Determ Bias

  • Upload
    smart28

  • View
    234

  • Download
    0

Embed Size (px)

Citation preview

  • 7/30/2019 Determ Bias

    1/8

    904 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 18, NO. 2, MAY 2003

    Estimation of for Adaptive Frequency Bias Settingin Load Frequency Control

    Le-Ren Chang-Chien, Student Member, IEEE, Naeb-Boon Hoonchareon, Member, IEEE,Chee-Mun Ong, Senior Member, IEEE, and Robert A. Kramer

    AbstractUtilities in the U.S. use tie-line bias control to sharegenerationand frequency support in the interconnection. To ensurethat the reliability and the responsibility of frequency supportare maintained, NERC guidelines specify that the frequency biascoefficient

    1 0

    that a control area uses in its tie-line controlbe set as close as practical to the areas frequency responsecharacteristic . This paper presents an algorithm to estimate

    online using variables commonly available from existing AGCsystem. Results showing the algorithms performance in simulatedconditions and on actual field data are presented. Issues relatedto using the estimated in an adaptive frequency bias-settingcontrol are examined.

    Index TermsAdaptive frequency bias control, frequency re-sponse characteristic, tie-line bias control.

    I. INTRODUCTION

    MOST utilities in the U.S. still operate with a conventional

    load frequency control (LFC) that is based on tie-line

    bias control. The fast-acting governor on a regulating unit

    serves as the primary control in load-generation balance, sup-

    plemented by a higher level, slow-acting automatic generation

    control (AGC), whose other functions are to ensure the area

    absorbs its own load change, and to maintain net interchange

    and frequency at their schedule values.

    The conventional wisdom in tie-line bias control is to use thefrequency bias coefficient, , to offset the areas frequency

    response characteristic, . Supposedly, with , the

    area control error (ACE) would only react to internal distur-

    bances [2], [3]. Unnecessary AGC action to external distur-

    bances not only results in extraneous regulation effort but also

    inter-area tie-flow oscillations. When matches of the

    control area, unnecessary control actions could be reduced and

    the control becomes more efficient [3]. NERCs Policy 1 rec-

    ommends that a control area sets its frequency bias coefficient

    as close as practical to the areas frequency response

    characteristic [4].

    Presently , which is not easily obtained on a real time basis,

    is approximated [1]. The object of getting a good estimate of the

    areas to improve the load-frequency control performance has

    motivated this work on estimation.

    Manuscript received October 15, 2002.L.-R. Chang-Chien andC.-M. Ongare with theSchool ofElectricaland Com-

    puter Engineering, Purdue University, West Lafayette, IN 47907 USA.N.-B. Hoonchareon is with the Department of Electrical Engineering, Chula-

    longkorn University, Ba ngkok, 10330, Thailand.R. A. Kramer is with NiSource Energy Technologies, Merrillville, IN 46410

    USA.Digital Object Identifier 10.1109/TPWRS.2003.810996

    The proposed estimation algorithm is based on the ACE

    model given in [5]. When implemented online, the algorithm

    can provide estimates of the areas in real-time. Since

    the estimation scheme uses commonly available variables in

    existing AGC system, it does not require additional SCADA

    measurements.

    In this paper, we first present an online estimation method

    for determining the of a control area. Following which, we

    examine some practical issues of implementing the algorithm

    and how should be set relative to the estimated for ac-

    ceptable control areas response to tie-line bias control. Resultsshowing the performance of the estimation algorithm on simu-

    lated condition and on actual field data are presented.

    II. MATHEMATICAL MODEL FOR ESTIMATION

    The per unit equation of the electromechanical power balance

    for the local control area may be expressed as

    pu (1)

    where and are the total generation excluding units pri-

    mary control effort and total demand within the local control

    area in per unit, respectively. is defined as the net tie flow

    from the local to the external areas in per unit; is the areasfrequency response characteristic in per unit.

    As the actual response of regulating units to the LFC

    controller depends on the status of the equipment and their

    operating constraints, the actual may not track the desired

    generation command. A slack term is introduced in

    the model to account for the difference between desired and

    actual generation

    pu (2)

    where and are the regulation and basepoint com-

    ponents in per unit, respectively. Note that includes the

    scheduled tie flows.

    In many of the ACE controllers, the regulating component,, in (2) is expressed as a proportional-integral function

    of the filtered ACE

    pu (3)

    Replacing in (2) by (3) and substituting in (1)

    with (2), we obtain

    pu (4)

    0885-8950/03$17.00 2003 IEEE

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 7/30/2019 Determ Bias

    2/8

  • 7/30/2019 Determ Bias

    3/8

    906 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 18, NO. 2, MAY 2003

    Fig. 2. Sensitivity of to local areas bias setting B .

    C. Effect of Nonlinearities on Estimate

    Within the LFC loop are many nonlinearities, some of whichcan affect the value of . Here, we will examine the impacts of

    the following nonlinearities on control areas .

    5 MW ACE deadband in the AGC control logic of the

    five control areas;

    30-MHz speed governor deadband on all online units;

    rate and range limits apply on units under regulation con-

    trol in local control area

    The dynamic 30-MHz governor deadband is implemented in

    the simulation using a backlash function given in reference [7].

    Units rate and range limits are included in the model of the

    governor and prime mover as described in [8]. The result of esti-

    mating for the same inputs and interval as those used in Fig. 1

    but with the above nonlinearities included is given in Fig. 3.With nonlinearities, the estimated islower than the cal-

    culated using a value of computed from the dc loop gains

    in (10).

    It is known that the effective speed droop in transient

    operation with governor backlash can be less than the speed

    droop based on steady-state dc gains [6]. Changes in effective

    speed droop is most noticeable in hydraulic units, followed by

    reheat units, and is the least in nonreheat units. The effective

    speed droop with or without nonlinearities for all the units in

    the local area over the simulation run may be determined from

    the dotted-line major axes of the versus trajectories in

    Fig. 4. Superimposed on the trajectories, are solid lines which

    represent equivalent steady-state or dc droop characteristics ofthe online governors in the whole control area computed from

    MW/Hz (11)

    where the summation is over all regulating units in the control

    area and is the speed droop of the th unit. For a unit with

    5% regulation

    rating of th unit (MW)Hz/MW (12)

    The dashed line, with slope , is the first order approximation

    of the major axis for the elliptical envelope containing the tra-

    Fig. 3. and with nonlinearities.

    Fig. 4. Effective governing characteristics of local area.

    jectories of the governor response with deadband and rate limits.

    With nonlinearities, the slope of is steeper than that of .

    Thus, the effective gain of governor control loop, , is less

    than that of its dc loop gain, . Much of this difference

    between and may be traced to the governors dead-

    band. When the frequency deviation is within the governors

    deadband, the governors response is inhibited. The higher ef-

    fective slope with deadband is also collaborated by the steep ini-

    tial slope of the System Response Characteristic (SRC) curve at

    low frequency deviation given in [3], [9]. For larger frequency

    excursions outside the deadband of the governors, the dash-line

    in Fig. 4 will be rotated counter clockwise. In other words, the

    effective slope will decrease further, as is evident by the flat-

    tening of the SRC at higher frequency deviation.

    Thus, the estimated in Fig. 3 is less than because of

    the effective droop, , with deadband nonlinearities is higher

    than the dc droop, .

    IV. PERFORMANCE OF ALGORITHM ON FIELD DATA

    The usefulness of the estimation algorithm can be deter-

    mined from its performance on actual field data taken from a

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 7/30/2019 Determ Bias

    4/8

    CHANG-CHIEN et al.: ESTIMATION OF FOR ADAPTIVE FREQUENCY BIAS SETTING IN LOAD FREQUENCY CONTROL 907

    Fig. 5. Estimated of utilitysystem between 19:0024:00 P.M. on 02/15/2001.

    utility company. A sample result from such a test is given in

    Fig. 5. The period between 19:00 and 22:00pm corresponded tothe on-peak hours when large loads were active. After 22:00pm,

    the areas demand went from high to low. This condition is re-

    flected by smaller variation in the estimated . The actual bias

    setting used by the utility for its tie-line bias control

    during the operating period was 600 MW/Hz.

    V. USING THE ESTIMATED FOR ADAPTIVE FREQUENCY BIAS

    CONTROL

    The ability to estimate online naturally raises the possi-

    bility of using the estimated value to adjust the value of

    to suit the prevailing system condition. For each control areain an interconnection, may be viewed as its share of in-

    ternal power imbalance to compensate for the deviation in fre-

    quency. When its frequency bias setting is set equal to its , that

    is , the control areas LFC would be responding to

    the appropriate internal power imbalance. When ,

    the control areas LFC not only compensate for the deviation in

    frequency but also assist other areas in frequency support. But

    when , the control areas LFC does not fully meet

    its share of frequency support even though the disturbance is

    external. The degree of supplementary control response and the

    amountof tie flow oscillationswill depend on the frequency bias

    setting in relation to its .

    The variable bias setting scheme described in [9], [10] usesa two-segment bias setting characteristic for different operating

    conditions. The nonlinear bias curve is kept between the SRC

    and horizontal axis in the vs. plane. In the assist mode,

    for the security of the interconnection, upon detecting a large

    frequency deviation, as in an emergency, a control area should

    use a larger bias value.

    In this section, we will explore how the frequency bias set-

    ting affects the AGC response and the tie flows oscillations to

    understand the dynamics and to establish some rationale for ad-

    justing .

    Fig. 6 shows the two-area system simulated to represent a

    local control area and its external equivalent. The capacity ratio

    Fig. 6. Model of internal and external areas.

    Fig. 7. Response to an external disturbance at t = 1 0 0 sec followed by a stepchange in 0 1 0 B after t = 3 0 0 s.

    of the external area to internal equivalent is arbitrarily set to

    6:1 for the base case. For clarity, the subscript will be used

    to denote variables of the local control area and subscript for

    those of the external area.

    A. Dynamics Introduced by a Change in

    Tests were first conducted to establish the response in fre-

    quency and tie flow to a change in frequency bias setting of

    the local areas LFC following a load disturbance applied tothe external area, with the LFC of the external area deactivated.

    Fig. 7 shows the changes in frequency response, , and tie

    flow, , when the of the local area was switched from

    to and 200 seconds after the change in external

    load. Following the disturbance applied at the 100th second, the

    response with is as expected from theory. When

    was subsequently raised to at the 300th second,

    there was an increased tie flow out to the external area accom-

    panied by a decrease in the frequency deviation. The changes

    in tie flow and frequency deviation were opposite when

    was lowered to at the 300th s, as indicated by the dotted

    traces.

    http://-/?-http://-/?-http://-/?-http://-/?-
  • 7/30/2019 Determ Bias

    5/8

    908 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 18, NO. 2, MAY 2003

    Fig. 8. Response plots for first three cases in Table I.

    B. Control Interaction

    Tests were also conducted to gauge the interaction between

    the two areas LFCs, as evident in , , , and .

    Throughout this second set of tests, the frequency bias setting

    of the external areas LFC is set equal to the external areas

    , when that of the local control areas LFC is varied. The

    disturbance is applied either inside or outside of the local control

    area.

    A sample of the kind of transient response is given in Fig. 8.

    It shows the , , and response to an internal

    step disturbance for the three values of given in the first

    half of Table I for AGC proportional and integral gains of 0.065.

    It is representative of the dynamic response obtained for the

    other cases in Tables I and II.

    A summary of the RMS errors of the four variables for a rel-

    atively high and a relatively low value of AGC gains about the

    nominal value is given in Tables IIII. Here, RMS error is de-fined as the root mean square (RMS) difference between mea-

    sured and steady state values over the observed time interval.

    The RMS errors in Table I for all four variables decrease with

    higher ratiofor a disturbance within the localcontrol

    area. Note also that the RMS errors of and with high

    AGC gains are lower than those obtained with lower AGC gains.

    Thus, a higher bias setting is beneficial in limiting the frequency

    deviation and tie-line oscillations when the load disturbance is

    inside the local control area.

    Tables II and III are for a load disturbance applied outside the

    local control area. For an external load disturbance, the RMS

    errors of and decrease with lower ratio in

    TABLE IRMS ERROR FOR STEP DISTURBANCE IN INTERNAL AREA GENERATING

    CAPACITY RATIO OF AREAS EXTERNAL:INTERNAL = 6:1

    TABLE IIRMS ERROR FOR STEP DISTURBANCE IN EXTERNAL AREA GENERATING

    CAPACITY RATIO OF AREAS, EXTERNAL:INTERNAL = 6:1

    TABLE IIIRMS ERROR FOR STEP DISTURBANCE IN EXTERNAL AREA GENERATING

    CAPACITY RATIO OF AREAS EXTERNAL:INTERNAL = 1:1

    high AGC gains. The benefit of using a is good for

    a limited period under the above condition.

    The above test results with different ratios and

    AGC gains indicate potential benefits in adjusting the frequency

    bias setting to suit different system conditions. For example,

    when a local area detects that a disturbance is inside the localcontrol area, the results in Table I show that temporarily raising

    its above would limit the frequency deviation and

    bring about faster frequency regulation without excessive oscil-

    lations in tie flow.

    When the disturbance is external, the results in Table II show

    that using a higher ratio of does not seem to have

    significant adverse impact in , , and when the

    size of the external area is six time larger than the local area.

    However, when the size of the internal area is comparable to

    that of the external area, the results in Table III show that there

    is advantage in reducing the frequency bias setting when the

    AGC gains are high for an external disturbance.

  • 7/30/2019 Determ Bias

    6/8

    http://-/?-http://-/?-
  • 7/30/2019 Determ Bias

    7/8

    910 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 18, NO. 2, MAY 2003

    Fig. 11. Trace of adaptive 0 1 0 B setting with respect to the trace of forthe local control area, concurrent external and internal load disturbances.

    are results from using the different fixed bias setting relative

    to . For purpose of comparison, the value of the

    (mean) is set at the mean value of the used by the

    logic throughout the simulation run.

    In Table IV, slightly smaller RMS values of and

    were obtained with compared to those with

    (mean), indicating that the adaptive bias logic yielded smaller

    oscillations in tie flow and local areas power output. In this

    case,using resultedin smalleroscillationsthanusing

    MW/Hz, which is larger than . Note also

    that the MW/Hz case gave smaller oscillations

    in tie flow and power generation than using , but has

    a larger frequency deviation.

    C. Case II: Internal Load Disturbance

    A second set of tests was conducted with a load disturbance

    applied inside the local control area. It can be seen from Table V

    that the RMS values of and with are still

    less than those with . The result of higher RMS

    values of and with MW/Hz, which

    is less than , confirms the previous observation that using a

    that is smaller than would result in larger tie flow

    and generating output oscillations when the load disturbance is

    internal.

    D. Case III: Simultaneous External and Internal Load

    Disturbances

    In practice, disturbances could simultaneously occur inside

    and outside the local control area. Although setting

    or MW/Hz in previous two cases gave less

    RMS error in and than using for external

    or internal load disturbance, the results for simultaneous internal

    and external disturbances could be different. The results with

    simultaneous external and internal load disturbances are given

    in Table VI. The RMS errors in and with

    are smaller than those using various settings.

    TABLE IVRMS ERRORS WITH DIFFERENT FREQUENCY BIAS SETTINGS FOR THE LOCAL

    CONTROL AREA, EXTERNAL LOAD DISTURBANCE

    TABLE VRMS ERROR WITH DIFFERENT FREQUENCY BIAS SETTINGS FOR THE LOCAL

    CONTROL AREA, INTERNAL LOAD DISTURBANCE

    TABLE VIRMS ERROR WITH DIFFERENT FREQUENCY BIAS SETTINGS FOR THE

    LOCAL CONTROL AREA, CONCURRENT EXTERNAL, AND INTERNALLOAD DISTURBANCES

    VII. CONCLUSION

    Our observations of tie-line bias control response behavior

    under different system conditions support NERCs recommen-

    dation to control areas to use a frequency bias setting close to

    . Since the of an area is a function of the effective speed

    droop, which in turn is dependent on the number and type of

    regulating units online and the nonlinearities present, its value

    will be time-varying.

    In this paper, we have presented a method to estimate the of

    a control area continually using inputs which are readily avail-

    able in most conventional automatic generation control using

    tie-line bias. Presented are test results on simulation and on fielddata indicating that the algorithm is performing as desired.

    Also presented in this paper are simulation and analytical

    results on the transient behavior of , and that

    suggest potential benefits of using a variable bias setting under

    certain operating conditions. Results fromour simulation studies

    of an adaptive frequency bias setting logic do confirm such

    benefits in reducing unit movements and tie flow oscillations.

    The estimation algorithm can be used in conjunction with

    the ACE model described in [5] to realize a model reference,

    adaptive bias setting control. We are currently working on the

    design of such an adaptive tie-line bias controller. Our plan is

    to implement the estimate algorithm online in the near future,

    http://-/?-http://-/?-
  • 7/30/2019 Determ Bias

    8/8

    CHANG-CHIEN et al.: ESTIMATION OF FOR ADAPTIVE FREQUENCY BIAS SETTING IN LOAD FREQUENCY CONTROL 911

    gather experience and data with it to help us design an adaptive

    bias control that will operate more efficiently under the new

    NERCs CPS1 and CPS2 criteria.

    ACKNOWLEDGMENT

    This work was performed under a research contract from

    NiSource Energy Technologies and the U.S. Department of

    Energy.

    REFERENCES

    [1] N. Jaleeli, L. S. VanSlyck, D. N. Ewart, L. H. Fink, and A. G. Hoffman,Understanding automatic generation control, IEEE Trans. PowerSyst., vol. 7, pp. 11061122, Aug. 1992.

    [2] N. Cohn, Control of Generation and Power Flow on InterconnectedPower Systems. New York: Wiley, 1966.

    [3] T. Kennedy, S. M. Hoyt, and C. F. Abell, Variable, nonlinear tie-linefrequency bias for interconnected system control, IEEE Trans. PowerSyst., vol. 3, pp. 12441253, Aug. 1988.

    [4] Policy 1 Generation Controland Performance, Version 1a, North Amer-ican Electric Reliability Council, 2000.

    [5] N.-B. Hoonchareon, C.-M. Ong, and R. A. Kramer, Feasibility of de-composing A C E to identify the impact of selected loads on CPS1 and

    CPS2, IEEE Trans. Power Syst., vol. 17, pp. 752756, Aug. 2002.[6] N.-B. Hoonchareon, Feasibility of Decomposing One-Minute Average

    Area Control Error for Apportioning Load-Frequency RegulationCosts, Ph.D. dissertation, Purdue University, West Lafayette, IN, 2000.

    [7] Dynamic modelsfor fossilfueled steam units in powersystem studies,IEEE Trans. Power Syst., vol. 6, pp. 753761, May 1991.

    [8] Dynamic models for steam and hydro turbines in power systemstudies, IEEE Trans. Power Apparat. Syst., vol. PAS-92, pp.19041915, Nov./Dec 1973.

    [9] L. S. VanSlyck, N. Jaleeli, and W. R. Kelly, Implication of frequencycontrol bias settings on interconnected system operation and inadvertentenergy accounting, IEEE Trans. Power Syst., vol. 4, pp. 712723, May1989.

    [10] N. Jaleeli and L. S. VanSlyck, Tie-line bias prioritized energy control,IEEE Trans. Power Syst., vol. 10, pp. 5159, Feb. 1995.

    [11] Chee-Mun Ong, Dynamic Simulation of Electric Machinery UsingMATLAB/SIMULINK. Englewood Cliffs, NJ: Prentice-Hall, 1998.

    [12] L.-R. Chang-Chien, An Automatic Generation Control With AdaptiveFrequency Bias Setting for Current NERC Performance Standard,Ph.D., Purdue University, West Lafayettte, IN, 2002.

    Le-Ren Chang-Chien (S00) received the B.S. degree in Engineering Sciencefrom National Cheng Kung University, Tainan, Taiwan, R.O.C., in 1993, theM.S.E.E. degree from the University of Wisconsin-Madison in 1998, and thePh.D. degree from Purdue University, West Lafayette, IN, in 2002.

    He joined the Department of Electrical Engineering at National Cheng KungUniversity, Tainan, Taiwan, R.O.C., as an Assistant Professor in 2003. His re-search interests include electric machines, power system operation, and control.

    Naeb-Boon Hoonchareon (M01) received the B.Eng.(Hons) degree in elec-trical engineering from Chulalongkorn University, Bangkok, Thailand, in 1993,the M.S.E.E. and Ph.D. degrees from Purdue University, West Lafayette, IN, in1996 and 2000, respectively.

    Currently, he is with the Department of Electrical Engineering, Chula-longkorn University in Bangkok, Thailand. He was a Post-Doctoral ResearchAssociate at Purdue University on the DOE/NIPSCo project. His researchinterests include interconnected power systems operation, modern automaticcontrol, and optimization.

    Chee-Mun Ong (SM80) received the B.E.(Hons) degree in electrical engi-neering from the University of Malaya in 1967, and the M.S. and Ph.D. degrees

    from Purdue University, West Lafayette, IN, in 1968 and 1974, respectively.During the periods, 19681973 and 19761978, he was a Lecturer in the Uni-versity of Malaya. In l969/70 he spent a year as an UNESCO Fellow with theCentral Electricity Generating Board and the English Electric in England. In1978 he joined the School of Electrical Engineering at Purdue University as anAssistant Professor and in 1985 became a Professor. His interests are in powersystems and electrical drives.

    Dr. Ong is a Fellow of the Institution of Electrical Engineers, and a registeredProfessional Engineer of Indiana.

    Robert A. Kramer received the M.S. and Ph.D. degrees in nuclear engineeringfrom Purdue University, West Lafayette, IN, and the B.S. and M.S. degrees inphysics, also from Purdue University.

    Currently, he is Vice-President and Chief Scientist of NiSource Energy Tech-

    nologies, Merrillville, IN. In this position, he is responsible for the introductionof new technology into the gas and electric functions of the utility as well asproviding support on various technical and competitive issues.