AE1307

Embed Size (px)

Citation preview

  • 7/28/2019 AE1307

    1/2

    1 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1307 R1

    Application Engineering

    B U L L E T I N

    New hermetic compressors and condensing unitshave been developed utilizing R-404A/507 refrigerantssuitable for Low Temperature applications. It must benoted, however, that under low evaporating temperatureconditions, the operating envelope for these models willbe restricted especially in comparison to semi-hermeticcompressors typically used in similar applications.The operating envelope and restrictions are shown in

    Figure 1.

    For a given saturated suction temperature, themaximum condensing temperature, the maximumreturn gas temperature, and the maximum dischargeline temperature as outlined in Figure 1must not beexceeded! Operation beyond these limits will causehigh compression ratios and/or excessive internalcompressor temperatures resulting in overheatingconnecting rod wear and premature compressor failure.

    If the system design is such that operation within theseguidelines cannot be guaranteed, then the followingadditional controls must be added:

    1. Discharge Line Thermostat: Located 6 inchesform the compressor and Set to cut-out thecompressor at 225F maximum

    2. Low Pressure Control: Set to cut-out at 7 psigminimum.

    Superheat Requirements

    In order to ensure that liquid refrigerant does not returnto compressor during the running cycle, attentionmust be given to maintaining proper superheat atthe compressor suction inlet. Emerson ClimateTechnologies recommends a minimum of 20Fsuperheat, measured on the suction line 6 inches fromthe suction inlet, to prevent refrigerant floodback.

    Another method to determine if liquid is coming back tothe compressor is to accurately measure the differencein temperature between the compressor lower shellopposite the suction inlet and the suction line. If thisdelta can be kept at a minimum of 50F, no liquid willbe present in the crankcase.

    Suction Accumulator Requirements

    Through our development testing we have found thecombination of HFC refrigerants and polyol ester oildevelop very high cylinder pressures during floodedstart conditions. As a result of this testing, we have setthe maximum charge limit to be 6 lbs.

    Any system that exceeds the charge limit will require

    a suction accumulator and/or pumpdown cycle. Thepurpose of these precautions is to prevent damage to thecompressor due to continuous floodback and/orfloodedstart conditions. An accumulator is an effective measureagainst floodback and provides some protection againstflooded starts; however, the pumpdown cycle is the mostpositive means of preventing flooded start conditions.

    Crankcase Heater Requirements

    Crankcase heaters are recommended on all outdoorapplications or indoor applications if expected tooperate in ambients below 40F, orany system withan accumulator.

    LubricantsHFC refrigerants such as R-404A and R-507 requirepolyol ester lubricants to provide proper miscibility andlubricity. Emerson has approved only the followinglubricants at this time:

    Copeland Ultra 22CC Mobile EAL Arctic 22CC ICI Emkarate RL32CF Thermal Zone 22CC

    Should a system require the addition of lubricant forany reason, only the lubricants specified above shouldbe used.

    Practical Considerations

    The application restrictions imposed on these modelswill require careful system design. Some considerationsfor the designer are:

    1. Units operating at low evaporator temperatureswill be susceptible to overheating with dirtycondensers and/or restricted air flow. Large

    Application Guidelines forCF Refrigeration Compressors and Condensing Units

    AE4-1307 R1 February 2000Reformatted November 2010

    Application Engineering

    B U L L E T I N

  • 7/28/2019 AE1307

    2/2

    2 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1307 R1

    Application Engineering

    B U L L E T I N

    condensers (with low TDs) should be designedinto systems using these compressors andproper condenser coil maintenance isrequiredand regular cleaning practices should befollowed.

    2. Minimum suction line pressure drops willbe important to maintain Saturated SuctionTemperature limits at the compressor.

    3. Traditional superheat settings at the ThermalExpansion Valves may be too high to maintainthe return gas temperature limits specified.

    4. Suction lines should be well insulated.

    5. Suction line to liquid heat exchangers maynot be desirable if return gas temperaturesspecified are to be maintained.

    Figure 1

    60

    70

    80

    90

    100

    110

    120

    130

    140

    150

    -40 -30 -20 -10 0 10 20 30 40

    EVAPORATING TEMPERATURE (oF)

    CONDENSING

    TEMPERATURE

    (oF)

    CF Envelope

    Evap Temp Max Return Max Cond Max Disch

    (SST)*(F) Gas (F) Temp (F) Line (F)

    10 40 140 225

    5 40 140 225

    0 40 140 225

    -5 40 140 225

    -10 40 140 225

    -15 40 140 225

    -20 40 130 225-25 40 125 225

    -30 40 120 225