 1200 1 42% 65 0.619 0.36500 1200 1 100% 65 0.446 0.384550 2400 2 55% 65 0.537 0.332750 2400 2 75% 65 0.479 0.33

1000 2400 2 100.0% 71.8 0.485 0.4361100 3600 3 73.4% 74.2 0.527 0.4441500 3600 3 100% 85 0.59 0.589

Variable Primary Pumping SystemConstant Speed

Variable Speed

Building Load GPM

Qty of Chillers

Chiller % Load ECWT

Chiller IKW/Ton

Chiller IKW/Ton

100 500 1 20% 65 0.954 0.548208 500 1 42% 65 0.619 0.358500 1200 1 100% 65 0.446 0.384550 1320 2 55% 65 0.537 0.332750 1800 2 75% 65 0.479 0.328

1000 2400 2 100% 71.8 0.485 0.4361100 2640 3 73.4% 74.2 0.527 0.4421500 3600 3 100% 85 0.59 0.589

VFD column better than constant speed column at every point!

* VFD was selected for same FL IKW/Ton – therefore a bit larger and $$$.

Variable Primary Systems

Page 51: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Outline

19XRV chillers in VPF systems.

19XRV Chillers in Variable Primary Systems

1. Review conventional Primary Secondary System.

2. Review Variable Primary Flow System.

3. Review the Benefits of “Max Cap” in both P/S and VPF systems.

4. Review the Benefits of VFD driven chillers in both P/S and VPF systems.

5. Review chiller selection guidelines for VPF applications.

.

Page 52: PRIMARY VFD AND CHILLER SYSTEM

Phone Topics

Minimum flow rate is 1.5 feet / second (intermittent) and 3.0 feet / second (extended)

Maximum flow rate is 12 feet / second.

Rate of change of flow can be up to 30% per minute.

Evaporator should be selected such that design flow rate is at least double the minimum flow rate (if equally sized chillers).

Evaporator flow rate and pressure drops must be carefully coordinated if unequally sized chillers.

VFD chiller selection guidelines for VPF applications.

VPF systems save pump energy – don’t forget to save on chiller energy too.

Remember – you can have both!

19XRV Chillers in Variable Primary Systems