    The Application Of A Ct BasedDisinfection Policy To OptimiseDrinking Water Disinfection Costs

  • 7/31/2019 ECt Presentation

    2/18

    Subject Areas That Will Be CoveredIn This PresentationDevelopment of a Ct based drinking water disinfection policy

    Software tools developed to support the policy

    The principle of maintaining the desired Effective Ct regardless

    of the works flow

    The control philosophy to make the maintenance of the desiredEffective Ct automatic.

    The significant potential Opex cost savings

  • 7/31/2019 ECt Presentation

    3/18

    Development of Ct Disinfection Policy

    The Ct principle assumes that the Concentration (mg/l) multipliedby Time (min.) provides an indication of potential disinfectionefficiency.

    Factors that can have a significant effect on that efficiency, for

    chlorine, are:

    pH - Conc. of the Disinfectant

    Plug Flow Efficiency - Actual Retention Time

  • 7/31/2019 ECt Presentation

    4/18

    Development of Ct Disinfection Policy

    pH

    HOCl is the principal free chlorine speciesdisinfectant

    At pH 6.0 (15C) - HOCl - 97.73 %

    At pH 9.0 (15C) - HOCl - 4.13 %

    Fluid Dynamics Of Vessels

    Actual Retention Times (Q1) can be verydifferent than the Theoretical Retention Times

  • 7/31/2019 ECt Presentation

    5/18

    Development of Ct Disinfection Policy

    pH and Fluid Dynamics accommodated in new Drinking WaterDisinfection Policy

    Modified Ct known as Effective Ct (ECt)

    Minimum ECt selected 20 mg.min/l at maximum flow

    Minimum Effective Chlorine Conc. 0.3 mg/l

    Giardia Inactivation Table developed from an extensive literaturesearch

  • 7/31/2019 ECt Presentation

    6/18

    Development of Software Tools

    Tailored Questionnaire/Calculation Form

    Simplistic Fluid Dynamics Formula Derived

    Checked by Expert in Fluid Dynamics

    Satisfactory for application

    Spreadsheet

    Simplistic Fluid Dynamics Formula built in

    HOCl Percentage Reference Module added

    Conversion factors required prior to entry of certaindata

  • 7/31/2019 ECt Presentation

    7/18

    Development of Software Tools

    Database developed that would:

    Provide a user friendly GUI (graphical userinterface) input screens

    Provide a full mathematics capability running in

    the background

    Allow the direct input of the details of any type ofprocess vessel or pipe/channel

  • 7/31/2019 ECt Presentation

    8/18

    Development of Software Tools

    Database developed that would: (contd...)

    Allow the results of tracer studies or CFD studiesto be input and thus bypass the built in

    calculation.

    Produce summary sheets identical to thoseproduced by the spreadsheet.

    Hold records of all the benchmarking exercises thathad been carried out previously.

  • 7/31/2019 ECt Presentation

    9/18

    Potential For Operational Cost Savings

    ECt assessments normally carried out for maximum plantflows

    Works flows are rarely at maximum

    Thus ECt is frequently greater than assessed

    Inverse relationship between flow and retention time

    Direct relationship between flow and required chlorineresidual

  • 7/31/2019 ECt Presentation

    10/18

    Potential For Operational Cost Savings

    Assessment of potential savings:

    a) Benchmark the works at maximum flow

    b) Decide if the ECt is adequate/more thanadequate

    c) Re-benchmark the works at maximumflow adjusting the chlorine residuals to obtain thedesired ECt

    d) Benchmark the works at minimum flowplus 3 others

    e) Graph the results to obtain themathematical relationship betweenthe flow and the required chlorine residual

  • 7/31/2019 ECt Presentation

    11/18

    Potential For Operational Cost Savings

    0.45

    0.56

    0.67

    0.78

    0.9

    0.00

    0.05

    0.10

    0.15

    0.20

    0.25

    0.30

    0.35

    0.40

    0.45

    0.50

    0.55

    0.60

    0.65

    0.70

    0.75

    0.80

    0.85

    0.90

    0.95

    30

    32

    34

    36

    38

    40

    42

    44

    46

    48

    50

    52

    54

    56

    58

    60

    62

    ResidualChlorine-AsMeas

    ured(mg/l)

    Rate Of Flow (Mld)

    Relationship Between Chlorine Residual (mg/l) And Rate Of Flow To Maintain An Effective Ct Of

    Approx.30 mg.min/l

    The slope of the line is 0.45/30 = 0.015

    Thus for every Mld reduction in flow, through the plant, the

    residual can be reduced by 0.015 m g/l

  • 7/31/2019 ECt Presentation

    12/18

  • 7/31/2019 ECt Presentation

    13/18

    Potential For Operational Cost Savings

    Look up table useful only as a guide to demonstrate theprinciple

    Requires fully automatic system

    This can be achieved using:

    a modified cascade control system

    a modified secondary dose control loopwhere Mn removal is being practiced

  • 7/31/2019 ECt Presentation

    14/18

    Potential For Operational Cost Savings

    Chlorine Contact TankFlow Meter

    PID

    PID

    Multiplier

    Cl2 Dose Cl2 IT Cl2 IT

    Schematic Diagram Of A Normal Cascade Control System

  • 7/31/2019 ECt Presentation

    15/18

    Potential For Operational Cost Savings

    Chlorine Contact TankFlow Meter

    PID

    PID

    Multiplier

    Multiplier

    Cl2 Dose Cl2 IT Cl2 IT

    Schematic Diagram Of A Cascade Control System With

    Automatic ECt Control

  • 7/31/2019 ECt Presentation

    16/18

    Potential For Operational Cost Savings

    Schematic Diagram Of A Secondary Chlorine Dose ControlSystem With Automatic ECt Control

    Chlorine Contact TankFlow Meter

    PID

    Multiplier

    Multiplier

    Cl2 Dose Cl2 IT

  • 7/31/2019 ECt Presentation

    17/18

    Potential For Operational Cost Savings

    The situation for a works carrying out superchlorination issome what more complex

    The logic for every works needs to thought through carefully

    Criteria that need to be assessed include:

    Any manganese removal requirements

    Any distribution chlorine residual requirements

  • 7/31/2019 ECt Presentation

    18/18

    The Application Of A Ct Based

    Disinfection Policy To Optimise Drinking

    Water Disinfection Costs

    Thank you for your attention

    and are there any questions ?