Model UT232OPERATING MANUAL
8/11/2019 UT232_EngManual
2/43
TABLE OF CONTENTSTITLE PAGE
Model UT232: OPERATING MANUAL
1
OverviewUnpacking InspectionSafety InformationRules For Safe OperationInternational Electrical SymbolsThe Meter Structure A.The Meter Front Structure B.The Meter Back and Bottom StructureFunctional ButtonsDisplay SymbolsMeasurement Operation A. AC Voltage + Frequency Measurement B. AC Current + AC Voltage Measurement C. Active Power + Phase Angle Measurement
D. Apparent Power + Reactive Power Measurement E. Power Factor + Phase Angle Measurement F. Active Energy + Time MeasurementTrue RMS Measurement and Average Value MeasurementSpecifications
3344677891214141618
2527293132
8/11/2019 UT232_EngManual
3/43
2
3233343434353536373838393939
40
Model UT232: OPERATING MANUAL
TABLE OF CONTENTSTITLE PAGE
A. General Specifications B. Environmental Requirements
Accuracy Specifications A. AC Voltage B. Frequency C. AC Current D. Active Power E. Apparent Power F. Reactive Power G. Power Factor H. Phase Angle I. Active EnergyMaintenance A. General Service
B. Replacing the Battery
8/11/2019 UT232_EngManual
4/43
3
Model UT232: OPERATING MANUAL
This Operating Manual covers information on safetyand cautions. Please read the relevant informationcarefully and observe all the Warnings and Notesstrictly.
Warning
To avoid electric shock or personal injury, read the Safety Information and Rules for Safe Operation carefully before using the Meter.
Model UT232 is a three phase intelligent handhelddigital power clamp meter (hereafter referred to as theMeter) which has both the features of digital currentmeter and also power measurement meter.
The Meter can measure Voltage, Current, Active Power, Apparent Power, Reactive Power, Power Factor, Phase Angle, Frequency, Active Energy and etc.
Open the package case and take out the Meter. Checkthe following items carefully to see any missing or damaged part:
Item12
345678910111213
DescriptionEnglish Operating ManualRed Test Lead
Black Test LeadBlue Test LeadYellow Test LeadRed Alligator ClipBlack Alligator ClipBlue Alligator ClipYellow Alligator ClipUSB Interface CableSoftwareTool Box1.5V Battery (LR6)
Qty1 piece1 piece
1 piece1 piece1 piece1 piece1 piece1 piece1 piece1 piece1 piece1 piece4 pieces
In the event you find any missing or damage, pleasecontact your dealer immediately.
Overview Unpacking Inspection
8/11/2019 UT232_EngManual
5/43
4
Model UT232: OPERATING MANUAL
Safety InformationThis Meter complies with the standards IEC61010: inpollution degree 2, overvoltage category (CAT. III 600V,CAT IV 300V) and double insulation.
CAT. III: Distribution level, fixed installation, with smaller transient overvoltages than CAT. IVCAT.IV: Primary supply level, overhead lines, cablesystems etc.
Use the Meter only as specified in this operating manual,otherwise the protection provided by the Meter may beimpaired.
In this manual, a Warning identifies conditions andactions that pose hazards to the user, or may damagethe Meter or the equipment under test.
A Note identifies the information that user should payattention to.
International electrical symbols used on the Meter and
l
l
l
l
in this Operating Manual are explained on page 6.
Rules For Safe Operation
Warning
To avoid possible electric shock or personal injury,and to avoid possible damage to the Meter or to theequipment under test, adhere to the following rules:
Before using the Meter inspect the case. Donot use the Meter if it is damaged or the case(or part of the case) is removed. Look for cracksor missing plastic. Pay attention to the insulationaround the connectors.Inspect the test leads for damaged insulationor exposed metal. Replace damaged test leadswith identical model number or electricalspecifications before using the Meter.Do not apply more that the rated voltage, asmarked on the Meter.When measurement has been completed,disconnect the connection between the testleads and the circuit under test, remove the
8/11/2019 UT232_EngManual
6/43
5
Model UT232: OPERATING MANUAL
l
l
l
l
l
l
l
testing leads away from the input terminals of the Meter and turn the Meter power off.Do not carry out the measurement when theMeters back case and / or battery door is openedto avoid electric shock.When the Meter working at an effective voltageover 30V in AC, special care should be taken.Use the proper terminals and function for your measurements.Do not use or store the Meter in an environmentof high temperature, humidity, explosive,inflammable and strong magnetic field. Theperformance of the Meter may deteriorate after dampened.Do not use the Meter if the surface of it is wetor the users hands are wet.When using the test leads, keep your fingersbehind the finger guards.Replace the battery as soon as the batteryindicator appears. With a low battery, theMeter might produce false readings that canlead to electric shock and personal injury.
l
l
l
l
ll
l
When opening the battery door, must make surethe Meter is power off.When servicing the Meter, use only the samemodel number or identical electricalspecifications replacement parts.The internal circuit of the Meter shall not bealtered at will to avoid damage of the Meter andany accident.Soft cloth and mild detergent should be usedto clean the surface of the Meter when servicing.No abrasive and solvent should be used toprevent the surface of the Meter from corrosion,damage and accident.The Meter is suitable for indoor use.Turn the Meter off when it is not in use and takeout the battery when not using for a long time.Constantly check the battery as it may leakwhen it has been using for some time, replacethe battery as soon as leaking appears.A leaking battery will damage the Meter.
8/11/2019 UT232_EngManual
7/43
6
Model UT232: OPERATING MANUAL
International Electrical Symbols
AC (Alternating Current)GroundingDouble InsulatedWarning. Refer to the Operating ManualDeficiency of Built-In BatteryDanger of High Voltage
Conforms to Standards of European Union
8/11/2019 UT232_EngManual
8/43
7
Model UT232: OPERATING MANUAL
Figure 1
1
2
34567
89
10
111213
Transformer Jaw: designed to pick up the ACand DC current flowing through the conductor. It could transfer current to voltage. The testedconductor must vertically go through the Jawcenter.Hand Guards: to protect users hand fromtouching the dangerous area.Power buttonMax/ buttonMENU buttonLOAD button (recall data)SELECT button (press to select alternatefunction and sum of Watts measurement)MIN/ buttonV3 Input Terminal (Third phase measurement)V2 Input Terminal
(Second phase measurement)V1 Input Terminal (First phase measurement)COM Input TerminalCLEAR button (maximum and minimum)
Black Red Blue Yellow
The Meter Structure
A. The Meter Front Structure (see figure 1)
8/11/2019 UT232_EngManual
9/43
8
Model UT232: OPERATING MANUAL
1 Infrared slot2 USB Interface Cable
Figure 2
14151617181920
button (Sum)SAVE button (data store button)USB buttonLIGHT button (auto display backlight button)HOLD buttonLCD DisplayTesting Leads (Red, Black, Blue and Yellow)
B. The Meter Back and Bottom Structure (see figure 2)
8/11/2019 UT232_EngManual
10/43
9
Model UT232: OPERATING MANUAL
Functional ButtonsBelow table indicated for information about the functionalbutton operations.
ButtonPOWER
HOLD
LIGHT
MENU
Operation PerformedPress and hold POWER for 1 second toturn the Meter on.Press POWER again to turn the Meter off.
Press HOLD to enter the Hold mode inany mode, appears and the Meter beeps. Press HOLD again to exit the Holdmode to return to measurement mode,the Meter beeps and disappears. Press LIGHT to turn the display backlighton. The display backlight will be off
automatically after 30 seconds.Press MENU to display the followingfunctions in sequence: AC Voltage (main display) + Frequency
ButtonMENU
MAX/
Operation Performed (secondary display) AC Current (main display) + AC Voltage (secondary display) Active power (main display) + Phase angle (secondary display) Apparent power (main display) + Reactive power (secondary display) Power factor (main display) + Phase angle (secondary display) Active Energy (main display) + Time (secondary display) Press to start recording of maximum value, it valid at voltage, current, active power and apparent power ranges only. Press once at LOAD mode, MR icon
shown, the Meter displays the next stored reading, the left secondary display showing the index increase one. Press once at mode, CAL icon shown,
8/11/2019 UT232_EngManual
11/43
10
Model UT232: OPERATING MANUAL
ButtonMAX/
USB
LOAD
Operation Performedthe Meter steps through sum of activepower (main display) + sum of reactivepower (secondary display) and sum of power factor (main display) + sum of apparent power. Press USB once to turn the USB interface on, USB appears and the
Meter beeps. Press USB again to turn the USB interface off, USB disappears and the Meter beeps. It is invalid at active energy mode Press once to enter LOAD mode, MR appears and the Meter beeps. Press again to exit LOAD mode, MR disappears and the Meter beeps.
Press and hold LOAD for 1 second to display the stored data quickly. At Active power (main display) + Phase angle (secondary display) mode, press once button to sum up the current
Button Operation Performed first phase of 3 phase measurement result. Then carry out second phase power measurement. Press again to sum up the second phase power measurement result, then carry out third phase power measurement.
Press again to sum up the third phase power measurement result, then press SELECT to enter the measurement of sum of the watts mode, the display shows the 3 phase sum of the watts value. Press once to store single reading, MEM appears and the Meter beeps. Press and hold for over 1 second to
continuous store reading, MEM blinks and the Meter beeps. The index number shown on the left secondary display keep on increasing. Press SAVE again
SAVE
8/11/2019 UT232_EngManual
12/43
11
Model UT232: OPERATING MANUAL
Button
At active power (main display) + phaseangle (secondary display) mode, pressSELECT button to step through first phase,second phase, third phase and sum of watts.
At other mode, press SELECT to stepthrough first phase, second phase and thethird phase.Press to start recording of minimum value,it valid at voltage, current, active power and apparent power ranges only.
Press once at LOAD mode, MR iconshown, the Meter displays the previousstored reading, the left secondary displayshowing the index decrease one.Press once at mode, CAL icon shown,
SELECT
MIN /
Buttonthe Meter steps through sum of activepower (main display) + sum of reactivepower (secondary display) and sum of power factor (main display) + sum of apparent power.
CLEAR
Operation Performedto exit. The maximum number of data storeis 99, when it achieves 99, the Meter showsFUL. Press CLEAR to clear the storedreading in order to store next reading.
Operation Performed
At active energy range, press to resettime the zero, then restart the timing.
At all other ranges, press to clear storedreadings.
8/11/2019 UT232_EngManual
13/43
12
Model UT232: OPERATING MANUAL
Display Symbols (see figure 3)
Figure 3
123456789
1011
MeaningData Output is in progressIndicator for DC measurementFirst phase symbolSecond phase symbolThird phase symbolUnit for hour Unit for minuteWatt: Sum of WattThe battery is low.
Warning: To avoid falsereadings, which could lead topossible electric shock or personal injury, replace thebattery as soon as the batteryindicator appears.
Unit for secondSymbol of Unit.Hz: Hertz.The unit of frequency.PG: The unit of phase angleKVAr. The unit of reactive power
SymbolUSBDC
123
hmm
W
s
Hz,PG,KVAr
Number
8/11/2019 UT232_EngManual
14/43
13
Model UT232: OPERATING MANUAL
Number 121314151617
18192021
22
23
242526
MeaningMinimum reading
Analogue Bar GraphOverloadingRuler Maximum readingIndicator for clear the storedreadingRuler negative symbolHigh voltage symbolIndicates negative readingIndicator for AC voltage or currentIndicator for recall the storedreadingFrequency symbol
Indicator for data storeIndicator for data stored is fullData hold is active
SymbolMIN
MAXCLR
AC
MR
FREQ
MEMFUL
8/11/2019 UT232_EngManual
15/43
14
Model UT232: OPERATING MANUAL
Figure 4
Black
Red
Blue
Yellow
Measurement Operation
Preparation
Press and hold POWER for one second to turn theMeter on. The default range is the last measurementrange when you turned off the Meter.Replace the battery as soon as the battery indicator appears on the display.
A. AC Voltage (main display) + Frequency (secondary display) Measurement (see figure 4)
8/11/2019 UT232_EngManual
16/43
15
Model UT232: OPERATING MANUAL
The AC Voltage ranges are:15V, 100V, 300V and 600V
The frequency range is:20Hz~500Hz
To measure AC voltage + frequency, connect the Meter as follows:
1.
2.
3.
4.
Insert the red test lead into the V1 terminal, bluetest lead into the V2 terminal, yellow test lead toV3 input terminal and black test lead to the COMinput terminal.Press the MENU to select Voltage (main display)+ Frequency (secondary display) range.Connect the red test leads ( V1 input terminal), bluetest leads ( V2 input terminal) and yellow test leads(V3 input terminal) to the corresponding threephases loaded live wire. Black test lead ( COM input terminal) to the corresponding three phases
loaded neutral wire.Press SELECT to select phase location, the displayshows the corresponding phase symbol. V1 meansthe first phase 1, V2 means the first phase 2,V3 means the first phase 3.
5.
6.
7.
8.
The display shows the corresponding True RMSvoltage value and frequency value of each phase.Press MAX/ , the LCD displays MAX, it startsrecording the maximum AC voltage True RMS value.Press MAX/ again to show the current AC voltageTrue RMS value.Press MIN/ the LCD displays MAX, it startsrecording the minimum AC voltage True RMS value.Press MAX/ again to show the current AC voltageTrue RMS value.The display shows OL when the input voltage ishigher than 600V rms.
Note
When the measurement has been completed,disconnect the connection between the testing leadsand the circuit under test and remove testing leads
from the input terminals.
8/11/2019 UT232_EngManual
17/43
16
Model UT232: OPERATING MANUAL
B. AC Current (main display) + AC Voltage (secondary display) Measurement (see figure 5)
Figure 5
The AC current ranges are: 40A, 100A, 400A and 1000A
The AC Voltage ranges are: 15V, 100V, 300V and 600V
To measure AC current + AC voltage, connect the Meter as follows:
1.
2.3.
4.
5.
Press the MENU to select AC Current (main display)+ AC Voltage (secondary display) range.Press the lever to open the transformer jaw.Center the conductor within the transformer jaw,then release the Meter slowly until the trasnformer
jaw is completely closed, Make sure the conductor to be tested is placed at the center of the transformer
jaw, otherwise it will casue deviation. The Meter can only measure one conductor at a time, tomeausre more than one condutor at a time willcause deviation.
The double display shows the AC current TrueRMS value and AC voltage True RMS value.Press MAX/ , the LCD displays MAX, it startsrecording the maximum AC current True RMS value.Press MAX/ again to show the present AC
8/11/2019 UT232_EngManual
18/43
6.
7.
True RMS value.Press MIN/ , the LCD displays MAX, it startsrecording the minimum AC current True RMS value.Press MAX/ , again to show the present AC currentTrue RMS value.The display shows OL when the current of thetested conductor is higher than 1000A rms.
17
Model UT232: OPERATING MANUAL
Note
When the measurement has been completed,disconnect the connection between the conductor under test and the jaw, and remove the conductor away from the transformer jaw of the Meter.
8/11/2019 UT232_EngManual
19/43
18
Model UT232: OPERATING MANUAL
C. Active Power (main display) + Phase Angle (secondary display) Measurement
The active power ranges are:40A, 100A, 400A and 1000A
The phase angle ranges are: 0~360
Warning
To avoid damages to the Meter or harms to you, doyou measure higher than AC voltage 600 v.r.s. andAC current 1000A v.r.s.
To measure active power + phase angle, connect theMeter as follows:
1.
2.
Press the MENU to select Active power (maindisplay) + Phase angle (secondary display) range.Press the lever to open the transformer jaw, andclamp them to the corrresponding phase of testedconductor. If user needs to mesaure any phase of the 3 phase, then clamp them to that phasesconductor.
3. Connecting method (see figure 6, 7, 8):
8/11/2019 UT232_EngManual
20/43
Figure 6
Model UT232: OPERATING MANUAL
19
Black
Red
Blue
Yellow
Insert red test leads to V1 input terminal.Insert blue test leads to V2 input terminalInsert yellow test leads to V3 input terminal andconnecting it to every live wire of the 3 phase.Insert black test leads to COM input terminal andconnect it to the neutrual wire of the 3 phase.You must specify that this connection is used onlywhen the main transformer have STAR connection.
8/11/2019 UT232_EngManual
21/43
Figure 7
Model UT232: OPERATING MANUAL
20
Insert red test leads to V1 input terminal.Insert blue test leads to V2 input terminalInsert yellow test leads to V3 input terminal andconnect it to every live wire of the 3 phase.
Red
Blue
8/11/2019 UT232_EngManual
22/43
21
Model UT232: OPERATING MANUAL
Figure 8
Insert red test lead to V1, V2 or V3 input terminalcorresponding to one of 1, 2 or 3 phaseInsert black test leads to COM input terminal.Connecting the two test leads to live and neutualwires.
Black
Red
8/11/2019 UT232_EngManual
23/43
22
Model UT232: OPERATING MANUAL
Figure 9
Figure 10
Figure 11
Figure 12
4. When measuring 3 phases 4 wires or 3 phases 3wires:(see figure 9, 10, 11, 12, 13, 14, 15)
Press SELECT to choose first phase 1, seefigure 9. The double displays show the acitvepower kW value and also the PG value of 1.
If necessary, press to get the sum of watts asfigure 10.
After sum up the current power measurement valueof the first phase, then press SELECT to choose thesecond phase 2, as figure 11
The double display shows the value of acitve power kW and PG of 2.If ncessary, press to get the sum of watts as figure12.
8/11/2019 UT232_EngManual
24/43
Model UT232: OPERATING MANUAL
23
Figure 14
Figure 15
Figure 13
After sum up the current power meaursuremnt valueof the second phase, then press SELECT again tochoose the third phase 3, as figure 13.
The double display shows the value of acitve power KW and PG of 3.If ncessary, press to get the sum of watts as figure14.
After sum up the current power measurement valueof the third phase, finally press SELECT again todisplay the 3 phase sum of acitve power value andreactive power value.Press MAX/ or MIN/ as figure 15 to step throughin sequence three phase sum of active power+threephase sum of reacitve power, and three phase sumof power factor + 3 phase sum of apparent power.
8/11/2019 UT232_EngManual
25/43
Model UT232: OPERATING MANUAL
24
active power, OL will be displayed when it is over than that.Press MAX/ , the display shows MAX, it startsrecording the maximum active power value. Pressagain to display the current active power value.Press MIN/ , the display shows MIN, it startsrecording the minimum active power value. Pressagain to display the current active power value.
6.
7.
The maximum power is 600kW of single phase, OLwill be displayed when it is over than that. Themaximum range is 1800kW of three phase sum of
5.
When there is no input or single phase, the Meter displays OL. button is not valid.It can only sum up the current measurement value.The maximum and minimum value cannot besummed up.Only at this range can carry out sum of wattsmeasurement, other ranges cannot carry out this
measurement.When testing has been completed, disconnect theconnection between the testing leads and the circuitunder test and remove testing leads from the inputterminals.
Note
8/11/2019 UT232_EngManual
26/43
Figure 17
Figure 18
25
Model UT232: OPERATING MANUAL
D. Apparent Power (main display) + Reactive Power (secondary display) Measurement
To avoid damages to the Meter or harms to you, doyou measure higher than AC voltage 600V rms andAC current 1000A rms.
Warning
To test for Apparent power (main display) + Reactivepower (secondary display), connect the Meter as follows:
1.
2.
3.
Press the MENU to select Apparent power (maindisplay) + Reactive power (secondary display)range.Press the lever to open the transformer jaw, andclamp them to the corrresponding phase of testedconductor. If user needs to mesaure any phase of the 3 phase, then clamp them to that phases
conductor.The connecting method of 3 phases 4 wires, 3phases 3 wires or single phase 2 wires, see figure6, 7 a nd 8
4. When measuring 3 phase 4 wires:(see figure 17, 18, 19)
Press SELECT to choose the first phase 1,see figure 17.
The double display shows the first phase valueof apparent power kVA and reactive power Kvar.Then press SELECT again to choose the secondphase 2, see figure 18.
8/11/2019 UT232_EngManual
27/43
Figure 19
26
Model UT232: OPERATING MANUAL
The double display shows the second phase valueof apparent power kVA and reactive power Kvar.Press SELECT again to choose the third phase 3,see figure 19.
The double display shows the third phase value of apparent power kVA and reactive power Kvar.
When measuring 3 phase 3 wires: The first phase and secodn phase operating method is same as three phase 4 wires. Jump over the third phase measurement.The maximum measuring range is 600kW whenmeasuring single phase apparent power kVA andreactive power Kvar, OL wil be displayed when it isover than that.Press MAX/ , the display shows MAX, it startsrecording the maximum apparent power value.Press again to display the current apparent power value.Press MIN/ , the display shows MIN, it startsrecording the minimum apparent power value.Press again to display the current apparent power value.
5.
6.
7.
8.
Note
When testing has been completed, disconnect theconnection between the testing leads and the circuitunder test and remove testing leads from the inputterminals.
8/11/2019 UT232_EngManual
28/43
Figure 20
Figure 21
Model UT232: OPERATING MANUAL
27
E. Power Factor (main display) + Phase Angle (secondary display) Measurement
To avoid damages to the Meter or harms to you, doyou measure higher than AC voltage 600V rms andAC current 1000A rms.
Warning
To test for Power factor (main display) + Phase angle
(secondary display), connect the Meter as follows:
Press the MENU to select Power factor (maindisplay) + Phase angle (secondary display) range.Press the lever to open the transformer jaw, andclamp them to the corrresponding phase of testedconductor. If user needs to mesaure any phase of the 3 phase, then clamp them to that phasesconductor.
The connecting method of 3 phases 4 wires, 3phases 3 wires or single phase 2 wires, see figure6, 7 and 8When measuring 3 phase 4 wires: (see figure 20,21, 22)
1.
2.
3.
4.
Press SELECT to choose the first phase 1 ,see figure 20.
The double display shows the first phase value of power factor PF and phase angle PG.Then press SELECT again to choose the secondphase 2, see figure 21.
8/11/2019 UT232_EngManual
29/43
Figure 22
Model UT232: OPERATING MANUAL
28
The double display shows the second phase valueof power factor PF and phase angle PG.Press SELECT again to choose the third phase 3,see figure 22.
The double display shows the third phase value of power factor PF and phase angle PG.
5. When measuring 3 phase 3 wires:
The first phase and second phase operatingmethod is same as three phase 4 wires.Jump over the third phase measurement.
6. MAX/ and MIN/ are not valid when measuring power factor.
When testing has been completed, disconnect theconnection between the testing leads and the circuitunder test and remove testing leads from the inputterminals.
Note
8/11/2019 UT232_EngManual
30/43
29
Model UT232: OPERATING MANUAL
Figure 23
F. Active Energy (main display) + Time (secondary display) Measurement
Warning
To avoid damages to the Meter or harms to you, doyou measure higher than AC voltage 600V rms andAC current 1000A rms.
To test for Active Energy (main display) + Time
(secondary display), connect the Meter as follows:
1.
2.
3.
4.
Press the MENU to select Power factor (maindisplay) + Phase angle (secondary display) range.Press the lever to open the transformer jaw, andclamp them to the corrresponding phase of testedconductor. If user needs to mesaure any phase of the 3 phase, then clamp them to that phasesconductor.
The connecting method of 3 phase 4 wires, 3 phases3 wires or single phase 2 wires, see figure 6, 7 and8Press SELECT to choose one of the three phases( 1, 2, 3), see figure 23.
The double display shows the value of tested objects
active engergy kWh value and the measuring timeof the corresponding phase.The measuring reading gets increasing along withthe time increases. Press HOLD to read a particular time kWh value. Then the reading and time arelocked, but still continuous accumulate measuringtime.
After read the data, press HOLD again to continousmeasurement. kWh value continous accumulateand the measuring time jumps to the presentmeasuring time.When the measuring time is over 24 hours or theMeter is switched to other measuring ranges, activeenergy measuring will stop.
8/11/2019 UT232_EngManual
31/43
30
Model UT232: OPERATING MANUAL
The maximum readinng of acitve energy is9999kWh. OL will be displayed when the readingis over than that.
5. MAX/ and MIN/ are not valid when measuring active energy.6. Press CLEAR to reset the time.
Note
When there is no input signal, it cannot carry outactive energy measurement.When there is input signal, the maximum waitingtime is around 10s before timing.When testing has been completed, disconnect theconnection between the testing leads and the circuitunder test and remove testing leads from the inputterminals.
8/11/2019 UT232_EngManual
32/43
Model UT232: OPERATING MANUAL
31
True RMS Measurement and Average ValueMeasurement
The True RMS measurement method can measureaccurately the effective value of non-sine wave inputsignal.
Average value measurement method can measure themean value of one sine wave input signal, and thendisplays it as RMS value
When the input waveform has distortion, measuringtolerance will be included. The total tolerance dependson the total distortion. Below table 1 shows the waveformcoefficient and the relationship and the requestedchanging factor of sine wave, square wave, pulserectangle wave, sawtooth triangle wave, RMS valueand average value.
Input Wave PK-PK 0-PK RMS AVGSine
PK0 PK-PK
sine commute(whole wave)
PK0 PK-PK
sine commute(half wave)
PK0 PK-PK
square wavePK0 PK-PK
commuted square wavePK0 PK-PK
pulse rectangle
X0 PK-PKY
D=X/Y
sawtooth trianglePK
0 PK-PK
2.828
1.414
2.828
1.800
1.800
0.9/D
3.600
1.414
1.414
2.828
0.900
1.800
0.9/ D
1.800
1.000
1.000
1.414
0.900
1.272
0.9D/2
1.038
0.900
0.900
0.900
0.900
0.900
0.9/D
0.900
8/11/2019 UT232_EngManual
33/43
Model UT232: OPERATING MANUAL
32
SpecificationsA. General Specifications
Maximum Voltage between any Terminals andgrounding: Refer to different range input protectionvoltage.Display: Multi LCD displays, Maximum display 9999.Ranges: AutoOverloading: Display OL .
Battery Deficiency: Display .Data Holding: DisplayData Logging: Maximum 99, Single or ContinuousrecordsData RecallMaximum and Minimum value display: Voltage,Current, Active Power and Apparent Power rangesDisplay Backlight: White colour Computer connection: USB
Calibration FeatureSleep Mode: To preserve battery life, the Meter automatically turns off if you do not turn press anybutton for around 15 minutes., except at active factor range.
Sampling: 3 times per second.Max. Jaw Size: 55mm diameter.
Analogue Bar GraphPower: 4 x 1.5V battery (LR6)Dimensions: 303mm x 112mm x 39mmWeight: Approximate 601g
8/11/2019 UT232_EngManual
34/43
33
Model UT232: OPERATING MANUAL
B. Environmental Requirements
The Meter is suitable for indoor use. Altitude: Operating: 2000m Storage: 10000mTemperature and humidity:
Operating: 0 ~ 30 ( 85%R.H) 30 ~ 40 ( 75%R.H) 40 ~ 50 ( 45%R.H)
Storage: -10 ~ +60 ( 85%R.H)Safety/ Compliances: IEC 61010 CAT.III 600V,CAT.IV 300V overvoltage and double insulationstandard, pollution degree 2.Certification:
8/11/2019 UT232_EngManual
35/43
34
Model UT232: OPERATING MANUAL
Accurate Specifications Accuracy: (a% reading + b digits), guarantee for 1 year.Operating temperature: 23 5Operating humidity: 45~75%R.H
A. AC Voltage (True RMS)
Range15V100V300V600V
Resolution
0.1V
Accuracy
(1.2%+5)
Allowable Maximum overload protection voltage
600 RMS
Input Impedance
10M
B. Frequency
Range20Hz~500Hz
Resolution1Hz
Accuracy(0.5%+5)
8/11/2019 UT232_EngManual
36/43
Model UT232: OPERATING MANUAL
35
D. Active Power ( W=V x A x COS )
Current / Voltage
CurrentRange
40A100A400A1000A
15V0.60kW1.50kW6.00kW15.00kW
100V4.00kW10.00kW40.00kW100.0kW
300V12.00kW30.00kW120.0kW300.0kW
600V24.00kW60.00kW240.0kW600.0kW
Voltages Range
AccuracyResolution
(3%+5)
8/11/2019 UT232_EngManual
37/43
Model UT232: OPERATING MANUAL
36
E. Apparent Power (VA = V x A)
Current / Voltage
CurrentRange
40A100A400A1000A
15V0.60kVA1.50kVA6.00kVA15.00kVA
100V4.00kVA10.00kVA40.00kVA100.0kVA
300V12.00kVA30.00kVA120.0kVA300.0kVA
600V24.00kVA60.00kVA240.0kVA600.0kVA
Voltages Range
AccuracyResolution
(3%+5)
8/11/2019 UT232_EngManual
38/43
37
Model UT232: OPERATING MANUAL
F. Reactive Power (Var = V x A x SIN )
Current / Voltage
CurrentRange
40A100A400A1000A
15V0.60kVar 1.50kVar 6.00kVar 15.00kVar
100V4.00kVar 10.00kVar 40.00kVar 100.0kVar
300V12.00kVar 30.00kVar 120.0kVar 300.0kVar
600V24.00kVar 60.00kVar 240.0kVar 600.0kVar
Voltages Range
AccuracyResolution
15V/1000A Range: (4%+10) Other Ranges: (4%+5)
8/11/2019 UT232_EngManual
39/43
38
Model UT232: OPERATING MANUAL
G. Power Factor (PF = W / VA)
Range0.3~1(capacitive or inductive)0.3~1(capacitive or inductive)
Accuracy
0.022
Resolution
0.001
Measuring ConditionThe minimum measuring current 10AThe minimum measuring voltage 45VMeasuring current less than 10A ORMeasuring voltage less than 45V
For reference only
H. Phase Angle (PG=acos (PF))
Range0~360
0~360
Accuracy
1
Resolution
1
Measuring ConditionThe minimum measuring current 10AThe minimum measuring voltage 45VMeasuring current less than 10A ORMeasuring voltage less than 45VFor reference only
Remarks: Allowable maximum overload protection voltage: 600V RMS Allowable maximum overload protection current: 1000A RMS
8/11/2019 UT232_EngManual
40/43
8/11/2019 UT232_EngManual
41/43
Figure 24
Model UT232: OPERATING MANUAL
40
high temperature, explosive, inflammable and strongmagnetic field.
B. Replacing the Battery (see figure 24)To avoid false readings, which could lead to possibleelectric shock or personal injury, replace the batteryas soon as the battery indicator appears.
Make sure the transformer jaw and the tests leadsare disconected from the circuit being tested beforeopening the case bottom.
Warning
To replace the battery:.
1.
2.3.
4.
5.
Press POWER to turn the Meter off and remove allthe connections from the input terminalsTurn the Meters front case down.Remove the screw from the battery door, andseparate the battery door from the case bottom.Take out the old battery and replace with 4 x 1.5Vbattery (LR6).
Rejoin the case bottom and the battery compartment,and reinstall the screw.
8/11/2019 UT232_EngManual
42/43
Model UT232: OPERATING MANUAL
41
This operating manual is subject to change without notice.
*END*