    rvic M nual

    Wall split type

  • 7/22/2019 20115272209

    2/45

    Table of Con tents

    1. Summary .............................................. .3

    2. Model explaining .............................................. .4

    3. Use and installation ............................... .4

    4. Exploded view and part list.............................................. 20

    5. Operation principle. ................................................ 28

    6. Parameter................................................. 28

    7. Wiring diagrams. .................................................. 30

    8. PCB principle chart................................................. 32

    9. Part list of PCB ..................................................... 32

    10. PCB function . .......................................... 34

    11. Troubleshooting. ........................... 40

  • 7/22/2019 20115272209

    3/45

    1. Summary

    1.1indoor unit

    Model 48

    1.2outdoor unit

    9000BTU 12000BTU

    model CQS-25H3A-G48AY1 CQS-35H3A-A48AH1

    indoor unit 790270180 790270180

    Net Dimension

    outdoor unit 700225500 795255540

  • 7/22/2019 20115272209

    4/45

    2Model explainingc

    Improve an ordinal number

    Divide the body outdoors box a body code

    External appearance characteristic code

    Separately the body indoor machine(or whole type) style code

    Code of refrigerant typeno code - R22C-R407cA-R410a

    Power type1:115v/60Hz 2:220V/60Hz3:220-240V/

    50Hz4:240V/50Hz

    Main function code: c-Cold breeze type;H-Hot pump type;A-Hot

    pump the type take assistance electricity to heat;E-The electricity

    heat

    Capacity code: x1000W

    Separately the body pit code inside the indoor machine(or whole

    type)

    Structure form code

    Special craft code:Q-Deal with contact quickly;S-Soft start;d-

    Outside tube in addition to frost

    The weather type code(T1 type code abridge)

    "C" CHIGO brand

    as: CQS-25H3A-G48AY1

    T1 climate type,deal with contact quickly ,hot pump type, wall split type air conditioner, cooling capacity

    is 2500Wpower is 220-240V/50Hz/1PHrefrigeration is R410A,the kernel of indoor unit is 418the pattern

    no. is 48first time design, outdoor unit is 1HP of 2003 year

    Indoor unit modle isCQS-25H3A-G48Aoutdoor unit model isCQS-25H3A-Y1

    3. Use and installation .

    BASIC ACCESSORIES

    This Installation section explains how and where to connect this new air conditioner. Please read make sure

    all accessories are included as shown below and read manual thoroughly. This Installation section is provided

    to assist the per-son knowledgeable in air conditioner installation and should not be installed by anybody

    who is not thoroughly familiar with this type of installation. Please contact a professional installer if

    necessary.

    ACCESSORIES SUPPLIED WITH THE UNIT:

    No Part Name Q'ty Remark No Part Name Q'ty Remark

    1 Remote Controller 1 3 Battery 2

    2 Remote Holder 1

  • 7/22/2019 20115272209

    5/45

  • 7/22/2019 20115272209

    6/45

  • 7/22/2019 20115272209

    7/45

  • 7/22/2019 20115272209

    8/45

  • 7/22/2019 20115272209

    9/45

  • 7/22/2019 20115272209

    10/45

  • 7/22/2019 20115272209

    11/45

  • 7/22/2019 20115272209

    12/45

  • 7/22/2019 20115272209

    13/45

    Before installation:

    Selection of installation positions for indoor unit

    To be installed at the position where the air delivered from the unit can reach every corner of the room

    Avoid to biockage the air inlet or outlet of the indoor nit

    To avoid too much oil smoke or steam

    Avoid possible generation infiow, lingering or leakage of flamm gasee

    Avoid high-frequency facilities (such as high frequency arc welders etc.)Not to install a fire alarm near the air outlet.

    To avoid the places where acid solutions are frequently used

    [Selection of installation positions for indoor unit]

    To be installed at the position where the air delivered from the unit can reach every comer of the room;

    To avoid being affected by the outdoor air;

    To avoid blockage to the air inlet or outlet of the unit;

    To avoid too much oil smoke or steam;

    To avoid possible generation,inflow,lingering or leakage of flammable gases;

    To avoid high-frequency facilities(such as high frequency arc welders,etc,)

    To avoid the places where acid solutions are frequenty used;

    To avoid the places where some special sprayers(sulfides) are frequently used

    Not to install on top of the musical instruments,TV,computer etc,valuable appliance.

    Not to install a fore alarmning device near the air outlet of the unit(during operation,the fire alarm device might be

    erroneously triggered by the warm air from the unit);

    Make sure of enough space for installation and maintenance To take into consideration the operational convenience and safety in installation,it is recommended ti ensure enough

    space between the unit and the walls,

    Attention:lf there are some additional function devices to install on the air conditioner,Besure add

    to the installation space for the function devices

    Height limits of indoor and outdoor units Either the indoor unit or the outdoor unit can be higher,but the height difference must comply the stated

    requirements Try to reduce the bending of the piping line as much as possible so as to avoid possidle negative impacts

    upon the performnances of the units

  • 7/22/2019 20115272209

    14/45

    [Selection of installation positions rot outdoor unit]

    To install the outdoor unit at the places which can stand the load of the machine weight and will

    not cause big vibrations and noises;

    To install the unit at the places not to exposed to rain or direct sunshine,and the places with

    good ventilation;

    The noises generated from the unit will not affect the neighboring places;

    Do not install the unit on non-metal frame;

    Not to install the unit at the places where there might occur the generation,inflow,stay or leakage

    of inflammable gases;

    pay attention to the drainage of the condensed water from the base plate during operations;

    To avoid the air outlet being directly against the wind.

    Detailed space requirements around the outdoor unit

    [lnstallation fixture of indoor unit]

  • 7/22/2019 20115272209

    15/45

  • 7/22/2019 20115272209

    16/45

  • 7/22/2019 20115272209

    17/45

  • 7/22/2019 20115272209

    18/45

  • 7/22/2019 20115272209

    19/45

  • 7/22/2019 20115272209

    20/45

    4Indoor outside explosion the diagram and spare parts catalogue4.1 CQS-25H3A-G48AY14.1.1 Explosive view of indoor unit

    4.1.2 Spare parts list of indoor unitPart No. Qty

    No. DescriptionCQS-25H3A-G48AY1

    1 Louver 100420003/100420083 2

    2 Outlet part 391200006 1

    3 Left angle plate 100360001 1

    4 Base 100060106 1

    5 Cross flow fan 100010016 1

    6 Fan Bearing 110010603 1

    7 Connecting Cable 342300055 18 Quick coonector 979900183 1

    9 Evaporator assembly 972900618 1

    10 Evaporator left fixed plate 109990108 1

  • 7/22/2019 20115272209

    21/45

    11 Screw cover 109990023 2

    12 Middle frame 391070007 1

    13 Air Filter 100190111 2

    14 Display box cover . 1

    15 Disp;ay box 100410004 1

    16 Front Panel 391022065 1

    17 Remote controller 336815006 1

    18 Roomtemp.Sensor Holder 100280105 1

    19 Pipe Clamp 100430025 1

    20 Eliminator 100420002 1

    21 Evapora torright fixed plate 109990109 1

    22 Motor platen 100130003 1

    23 Motor 030020173 1

    24 Wire Clip 391110017 1

    25 Power Cord 050010042 1

    26 Terminal Board 030090005 127 Display lamp panel 331800039 1

    28 Tube Temp.Sensor 079990030 1

    29 Electric control plate 331300107 1

    30 Room Temp.Sensor 049990012 1

    31 Electric box 100100035 1

    32 Transformer 030180061 1

    33 Connecting Wire 120310028 1

    34 Base right angle plate 100300003 1

    35 Wall-mounting frame 020100010 136 Step motor 320273001 1

    37 Step Motor plate 320273001 1

    38 Crank connecting rod 100420082 1

  • 7/22/2019 20115272209

    22/45

    4.1.3 Explosive view of outdoor unit for 1HP

    4.1.4 Spare parts list of outdoor unitPart No. Qty

    No. DescriptionCQS-25H3A-G48AY1

    1 Front Grill 020120002 1

    2 Grill Clip 109990256 8

  • 7/22/2019 20115272209

    23/45

    3 Front Plate 020070001 1

    4 Small handle 100050001 1

    5 Nut 150020009 1

    6 Gasket 150030013 1

    7 Axial flow fan 100030013 1

    8 Motor 030020201 1

    9 Motor support 313040004 1

    10 PE Sponge PE 090020234 1

    11 Base 020010129 1

    12Anti-vibration pad for the

    compressor 010011455 3

    13 Compressor 302114004 1

    14 Nut 010011578 1

    15 Gasket 010011456 3

    16 Nut 150020003 1

    17 Top panel 020080001 1

    18 PU Sponge 090020226 1

    19 Partition board 020030001 1

    20 Electric installation board 020130006 1

    21 Compressor Capacitor 030010015 1

    22 Capacitor Clamp 020140006 1

    23 Fan Capacitor 030010005 1

    24 Terminal Board 030090025 1

    25 Wire Clip 321100011 1

    26 PU Sponge 090020227 1

    27 Condenser 372100103 1

    28 tube temp. sensor wire 338000008 1

    29 Copper pipe or sensor 079990030 1

    30 Capillary Assy 971900314 1

    31 Damping rubber 110030023 1

    32 Drainpipe for the condensor 360510003 1

    33Intake pipe for the

    condensor 360440093 1

    34 4-way Valve 973500175 1

    35 Discharge pipe 360220111 1

    36 Damping block 110020011 1

    37 Damping rubber 110030017 2

    38 Suction pipe 360120107 1

    39 Quick connector 1 1 351600014 1

    40 Quick connector 2 2 351600014 1

    41Low-pressure Connecting

    Pipe 979900184 1

    42High-pressure Connecting

    Pipe

    361300062 1

    43 Filling valve 359000004 1

    44 Valve installation plate 313020016 1

    45 Large handle 100040001 1

  • 7/22/2019 20115272209

    24/45

    46 Right panel 313060035 1

    47 Connecting Wire 425300038 1

    48 Connecting Cable 342300046 1

    49 Electric heater 320440005 1

    50 Electric heating wire clip 313990014 4

    4.2 CQS-35H3A-A48AH1

    4.2.1 Explosive view of indoor unit

    4.2.2 Spare parts list of indoor unitPart No.

    No. DescriptionCQS-35H3A-A48AH1

    Qty

    1 Louver A 100420003 1

    2 Louver B 100420083 1

    3 Swing Louver 100420007 12

    4 Connecting rod 100420072 3

    5 Guide Louver Bearing 100420008 6

    6 Outlet part 100090110 1

  • 7/22/2019 20115272209

    25/45

    7 Left angle plate 100360001 1

    8 Base 100060108 1

    9 Cross flow fan 100010016 1

    10 Cross flow fan bearing 1

    11 Fan Bearing 110010603

    1

    12 Connecting Cable 342300097 1

    13 Quick connector 979900178 1

    14 Evaporator assembly 972901480 1

    15 Evaporator left fixed plate 109990108 1

    16 Remote controller 336815006 1

    17 Screw cover 109990023 2

    18 Middle frame 391070007 1

    19 Front Clip 391220004 4

    20 Air Filter 100190127 2

    21 Cold Catalyst 119990011 1

    22 Display box cover

    100410004 123 Display box 100410004 1

    24 Front Panel 391022065 1

    25 Middle frame coverplate 100080034 1

    26 Room temp. Sensor Holder 100280105 1

    27 Insert Block 079990240 1

    28 Copper pipe of sensor 079990030 1

    29 Pipe Clamp 100430025 1

    30 Evaporator right fixed plate 109990109 1

    31 Motor platen 100130003 1

    32 Motor 030020173 1

    33 Electric box cover 100100041 1

    34 Display lamp plate 331800039 1

    35 Tube Temp. Sensor 079990030 1

    36 Room Temp. Sensor 049990012 1

    37 Electric control plate 331300009 1

    38 Connecting Wire 425300063 1

    39 Transformer 030180061 1

    40 Electric box 100100035 1

    41 Wire Clip 391110018 1

    42 Terminal Board 030090005 1

    43 Power Cord 050010050 1

    44 Right angle plate 100300003 1

    45 Wall-mounting frame 020100010 1

    46 Screw 150010019 2

    47 Step motor 320273001 1

    48 Motor fixed plate 100420002 1

    49 Crank connecting rod 100420082 1

    50 Upper crank 100420001 1

    51 Lower crank 100420081 1

    52 Thermal insulation pipe 099990080 1

  • 7/22/2019 20115272209

    26/45

    4.2.3 Explosive view of outdoor unit for1.5HP

    4.2.4 Spare parts list of outdoor unitPart No. Qty

    No. DescriptionCQS-35H3A-A48AH1

    1 Front Grill 020120015 1

    2 Grill Clip 109990256 8

  • 7/22/2019 20115272209

    27/45

    3 Front Plate 020070056 1

    4 Small handle 100050021 1

    5 Nut 150020009 1

    6 Gasket 150030018 1

    7 Axial flow fan 393010001 1

    8 Motor 320222005 1

    9 Motor support 313040002 1

    10 PE Sponge PE 090020234 1

    11 Base 313011093 1

    12Anti-vibration pad for the

    compressor 305146005 3

    13 Compressor 302114009 1

    14 Gasket 305142002 3

    15 Nut 305143002 3

    16 Top panel 020080002 1

    17 Partition board 313030014 1

    18 PU Sponge 090020027 1

    19 Electric installation board 020130006 1

    20 Compressor Capacitor 030010017 1

    21 Capacitor Clamp 020140006 1

    22 Terminal Board 321000025 1

    23 Fan Capacitor 030010005 1

    24 Wire Clip 321100003 1

    25 PU Sponge 090020028 1

    26 Condenser 372100086 1

    27 Tube temp.sensor wire 338000008 1

    28 Copper pipe or sensor 079990030 1

    29 4-way Valve 973500062 1

    30Intake pipe for the

    condensor 360450021 1

    31 Capillary Assy 971900295 1

    32 Damping rubber 110030017 1

    33 Filter 361910002 1

    34 Right panel 020060041 1

    35 Large handle 100040002 1

    36 Quick connector 1 1 351600014 1

    37 Quick connector 2 2 351600014 1

    38 Connecting Cable 342300045 1

    39Low-pressure Connecting

    Pipe 979900176 1

    40High-pressure Connecting

    Pipe 361300062 1

    41 Filling valve 359000004 1

    42 Valve installation plate 020020008 143 Drainpipe for the condensor 360540042 1

    44 Discharge pipe 360220103 1

    45 Damping block 110020011 1

  • 7/22/2019 20115272209

    28/45

    46 Suction pipe 360130149 1

    47 Damping rubber 110030023 2

    48 Connecting Wire 425300038 1

    49 Electric heater 320440005 1

    50 Electric heating wire 313990014 4

    5. Operation principle

    outdoor unit

    outdoor fan

    1

    14

    13

    215

    connection pipe12

    coolingpay attention to sealing

    heating

    163

    4

    5

    7

    8

    6

    indoor fan

    1011

    9

    indoor unit

    connection pipe

    1.compressor 2. 4-way value 3.condenser 4.flow divider for condenser 5.Non-return valve 6.auxiliary capillary

    7.cooling capillary 8.high-pressure valve 9.flow divider for evaporator 10.evaporator 11. pipe temp. sensor for

    evaporator 12.low-pressure valve 13.Vapor liquid separator 14.low-pressure switch 15. high-pressure switch 16pipe

    temp. sensor for condenser

    Cooling cycly compressor4-way valuecondenserflow divider for condenserNon-return valvecooling capillary

    high-pressure valveflow divider for evaporatorevaporatorlow-pressure valve4-way valueVapor liquid separator

    compressor.

    Heating cyclycompressor4-way valuelow-pressure valveevaporatorflow divider for evaporatorhigh-pressure valve

    cooling capillaryauxiliary capillaryflow divider for condensercondenser4-way valueVapor liquid separator

    compressor.

    NoteTo the model of RF or LF beginning, use outdoor unit model to express the whole unit.

    6. Parameter Performance parameter

    Model CQS-25H3A-G48AY1 CQS-35H3A-A48AH1Apattern NO. 48 48

    Power supply Ph-V-Hz 220-240V/50Hz 220-240V/50Hz

    Cooling Cooling capacity W 2780 3590

  • 7/22/2019 20115272209

    29/45

    Cooling Input W 865 1120

    Cooling Rated current A 4.0 5.1

    EER w/w. 3.21 3.21

    Heating Capacity W 2780 3680

    Heating Input W 770 1020

    Heating Rated current A 3.5 4.7Heating

    COP w/w. 3.61 3.61

    Max. input consumption W 1660 2170

    Max. current A 8.2 10.6

    Model PA108X1C-4DZDE PA140X2C-4FT

    Type ROTARY ROTARY

    Brand TOSHIBA TOSHIBA

    Capacity W 2570/2670 3365/3385

    Input W 885/915 1160/1200

    Start electric current A 21.7 2601

    Thermal protector inner inner

    Compressor

    Capacitor uF 25 35

    Model YDK-16-4 YDK-16-4

    Input W 47 47

    Capacitor uF 1.2 1.2Fan motor

    Speed r/min 1350 1350

    Fan motor diameterheight mm 93633 93633

    Air flow m3/h 500 600

    Noise level dB(A) 29-39 35-42

    Net Dimension (W*H*D) mm 790*270*180 790*270*180

    Packing Dimension (W*H*D) mm 875*345*340 875*345*340

    Indoorunit

    Net/Gross weight Kg 12/14 12/14

    Model YDK-30-6 YDK-35-6A H

    Input W 85 67

    Capacitor uF 2 2Fan motor

    Speed r/min 890 900

    Fan motor diameterheight mm 384136 401115

    Noise level dB(A) 49 54

    Net Dimension (W*H*D) mm 700*225*500 795*255*540

    Packing Dimension (W*H*D) mm 825320535 920*335*585

    Net/Gross weight Kg 30/32 36/40

    Outdooruni

    Refrigerant type g R410A/610g R410A/1020g

  • 7/22/2019 20115272209

    30/45

    7.Wiring diagrams

    7.1 CQS-25H3A-G48AY1

    Indoor unit:

    Outdoor unit:

  • 7/22/2019 20115272209

    31/45

    7.2CQS-35H3A-A48AH1

    Indoor unit:

    Outdoor unit:

  • 7/22/2019 20115272209

    32/45

  • 7/22/2019 20115272209

    33/45

    A15 0101702601 10K RT-1/4W 9

    R3R16R17R19

    R22R23R25R31

    R48

    A16 0101701201 330 RT-1/4W 1 R14

    A17 0101701401 510 RT-1/4W 2 R49R52

    A180101102201 4.3K RJ-1/4W 2 R18R20

    A19 0101701901 R carbon film 2 K RT-1/4W 2 R4R37

    A20 0101701301 R carbon film 390 RT-1/4W 1 R35

    A21 0101703401 R carbon film 300 K RT-1/4W 1 R15

    A22 0101200503R oxidation film

    220 RY-1W 1 R36

    A23 0101701001R carbon film

    220 RT-1/4W 2 R50R51

    A24 01042002021.2F5%CBB61

    450VAC1 CFI

    A25 0104300201 473/275V 1 C20A26 0104300301 104/275V 2 C21C22

    A27 0104600811 102 8C3C4C11C12

    C15C16C19C25

    A28 0104601311 104 10C1C2C5-C9C13

    C17C26

    A29 0104101102 1000F/35V 1 E7

    A30 0104101001 220F/16V 1 E2

    A31 0104100401

    capacitance

    10uF/25V 1 E5

    A320701100201 XH-2A white 1 CNC

    A33 0701100301 XH-3A white 1 CNW

    A340701100302

    XH-3A

    yellow 1 CND

    A35 0701100501 XH-5A white 1 CNM

    A36 0701100401 XH-4A white 1 CNG

    0701100601 XH-6A white 1 CNEA37

    0701200301 VH-3A white 1 CNB

    A38 0701200401 VH-5A white 1 CNU

    A39 1501300600

    connector

    XH-2A white 1 CNC

    A401501300600

    Compressor

    relay HF2160-1A-12DE1 52C

    A41 2104000100 safety clip 520mm 2 FUSE

    A42 0116100100

    I nsur ance

    t ube 3.15A/250AC 1 FUSE

    A43 9803010400 safety ZGAY/621-10-126 1 ZR

    A44 0304200500Si ngl e- I nt er

    cal at i on 6.3 KET 1 N2

  • 7/22/2019 20115272209

    34/45

    A45 2903300103 jumper 0.510mm 9 J1-J6J8-J10

    A46 0125300100 inductance 0.043mH 1 L1

    A47 0119200601 button A06-(c)9.5mm 1 SW1

    A48 1303000211 transformer B03-01A

    A49 1102101680 jumperJF1DJ46/48DCP21

    2-Q

    1

    156 113.5 B items cooling and hot plate materialsB01 0107701301 diode IN4148 2 D6D9

    B02 1501200400 relay JZC-32F 12V 2 X3X1

    B03 2903300103 jumper 0.510mm 1 J7

    B04 0304200500Si ngl e- I nt er

    cal at i on6.3 KET 2 20SFMO

    B05 0107100201 audi on 9013 1 Q2

    B06 0101702201resistance

    47K RT-1/4W 1R13

    C items Electric heating materialsC01 diode IN4148 3 D6D9D10

    C02 relay JZC-8F 12V 2 X1X3

    C03 relay SJ-S-112DM 1 X210A/250VAC

    10A/250VAC

    C04 jumper 0.510mm 1 J7

    C05

    Si ngl e- I nt er cal at ion

    6.3 KET 2 20SFMO

    C06Si ngl e- I nt er cal at ion

    4.8 1 HEAT

    C07 audion 9013 1 Q2

    C08 resistance 4.7K RT-1/4W 1 R13

    D items Bl ackout memory mat er i al sD01 0107501000 Mani f ol d AT24C02 1 IC7

    D02 0104601311 capacitance 104 1 C18

    E items Ani on mat er i al sE01 0304200500

    Singer-zntercalation

    6.3 KET 1 N1

    10 PCB function:NOTE: Ts is the set temperature, Tr is indoor room temperature, TP1 is indoor coil pipe temperature, TP2 is outdoor coil pipe

    temperature.

    Display panelLED

    according to display mode: dehumidification, cooling, ventilation, heating, auto, sleep, fan speed, swing, timer, indoor

  • 7/22/2019 20115272209

    35/45

    fan running.

    wind speed indication correspond fan speed of indoor blower fan.

    Cooling

    Start up the compressor: when the room temperature is more than Ts+1, compressor start-up

    Shut down the compressor: when the room temperature is less than or equal to the set temperature Ts-1,

    compressor shutdown

    When the temperature of coil pipe of the indoor units is less than or equal to 1 for one minute and the

    compressor has continuous run for more than ten minutes, the compressor and outdoor blower fan shut down

    through the electric control board and the indoor blower fan is running at low speed.

    When the temperature of coil pipe of the indoor units is more than or equal to 7 and the compressor has

    shutdown for more than three minutes, the compressor and outdoor blower fan start to run and the indoor blower

    fan is running at set speed.

    When the temperature of coil pipe of the indoor units is equal to or less than 10 for three minutes in the

    compressor has continuous run for three minutes, the compressor, indoor and outdoor blower fans and swinging

    wind shut down. Restart up six minutes later; if the above situations appear again within six minutes, all the

    outputs are shut down through the electric control board and display failure.

    After the compressor runs five minutes, the lamp flashes 4 times per six seconds or display E4 if the temperature

    of indoor coil pips is more than 25 in the continuous 20 minutes. The controller will automatically shut down if

    the temperature of indoor coil pips is more than 25 in another continuous 20 minutes, that is the abnormality

    protection of outdoor units and the indicator lamp keeps its former state of flashing. If the temperature of indoor

    coil pips is less than 25 in the second 20 minutes or the compressor shuts down, the electric control board willstore to the normal display and the time is restarted when starting up the compressor next time.

    Heating (only applicable to heat pump units)

    Start up the compressor: when the room temperature is less than Ts-1, compressor start-up

    Shut down the compressor: when the room temperature is more than or equal to the set temperature Ts+3,

    compressor shutdown

    The electric heating start-up in the heating mode shall meet the following conditions: start up the compressor

    and indoor blower fan none defrost TP1< 49 Tr 20.

    The electric heating shutdown in the heating mode shall meet one of the following conditions: shutdown

    indoor blower fan Tr 23 TP150.

  • 7/22/2019 20115272209

    36/45

    In the heating mode, the indoor flower fan can be set as high/ medium/ low /automatic running mode by remote

    control. however the anti cool air function is prior. In the heating mode, the anti cool air control function is to

    control shutdown of the indoor blower fan by detecting the temperature of coil pipe of evaporator so as to attain

    the purpose of preventing cold air from blowing.

    For the waste heat emission function in the heating mode, in principle, the indoor blower fan shall be on for

    fifteen seconds after the electric heating is closed.

    When the temperature of coil pipe of indoor units is more than or equal to 56, the outdoor blower fan shuts

    down and it enters the overload protection; when the temperature of coil pipe of indoor units is less than or equal

    to 52, the outdoor blower fan starts up and it exit the overload protection.

    When the temperature of coil pipe of indoor units rises to 63, the compressor and outdoor blower fan are closed

    and two minutes later, the change valve is closed. The indoor blower fan is running at the set speed. Restart up six

    minutes later; if the above situations appear again within ten minutes, all the outputs are shut down through the

    electric control board and display failure.

    When you press turbo button of remote, the air conditioner enter turbo running, compressor ,outdoor blower fan

    and four-way valve turn on all along, indoor blower fan run at high speed and it must meet start condition, turbo

    indication is light.

    After the compressor runs five minutes, the lamp flashes 4 times per six seconds or display E4 if the temperature

    of indoor coil pips is less than 30 (heating) in the continuous 20 minutes. The controller will automatically shut

    down if the temperature of indoor coil pips is less than 30 in another continuous 20 minutes, that is the

    abnormality protection of outdoor units and the indicator lamp keeps its former state of flashing.

    Defrost (only applicable to the heating mode)

    1. the intelligent defrost

    In the heating mode, the electric control board checks and compares the temperature of indoor room and indoor coil

    pipe after the compressor works for a while; judge whether the outdoor heat exchanger part is frosted or not according to

    conditions such as the change of indoor coil pipe temperature; if it is judged as frosted, it automatically enters defrosting

    process. When defrosting, close the indoor and outdoor blower fan and four-way valve.

    2. Outdoor PCB for defrost.

    In the heating mode, the unit defrost by outdoor control board

    unit start defrost shall all meet the following conditions

    acompressor continuous running over 7 minutes

    bdefrost relay shut off-5

    ccompressor cumulate running time over 50 minutes.

    first defrost interval time is 50 minutes, later defrost interval time decided by last defrost time.

    Defrost time(minute) Next defrost interval time(minute)

    15 30

    10--15 40

    7--10 60

    3--7 70

    3 802end defrost condition(meet one of follows)

    adefrost time have fifteen minutes.

    bdefrost relay turn on8

  • 7/22/2019 20115272209

    37/45

    cpress ON/OFF key in defrost process.

    3. Outdoor sensor for defrost

    unit start defrost shall meet one of the following conditions

    a. compressor cumulate running time over 30 minutes and it continuous running over 3 minutes, the

    temperature of coil pipe of the outdoor units is equal to or less than 15 for one minutes (Tp2-15).

    b. compressor cumulate running time over 40 minutes and it continuous running over 3 minutes, the

    temperature of coil pipe of the outdoor units is equal to or less than 5 for one minutes (Tp2-15).c. Air conditioner first power on or it wait over 30 minutes ,the temperature of coil pipe of the outdoor units is

    equal to or less than 2 (Tp2-15)

    end defrost condition(meet one of follows)

    a. the temperature of coil pipe of the outdoor units is more than 15 (Tp2-15).

    b. defrost time have fifteen minutes.

    Sequence chart in defrosting mode

    Dehumidification

    Dehumidification running is to eliminate the water vapor in the air by using the cool circulating capacity, but the

    dehumidification will not decrease the indoor temperature in great deal. The air conditioner automatically repeats on

    and off circulation according the room temperature, which is shown in the following figure.

    indoorblower fan

    C

    C

    door

    blower fan

    Tr

    shutdown shutdownshutdown shutdown shutdown

    shutdownshutdownshutdownshutdownshutdown

    low speed

    Tr10

    shutdown

    start-up

    start-up start-up

    start-up start-up

    start-up start-up

    start-up

    forbiddehumidify

    In the dehumidification mode, the indoor fan is running at the low speed for twenty seconds at first, then it select

    working mode.

    Automatic mode

    Conditions for entering the automatic running mode are: After power-up for the first time, start up and select the

    automatic operating mode of remote or press emergency key, the working mode depends on Tr and if the working

    mode had set , it doesnt change by Tr and the default set temperature is 25 .

  • 7/22/2019 20115272209

    38/45

    25

    Tr

    21

    26 C

    mode

    Time on and time off

    When the time on or time off is used, the clock of remote controller shall be corresponding to the current clock and the

    timing times is less than or equal to 24 hours, when the timing time is reached, unit will start-up or shutdown.

    Sleep functionWhen the sleep key is press, air conditioner enter sleep state, indoor blower fan running at low speed, only sleepindication display.

    Emergency key function

    There is a forcible execution key on the panel of indoor units and the air conditioner can run by pressing the key when

    the remote control is out of work or missing.

    When pressing down the forcible execution key, then power up and enter the self-check program.

  • 7/22/2019 20115272209

    39/45

    Failure display

    Display state

    LEDserial failure

    Running lamp Timer lampLCD

    Indoor unit

    1 Indoor TEMP. sensor failure Flash 1 time/8 SEC light E2

    2 Indoor coil pipe TEMP. sensor failure Flash 2 time/8 SEClight

    E3

    3 Overheat (frost) protection Flash 3 time/8 SEClight

    E8

    4 Pump failure Flash 4 time/8 SEClight

    E9

    5 Indoor blower fan failure Flash 6 time/8 SEClight

    E5

    6 Outdoor feedback failure Flash 7 time/8 SEClight

    E7

    7 Open door failurelight

    Flash 3 time/8 SEC E0

    8 Outdoor coil pipe TEMP. sensor failurelight

    Flash 4 time/8 SEC E1

    9 (EEPROM) communicate failurelight

    Flash 6 time/8 SEC E6

    Outdoor unit

    1 Outdoor TEMP. sensor failurelight

    Flash 1 time/8 SEC E2

    2 Outdoor coil pipe TEMP. sensor failurelight

    Flash 2 time/8 SEC E3

    3 Over current protect of compressorlight

    Flash 3 time/8 SEC E7

    4 TEMP. sensor of exhaust failurelight

    Flash 4 time/8 SEC E1

    5 Communicate failurelight

    Flash 6 time/8 SEC E6

    6 Module protectionlight

    Flash 7 time/8 SEC E5

  • 7/22/2019 20115272209

    40/45

    11 . TROUBLE SHOOTING

    Is CN (Tr sensor connector)

    connected properly?

    Is Tr sensor resistance value

    (5KO at 25? ) normal?

    Indoor P. C. board is defective. Replace P. C. board.

    Connect CN properly.

    Replace TA sensor.

    Is CN (TP1 sensor connector)

    connected properly?

    Is TP1 sensor resistance value

    (5KO at 25? ) normal?

    Indoor P. C. board is defective. Replace P. C. board.

    Connect CN properly.

    Replace TC sensor.

    YES

    YES

    YES

    YES

    NO

    NO

    NO

    NO

    Indoor Tr sensor

    error

    Indoor TP1 sensor

    error

  • 7/22/2019 20115272209

    41/45

    Turn off power

    supply once, andturn it on again.

    Does

    compressor

    continue to

    operate?

    Start to operate indoor

    unit in cooling

    operation at airflow

    level LOW,wait

    three minutes..

    Does indoor

    fan operate?

    Fan motor

    operatesnormally.

    Is it possible to detect AC

    220V between

    pin(high/middle/low) andpin(common) of motor

    connector .

    Replace indoor

    fan motor.

    Replace main

    P.C. board.

    Replace

    bearing.

    YES

    YES

    YES

    NO

    NO

    NO

    Turn off indoor unit and rotate

    cross-flow fan by hand when the

    unit is on standby.Is it possible to

    rotate cross-flow fan by hand

    properly?

    Only indoor fan motor does not operate.

    Is capacitor of indoor fan ok?

    YES

    NO

    YES

    Replace

    capacitor

    NO

    (1) Is it possible to detect the power supply voltage (200-240V) between L and N on the terminal

    block?

    (2) Does the indoor fan motor operate in cooling operation?

  • 7/22/2019 20115272209

    42/45

    Compressor does not operate.

    Turn on power supply.

    Does compressor delay

    three minutes by

    temperature changes or

    others?

    Does OPERATION

    indication indicate?

    Is it possible to detect AC

    220-240V on terminal

    block or contactor of

    compressor?

    Are all of compressor

    cords normal?

    Is compressor motor

    winding normal?(Check

    winding resistor.)

    Is capacitor for

    compressor normal?

    Is overload relay normal?

    Does compressor start?

    Does compressor stop

    after a while?

    Is gas quantity normal?

    (Check gas pressure.)

    Microcontroller is defective or

    miniature relay is defective..

    Is resistance value of room

    sensor (Tr) and heat exchanger

    sensor (TP1) normal?

    Room sensor or heat

    exchanger sensor is

    defective.

    Replace room sensor

    or heat exchanger

    sensor.

    Compressor is defective.

    Capacitor is defective.

    Overload relay is defective.

    Compressor is defective.

    Gas shortage (Gas leak)

    Compressor is defective.

    Replace P.C. board.

    Rewire or replace

    defective cords.

    Replace compressor.

    Replace capacitor.

    Replace overload

    relay.

    Supply gas.

    Replace compressor.

    YES

    YES

    YES

    YES

    YES

    YES

    YES

    YES

    YES

    YES

    YES

    YES

    NO

    NO NO

    NO

    NO

    NO

    NO

    NO

    NO

    NO

    Check power supply.

    Replace compressor.

    Wait three minutes

    (1) Is the room temperature higher than the preset temperature in cooling operation?

    (2) Is the crossover cable connected properly?

  • 7/22/2019 20115272209

    43/45

    Replace

    P.C. board.

    Is receiver on

    indoor unit exposed

    to direct sunlight?

    Batteries are

    exhausted.

    Press START/STOP

    button.

    Is there any thyristor

    fluorescent light

    nearby?

    Does indoor unit

    operate when

    moving remote

    control near receiver

    or indoor unit?

    P.C. board isdefective.

    Is transmission

    mark indicated?

    Press RST button

    on remote control

    with tip of pencil.

    Press START/STOP

    button.

    Does radio sound is

    affected by remote

    control when a

    signal is transmitted

    at distance of 5 cm

    from radio?

    Does indoor unit

    start to operate by

    automatic restart

    function?

    Is transmission

    mark indicated?

    Does indoor unit

    beep and operate?

    Remote control is

    defective.

    Keep indoor unit

    away from

    thyristor

    fluorescent light.

    Avoid direct

    sunlight.

    Replace

    batteries.

    Normal

    operation

    Replace remote

    control.

    The unit does not beep at all.

    OPERATION indication on

    indoor unit is not indicated.

    NONO

    NONO

    NO

    NO

    NO

    YES

    YES

    YES

    YES

    YES

    YES

    YES

    YES

    NO

    YES

    YES

  • 7/22/2019 20115272209

    44/45

    Trouble

    Is the power

    applied to the unit?

    Check power supply mains or

    interconnection wires

    Is the power normal? check

    the voltage between L&N of

    terminal block

    Check the wiring of indoor and

    outdoor

    Press the power ON/OFF button

    of wire control or remote control

    YES

    YES

    NO

    NO

    Does the beeperbeep?

    Is the display all

    off?

    Check the connector on display

    PCB connected to control PCB

    Check the display PCB itself

    Is the unit display

    normal?

    Does outdoor unit run?

    Does the

    compressor run

    normally?

    Check the failure code

    according to the failure

    table

    Normal

    Check the

    compressor ,wires

    and its

    capacitor.

    YES

    YES

    YES

    YES

    YES

    YES

    NO

    NO

    NO

    Does the control

    ok?

    Does the control

    PCB ok?

    Control failure

    Control PCB failure

    NO

    NO

    YES

    NO

    Trouble shooting

    NO

    Does the indoorunit run?

  • 7/22/2019 20115272209

    45/45

    Indoor unit and outdoor unit dont operate

    Indoor and outdoor unit

    dont operate

    Press emergency key, does

    the air conditionerrunning?

    Replace fuse of

    indoor PCB.

    YES

    YES

    YES

    NO

    NO

    NO

    NO

    Make the power

    supply ok.

    Replace remote

    control.

    YES

    NO

    Replace remote

    receiver or displaypanel.

    NO

    YES

    YES

    Replace transformer.Does the transformer has

    output?

    Does the fuse of indoor

    PCB burn out?

    Change a good remote,

    does the air conditioner

    running?

    Is the power supply no

    problem?

    Does the 12V and 5V of

    indoor PCB have?Replace PCB.

    normal

    Does the electric switch

    cut off?

    Does the electric switch

    cut off after a few

    nimutes?

    Is the wires of indoor

    unit and outdoor unit no

    problem?

    YES

    Reconnect the wires.NO

    Is the insulationof

    indoor unit and outdoorunit no problem?

    YES

    Find the reason and

    replace the failurecomponet.

    NO

    Is the resistanceof each

    main component no

    problem?

    Rreplace the failure

    componet.

    NO

    YES

    YES

    YES