Upload
abdelhamid-oughanem
View
216
Download
0
Embed Size (px)
Citation preview
7/30/2019 10.1.1.32.165
1/161
DESIGN ANALYSIS OF A FINNED-TUBE CONDENSER FOR A RESIDENTIAL
AIR-CONDITIONER USING R-22
A Thesis
Presented to
The Academic Faculty
By
Emma May Sadler
In Partial Fulfillment
of the Requirements for the Degree
Master of Science in Mechanical Engineering
Georgia Institute of Technology
April 2000
7/30/2019 10.1.1.32.165
2/161
ii
DESIGN ANALYSIS OF A FINNED-TUBE CONDENSER FOR A RESIDENTIAL
AIR-CONDITIONER USING R-22
Approved:
____________________________________
S. V. Shelton, Chairman
____________________________________
P. V. Kadaba
____________________________________
A. V. Larson
Date Approved________________________
7/30/2019 10.1.1.32.165
3/161
iii
ACKNOWLEDGEMENTS
This work would not have been completed without the help and support of many
others. In particular, I would like to thank my advisor, Dr. Shelton, for his enthusiasm
for my scholastic, professional, and personal success. He has provided motivation and
insights that have been invaluable to this project and my sanity. Id also like to thank
Monifa Wright and Shawn Klawunder for sharing their resources and discoveries.
I would never have made it this far without my parents who have unconditionally
supported any endeavor that would lead to my happiness, be it a Masters degree or a
career as a goat herder. This thesis is dedicated to my grandparents, Sol and Frieda
Gersen, who have been more concerned about my progress than anyone else.
7/30/2019 10.1.1.32.165
4/161
iv
TABLE OF CONTENTS
Chapter IIntroduction........................................................................................................ 1Background ..................................................................................................................... 1
Considerations................................................................................................................. 1Past Work........................................................................................................................ 2Purpose............................................................................................................................ 4
Chapter IIResidential Air Conditioning Systems.............................................................. 6Refrigeration Cycle ......................................................................................................... 6
Air Conditioner Components .......................................................................................... 8Compressor.................................................................................................................. 8Condenser.................................................................................................................. 11
Condenser Fan........................................................................................................... 12Expansion Valve ....................................................................................................... 13
Evaporator................................................................................................................. 13Evaporator Fan.......................................................................................................... 15
Coefficient of Performance........................................................................................... 16
Seasonal COP................................................................................................................ 16
Chapter IIIHeat Exchangers............................................................................................ 20
Geometry....................................................................................................................... 20NTU-Effectiveness Relations........................................................................................ 23
Refrigerant Side Models................................................................................................ 30Single Phase Heat Transfer Coefficient.................................................................... 30Condensation Heat Transfer Coefficient ................................................................... 33
Evaporative Heat Transfer Coefficient ..................................................................... 35Pressure Drop in Straight Pipe.................................................................................. 36Pressure Drop in Bends............................................................................................. 39
Air Side Models ............................................................................................................ 44Heat Transfer Coefficient.......................................................................................... 44
Pressure Drop............................................................................................................ 46
Chapter IVOptimization of Operating Parameters.......................................................... 52Subcool and Seasonal Effects ....................................................................................... 54
Effect of Varying Air Velocity...................................................................................... 58Effect on Cost Factor..................................................................................................... 60
Chapter VEffects of Geometry with Fixed Cost ............................................................. 62Number of Rows ........................................................................................................... 64Fin Pitch........................................................................................................................ 66
Tube Diameter............................................................................................................... 71Tube Circuiting.............................................................................................................. 75
7/30/2019 10.1.1.32.165
5/161
v
Operating Costs............................................................................................................. 79
Chapter VIEffects of Geometry with Fixed Frontal Area............................................... 85
Number of Rows ........................................................................................................... 85Fin Pitch........................................................................................................................ 90Tube Diameter............................................................................................................... 92Comparing Fixed Area to Fixed Cost ......................................................................... 101
Chapter VIIConclusions and Recommendations .......................................................... 103
Appendix I Mass of Refrigerant in a Heat Exchanger Coil Undergoing Phase Change
............................................................................................................................. 106
Appendix II EES Simulation Program........................................................................... 109
Appendix III Condenser Operating Conditions............................................................. 136
References....................................................................................................................... 146
7/30/2019 10.1.1.32.165
6/161
vi
LIST OF TABLES
Table 1. Distribution of Cooling Load Hours ................................................................... 17Table 2. Euler number coefficients for inverse power series............................................ 49
Table 3. Staggered Array Geometry Factor...................................................................... 50Table 4. Individual row correction factors........................................................................ 51Table 5. Air-Conditioner Design Conditions .................................................................... 52
Table 6. Base Case Condenser and Evaporator Characteristics........................................ 53Table 7. Mass of Refrigerant in Air-Conditioner for Different Subcool Specifications... 54
Table 8. Material Costs ..................................................................................................... 63Table 9. COPs and Area Factors Based on Fin Pitch...................................................... 67
Table 10. Data for Copper Tubes...................................................................................... 71Table 11. COPs and Area Factors Based on Tube Diameter........................................... 72Table 12. Condenser Configurations for Circuiting Analysis........................................... 76
Table 13. Maximum Seasonal COPs for Different Tubes per Circuit with Fixed Cost .. 77Table 14. Pressure Drop Distributions at 83 F................................................................ 78Table 15. COP and Flow Area for Different Circuiting Configurations........................... 80Table 16. Data for Varying Number of Rows at 83 F..................................................... 87Table 17. Overall UA and UA/ Length for Varying Rows at 83 F ................................. 89Table 18. Optimum Operating Conditions For Varying Number of Rows with Fixed Area
................................................................................................................................... 90Table 19. Optimum Operating Conditions For Varying Tube Diameter with Fixed Area94
7/30/2019 10.1.1.32.165
7/161
vii
LIST OF FIGURES
Figure 1. Thermodynamic State of Refrigerant in Refrigeration Cycle.............................. 7Figure 2. Refrigeration Cycle Equipment ........................................................................... 8
Figure 3. Typical Plate Finned-Tube Heat Exchanger...................................................... 11Figure 4. Effective Specific Heat ...................................................................................... 14Figure 5. General Heat Exchanger Dimensions................................................................ 22
Figure 6. Layout of Heat Exchanger Geometry Parameters ............................................. 23Figure 7. Layout of Hexagonal Fins.................................................................................. 28
Figure 8. Effects of Operating Conditions on Evaporator Frontal Area........................... 54Figure 9. Condenser Subcool at Varying Ambient for Different Refrigerant Charges..... 56
Figure 10. Effect of Ambient Temperature on Evaporator Capacity and Mass Flow Rate................................................................................................................................... 57Figure 11. Trends in Seasonal COP vs. COPs at Other Temperatures............................ 58
Figure 12. Effect of Air Velocity on Seasonal COP for Different Subcool Conditions ... 59Figure 13. Effect of Air Velocity on Compressor and Condenser Fan Work................... 60Figure 14. Number of Rows vs. Seasonal COP with Fixed Cost...................................... 64
Figure 15. Number of Rows vs. Compressor Power and Refrigerant Pressure Drop....... 65Figure 16. Rows vs. Air Side Pressure Drop and Fan Power for Fixed Cost at 83 F....... 66
Figure 17. Seasonal COPs for Different Fin Pitches at Optimum Operating Conditionswith Fixed Cost ......................................................................................................... 67
Figure 18. Effect of Fin Pitch on Seasonal COP at Different Air Velocities.................... 68
Figure 19. Effect of Fin Pitch on Frontal Area ................................................................. 69Figure 20. Fin Pitch vs. Airside Pressure Drop at 83F...................................................... 70
Figure 21. Effect of Fin Pitch on Power Requirements at 83F......................................... 70Figure 22. Maximum Seasonal COP for Different Tube Diameters................................. 72Figure 23. Optimal Operating Conditions for Different Tube Diameters......................... 73
Figure 24. Condenser Allocation for Different Tube Diameters at 83F ........................... 74Figure 25. Refrigerant Side Pressure Drop vs. Tube Diameter at 83F ............................. 75
Figure 26. Maximum Seasonal COP for Different Circuiting.......................................... 77Figure 27. Pressure Drop vs. Circuiting at 83 F.............................................................. 78Figure 28. Operating Costs vs. Area Factor for Different Geometry Factors................... 82Figure 29. Operating Costs For Different Tube Diameters and Circuiting at 83 F with
Fixed Cost ................................................................................................................. 83Figure 30. Effect of Varying Fin Pitch for Base Case and Optimum Case at 83 F withFixed Cost ................................................................................................................. 84
Figure 31. Seasonal COP for Varying Rows with Fixed Area.......................................... 86Figure 32. Tradeoffs Between Compressor and Fan Power for Varying Number of Rows
with Fixed Area at 83 F............................................................................................. 87Figure 33. Condenser Allocation for Varying Rows at 83 F........................................... 88
7/30/2019 10.1.1.32.165
8/161
viii
Figure 34. Air Velocity vs. Seasonal COP for Different Row Configurations with Fixed
Area........................................................................................................................... 90Figure 35. Variance of Optimal Air Velocity with Fin Pitch for Fixed Frontal Area....... 91
Figure 36. Condenser Allocation for Varying Fin Pitch at 83F........................................ 92Figure 37. Variance of Optimal Air Velocity with Tube Diameter at Optimum Subcool
for Fixed Frontal Area............................................................................................... 93
Figure 38. Air Side Pressure Drop for Varying Tube Diameters at 83 F........................ 95Figure 39. Compressor and Fan Power Trends vs. Tube Diameter at 83 F .................... 96Figure 40. Operating Costs vs. Cost Factor for Different Geometry Factors ................... 98
Figure 41. Operating Costs For Different Tube Diameters and Circuiting at 83 F withFixed Area................................................................................................................. 99
Figure 42. Optimum Condenser Circuiting for Fixed Area at 83 F with Varying Rows100
Figure 43. Comparison of Area Factor to Cost Factor Based on Number of Rows....... 101Figure 44. Comparison of Area Factor to Cost Factor Based on Fin Pitch.................... 102
Figure 45. Comparison of Area Factor to Cost Factor Based on Tube Diameter........... 102
7/30/2019 10.1.1.32.165
9/161
ix
LIST OF SYMBOLS
Symbol Refers to
a Stanton number coefficient
a Ratio of transverse tube spacing to tube diameter
A Total heat transfer area
Ac Minimum free-flow cross sectional area
Af Total fin surface area
Afr Frontal area
Amin Minimum flow area
Ao Total airside heat transfer area, fins and tubes
AF Area Factor
b Stanton number coefficient
b Ratio of longitudinal tube spacing to tube diameter
B Bend coefficient
BL Building Load
C Heat capacityCF Cost Factor
CLF Cooling Load Factor
COP Coefficient of performance
cp Specific heat
cp,eff Effective specific heat
Cr Heat capacity ratio
Cz Average row correction factor
cz Individual row correction factor
D Tube Diameter
E& Electrical Power Demand
Eu Euler number
f Friction factor
7/30/2019 10.1.1.32.165
10/161
x
FP Fin Pitch
Fr Froude number
G Mass flux
gc Gravitational constant
h Enthalpy
h Heat transfer coefficient
H Heat exchanger height
j Colburn factor
JP j-factor parameter
k Conductivity
k Bend pressure coefficient
k1 Staggered array geometry factor
L Length
m Fin parameter
m Mass
m& Mass flow rate
n Blasius coefficient
NTU Number of transfer unitsNu Nusselt number
pr Reduced pressure
Pr Pressure ratio
PD Piston displacement
PLF Part load factor
Pr Prandtl number
eQ& Evaporator capacity
r Outside tube radius
rb Radius of bend
re Equivalent radius
rr Relative radius
R Ratio of clearance volume to displacement
7/30/2019 10.1.1.32.165
11/161
xi
Rw Wall Resistance
R Fouling factor
Re Reynolds number
SF Size Factor
St Stanton number
t Fin thickness
Tr Temperature ratio
tpc Tubes per circuit
U Overall heat transfer coefficient
v Specific volume
Va Air face velocity
W Heat exchanger width
wa Actual specific compressor work
ws Isentropic specific compressor work
comW& Compressor power
fW& Fan power
x Quality
Xl Longitudinal tube spacing (parallel to air flow)
Xt Transverse tube spacing (normal to air flow)
z Number of rows
z/D Equivalent length
Fin parameter
tt Lockhart-Martinelli parameter
h Enthalpy change
hlatEnthalpy change due to condensation
hsens Enthalpy change due to temperature change
Pa Air-side pressure drop
Pf Refrigerant side two-phase friction pressure drop
Pm Refrigerant side two phase momentum pressure drop
7/30/2019 10.1.1.32.165
12/161
xii
Heat exchanger effectiveness
Roughness
Fin parameter
2 Bend physical property coefficient
2 Two phase bend multiplier
Friction factor
Viscosity
Density
c Compressor thermal efficiency
f Fan efficiencys Surface efficiency
v Volumetric efficiency
Fin parameter
#circ Number of parallel circuits
7/30/2019 10.1.1.32.165
13/161
xiii
SUMMARY
The purpose of this study was to develop an optimization methodology and
software for the detailed design of a finned-tube condenser heat exchanger coil in a
residential air-conditioning unit using the Engineering Equation Solver (EES) software.
The superheat, saturated, and subcool portions of the heat exchanger have been modeled
separately and in detail using appropriate pressure drop and heat transfer fundamental
equations for both the air-side and refrigerant-side of the heat exchangers. The study uses
accurate refrigerant property data for R-22, but can easily be modified to accommodate
other refrigerants. The cooling output and electrical input for the compressor and fans
have been calculated for various ambient temperature conditions. The compressor,
condenser fan, and evaporator components of the cycle are also modeled but in a more
global manner using thermal science laws. Ambient temperature weighting factors used
by the U.S. Department of Energy are used to determine the seasonal coefficient of
performance (COP) of the system.
A base condenser model was arbitrarily chosen and design conditions were
established at 95 F. The operating parameters of condenser subcool and air face velocity
were examined over a wide range of ambient conditions to determine their effects on the
seasonal COP. It was determined that there is a range of subcools and face velocities
where the effects on the seasonal COP were negligible. The COP the system at an
7/30/2019 10.1.1.32.165
14/161
xiv
ambient temperature of 83 F was nearly identical to the seasonal COP and could be used
for quick comparisons.
The effects of changing the tube diameter, tube circuiting, number of rows, and
fin pitch have been investigated for both fixed cost and fixed frontal area. When the
parameters were varied from the base case individually, the changing the number of
circuits to 4 or changing the tube diameter to 1/2 gave the highest COPs. It was
determined that tube diameter and tube circuiting should not be considered separately
because they both affect the refrigerant side pressure drop. When the cost or area was
fixed, the best tube diameter- circuiting configuration was 5 circuits of 5/16 tubing. In
both cases, 4 circuits of 3/8 tubing provided similar performance with better packaging.
In general, the COP will be the highest when the frontal area is maximized and
rows should only be added if there is a frontal area constraint. This is because of the
relationship between the air velocity, depth, and air-side pressure drop. When the cost is
fixed, fewer rows provide better performance. If the frontal area is constrained, adding
rows will increase the performance as long as the refrigerant side pressure drop does not
become too great.
Changing the fin pitch had a relatively negligible effect on the seasonal COP.
The fan power increases as the number of fins increases, but the compressor power
decreases by about the same amount. If cost is fixed, fewer fins provide better
performance. When the area is restricted, more fins provide better performance.
7/30/2019 10.1.1.32.165
15/161
1
CHAPTER I
INTRODUCTION
Background
Refrigeration for personal comfort was first used in 1902. By 1997, 72% of all
American households had air-conditioning and 47% of all households were cooled with
central airi. According to the Air-Conditioning and Refrigeration Institute (ARI), 81% of
all new homes constructed were equipped with central air-conditioning in 1996. ii For a
single family, detached home, the amount of energy dedicated to air-conditioning can be
quite significant. In Atlanta, for example, air-conditioning accounts for approximately
19% of energy costs, which includes both gas and electricity, or 310 dollars per year. It
also accounts for 32% of the total peak power demand of electricity in these homes.iii
Obviously, improving the efficiency of residential air-conditioning units would decrease
utility bills and pollution produced by the power generation.
Considerations
Optimizing an air-conditioning system presents a complex problem for many
reasons. To start, there are many parameters that can be varied for each component. The
effect of varying most parameters is not independent on a component or system basis.
7/30/2019 10.1.1.32.165
16/161
2
Even if a component is optimized for specific operating conditions, like inlet and outlet
conditions, it is necessary to optimize each component at its unique operating conditions
with all other system components. To get a fair comparison among different designs,
operating conditions such as air velocity and refrigerant charge need be optimized for
each design. However, optimizing these parameters will affect the cooling capacity of
the evaporator, skewing the comparison.
Past Work
Until recently, limited computing power and the complex relations for refrigerant
properties had restricted the system design process to experimental testing. In 1975,
James Propst performed a similar study on condenser performance. iv Because of the lack
of computing power, Propst used a simplified model that neglected the refrigerant
properties so the analysis is based on the performance of the air side only. Propst
developed his equations to be solved explicitly and did not depend on any refrigerant side
properties including the condensing temperature. He used a constant refrigerant side
convective heat transfer coefficient, neglected pressure drops in the system, ignored the
superheated and subcooled sections and assumed constant compressor performance.
With increased computing power, it is now possible to create detailed computer
models with accurate refrigerant properties. While manufacturers such as HeatCraft have
created proprietary models for their components, they are not available for general study
and the programs are limited to simulating the performance of the products they sell. The
analytical techniques and assumptions used to develop these models are not known.
7/30/2019 10.1.1.32.165
17/161
3
Also, since most air-conditioner manufacturers outsource their components, the
components are not optimized in the context of the entire system. There have not been
very many recent developments in fundamental heat exchanger modeling. Recent studies
have focused on enhanced fin and wet coil modeling which are not pertinent to flat plate
condenser optimization. Most of the recent heat exchanger studies for air conditioning
applications have focused on the effects of enhanced fin and wet coils. These studies
have not integrated the heat exchanger models in a complete system. Several component
models were reviewed for this study and will be discussed in the chapters where the
component models are developed.
In the past ten years, there have been a few studies that have used modern
technology to evaluate cooling equipment on a system basis. Beans v developed a
computer simulation of a refrigeration cycle using R-12. The program requires the inlet
air properties, cooling load, heat exchanger working pressures and some compressor
characteristics to determine the heat exchanger UA and effectiveness, outlet air
properties, and COP, and the free compressor variables. Using the heat exchanger and
compressor characteristics, the program can also find the COP for off-design inlet air
conditions. Haselden and Chen created a simulation program for air-conditioning
systems focusing on the effects of different refrigerant mixtures. vi This program will
predict the system COP, compressor size, required heat exchanger areas, relevant
temperatures, pressures, and flows. Klein and Reindl have investigated the effects of heat
exchanger allocation between the evaporator and condenser on system performance.vii
The condenser and evaporator are modeled as counterflow heat exchangers, neglecting
7/30/2019 10.1.1.32.165
18/161
4
the superheated and subcooled sections. They also assume the air-side heat transfer
coefficients and fan powers are equal for the condenser and evaporator. Chen et. al have
studied the effect of cooling load on COP using finite-time heat transfer analysis for
steady flow Carnot and Brayton refrigeration cycles.viii They later expanded this study to
include nonisentropic compression and expansion. ix
Purpose
This purpose of this study was to develop an optimization methodology and
software for the detailed design of a finned-tube condenser heat exchanger coil in a
residential air-conditioning unit using the Engineering Equation Solver (EES) software.
The superheat, saturated, and subcool portions of the heat exchanger have been modeled
separately and in detail using appropriate pressure drop and fundamental heat transfer
equations for both the air-side and refrigerant-side of the heat exchangers. The study uses
accurate refrigerant property data for R-22, but can easily be modified to accommodate
other refrigerants. The compressor, condenser fan, and evaporator components of the
cycle are also separately modeled. The cooling output and electrical input for the
compressor and fans have been calculated for various ambient temperature conditions.
Ambient temperature weighting factors used by the U.S. Department of Energy
are used to determine the seasonal coefficient of performance (COP) of the system. The
seasonal COP is the figure-of-merit used to optimize the condenser face velocity, tube
7/30/2019 10.1.1.32.165
19/161
5
diameter, fin spacing, tube circuiting, number of rows and refrigerant charge. Because
there are tradeoffs between capital and operating costs that must be considered if the
system is to succeed on the consumer market, non-dimensional cost and area factors have
been used as constraints. Based on simulation results and considering monetary or
frontal area constraints, optimal condenser configuration recommendations have been
made.
7/30/2019 10.1.1.32.165
20/161
6
CHAPTER II
RESIDENTIAL AIR CONDITIONING SYSTEMS
Before a detailed analysis of the operating conditions and geometry of the
condenser can be attempted, it is necessary to understand how the air conditioning system
works. In this chapter, the overall refrigeration cycle, system components and coefficient
of performance will be discussed.
Refrigeration Cycle
Low pressure, superheated refrigerant vapor from the evaporator enters the
compressor (State 1) and leaves as high pressure, superheated vapor (State 2). This vapor
enters the condenser where heat is rejected to outdoor air that is forced over the
condenser coils. The refrigerant vapor is cooled to the saturation temperature (State 2a),
condensed to a liquid (State 2b), and cooled below the saturation point (State 3). The
high pressure liquid is forced through an expansion valve into the evaporator (State 4).
The pressure in the evaporator is much lower than the pressure in the condenser, so the
refrigerant enters the evaporator as a liquid-vapor mix at low temperature and pressure.
The refrigerant absorbs heat from warm indoor air that is blown over the evaporator coils.
The refrigerant is completely evaporated (State 4a) and heated above the saturation
7/30/2019 10.1.1.32.165
21/161
7
temperature before entering the compressor. The indoor air is cooled and dehumidified
as it flows over the evaporator and returned to the living space. The refrigeration cycle is
shown in Figure 1 and the equipment setup is shown in
Figure 2.
s
T
4
3
2
1
4a
2b 2a
Figure 1. Thermodynamic State of Refrigerant in Refrigeration Cycle
7/30/2019 10.1.1.32.165
22/161
8
3Subcooled Saturated
Saturated
Superheated
Superheated
1
22a
4 4a
CompressorExpansion
Valve
2b
Condenser
Evaporator
Figure 2. Refrigeration Cycle Equipment
Air Conditioner Components
Compressor
The purpose of the compressor is to increase the working pressure of the refrigerant.
Compressors fall into two general categories: positive displacement, which increase the
pressure of the vapor by reducing the volume, and dynamic, which convert angular
momentum into a pressure rise and transfer it to the vaporx. Scroll type, positive
displacement compressors which dominate the residential compressor market were
considered for this study. The amount of specific work done by an ideal compressor can
be found by the energy equation:
( )12, hhw scoms =
7/30/2019 10.1.1.32.165
23/161
9
where: h = refrigerant enthalpy
For a non-ideal compressor, the actual amount of work required depends on the
efficiency.
( )12,
, hhw
wc
coms
coma==
where: c = compressor thermal efficiency
For a scroll type compressor, Klein has determined the thermal efficiency is related to the
reduced pressure and reduced temperature with the following equation. xi
rrrrrrc
TPTTPP 061.331.503.1110281.0814.325.60 22
++=
where: Pr = Pressure ratioevap
cond
rP
PP =
Tr = Temperature ratioevapsat
condsat
rT
TT
,
,=
In his paper, Klein only considers the saturated sections of the heat exchangers.
Therefore, the coefficients in the compressor efficiency correlation are based on the
saturated temperatures rather than the actual inlet and outlet temperatures to the
7/30/2019 10.1.1.32.165
24/161
10
compressor. Since pressure drops are included in the condenser model, the compressor
efficiency is based on the inlet saturation temperature and pressure in the condenser and
the outlet saturation temperature and pressure from the evaporator.
It is important to consider the volumetric efficiency in addition to the thermal
efficiency. The volumetric efficiency is the ratio of the mass of vapor that is compressed
to the mass of vapor that could be ideally compressed if the intake volume were equal to
the piston displacement and filled with evaporator exit state vapor. The volumetric
efficiency can be found by xii
= 1
v
v1
out
in
v R
Where:v = compressor volumetric efficiencyR = ratio piston/ cylinder of clearance volume to swept displacementv = specific volume
The volumetric efficiency is used to determine the mass flow rate of the refrigerant
through the compressor for a given compressor size.xiii
out
vmv
PD=&
where: PD = piston displacement
7/30/2019 10.1.1.32.165
25/161
11
Condenser
The condenser is a heat exchanger that rejects heat from the refrigerant to the
outside air. Heat exchangers come in many configurations, but finned-tube heat
exchangers are most common for residential air conditioning applications. Refrigerant
flows through the tubes and a fan forces air between the fins and over the tubes. The heat
exchangers used in this study will be the plate finned-tube type as shown in Figure 3.
Figure 3. Typical Plate Finned-Tube Heat Exchanger
When the refrigerant leaves the compressor, it enters the condenser as a
superheated vapor and leaves as a sub-cooled liquid. The condenser can be separated
into three sections: superheated, saturated, and sub-cooled. The specific heat rejected
from each section can be found by evaluating the refrigerant enthalpies at the inlets and
outlets.
7/30/2019 10.1.1.32.165
26/161
12
32,
22,
22,
hhq
hhq
hhq
bsccon
basatcon
ashcon
=
=
=
The heat transfer details on the air and refrigerant sides of the heat exchangers
will be discussed in Chapter 3.
Condenser Fan
Because natural convection will not produce sufficient airflow and heat transfer
over a reasonably sized condenser, a fan must be employed to keep the air moving.
Although the compressor uses the majority of the power consumed by the system, the fan
power must also be considered. The power required by the fan is directly related to the
air pressure drop across the condenser and the volume flow rate of the air.
conf
confrconacona
conf
APVW
,
,,,
,
=&
where: Va = air face velocity
Pa = air-side pressure drop
Afr= frontal areaf= fan efficiency
The isentropic efficiency of the combined fan and motor is taken to be 65%. The air-side
pressure drop will be discussed in Chapter 3.
7/30/2019 10.1.1.32.165
27/161
13
Expansion Valve
The expansion valve is used to control the refrigerant flow through the system.
Under normal operating conditions, the thermo-static expansion valve opens and closes to
maintain a fixed superheat exiting the evaporator. In this study, that superheat will be
held at 10 F. Because the expansion valve is designed to pass a certain volume of
refrigerant, it cannot function properly if the refrigerant is not completely condensed.
The vapor refrigerant backs up behind the valve and the condenser pressure increases
until the refrigerant vapor is condensed. When this happens, the expansion valve cannot
regulate the refrigerant superheat exiting the evaporator. Under this condition, it converts
from maintaining superheat to maintaining a saturated liquid leaving the condenser. The
energy equation shows that the enthalpy is constant across the expansion valve.
43 hh =
Evaporator
The purpose of the evaporator is to transfer heat from the room air making the air
cooler and less humid. Because the refrigerant enters the evaporator in as a liquid-vapor
mix, it is only divided into saturated and superheated sections. The analysis for the
evaporator is nearly identical to that of the condenser, but some considerations must be
made for the dehumidification process. To keep the evaporator model simple, the coil is
assumed to be dry, so the air-side heat transfer coefficient is not affected, but the specific
heat is corrected to account for condensation. Because the air flowing over the
7/30/2019 10.1.1.32.165
28/161
14
evaporator is cooled below the wet bulb temperature, some of the heat rejected by the air
results in condensing water out of the air rather than lowering the temperature. The total
enthalpy change of the air is the sum of the enthalpy change due to temperature drop, or
sensible heat, and the enthalpy change due to condensation, or latent heat.
latsenstot hhh +=
As shown in Figure 4, using the specific heat for dry air will result in exit temperatures
that are too low. By using an effective specific heat, a more accurate exit temperature
can be obtained without the complications associated with using an air-water mixture.
Temperature
Enthalpy
Effective
Dry Air
Moist Air
hlat
hsens
Figure 4. Effective Specific Heat
7/30/2019 10.1.1.32.165
29/161
15
Dividing the previous equation for enthalpy by the temperature change gives
T
h
T
h
T
h latsenstot
+
=
By definition, the specific heat is the ratio of the sensible enthalpy change to the
temperature change. Substituting and rearranging results in the following:
T
hcc latpeffp
+=,
where: cp = specific heat for dry air
cp,eff = effective specific heat
The latent enthalpy accounts for about 25% of the total enthalpy change for air flowing
over an evaporator in residential applications. The effective specific heat can be
expressed in terms of the specific heat for dry air only.
p
tot
senstot
peffp ch
h
T
hcc 33.1
75.0
25.0, =
+=
Evaporator Fan
Because the evaporator is not the focus of this study, introducing wet coils would
introduce unwelcome complications. In addition to affecting the heat transfer, wet coils
7/30/2019 10.1.1.32.165
30/161
16
also affect the air-side pressure drop. Although there are correlations available to find the
pressure drop over wet coils, this is not the only issue. After the air flows over the
evaporator, it enters a series of ducts that return it to the inside living space. Because the
power required depends on the losses in the ducts which will change from case to case,
the default used by the Air-conditioning and Refrigeration Institute test standard of 365
W per 1000 cfm of airxiv will be used.
Coefficient of Performance
The coefficient of performance (COP) measures the efficiency of the entire
system. It is the ratio of the heat absorbed by the evaporator to the amount of electrical
energy used by the mechanical components, i.e. the compressor and two fans.
evapfconfcom
e
WWW
QCOP
,,&&&
&
++=
Seasonal COP
The American Refrigeration Institute has determined that the frequency
distribution of temperatures over the summer cooling season is roughly the same across
the country. However, in warmer, southern climates, there are more cooling load
hours, which are defined as the hours when the temperature is above 65 F, per year than
7/30/2019 10.1.1.32.165
31/161
17
in cooler climates. In Atlanta, for example, the number of cooling load hours is
approximately 1300 hours per year, while it is only about 700 hours per year in
Cleveland, OH. Of these hours, the outside temperature will be between 80 F and 84 F
approximately 16.1% of the cooling season in either city. Table 1 shows the distribution
of the cooling load hours.
BinNumbe
r
Temperature
Range (F)
Representative
Temperature
(F)
Fraction of TotalTemperature
Hours
1 65-69 67 0.214
2 70-74 72 0.231
3 75-79 77 0.216
4 80-84 82 0.161
5 85-89 87 0.104
6 90-94 92 0.052
7 95-99 97 0.018
8 100-104 102 0.004
Table 1. Distribution of Cooling Load Hoursxv
The COP changes with the outside air temperature and the overall COP, or
seasonal COP, for an air conditioner depends on the temperatures at which the appliance
runs over an entire year. According to the ANSI/ASHRAE standard,xvi the seasonal COP
for a single speed, single compressor unit is found by:
7/30/2019 10.1.1.32.165
32/161
18
( )
( )
=
8
j
j
8
j
je
seas
TE
TQ
COP
&
&
where: Qe(Tj) = adjusted evaporator capacity at ambient temperature Tj
E(Tj) = adjusted electrical power demand at ambient temperature Tj
( )j = values corresponding to temperature bin j (from Table 1)
The adjusted evaporator capacity and adjusted electrical power demand are based on the
cooling load factor and the fraction of total temperature hours.
( ) ( )jjssje nTQCLFTQ = &
( )( )
PLF
nTECLFTE
jjss
j
=
&&
where: CLF = cooling load factor
Qss(Tj) = steady state evaporator capacity at Tj
nj = fraction of total temperature hours (from Table 1)
Ess(Tj) = steady state electrical power demand at Tj
PLF = part load factor
The part load factor takes into account system cycling. For this study, the system
7/30/2019 10.1.1.32.165
33/161
19
cycling is neglected so the part load factor is equal to 1. The cooling load factor is
defined:
( )( )
( ) ssj
ssj
jss
j
QTBL1CLF
QTBLTQ
TBLCLF
&
&
&
>=
=
where: BL = building load
The building load given by:
( )( )
SF
TQ
65T
35jTBL ODss
OD
j
&
=
where: TOD = outdoor design temperature in Fahrenheit (in this case 95 F)SF = size factor
The size factor determines the amount of over or undersizing of the system and is 1 for
this study because the system designed to meet the requirements at 95 F.
7/30/2019 10.1.1.32.165
34/161
20
CHAPTER III
HEAT EXCHANGERS
Because this study focuses on optimizing the condenser geometry and operating
conditions, the characteristics of heat exchangers must be explored more thoroughly than
other components. In this chapter, the heat transfer and pressure drop models specifically
related to plate finned heat exchangers will be discussed. Plate finned heat exchangers
are made up of in-line or staggered tube bundles that are held in place by continuous,
rectangular fins. For this study, staggered, copper tubes are coupled with aluminum fins.
Geometry
It is important to understand the terminology used to describe the geometric
parameters of the heat exchangers used in this study. The term tubes per circuit is the
number of parallel passages the refrigerant mass flow rate is divided among. If the mass
flow rate is 100 lbm/hr and there is one tube per circuit, 100 lbm/ hr of refrigerant will
pass through that tube. If there are 2 tubes per circuit, then 50 lbm/hr of refrigerant will
flow through each tube. The number of parallel circuits is used to determine the number
of tubes in each row. The number of rows refers to the number of tube rows in the
direction normal to air flow. If the number of parallel circuits is set to 12, and the
number of tubes per circuit is 2, then there will be a total of 24 tubes in each row. The fin
7/30/2019 10.1.1.32.165
35/161
21
pitch is the number of fins per unit length along the axial direction of the tubes. These
parameters and the overall dimensions of the heat exchanger are illustrated in Figure 5
and Figure 6. The model used to determine the air-side heat transfer coefficient depends
on the layout of the tubes, but not on the temperature of the refrigerant which would be
affected by circuiting. The only factors pertinent to the refrigerant side models affected
by the circuiting are the mass flow rate in each tube and the length associated with each
circuit. The layout in Figure 6 meets the requirements of the models and is easy to
conceptualize.
7/30/2019 10.1.1.32.165
36/161
22
Figure 5. General Heat Exchanger Dimensions
7/30/2019 10.1.1.32.165
37/161
23
Figure 6. Layout of Heat Exchanger Geometry Parameters
NTU-Effectiveness Relations
For any heat exchanger, the total heat rejected from the hot fluid, in this case,
refrigerant, to the cold fluid, air, is dependent on the heat exchanger effectiveness and the
heat capacity of each fluid.
( )icih TTCQ ,,min =
7/30/2019 10.1.1.32.165
38/161
24
where: = effectivenessCmin = smaller of heat capacities Ch and CcTh,i = inlet temperature of hot fluid
Tc,i = inlet temperature of cold fluid
The heat capacity, C, the extensive equivalent of the specific heat, determines the
amount of heat a substance absorbs or rejects per unit temperature change.
pcmC=
where: m = masscp = specific heat
The amount of air flowing over each section of the condenser is assumed to be
proportional to the tube length associated with that section. For example:
to t
sat
tota
sata
L
L
m
m=
,
,
The effectiveness is the ratio of the actual amount of heat transferred to the
maximum possible amount of heat transferred.
maxQ
Q
&
&
=
7/30/2019 10.1.1.32.165
39/161
25
The equations used to determine the effectiveness depend on the temperature
distribution within each fluid and on the paths of the fluids as heat transfer takes place, ie.
parallel-flow, counter-flow or cross-flow. In typical condensers and evaporators, the
refrigerant mass flow is separated into a number of tubes and does not mix. As the air
flows through the fins, the plates prevent mixing and air at one end of the heat exchanger
will not necessarily be the same temperature as air at the other end. For a cross-flow heat
exchanger with both fluids unmixed, the effectiveness can be related to the number of
transfer units (NTU) with the following equation:
( ) ( )[ ]{ }
= 1exp1exp1 78.022.0 NTUCNTU
Cr
r
where: Cr = heat capacity ratio
max
min
C
CCr =
In the saturated portion of the condenser, the heat capacity on the refrigerant side
approaches infinity and the heat capacity ratio goes to zero. When Cr=0, the
effectiveness for any heat exchanger configuration is:
7/30/2019 10.1.1.32.165
40/161
26
( )NTU= exp1
The NTU is a function of the overall heat transfer coefficient.
minC
UANTU=
The overall heat transfer coefficient, U, takes into consideration total thermal
resistance to heat transfer between two fluids. Even though the convective heat transfer
coefficients may be different on the air and refrigerant sides of the heat exchanger, the
UA product is the same on either side. This is because all of the heat taken from the
refrigerant must be transferred to the air.
aarr AUAUUA
111==
where: A = total heat transfer area( )r= refrigerant side( )a = airside
Taking all of the thermal resistances into account produces the following
expression for the UA product:
7/30/2019 10.1.1.32.165
41/161
27
rrrsrrs
rf
w
aas
af
aaas AhA
RR
A
R
AhUA ,,
,
,
,
,
111
+
++
+=
where: R= fouling factor
Rw= wall resistances = surface efficiencyh = heat transfer coefficient
Since there are no fins on the refrigerant side of the tubes, the refrigerant side surface
efficiency is 1. Neglecting the wall resistance, Rw, and the fouling factors, R, the overall
heat transfer coefficient reduces to
1
,
11
+=
rraaas AhAhUA
The methods for finding the heat transfer coefficients will be discussed later in
this chapter. To find the overall surface efficiency for a finned tube heat exchanger, it is
first necessary to determine the efficiency of the fins alone. The total air side surface
efficiency is given by:
( )f
o
f
sA
A = 11
where: s = surface efficiencyAf = total fin surface areaAo = total air side surface area, tube and fins
f= fin efficiency
7/30/2019 10.1.1.32.165
42/161
28
The fin efficiency, f, for a circular fin is a function of m, re and .
( )
( )
e
e
fmr
mrtanh=
For a plate fin heat exchanger with multiple rows of staggered tubes, the plates
can be evenly divided into hexagonal shaped fins as shown in Figure 7.
Figure 7. Layout of Hexagonal Fins
7/30/2019 10.1.1.32.165
43/161
29
Schmidtxvii analyzed hexagonal fins and determined that they could be treated like
circular fins by replacing the outer radius of the fin with an equivalent radius. The
empirical relation for the equivalent radius is given by
( ) 213.027.1 = r
re
where: re=equivalent radius of fins
r = outside tube radius
The coefficients and are defined as:
r
Xt
2=
212
2
4
1
+= tL
t
XX
X
where: Xl = tube spacing in direction parallel to air flowXt = tube spacing normal to air flow
Once the equivalent radius has been determined, the equations for standard
circular fins can be used. For the fins in this study, the length is much greater than the
thickness, so a parameterm can be expressed as:
7/30/2019 10.1.1.32.165
44/161
30
21
2
=
kt
hm a
where: ha = air side heat transfer coefficient
k = conductivity of fin materialt = thickness of fins
For circular tubes, a parameter is defined as
+
=
r
r
r
r ee ln35.011
Refrigerant Side Models
Single Phase Heat Transfer Coefficient
To find the single phase heat transfer coefficient, the standard heat transfer
equations and the experimental work of Kays and London were considered. For constant
surface heat flux in the laminar regime, the Nusselt number is a constant.
Nu=4.36
In the turbulent region, the Dittus-Boelter equation holds for fully developed flow in
circular tubes with moderate temperature differences. For refrigerant cooling in the
condenser, the Dittus-Boelter equation is:
7/30/2019 10.1.1.32.165
45/161
31
NuD D
= 0023 0 8 0 3. Re Pr . .
where: ReD = Reynolds number based on diameterPr = Prandtl number
This equation has been confirmed by experimental data for the range:
0.7 Pr160
ReD 10,000
L/D 10
where: L = tube length in single phase region
In the subcooled portion of the condenser, the temperature difference at the inlet
and exit is usually less than 20F, but in the superheated portion, the inlet and exit
temperature can vary by as much as 90F. The temperature differential between the air
flowing over the tubes and, as a result, the inner surface of the tubes and the refrigerant is
also much greater. Under these conditions, the Dittus-Boelter equation does not produce
an accurate value for the heat transfer coefficient. Sieder and Tatexviii have developed a
correlation equation for large property variations based on the mean fluid temperature
and the wall surface temperature.
7/30/2019 10.1.1.32.165
46/161
32
NuD Dm
s
=
0027 0 8 1 3
0 14
. Re Pr ..
where: = viscosity( )m = evaluated at mean fluid temperature
( )s = evaluated at surface
The viscosity s is evaluated at the surface and all other properties are evaluated at the
mean fluid temperature.
Kays and London use empirical data taken from a variety of refrigerants in
circular tubes under different conditions. Unlike the other correlations, Kays and London
have established equations in the transition region. The heat transfer coefficient was
related to the Stanton number, St. The Stanton number is defined by the following:
p
cG
hSt=
St a bPr Re2 3 =
where: cp= specific heat
The coefficients a and b are based on the flow regime.
7/30/2019 10.1.1.32.165
47/161
33
Laminar Re < 3,500 a=1.10647
b=-0.78992
Transition 3,500 < Re < 6,000 a=3.5194 x 10-7b=1.03804
Turbulent 6,000 < Re a=0.2243
b=-0.385
In the laminar and early transition regions, the Kays and London heat transfer
coefficient is lower than the others, but is it is higher in the turbulent region. The Dittus-
Boelter and Sieder and Tate equations assume that the pipe is smooth which would
explain this result. Because the Kays and London relation is based on data taken from
heat exchangers similar to those studied here and because transitional flow has been
addressed, this relation will be used in the simulation.
Condensation Heat Transfer Coefficient
Condensation heat transfer correlations by Shah and Traviss, Rohsenow and
Baronxix were considered for this study. Patexx showed that the results of Shah and the
results of Traviss et al. were not significantly different, however, Traviss model only
applies to annular flow regime while Shahs relation is good in all flow regimes.
Traviss model also requires an iterative scheme while Shahs method is very easy to use.
It is a simple dimensionless correlation which has been verified over a large variety of
experimental data. This model has a mean deviation of about 15% and has been verified
7/30/2019 10.1.1.32.165
48/161
34
for many different condensing fluids, tube sizes and tube orientations. For any given
quality, the two-phase heat transfer coefficient is
( )( )
+=
38.0
04.076.08.0 18.3
1r
LTPp
xxxhh
where: hTP= two phase heat transfer coefficient
x= quality
hL= liquid only heat transfer coefficientpr= reduced pressure
By integrating the two-phase heat transfer coefficient over the length, the mean
two-phase heat transfer coefficient can be determined.
( )( )
( )
+
= 2
138.0
04.076.08.0
12
18.31
L
Lr
LTPM dL
p
xxx
LL
hh
If the quality varies linearly with length which is consistent with constant heat
transfer per unit length, hTPM can be approximated by:
( )
( )2
1
76.2
04.0
76.1
8.3
8.1
1 76.276.1
38.0
8.1
12
x
xr
L
TPM
xx
p
x
xx
hh
+
=
7/30/2019 10.1.1.32.165
49/161
35
For complete condensation, that is x varies from 1 to 0, the mean two-phase heat
transfer coefficient reduces to:
+=
38.0
09.255.0
r
LTPMp
hh
Evaporative Heat Transfer Coefficient
The expression for the average evaporative two-phase heat transfer coefficient is
taken from Tongxxi. This relationship assumes a constant temperature differential
between the wall and the fluid along the length of the pipe.
( )325.0325.0
075.0375.04.08.0
2.00186875.0
ie
ie
l
v
v
l
l
ll
l
levap
xx
xx
k
CpG
D
kh
=
where: D = tube diameter
G = mass flux
k = conductivity
( )l = properties evaluated at saturated liquid stage
( )v = properties evaluated at saturated vapor stage
( )e = properties evaluated at exit
( )i = properties evaluated at inlet
7/30/2019 10.1.1.32.165
50/161
36
Pressure Drop in Straight Pipe
The pressure drop in the superheated and subcooled portions of the condenser can be
found easily by applying the standard pipe pressure drop equation.
pf G L
=2
where: f = friction factor
= density
The friction factor, f, for circular pipe depends on the Reynolds number where the
turbulent expression is taken for the transition region.
000,2ReRe
51.2
7.3log2
1
000,2ReRe
64
211021>
+=
7/30/2019 10.1.1.32.165
51/161
37
dP
dz
dP
dz
dP
dz
dP
dzf g m
=
+
+
The frictional component is found using the following equation:
( ) [ ]dP
dz
G
g D G Df
v
v
c
v
v
tt =
+
2
0.2
0.523
2
0 09 1 2 85
. .
The momentum component is:
( ) ( ) ( )dP
dz
G
g
dx
dz x x x xm c v
v
l
v
l
v
l
=
+
+
2 1 3 2 3
2 1 2 1 2 2 1
Unfortunately, it is very difficult to predict the variation of quality with length, dx/dz so a
linear profile is assumed for simplicity, which is consistent with constant heat transfer per
unit length. The gravitational pressure drop for horizontal tubes is zero. Hillerxxii
integrates the pressure differential over the change in quality for the frictional and
momentum losses. The frictional pressure drop in the two-phase region is reduced to
7/30/2019 10.1.1.32.165
52/161
38
( ) ( )[ ] ei
x
xf xxCxxxCxCP
86.12
3
33.22
3
8.2
2 329.0538.00288.0141.0429.02357.0 ++=
where:
Cl
v
v
l
3
0 0523 0 262
285=
.
. .
CG
C g D
v
c v
2
1 8
1
1 2
009=
. .
.
L
xxC ie
=1
The momentum pressure drop in the two-phase region integrates to:
e
i
x
xl
v
l
v
l
v
l
v
l
v
l
v
cv
m xxg
GP
+=
3231
2
32312
21
The total pressure drop is just the sum of the momentum and frictional pressure drops.
fmtot PPP +=
7/30/2019 10.1.1.32.165
53/161
39
Pressure Drop in Bends
The pressure drop in bends is found by assigning an equivalent length to each bend
based on the flow diameter and the bend radius. For two-phase flow, the method for
finding the pressure drop in bends based on Chisolmxxiii is used. The pressure drop is
calculated for liquid-only flow and correction factors are applied to determine the
approximate two-phase pressure drop. The method predicts the pressure drops for two-
phase flow in horizontal bends rather than the inclined bends found in a typical
condenser. However, the two-phase flow pattern in an inclined bend cannot be
accurately predicted and pressure gradients due to elevation changes are negligible
compared to friction pressure losses, so the horizontal bend model should be sufficient.
Since the bends are not finned and do not have air flowing over them, the heat transfer
and phase change in the bends is neglected.
The first step in computing the pressure drop is to determine the equivalent length of
the bend. The equivalent length is a function of the relative radius, rr.
rr
Drb
i
=
where: rb = radius of bendDi = inner diameter of pipe
7/30/2019 10.1.1.32.165
54/161
40
Chisolm uses the correlation by Beij to determine the equivalent length, z/D. Typical
condensers will have a relative radius between 1 and 3 which corresponds to an
equivalent length between 12 and 15 for 90 bends. The equivalent length for a 180
return bend is about twice that of a 90 bend. For this analysis, the equivalent length of
the return bend will be taken as 26. The single-phase pressure drop on a bend can be
evaluated by substituting the equivalent length for the straight pipe length in the standard
pressure drop equation.
e
bD
zGp
=
2
2
where: pb = pressure drop in bend = friction factor
The friction factor can be determined with Haalands approximationxxiv:
211.1
7.3Re
9.6log8.1
+=
D
where: = pipe roughness
For drawn copper pipes, the pipe roughness is taken to be 0.000005 ft. For two-phase
flow, the pressure drop in a bend is the product of the bend pressure drop for liquid only
and the two-phase multiplier.
7/30/2019 10.1.1.32.165
55/161
41
2
,,, loblobTPb
pp =
where: pb,lo = liquid oly bend pressure drop2 = two-phase multiplier
The two-phase multiplier2 in a bend is:
( ) ( ) ( ) ( ) ( )[ ] b lo bn n nB x x x,
2 2 2 2 2 2 21 1 1= + +
where: b2 = physical property coefficientB = bend coefficient
n = Blasius coefficient
The physical property coefficient 2 for a bend is
b
l
v
v
l
n
2 =
The Blasius coefficient n used to determine 2 and 2 is defined as
n
Lo
vo
l
v
=
ln
ln
7/30/2019 10.1.1.32.165
56/161
42
The friction factors, lo and vo, are found using Haalands approximation. In these
cases, one assumes all of the mass is flowing as either a liquid or a vapor so the mass flux
G used to find the Reynolds number will be the same, but the viscosity will depend on the
refrigerant state.
n
Lo
vo
l
v
=
ln
ln
The B coefficient for bends other than 90 is
[ ]B Bk
k
b
b
= +
1 19090,
The coefficient B90 is defined as
( )B
k R Db90
90
12 2
2
= ++.
,
7/30/2019 10.1.1.32.165
57/161
43
The recovery downstream of bends greater than 90 is assumed to be the same as 90
bends. The pressure coefficient for a 90 bend, kb,90, is used for convenience where
kz
Dbe
,90 =
Assuming homogeneous two-phase flow, the friction factor for two-phase flow is found
using the same Haalands approximation, but the Reynolds number is based on the two-
phase viscosity.
Re =GD
TP
The two-phase viscosity is a function of quality.
( ) TP v l x x= + 1
In the case of 180 bends, the kb,180 is approximately twice kb,90 so B180 reduces to
[ ]B B180 900 51 = +.
7/30/2019 10.1.1.32.165
58/161
44
Air Side Models
Heat Transfer Coefficient
The work of Rich and McQuiston were used to evaluate the air-side convective heat
transfer coefficient for a plate fin heat exchanger with multiple rows of staggered tubes.
The condenser coils are assumed to be dry. The heat transfer coefficient is based on the
Colburn j-factor which is defined as:
j St= Pr2 3
Substituting the appropriate values for the Stanton number gives this relationship for the
convective heat transfer coefficient, h.
hj c G
a
p=
max
Pr2 3
where: Gmax = mass flux through minimum flow area
Gm
Aair
max
min
&=
For cases in this study, the minimum flow area is
( ) ( )( )( )DcirctpcHtFPWA #1min =
7/30/2019 10.1.1.32.165
59/161
45
where: W = width of heat exchanger
FP = fin pitch
H = height of heat exchanger
tpc = tubes per circuit
#circ = number of parallel circuits
McQuiston found the j-factor for a 4 row finned-tube heat exchanger to fit a linear model
based on the parameter JP.
j JP460 2675 1325 10= + . .
and
JP AAD
o
t
=
Re ..
0 4
0 15
The Reynolds number is based on the outside diameter of the tubes, Do, and the
maximum mass flux Gmax. The heat transfer coefficient for heat exchangers with four or
less rows can be found using the following correlation:
( )( )
j
j
nn L
L4
1 2
1 2
1 1280
1 1280 4=
Re
Re
.
.
7/30/2019 10.1.1.32.165
60/161
46
ReL is based on the row spacing.
Remax
L
LG X=
Pressure Drop
The work of Richxxv concludes that the air side pressure drop can be separated into
two components: the pressure drop due to the tubes and the pressure drop due to the fins.
fttot ppp +=
where: pt = pressure drop due to tubespf = pressure drop due to fins
The pressure drop due to the fins can be expressed:
c
f
mffA
AGvfp
2
2
max=
where: ff = fin friction factor
vm = mean specific volumeGmax = mass velocity through minimum area
Af = fin surface areaAc = minimum free-flow cross sectional area
7/30/2019 10.1.1.32.165
61/161
47
In experimental tests, Rich found that the friction factor depends on the Reynolds
number, but is independent of fin spacing. For fin spacing between 3 and 14 fins per
inch, the fin friction factor is
5.0Re70.1
= lff
where the Reynolds number is based on the transverse (in the direction of air flow) tube
spacing.
ll
GX=Re
To find the pressure drop over the tubes, the relationships developed by Zukauskas and
Ulinskasxxvi are used. The pressure drop over the banks of plain tubes is:
zG
Eup ct2
2
=
where: Euc = corrected Euler number
z = number of rows
The corrected Euler number is:
7/30/2019 10.1.1.32.165
62/161
48
EuCkEu zc 1=
where: Eu = Euler numberk1 = staggered array geometry factorCz = average row correction factor
The Euler number is related to the tube friction factor and depends on the
Reynolds number and the tube geometry. For staggered, equilateral triangle banks with
many rows, the Euler number is related to the Reynolds number by a fourth order inverse
power series.
432 ReReReRe
utsrqEu ++++=
The coefficients, q, r,s, t, and u are dependent on the parametera, the ratio of the
transverse tube spacing to tube diameter, and the Reynolds number. The coefficients for
distinct values ofa determined by Zukauskas and Ulinskas from experimental data are
summarized in Table 2.
7/30/2019 10.1.1.32.165
63/161
49
a Reynolds number q r s t u
1.25 3< Re < 103 0.795 0.247 x103
0.335 x103
-0.155 x104
0.241 x 104
103< Re < 2 x 106 0.245 0.339 x104
-0.984 x107
0.132 x1011
-0.599 x1013
1.5 3< Re < 103 0.683 0.111 x 103 -0.973 x102
0.426 x 103 -0.574 x 103
103< Re < 106 0.203 0.248 x
104
-0.758 x
107
0.104 x 1011 -0.482 x
1013
2.0 7< Re < 102 0.713 0.448 x
102
-0.126 x
103
-0.582 x
103
0
102< Re < 104 0.343 0.303 x103
-0.717 x105
0.88 x 107 -0.38 x 109
104< Re < 2 x 106 0.162 0.181 x104
0.792 x108
-0.165 x1013
0.872 x1016
2.5 102< Re < 5 x 103 0.33 0.989 x102
-0.148 x105
0.192 x 107 0.862 x 108
5 x 103< Re < 2 x
106
0.119 0.849 x
104
-0.507 x
108
0.251 x
1012
-0.463 x
1015
Table 2. Euler number coefficients for inverse power series
For non-equilateral triangle tube bank arrays, the staggered array geometry factork1,
must be used as a correction. The staggered array geometry factor is dependent on the
Reynolds number, a and b, the ratio of tube spacing in the direction normal to the air flow
and the tube diameter. The equations fork1 are found in Table 3.
7/30/2019 10.1.1.32.165
64/161
7/30/2019 10.1.1.32.165
65/161
51
The equations for the individual row correction factors are given in Table 4.
Re z* cz
10
7/30/2019 10.1.1.32.165
66/161
52
CHAPTER IV
OPTIMIZATION OF OPERATING PARAMETERS
When comparing the performance of air conditioning systems, it is not valid to assert
that one condenser geometry is better than another if the operating conditions are not
optimized for each configuration. The operating parameters considered for this study are
refrigerant charge and air face velocity over the condenser. Because the performance of
an air-conditioner varies with ambient temperature, design conditions were established at
95 F to provide a fair basis for comparison. These conditions are summarized in Table
5.
Ambient Temperature 95 F
Evaporator Capacity 30,000 Btu/hr
Evaporator Saturation Temperature 45 F
Superheat in Evaporator 10 F
Table 5. Air-Conditioner Design Conditions
To see the effects the operating parameters have on the seasonal COP, a base case
condenser and evaporator coil pair typical for this application was selected. All of the
characteristics of the condenser and all but the width of the evaporator were specified.
These dimensions are given in Table 6.
7/30/2019 10.1.1.32.165
67/161
53
Dimension Condenser Evaporator
Tube spacing (in x in) 1.25 x 1.083 1.00 x 0.625
Tube inner diameter (in) 0.349 0.349
Tube outer diameter (in) 0.375 0.375
Frontal area (ft2) 7.5 n/a
Finned width (ft) 3 n/a
Finned height (ft) 2.5 1.5
Depth (in) 3.25 2.5
Fin pitch (fin/ in) 12 12
# rows 3 4
# circuits 12 9
Tubes per circuit 2 2
Table 6. Base Case Condenser and Evaporator Characteristics
The evaporator frontal area depends on the design conditions and is virtually
independent of operating conditions. In Figure 8, the evaporator frontal area remains
constant for different air velocities and refrigerant charges. The refrigerant charges are
specified by the number of degrees subcool, Tsc, in the condenser at the design
conditions.
7/30/2019 10.1.1.32.165
68/161
54
0
0.5
1
1.5
2
2.5
3
3.5
4
0 2 4 6 8 10 12 14 16 18
Air Velocity (ft/s)
EvaporatorFrontalArea(ft
Tsc=5
Tsc=10
Tsc=15
Tsc=20
Figure 8. Effects of Operating Conditions on Evaporator Frontal Area
Subcool and Seasonal Effects
The refrigerant charge is the mass of refrigerant in the system necessary to provide a
specified amount of subcool in the condenser at the design conditions. The relationship
between the specified subcool and refrigerant system mass is demonstrated in Table 7 for
air velocity of 8 ft/s.
Degrees
Subcool
@ 95 F(F)
Mass of
Refrigerantin System
(lbm)
5 3.50
10 4.38
15 5.49
20 6.45
Table 7. Mass of Refrigerant in Air-Conditioner for Different Subcool Specifications
7/30/2019 10.1.1.32.165
69/161
55
The effects of a fixed refrigerant charge must be considered with varying ambient
temperature. As the outdoor air temperature drops, the condensing temperature also
drops and the enthalpy of the refrigerant entering the evaporator is lower. This means
that the inlet quality is lower and more of the refrigerant in the evaporator is in the liquid
state. Since the total mass of refrigerant in the system is held constant, the mass of the
refrigerant in the evaporator increases and the mass of refrigerant in the condenser
decreases as the ambient outdoor temperature decreases. When the mass of the
refrigerant in the condenser drops, the volume fraction of the condenser that is filled with
vapor must increase. If the mass of refrigerant in the condenser drops to the point where
the refrigerant is not completely condensed when it enters the valve, the valve goes wide
open and cannot maintain a fixed superheat in the condenser. Since a negligible amount
of vapor can pass through the expansion valve orifice, a saturated state is forced at the
valve entrance and the subcool in the condenser will be fixed at zero. The superheat in
the evaporator then varies from the specified 10 F. This condition occurs at higher and
higher ambient temperatures as the amount of subcool specified at 95 F decreases as
shown in Figure 9.
7/30/2019 10.1.1.32.165
70/161
56
.
0
5
10
15
20
25
40 50 60 70 80 90 100 110
Ambient Temperature (F)
CondenserSubcool(F)
Tsc=5
Tsc=10
Tsc=15
Tsc=20
Figure 9. Condenser Subcool at Varying Ambient for Different Refrigerant Charges
Because the seasonal COP depends on the performance of the system over a range of
temperature, it is important that the refrigerant charge is high enough to ensure there be
subcool in the condenser at the lower temperatures. When the subcool disappears, the
superheat in the evaporator increases leading to lower density vapor at the compressor
inlet. This lower density vapor causes the mass flow rate to drop significantly, lowering
the evaporator capacity and the COP as shown in Figure 10.
7/30/2019 10.1.1.32.165
71/161
57
385
390
395
400
405
410
415
420
425
50 60 70 80 90 100 110
Ambient Temperature (F)
MassFlowRate(lbm/h
r)
28500
29000
29500
30000
30500
31000
31500
32000
32500
33000
EvaporatorCapacity
(Btu/hr)
Mass Flow Rate Evaporator Capacity
Subcool = 0
Figure 10. Effect of Ambient Temperature on Evaporator Capacity and Mass Flow Rate
The optimum refrigerant charge will be different for each ambient temperature,
but the COP will remain relatively constant at every temperature as long as the subcool is
specified between 10 F and 15 F at 95 F ambient. In the range of 5-20 subcool, the
seasonal COP is within 0.5% of the COP at 83 F ambient. The trends in COP over the
season and at different ambient temperatures are plotted over a range of subcools in
Figure 11.
7/30/2019 10.1.1.32.165
72/161
58
3.5
3.6
3.7
3.8
3.9
4
4.1
4.2
0 5 10 15 20 25
Subcool @ 95F
COP
Seasonal
Tamb=77
Tamb=82
Tamb=83
Tamb=87
Figure 11. Trends in Seasonal COP vs. COPs at Other Temperatures
Effect of Varying Air Velocity
As expected, for a fixed amount of subcool at 95, there is an air velocity that
produces the highest seasonal COP. The COP varies exhibits a maximum with the air
velocity for any subcool as shown in Figure 12. For subcools ranging from 5 to 20, the
optimum air velocity is somewhere between 7 ft/s and 10 ft/s. In this range, the seasonal
COP is insensitive to the air velocity; for any refrigerant charge, it varies by less than 1%.
7/30/2019 10.1.1.32.165
73/161
59
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
0 2 4 6 8 10 12 14 16 18
Air Velocity (ft/s)
Tsc=5
Tsc=10
Tsc=15
Tsc=20
Figure 12. Effect of Air Velocity on Seasonal COP for Different Subcool Conditions
Because the seasonal COP varies so little with air velocity, it is difficult to
pinpoint the optimum air velocity for each subcool within more than 0.1 ft/sec. In
practice, this is acceptable because the air speed cannot be specified to a such high
tolerance.
Since the fan work increases proportionally with the cube of the velocity, it does
not initially make sense that the COP would not be affected. However, in this range, as
the fan work is increasing, the compressor work is decreasing by roughly the same
amount, as demonstrated in Figure 13. As the air velocity increases, the condensing
temperature decreases, and the inlet enthalpy to the evaporator also decreases. When this
7/30/2019 10.1.1.32.165
74/161
60
happens, the mass flow rate of refrigerant needed to maintain the design evaporator
capacity drops decreasing the compressor work. Since condensing temperature of the
refrigerant cannot be lower than the air inlet temperature, there is a minimum compressor
work. As the air velocity increases beyond the optimum range, the fan work will grow
exponentially and the decrease in compressor work does not compensate for it.
Air Velocity (ft/s)
Work(BTU/hr
Compressor
Condenser Fan
Total
Figure 13. Effect of Air Velocity on Compressor and Condenser Fan Work
Effect on Cost Factor
Changing the air velocity and refrigerant charge will slightly affect the cost of the
system because different compressors or fans should be used for different heat
exchangers. This would involve cost studies of compressors and fans which is outside
7/30/2019 10.1.1.32.165
75/161
61
the scope of this study. They will be excluded from the cost factor calculation, but the
designer should be aware of the possible effects.
7/30/2019 10.1.1.32.165
76/161
62
CHAPTER V
EFFECTS OF GEOMETRY WITH FIXED COST
When designing a heat exchanger for maximum system COP, the two most
important constraints are the cost of the exchanger and the amount of frontal area it takes
up. It is not possible to keep both the frontal area and cost constant while only varying
one geometry factor, but simultaneously changing more than one variable would make it
difficult to determine the effect each variable has on the system. To examine the tradeoffs
between frontal area and cost, cases with fixed cost and fixed frontal area were
considered.
To compare the relative frontal area of each condenser configuration, the area
factor parameter is defined as the ratio of the frontal area of the test configuration to the
frontal area of the base configuration.
baseAreaFrontal
AreaFrontalAF=
A similar factor, the cost factor, is used to compare the cost of condenser-
evaporator configurations:
7/30/2019 10.1.1.32.165
77/161
63
base
Cost
CF Cost=
The cost of the heat exchanger is largely determined by the cost of the materials xxvii so the
cost factor of each configuration is taken as:
( ) ( ), , , ,Cucon Cu evap Cu Cu Al con Alevap Al Al Cost Vol Vol Cost Vol Vol Cost = + + +
The costs of the materials are summarized in Table 8.
Material Cost ($/lbm)
Copper 0.8
Aluminum 0.7
Table 8. Material Costsxxviii
The heat exchanger cost factor of the base configuration is $35.88. Although the piston
displacement will change slightly for each configuration, it varies from the base case by
no more than 3% under most conditions, so the cost variations of the compressor will be
ignored.
7/30/2019 10.1.1.32.165
78/161
64
Number of Rows
Although altering any geometry factor will change the frontal area of the
condenser with the cost factor fixed, it is easiest to conceptualize this by changing the
number of rows. For these tests, the height of the condenser will remain fixed, but the
width is free to change. Intuitively, a heat exchanger with no bends and the largest
frontal area possible would provide the best performance.
Figure 14verifies this notion.
3.70
3.75
3.80
3.85
3.90
3.95
4.00
4.05
4.10
4.15
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5
Number of Rows
SeasonalCOP
Fixed Parameters
Fin Pitch =12 fpi
Tube Diameter = 3/8
Tubes/ Circuit = 2
3.703.753.803.853.903.954.00
4.054.104.15
Fixed Parameters
Fin Pitch =12 fpi
Tube Diameter = 3/8
Tubes/ Circuit = 2
Figure 14. Number of Rows vs. Seasonal COP with Fixed Cost
As the number of rows increases, the number of bends also increases. Obviously,
fewer bends in the tubing means less frictional losses and less compressor work. By
7/30/2019 10.1.1.32.165
79/161
65
having the air only flow over one row of tubing, the temperature differential between the
air and the refrigerant is kept to a maximum, decreasing the refrigerant mass flow rate
and compressor work. The refrigerant side pressure drop and compressor power as
functions of the number of rows are plotted in Figure 15.
6100
6200
6300
6400
6500
6600
6700
0 1 2 3 4 5
Number of Rows
CompressorPower(Btu/hr)
0
5
10
15
20
25
30
R22PressureDrop(psi)
Compressor
Power
R22PressureDrop
Figure 15. Number of Rows vs. Compressor Power and Refrigerant Pressure Drop
While this is the main cause for the COP increase, the fan power also decreases as
with the number of rows. The pressure drop will go down as the depth of the air passage,
which is controlled by the number of rows, decreases. For larger number of rows, the
optimal air velocity is higher. This coupled with the increased pressure drop causes the
fan power to nearly double from 1-row to 4-rows as shown in Figure 16. However, if the
velocity remains constant, the fan power does not change.
7/30/2019 10.1.1.32.165
80/161
66
0
0.001
0.002
0.003
0.004
0.005
0.006
0.007
0 1 2 3 4 5
Number of Rows
Air-SidePressureDrop(Psi)
0
50
100
150
200
250
300
350
400
FanPower(Btu/hr)
Pressure Drop
Fan Power
Figure 16. Rows vs. Air Side Pressure Drop and Fan Power for Fixed Cost at 83 F
Fin Pitch
Keeping the cost factor and all design parameters except the frontal area the same
as the base case, the model was run for fin pitches between 8 and 14 fins per inch (fpi).
The maximum seasonal COPs and area factors based on fin spacing are summarized in
Table 9 and shown graphically in Figure 17. Based on these results, the fin spacing has
almost no effect on the seasonal COP or the optimal operating conditions. As seen in
Figure 18, the optimum velocity, for every fin pitch is between 8.5 and 9.5 ft/sec. This
figure is based on 10 F subcool at 95 F outdoor air temperature. Figure 18 also shows
that the seasonal COP varies shows an optimum with fin pitch, but the variation is
marginal.
7/30/2019 10.1.1.32.165
81/161
67
Fin Pitch(fpi)
SeasonalCOP
AreaFactor
8 3.839 1.258
10 3.856 1.114
12 3.862 1.000
14 3.860 0.906
Table 9. COPs and Area Factors Based on Fin Pitch
Effect of Fin Pitch on Seasonal COP at
Optimum Operating Conditions
3.835
3.840
3.845
3.850
3.855
3.860
3.865
6 8 10 12 14 16
Fin Pitch (fins/in)
Sea
sonalCOP
Fixed Parameters
# Rows = 3Tube Diameter = 3/8
Tubes/ Circuit = 2
3.8453.8503.8553.8603.865 Fin Pitch (fins/in)
Fixed Parameters
# Rows = 3Tube Diameter = 3/8
Tubes/ Circuit = 2
Figure 17. Seasonal COPs for Different Fin Pitches at Optimum Operating Conditions with Fixed
Cost
7/30/2019 10.1.1.32.165
82/161
68
3.77
3.78
3.79
3.80
3.81
3.82
3.83
3.84
3.85
3.86
3.87
6 7 8 9 10 11 12
Air Velocity (ft/sec)
SeasonalCOP
FPI=8
FPI=10
FPI=12
FPI=14
Figure 18. Effect of Fin Pitch on Seasonal COP at Different Air Velocities
The maximum COP will occur when fin spacing is increased just before the point
where the airside pressure drop causes the fan work to increase faster than the compressor
work is decreasing, in this case, 12 fins per inch. As long as the operating conditions are
kept in the recommended range of 10-15 degrees subcool and 7-10 ft/sec air face
velocity, the maximum and minimum seasonal COPs will only differ by about 1.6%.
The maximum occurs with 12 fins per inch, 8.8 ft/sec air face velocity and 10 F subcool.
The minimum occurs with 8 fins per inch, 10-ft/sec air face velocity, and 15 F subcool.
Although the fin spacing does not dramatically affect the COP, it does affect the
packaging size. If a more compact heat exchanger is desired, increasing the fin pitch will
decrease the frontal area as shown in Figure 19.
7/30/2019 10.1.1.32.165
83/161
69
0
1
2
3
4
5
6
7
8
9
10
6 7 8 9 10 11 12 13 14 15
Fin Pitch (fins/in)
Figure 19. Effect of Fin Pitch on Frontal Area
As the fin pitch increases, the pressure drop across the fins also increases as seen
in Figure 20. This figure is based on operation at 77 F, but