Moeller FK4810-1143GB-INT
Contents
Introduction 0General
Type tested switchgear systems up to 4000 ADocumentation for xEnergy
1Introduction
TTA, Type test and regulations for building and testingSystem descriptionOverview of circuit-breakers up to 4000 A
Overview device installation, outgoer sections
Rear busbar up to4000 A 2
Incoming supplies, outgoers and couplings 800 to 4000 A forcircuit-breakers IZM and NZM4
OverviewSectionsInternal partitioning up to form 4bMounting kits
3
Outgoers up to 630 A for circuit-breakers NZM1 – 3
OverviewInstallable circuit-breakersMounting kitsDropper barsOutgoer sectionsInternal partitioning up to form 4b
4
Outgoers up to 630 A for SASIL fuse-switch units andSL fuse-load switch units
OverviewFitting kits for SASIL switch-fuse unitsOutgoer sections for SASIL switch-fuse unitsDropper bars for SASIL outgoer sectionsFitting kits for SL fuse-load switch unitsOutgoer sections for SL fuse-load switch unitsDropper bars for SL outgoer sections
5
General fittings for modular installation devices, power electronic components,compensation, etc.
OverviewFitting kit for service distribution boards, fast mounting and wiring system etc.SectionsMounting plate, reactive power compensation, corner sections, side-by-side mount frame
6Rear main busbar up to 4000 A
OverviewMounting kits
Top busbar up to3200 A 7
Incoming supplies and outgoers 800 to 3200 A for circuit-breakers IZM and NZM4OverviewSectionsMounting kitsInternal partitioning up to form 4b
8
Outgoers up to 630 A for circuit-breaker NZM1 – 3 and combined incomers up to1600 A for circuit-breaker NZM4
OverviewInstallable circuit-breakersMounting kitsOutgoer sectionsInternal partitioning up to form 4bDropper bars
9
General fittings for modular installation devices, power electronic components,compensation, etc.
OverviewFitting kit for service distribution boards, fast mounting and wiring system etc.SectionsMounting plate
10Top main busbars up to 3200 A
OverviewMounting kits
Appendix 11General accessories
Enclosure individual partsIndividual parts and material conform to assembly manual BA4810-0015
12Ordering information
Type keyOrdering examplesOrdering assistance SASIL/SL, Jean MüllerOrdering assistance reactive power compensation FRAK0
13Planning Information
14Technical data
15Dimensions
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 2/143
Moeller FK4810-1143GB-INT
G e n e r a l
Moeller FK4810-1143GB-INT
0/2 Type tested switchgear systems up to 4000 AConnect to the future. With xEnergy.
Smooth trouble-free processes at the Messe Basel
xEnergy, the new freely combinable system range on offer from Moellerstands for energy distribution – especially for building infrastructure up to4000 A. Moeller supplies an intelligent system platform from a single sourcefor the switchgear and protective devices which the panel builder canindividually engineer, quickly build – and which is easy in terms of handling.
The Moeller xEnergy system – which is comprised of switching andprotective devices, the installation system technology and the control panelincluding the planning and calculation tools – is ideally suited to the needsof safe energy distribution. xEnergy achieves a level of flexibility whichallows optimum usage resulting from its consequent implementation of acommon platform concept.
Individual projects – regardless of if they are in the area of functionalbuildings, office buildings or industrial building infrastructure – can be quicklyand efficiently implemented. Our customers not only save on time, money andspace; they also put their trust on the well tried and tested security fromMoeller.
The new xEnergy system range from Moeller forms a technical andeconomic unit comprised of switchgear and protective equipment, therespective installation system technology and the control panelcomponents. Low mounting time requirement and high levels of flexibilityare required for optimum mechanical adaptation of the control panelcomponents to the Moeller switchgear.
The type test of the complete units consisting of switchgear, installationsystem technology and control panel to IEC EN 60439 also ensure a highlevel of security. This modular system can be extended to cope withincreased demands within minutes.
Moeller is certified to DIN ISO 9001. You can rely on the type-testedproducts from Moeller. Moeller relies on a modular system with xEnergy,which is made up of made-to-measure type-tested function modulesconform to IEC/EN 60439. The system modules – available from Form 1 toForm 4 – are constructed to suit local installation habits (DIN VDE, CEI,
NF, UNE). Put briefly, Moeller has tested the respective degree ofprotection up to 4000 A for all relevant switchgear combinations.
The Moeller xEnergy system
Reliability, security and economic efficiency
Type tested quality
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 3/143
Moeller FK4810-1143GB-INT
G e n e r a l
0/3Type tested switchgear systems up to 4000 AConnect to the future. With xEnergy.
Moeller supplies the entire range as a flatpack, which is functionallypackaged in modules or supplied as a pre-assembled cabinet if requested bythe customer. Short delivery times are assured with xEnergy. In this way youare ready to go and can react in the shortest possible time – on request andto special customer demands:
– simple configuration and ordering using special tools which supportgeneration of parts lists.
– fast delivery ex-stock with lean logistics processes.– simple handling of the individual parts using practical standard packs.– safe and timesaving mounting using Moeller assembly instructions.– flexible sale of safety-tested low-voltage switchgear assemblies (TTA/
PTTA).
The xEnergy system range is optimised for installation of internationallyavailable Moeller switchgear and protective devices, and is rounded off bya range of configuration and planning tools from Moeller – a suitable powerdistribution tool for every project phase.
Get clever with tips and tricks used in practice. Moeller offers you technicalsupport and training for construction of the type-tested xEnergy switchgearsystem.
The opportunity to register for training can be found on the Internet at http:/
/www.moeller.net/de/company/training/training.jsp.Come and participate – you will be receiving tailor-made training for thedemands of the field; protect your investment and receive a certificate aftera test.
Furthermore, the Field Service is ready with useful tips and advice at +49(0)228 602 3640.
Do you still have questions about the product, the functionality or the rangeof uses?Simple mail us at [email protected] visit our website at www.moeller.net/xenergy
Simple, fast and flexible Service on request
Moeller provides you with efficienttools for system planning: from theplanning, to the preparation oftenders and quotations right up toordering.
You generate your documentationand the front view of the systemwith the order list.
Moeller supplies you with the entirerange as flat packs or as pre-assembled enclosures.
The detailed assembly instructionsprovide you with exact assemblydetails.
364.00
187.00
Int. part.2b,inc. WBG2 3p LD/X Moeller GmbH
W= 600mm
B 2+MPW-SP2I2306-L 182.00 364.00
OELLERMDate: 10.03.04
Description
Parts list total
SB46/ PL-33260(ME-04540)Drawing no. Order no.
Type
2000/5Acurr.trns.
5-p. set 2x120mm2 standard B
cable
324391Pos.100
Moeller GmbH 2
Manufacturer
+S5L2X120-BK 2006.001003.00
No. EUREUR
182.00
Cl.3,15VA,phase L1
RM Ritz
Messwandler
B
EUR 28719.20
4ASTW985-2000/5 169.00
Formular: total parts list from 5.11.2003,
676.00
B
Cl.3,15VA,phase L2
2000/5Acurr.trns.
Messwandler
R M R it z 2 1 69 .0 0ASTW985-2000/5
64.00Top plate LD1-3 sol id W= 600
D= 400
M oe ll er Gm bH B
338.00
2+MP-STEC1L0604 128.00
Inc/Outg.WIA,size2 2000A3p 4c
Cl.3,15VA,phase L3
2000/5Acurr.trns.
1.0xPEN
Moeller GmbH 2B
RM Ritz
+MPW-L2IA-20342 845.00
Messwandler
B
1690.00
Circuit-breaker 3p 2000A,size
2ASTW985-2000/5
Inc/Outg.WIB,size2 2000A3p 4c
1.0xPEN
169.00
M oe ll er Gm bH B
338.00
1
+MPW-SP2I2306
+MPW-L2IB-20342 1080.00
Page : 4 of 6
1080.00
2,wdr
M oe ll er Gm bH BIZMB2-V2000 3
Int. part.2b,inc. WBG2 3p cab.
W= 600mm
Moeller GmbH
9 35 4. 6 0 2 80 6 3. 8 0
B
+IZM-XA1(230AC/ Shunt re lease, 100% duty r .
220DC)
Moeller GmbH
2
B 1
Moeller/xEnergy Team/F-E 04/2004 BA 4810-Muster 1
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 4/143
Moeller FK4810-1143GB-INT
G e n e r a l
Moeller FK4810-1143GB-INT
0/4 Documentation for xEnergy
• Product manual
Contents– FK 4810-1143GB special catalogue
– Declaration of conformity– xEnergy and NZM product information– ZVEH guidelines– Confix software (Examples)– Presentations, training
• Technology package manual up to 2500 A, workshop
Contents– AWA assembly instructions– BA assembly manual up to 2500 A
• CD technology package
Contents– Product manual– Technology package manual up to 2500 A, workshop
Further documentation for xEnergy (on request)
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 5/143
1/1
Moeller FK4810-1143GB-INT
I n t r o d u c t i o n
TTA, Type test and regulations for building and testing
xEnergy sections are type-tested low-voltage switchgear combinationsTTA conform to IEC EN 60439-1. Type testing has been performed in acertified test laboratory.The sections – meeting the stipulations (relating to switchgear andxEnergy kits) in this catalogue – conform to the demands regarding thefollowing type tests:• short-circuit rating• temperature-rise limit• effectiveness of the protective conductor• air and creepage distances• insulation resistance• mechanical function• degree of protection
Deviations in the versions of the xEnergy sections in the following areaslead to an amendment of the properties of the type-tested sections:• components installed• dimensionsamendments in the following areas are not permissible:• short-circuit rating• heating• air and creepage distances• degree of protection• arcing chambers of the switchgear• etc.
The manufacturer of the xEnergy power distribution system is the panelbuilder according to the IEC/EN 60439-1 standard. During constructionand mounting of the power distribution system he must observe theassembly manuals (BA) and the installation instructions (AWA) supplied byMoeller the supplier. The power distribution system is to be implementedby the panel builder conform to the IEC/EN 60439-1 standard.
The details concerning current derating and short-circuit ratings must beurgently considered when designing and dimensioning the switchgearsystem.Refer to chapter 14
Routine tests for these areas are to be undertaken by the panel builder andare to be protocolled:• protection measures
• insulation• electrical function• wiring
No. Type of test Tests VDE 0660Part 500Section
Resulttested by
Tester
1 – Type test 8.2.1 –8.2.7
Test passed
2 P Mechanical function test(actuators, interlocks, etc.)
R o u t i n e
t e s t
8.3.1
3 S Component mounting to standard
4 S Correct cable routine
5 S/P Deg ree o f p ro tect io n o f the enc lo su re
6 S/P C learan ces, c reep ag e d is tances an d s pacing
7 P Connection between components, between conductors and betweenconductors and their devices(random testing of tightening torque's)
8.1 P/V Conformance of the wiring with the circuit documentation
8.2 V Conformance with:designations, markings, completeness of instruction leaflets etc.,with the circuit diagrams and other documentation
9 P Insulation test 8.3.2
10 S/ P Protective measures and earth continuity 8.3.3
11 P Electrical function test(when expressly specified)
8.3.1
Check list for TTA
for a low-voltage switchgear assembly toIEC/EN 60439-1, IEC/EN 60439-2 and IEC/EN 60439-3DIN VDE 0660, Part 500, 502 and 504
Special application conditions ................. .................................
Routine tests
Explanation of terms:
S = Visual inspection for compliance with requirementsP = Manual testing using mechanical or
electrical measuring equipmentV = Comparison with production specification
Customer:
Unit:
Order No.:
Date Signature (Head of the construction organizational unit)
Type test Regulations for building and tests
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 6/143
Moeller FK4810-1143GB-INT
I n t r o d u c t i o n
1/2 System description
Rear busbar up to 4000 A
xEnergy = devices + mounting systems + enclosure + technical support
XP power sections XF fixed mounted sections XG freely configurable sections
a page 2/1 a page 3/1 a page 4/1 a page 5/1
Product features Clear separation into functional areas from Form 1 up to Form 4b• Enclosure for side-by-side and individual mounting• Degree of protection1) IP31 or IP55• Main rear busbars up to 3200 A, 600 mm section depth or 4000 A, 800 mm section depth; 2 systems can be installed per section• TTA conform to IEC EN 60439-1• TN-C, TN-C-S, TN-S, TT, IT electrical grid types
• Incoming supply, outgoers orcouplings with circuit-breakers NZM4or IZM up to 4000 A
• Fixed mounted/withdrawable• 3 or 4-pole circuit-breakers• Cable or busbar trunking system
connection from top or bottom
• Outgoers with circuit-breakers PKZ,NZM up to 630 A
• Fixed mounted/withdrawable(630– 1600A)
• 3 or 4-pole circuit-breakers• Cable connection from top or bottom
• Outgoers with SASIL switch-fuseunits up to 630 A, removable, verticalor horizontal mounting
• Outgoers with SL fuse-load switchunits up to 630 A, fixed mounted,vertical installation
• 3-pole• Cable connection from top or bottom
• Mounting systems for rail-mountedservice installation devices
• Individual fixed mounting onmounting plated up to 630 A, e.g.soft starter, frequency inverter,reactive power compensation
• Automation engineering• xStart, control engineering, adapter
systems
Notes 1) The degree of protection of the fitted components – dependent on the specifications of the component catalogue – must beobserved.
Technical data Rear busbar up to 4000 ATop busbar up to 3200 A
Standards/regulations IEC/EN 60439-1
Ambient temperature °C 35 (24h mean value)
Relative humidity % 50 at 40 °C
Protection measures Protection class I, protective earth connection
Degree of protection1) IP31 and IP55
Rated insulation voltage Ui V 1000
Insulation coordination III/3
Rated operational voltage Ue V 690
Rated frequency Hz 40 – 60
Busbar rated current I e A up to 4000
Busbar rated short-time withstand current I cw kA up to 100 (1 s)
Busbar rated peak withstand current I pk kA up to 220
Dimensions mm height = 2000, depth = 400, 600 or 800
Sheet thickness' mm Door, frame = 2, back plates and enclosure side plate and top plates = 1.5
Metal surfaces Electrolytic galvanisation, powder-coated paint-finish
Colour RAL 7035, light grey
Lock mechanism Espagnolette lock with 2 or 4 point locking and 3 mm turn-lock, double-ward key
Installation site conditions Indoor installation
Notes 1) The degree of protection of the fitted components – dependent on the specifications ofthe component catalogue – must be observed.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 7/143
1/3
Moeller FK4810-1143GB-INT
I n t r o d u c t i o n
System description
Top busbar up to 3200 A
XP power sections XF fixed mounted sections XG freely configurable sections
a page 7/1 a page 8/1 a page 9/1
Product features• Clear separation into functional areas from Form 1 up to Form 4b• Enclosure for side-by-side and individual mounting• Degree of protection1) IP31 or IP55• Main top busbar up to 1600 A, 400 mm section depth or 1600 – 3200 A, 600 mm section depth• TTA conform to IEC EN 60439-1• TN-C, TN-C-S, TN-S, TT, IT electrical grid types
• Incoming supply or outgoers with NZM4 or IZMcircuit-breakers up to 3200 A
• Fixed mounted/withdrawable• 3 or 4-pole circuit-breakers• Cable or busbar trunking system connection from
bottom
• Outgoers with NZM circuit-breakers up to 630 A• Incoming supply or outgoers with NZM4 or IZM
circuit-breakers up to 1600 A• Fixed mounted/withdrawable (630 – 1600 A)• 3 or 4-pole circuit-breakers• Cable connection from bottom or rear
• Mounting systems for rail-mounted serviceinstallation devices
• Individual fixed mounting on MR25 mounting plateup to 630 A, e.g. soft starter, frequency inverter,reactive power compensation
• Automation engineering• xStart, control engineering, adapter systems
Notes 1) The degree of protection of the fitted components – dependent on the specifications oF the component catalogue – must be observed.
Components
Circuit-breakersNZM and IZMGST fuse switch-disconnectorsSL/SASIL switch-fuse units
xStart adapter systems MR25 mounting plate X pole installation outgoers
a HPL0211, Industrial Switchgearmain catalogue
a HPL0211, Industrial Switchgearmain catalogue
a HPL0214, Power Distribution Systemsmain catalogue
a HPL0211, Industrial Switchgearmain catalogue
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 8/143
Moeller FK4810-1143GB-INT
I n t r o d u c t i o n
1/4 System description
• Modular kit system for flexible and diverse system combinations• Individual or side-by-side mounted sections, expand as required• Type-tested range for assembly units with Moeller circuit-breakers guarantee the highest packing density and safety• Standardised assembly units for simple and timesaving mounting of Moeller switchgear• Internal partitioning up to form 4 enhances the safety when maintaining and operating the system• Plinth accessible from all sides simplifies transport and installation• Self-tapping screws support fast and safe earthing of the enclosure sections
Enclosure• Closed doors fulfil IP55 degree of protection as standard,• Door hinges possible on left and right or exchangeable. Few variants for diverse
applications.• Transparent design doors for a fast overview.• Large opening angle up to 180° for retention of free escape routes in narrow
control rooms.• Section height doors with Espagnolette lock and 4-point locking for simple
operation.
Mounting kits• Adjustable height mounting plates on a 17.5 mm grid enable perfect alignment
of the operating level of the Moeller circuit-breakers to a common level, withoutrequirement for other components.
• Pre-drilled mounting plates with all the required cut-outs for cable entries orconnection on rear of the Moeller circuit-breakers reduce the mounting times toa minimum.
• Cover plates bolted-on to both sides or on one side with hinges for improvedinstallation and maintenance accessibility.
• A maximum of 38 fixed installation modules, height 50 mm can be fitted into anIP55 outgoer section.
Busbars• Duplex copper profile rails for double side connection without drilling of cables
or busbars along the entire conductor length. High stability on a short-circuit.• Self-locking T-head bolt for fast and safe terminals.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 9/143
1/5
Moeller FK4810-1143GB-INT
I n t r o d u c t i o n
Overview of circuit-breakers up to 4000 A
Configuration Circuit-breaker I e up to I cc (400 V) upto
Installationtype
Connectionsystem1)
Pole / sectionwidth
Cable entry
A kA mm
Rear busbar area up to 3200 Aa section depth 600 mm, 4000 Aa section depth 800 mm
IZM..1-.. 1600 65 Fixed,drawer unit
KSD 3/425 Top/bottom
4/600
IZM..2-.. 2000 100 KSD 3/600
4/800
3200 KSY, KSD 3/600
4/800
IZM..3-.. 4000 KSY 3/800
4/1200
NZM4 1600 KSD 3/425
Fixed 4/425
Drawer unit 4/600
IZM..1-.. 1600 65 Fixed, drawerunit
KSD 3/425
4/600IZM..2-.. 2000 100 KSD 3/600
4/800
3200 KSY, KSD 3/600
4/800
IZM..3-.. 4000 KSY 3/800
4/1200
NZM4 1600 KSD 3/425
Fixed 4/425
Drawer unit 4/600
IZM..1-.. 1600 65 Fixed, drawerunit
3/425
4/600
IZM..2-.. 2000 100 3/600
4/8003200 3/600
4/800
IZM..3-.. 4000 3/800
4/1200
NZM4 1600 3/425
Fixed 4/425
Drawer unit 4/600
Top busbar area up to 1600 Aa section depth 400 mm, up to 3200 Aa section depth 600 mm
IZM..1-.. 1600 65 Fixed, drawerunit
KSD 3/425 Bottom
4/600
IZM..2-.. 2000 100 KSD 3/600
4/800
3200 KSY, KSD 3/600
4/800
NZM4 1600 3/400
Fixed KSD 4/425
Drawer unit 4/600
Notes 1) Connection of busbar trunking systems on request.Note: internal partitioning up to form 4b can be implemented.KSD = cable connection direct via clipsKSY = cable connection to section wide connection system
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 10/143
Moeller FK4810-1143GB-INT
I n t r o d u c t i o n
1/6 Device installation overview
Components/Systems Busbarposition
Degree ofprotectionIP
Internal parti-tioning
Poles Mounting Installationtype
Cable connec-tion
Operation Page
T o p
R e a r
3 1
5 5
F o r m
2 b
F o r m
3 b
F o r m
4
3 4 V e r t i c a l
H o r i z
o n t a l
F i x e d
P l u g
D r a w
e r u n i t
T o p
B o t t o
m
R e a r
F r o m
o u t s i d e
B e h i n
d d o o r
IZM...
Circuit-breakers up to 3200 A x x x x x x x x x x x x x x 2/6, 7/6
IZM...
Circuit-breakers 4000 A x x x x x x x x x x x x x 2/6
NZM4
Circuit-breakers up to 1600 A x x x x x x x x x x x x x (x) x 2/2, 2/7,7/2, 7/6,8/7
NZM1
Circuit-breakers up to 125 A x x x x x x x x x x x x x x x x 3/3, 3/4,8/3, 8/4
NZM2
Circuit-breakers up to 250 A x x x x x x x x x x x x x x x x x 3/3, 3/4,8/3, 8/4
NZM3
Circuit-breakers up to 630 A x x x x x x x x x x x x x x x x x 3/3, 3/4,8/3, 8/4
PKZM0
Circuit-breakers up to 25 A x x x x x x x x x x x x x x x 3/3, 3/4,8/3, 8/4
PKZ2
Circuit-breakers up to 40 A x x x x x x x x x x x x x x x x 3/3, 3/4,8/3, 8/4
PKZ4Circuit-breakers up to 63 A x x x x x x x x x x x x x x x 3/3, 3/4,8/3, 8/4
FAZ..
Miniature circuit-breaker ormodular installation devices
x x x x x x x x x x x x 3/5, 8/5
GS00 – 3
Fuse bases up to 630 A x x x x x x x x x x x 3/3, 3/4,8/3, 8/4
GSTA00-3
Fuse switch-disconnectors up to630 A
x x x x x x x x x x x 3/3, 3/4,8/3, 8/4
SL00 – 3
Fuse-load switch units up to630 A
x x x x x x x x x x 4/8
SASIL00-3
Switch-fuse units up to 630 A x x x x x x x x x x x x x 4/2, 4/4
Modular installation devices
x x x x x x x x x x 3/5, 8/5
X pole
Installation switchgear x x x x x x x x x x 3/5, 8/5
xStart
Modular, bus-capable motorstarters
x x x x x x x x x x 5/2, 8/2
MR25
Fast mounting system x x x x x x x x x 5/2, 8/2
Notes x(x)
= possible= optional
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 11/143
2/1
Moeller FK4810-1143GB-INT
I n c o m e r s ,
o u t g o
e r s ,
c o u p l i n g s
u p t o 4 0 0 0 A f o r I Z M / N Z M 4
Incomers, outgoers and couplings 800 to 4000 A for IZM/NZM4
Overview Page
1 Circuit-breakerfitting kits
2/6
2 Sections 2/2
3 Doors 2/3
4 Back plates 2/35 Protective cover plates 2/3
6 Top and bottom plates 2/3
7 Side walls 11/1
8 Plinths 11/1
– Cable anchoring rails 11/1
– Eyebolts 11/2
– Section connection kits 11/2
– Circuit diagram pockets 11/2
9 Lock mechanisms 11/2
– Supports 11/2
10 Internal partitioning 2/4
11 Rear mainbusbars
6/2
Catalogue
IZM circuit-breakers HPL0211,IndustrialSwitchgear maincatalogue
NZM4 circuit-breakers
7
10
10
4
2
1
9
16
2
8
3
10
5
6
10
11
• Frames: frame top and bottom incl. green design rail• Doors: incl. lock system for 3 mm double-ward key• Mounting kits: predrilled mounting plate for the circuit-breaker incl. all fixing
sundries, cover plates with cut-out for circuit-breakers IZM or for NZM4, incl. allfixing sundries
• Incoming supplies, outgoers or couplings, 3 or 4-pole, fixed mounted or drawerunits
• External operation, IP31 or IP55 degree of protection• IZM circuit-breaker up to I e = 4000 A and I cc = 100 kA (400 V AC)• NZM4 circuit-breaker up to I e = 1600 A and I cc = 100 kA (400 V AC)
• Cable or busbar trunking system connection from top or bottom
• See HPL0211 for IZM circuit-breaker and accessories, please order IZM chapterseparately. Order of the IZM-XRT door sealing frame and with IP55 IZM-XDTprotective cover always necessary.
• Details concerning the connection system and connections to the busbar systemfor circuit-breakers can be found in the BA4180-0015.
• Busbar system for 4000 A can only be installed in sections with 800 mm depth.• Current derating values for the defined rated currents are to be observed, see
chapter 14.• On all switchgear the use of additional fittings must be checked in accordance
with the catalogue or should be clarified with product support. Example: IZM1with mechanical interlock can only be fitted in a600 mm wide section (instead of 425 mm).
Basic features
Features
Notes for selection, engineering and construction
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 12/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 13/143
Moeller FK4810-1143GB-INT
u p t o 4 0 0 0 A f o r I Z M / N Z M 4
2/4 Internal partitioning up to form 2b for incoming supplies, outgoers and couplings800 A – 1600 A, rear busbars
Features:• Internal partitioning of
forms 2b• Degree of protection IP20
TypePartitions form 2b
TypeShroud
Section width Section depth Component mounting/busbar areas
Article no.
Cable connection area/ busbar area
Article no.
Component mountingarea / cable connectionarea / busbar area1)
Article no.
Coupling area(transparent)
Article no.
mm mm 1 off each 1 off each 1 off each 1 off each
Circuit-breakers
NZM4 425 600 XPBMB0604284107
XPNBCT0404285502
– XPC0604284115
600 600 XPBMB0606284108
XPNBCT0604285504
– XPC0606284116
425 800 XPBMB0604284107
XPNBCB0406285523
– XPC0604284115
600 800 XPBMB0606284108
XPNBCB0606285522
– XPC0606284116
Notes 1) Partition with circuit-breaker NZM4 already included as a fitting kit in the mounting plate.For couplings: use partitions for component mounting area / busbar area and component mounting / component mounting area top and bottom.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 14/143
2/5
Moeller FK4810-1143GB-INT
I n c o m e r s ,
o u t g o
e r s ,
c o u p l i n g s
u p t o 4 0 0 0 A f o r I Z M / N Z M 4
Notes
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 15/143
Moeller FK4810-1143GB-INT
u p t o 4 0 0 0 A f o r I Z M / N Z M 4
2/6 Internal partitioning for incoming supplies, outgoers and couplings 800 – 4000 Aup to form 4b
Features:• Rated current 800 – 4000 A• I cc (400 V AC) up to 100 kA• Fixed mounted or drawer units• 3 or 4-pole• External actuation• Module height 650 mm
I cc to(400 V AC)
I e up to Installation type Poles Section width TypeAssembly unit3)
Article no.
kA A mm 1 off each
Air circuit-breaker
IZMB(N)1-.. 65 800 – 1600 Fixed, drawer unit 3 425 XMI1304283955
4 600 XMI1406283964
Drawer unit1) 3 425 XMI1304-1285680
4 600 XMI1406-1
285681IZMB(N)1-..IZMB(N,H)2-..
65100
800 – 1600800 – 3200
Fixed, drawer unit 3 600 XMI2306283973
4 800 XMI2408283975
Drawer unit1) 3 600 XMI2306-1283974
4 800 XMI2408-1283976
IZMB(N)1-..IZMB(N,H)2-..IZMH3-..
65100100
800 – 1600800 – 320040002)
Fixed, drawer unit 3 800 XMI3308283977
4 1200 XMI3412283978
Notes 1) Only for cable or top busbar connection on top main busbar or cable and busbar connection
at bottom of main busbar: The door frontplate has been offset in the circuit-breaker area by approx. 50 mm.2) Can only be installed in 800 mm deep sections.3) The door seal IZM-XRT and for IP55 protective cover IZM-XDT are always additionally required.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 16/143
2/7
Moeller FK4810-1143GB-INT
I n c o m e r s ,
o u t g o
e r s ,
c o u p l i n g s
u p t o 4 0 0 0 A f o r I Z M / N Z M 4
Internal partitioning for incoming supplies, outgoers and couplings 800 – 4000 Aup to form 4b
Features:• Rated current 800 – 1600 A• I cc (400 V AC) up to 100 kA• Fixed mounted or drawer units
• 3 or 4-pole• External actuation• Module height 650 mm
I cc to(400 V AC)
I e up to Installation type Poles Section width TypeAssembly unitArticle no.
kA A mm 1 off each
Compact circuit-breaker
NZM4-.. 100 800 – 1600 Fixed 3 425 XMN4304284068
600 XMN4306292903
Drawer unit 3 425 XMN4304-1
284853600 XMN4306-1
292904
Drawer unit +remote operator
3 425 XMN4304-2290205
600 XMN4306-2292905
Fixed 4 425 XMN4404284077
600 XMN4406-1292906
Drawer unit 4 600 XMN4406284078
Drawer unit +remote operator
4 600 XMN4406-2290206
Circuit-breakers Installation Poles I e Connection barsCu cross-section andquantity
Current transformer type(MBS or Ritz)
Window size Currenttransformerwidth
A mm
Installable current transformers
IZM1... Fixedmounted/drawer unit
3-pole/4-pole
10001600
1x 60x 102x 60x 10
ASK63.4 60x 40 95
IZM2... 200025003200
1x 100x 102x 100x 102x 100x 10
KSO213 100x 55 129
IZM3... 4000 3x 120x 10 ASK127.6 72x 120 205
NZM4... 1600 2x 50x 10 ASK561.4ASK63.6
50x 30 – 1250 A60x 30 1600 A
8588
Notes Installation of the current transformer is implemented on circuit-breaker busbars to the cable connection system.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 17/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 18/143
Moeller FK4810-1143GB-INT
2/10
Moeller FK4810-1143GB-INT
Internal partitioning up to form 4b for incoming supplies, outgoers and couplings Internal partitioning up to form 4b f800 – 4000 A
Features:• Internal partitioning of forms 4b• Degree of protection IP20
TypePartitions form 4b1)
Section width Section depth Componentmounting/busbarareas
Article no.
Cable connection area /busbar area
Article no.
Cable concomponearea
Article no
mm mm 1 off each 1 off each 1 off each
Circuit-breakers
IZM.. 425 600 XPBMB0604284107
XPBCB0402284099
–
600 600 XPBMB0606284108
XPBCB0602284101
–
800 600 XPBMB0608284109
XPBCB0802284103
–
425 800 XPBMB0604284107
XPBCB0404284100
–
600 800 XPBMB0606284108
XPBCB0604284102
–
800 800 XPBMB0608284109
XPBCB0804284104
–
1200 800 XPBMB0612284110
XPBCB1204284106
–
NZM4 425 600 XPBMB0604284107
XPNBCB0402289174
XPNMCB0284174
600 600 XPBMB0606284108
XPNBCB0602289175
XPNMCB0284175
425 800 XPBMB0604284107
XPNBCB0404289176
XPNMCB0284174
600 800 XPBMB0606284108
XPNBCB0604289177
XPNMCB0284175
Notes 1) Additionally for form 4b, use partition2) Partition with circuit-breaker NZM4 al
For couplings with NZM4: use partitmounting area top and bottom.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 19/143
Moeller FK4810-1143GB-INT
u p t o 4 0 0 0 A f o r I Z M / N Z M 4
2/12 Notes
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 20/143
3/1
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
Outgoers up to 630 A for NZM1 – 3
Overview Page
1 Mounting plate forcircuit-breaker up to 630 A
3/3
– Mounting plate for emptysections etc.
3/6
2 Front surround for
circuit-breakers up to 630 A
3/3
3 Front surround for emptysections, meter installation, etc.
3/6
4 Sections 3/8
5 Doors 3/9
6 Back plates 3/9
7 Protective cover plates 3/9
8 Top and bottom plates 3/9
9 Side walls 11/1
10 Plinths 11/1
– Cable anchoring rails 11/1
– Eyebolts 11/2
– Section connection kits 11/2
– Circuit diagram pockets 11/211 Lock mechanisms 11/2
12 Internal partitioning 3/11
13 Dropper bars 3/12
14 Rear main busbar 6/2
Catalogue
PKZ circuit-breakers HPL0211,IndustrialSwitchgearmaincatalogue
NZM1, NZM2, NZM3circuit-breakers
2
12
12
12
12
10
12
8
4
6
14
9
11
3
8
7
5
13
1
• Frames: frame top and bottom incl. green design rail• Doors: incl. lock system for 3 mm double-ward key• Mounting plates for circuit-breakers: pre-drilled mounting plates with cut-out
for cable entries incl. all fixing sundries• Front surrounds for circuit-breaker: front surrounds with cut-out for circuit-
breakers incl. all fixing sundries and hinges
• Outgoers with PKZ, NZM1 – 3, 3-pole or 4-pole, fixed mounted, connectors forNZM2 or drawer units for NZM3
• External actuation, IP31 degree of protectionor actuation behind the door degree of protection IP55 (only with door)
• Circuit-breaker PKZ, NZM1 – 3 up to I e = 630 A and I cc = 100 kA (400 V AC)• Cable connection from top or bottom
• Details concerning wiring to the busbar system for circuit-breakers can be foundin the BA4180-015.
• Busbar system for 4000 A can only be installed in sections with 800 mm depth.• Current derating values for the defined rated currents are to be observed, see
chapter 14.• Engineer additional terminals if required for implementation of form 4b.• Cover plates can only be used in combination with fitting kit type XSMFDB... .• Mounting plates for NZM and PKZ devices are rated for mounting the basic
units. Fittings (e.g. auxiliary contacts) should be tested with regard to theirinstallation suitability using the dimensional drawings in chapter 15.
Basic features
Features
Notes for selection, engineering and construction
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 21/143
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
3/2 Outgoer sections: installable circuit-breakers and accessories
Side mounted accessories are not considered and must be separately tested for installation suitability.Installation of the drawer units is always relevant to the connected position, i.e. not disconnected.
Busbar position Rear
Form fitting kit 2b 4b
Section depth mm 600 800 600 800max. mounting depth in section mm 284 274
max. mounting depth up to cover plate mm – 205
Basic unit mounting depth + accessories mm
PKZM0 76 X X X X
+ current limiter 127 X X X X
PKZ2 134 X X X X
PKZ4 160 – 171 X X X X
NZM1 85 X X X X
+ rotary drive 148 X X X X
NZM2 149 X X X X
+ rotary drive 191 X X X X
+ remote operator 236 X X X X+ plug-in technology 236 X X X X
+ plug-in technology + rotary drive 279 X X – –
+ plug-in technology + remote operator 326 – X – –
NZM3 166 X X X X
+ rotary drive 229 X X X1) X1)
+ remote operator 271 X X X X
+ drawer units 271 X X – –
+ drawer units + rotary drive 334 – X – –
+ drawer units + remote operator 379 – X – –
NZM4 207 X X X X
+ rotary drive 264 X X X X
Notes 1) Can only be installed without front door.
X device can be fitted– device cannot be fitted
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 22/143
3/3
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
Mounting kits for horizontal installed compact circuit-breaker NZM1 – 3up to 630 A and PKZ... up to 63 A for outgoers
Features:• Rated current up to 630 A• I cc (400 V AC) up to 100 kA• Fixed mounted (plug-in or withdrawable unit)• 3 or 4-pole• External actuation or behind component area door• Horizontal installation
I e up to Installation type Poles Number ofswitches permodule
Moduleheight
Modulewidth
TypeMounting plate
Article no.
TypeFront surround1)
Article no.
A A mm mm 1 off each 1 off each
Circuit-breakers
Mounting kit for 3-pole circuit-breaker (installation of a switch insulating surround not possible.)
PKZM0 32 Fixed 3 1 50 425 XMP030204M284088
XMP030204C284087
600 XMP030206M284090
XMP030206C284089
PKZ2, PKZM4 63 100 4252) 6) XMP430404M284096
XMP430404C284095
6002) 6) XMP430406M284098
XMP430406C284097
NZM1 125 4254) XMN130404M283996
XMN130404C283995
600 XMN130406M283998
XMN130406C283997
NZM2, GSTA007) 250 Fixed 150 4254) XMN230604M284012
XMN230604C284011
600 XMN230606M284014
XMN230606C284013
Fixed+remoteoperator
150 600 XMN230606M284014
XMN230606CR292907
Plug-in 150 600 XMN230606MP284724
XMN230606C284013
NZM3, GSTA17)
630 Fixed8)
200 600 XMN330806M284038 XMN330806C284036
Fitting kit for 4-pole circuit-breaker(switch insulating surround NZM-XBR required for degree of protection and must be ordered separately.Installation of 3-pole circuit-breaker is possible.)
PKZ24 40 Fixed 4 1 100 4255) XMP430404M284096
XMP430404C284095
6005) XMP430406M284098
XMP430406C284097
NZM1 125 150 4254) XMN140604M284004
XMN140604C284003
600 XMN140606M284006
XMN140606C284005
NZM2 250 Fixed 200 4254) 3) XMN240804M284025
XMN240804C284024
600 XMN240806M284027
XMN240806C284026
Plug-in 200 600 XMN240806MP284726
XMN240806C284026
Fixed andfault-current trip4-pole NZM2-4-XFI...
200 600 XMN240806M284027
XMN240806CF284659
NZM3, GSTA27) 630 Fixed8) 250 600 XMN341006M284054
XMN341006C284052
Notes 1) Front surround can be attached with or without hinge.2) PKZ2 installation with R...-PKZ2 remote operator not possible.3) Installation of NZM2-4-XFI... fault current release not possible.4) Installation of covers for NZM...-...-XKSA connections not possible.5) PKZ24 installation with side mounted accessories not possible.6) PKZM4 installation with front standard auxiliary contact NHI-E-... not possible;
please use side mounted auxiliary contacts.7) Installation possible without front surround only.8) Drawer unit only possible with vertical installation.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 23/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 24/143
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
3/6 Accessories for fitting kits for outgoers
Covers1) for empty or reserved sections and installation of control circuit devices
TypeMounting platewithout apertures
TypeFront surround with-out cut-out
TypeVentilated frontsurround2)
TypeFront surround for control circuit deviceinstallation
Module height Module widthArticle no. Article no. Article no.
8x RMQ-TitanArticle no.
12x RMQ-TitanArticle no.
mm mm 1 off each 1 off each 1 off each 1 off each 1 off each
50 425 XME0204M283923
XME0204C283922
– – –
100 XME0404M283929
XME0404C283926
XME0404CV283928
XME0404CI283927
–
150 XME0604M284727
XME0604C283936
– – –
200 XME0804M283941
XME0804C283939
– – –
400 XME1604M283949
XME1604C283948
– – –
50 600 XME0206M283925
XME0206C283924
– – –
100 XME0406M283933
XME0406C283930
XME0406CV283932
– XME0406CI283931
150 XME0606M284728
XME0606C283936
– – –
200 XME0806M283945
XME0806C283942
– – –
400 XME1606M283951
XME1606C283950
– – –
Notes 1) Covers can only be combined in conjunction with fitting kit XSMFDB... .2) Surround in lowest installation position always required for sections with IP30/IP31 degree of protection
Covers1) for installation of meters
TypeFront surround for meter installation
Module height Module width 4 x 72 x 72 mm+ 1 changeoverArticle no.
2 x 72 x 72 mm+ 2 changeoversArticle no.
4 x 72 x 72 mm+ 1 changeoverArticle no.
2 x 72 x 72 mm+ 2 changeoversArticle no.
4 x 96 x 96 mm+ 1 changeoverArticle no.
2 x 96 x 96 mm+ 2 changeoverArticle no.
mm mm 1 off each 1 off each 1 off each 1 off each 1 off each 1 off each
150 425 – XME0604CM283935
– – – –
200 XME0804CM283940
– – – – –
150 600 – – XME0606CM4283938
– – –
– – – XME0606CM2238937
– –
200 600 – – – – XME0806CM4283944
–
– – – – – XME0806CM2283943
Notes 1) Covers can only be combined in conjunction with fitting kit XSMFDB... .
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 25/143
3/7
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
Accessories for fitting kits for outgoers
TypeCircuit-breaker cut-out cover (vertical installation) for empty compartment in the cover plate
NZM1 NZM2 NZM3
3-pole 4-pole 3-pole 4-pole 3-pole 4-pole
Article no. Article no. Article no. Article no. Article no. Article no.
1 off each 1 off each 1 off each 1 off each 1 off each 1 off each
XAS1-4284740
XAS1-4284740
XAS2-3284741
XAS2-4284742
XAS3-3284743
XAS3-4284744
TypeCable duct support for FAZ mounting kit, 425 mm wide
TypeCable duct support for FAZ mounting kit, 600 mm wide
Article no. Article no.
1 off each 1 off each
XADB04284710
XADB06284711
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 26/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 27/143
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
3/10 Outgoer sections for rear dropper bars
Features:• Section height 2000 mm• Degree of protection IP31 or
IP55• Protection class I• Opening angle
– 180° with separatemounting
– 170° with side-by-sideinstallation1)
• Exchangeable door hinges
TypeTop plate
TypeTop or bottom plate
Busbar I e
Section depth Section width IP31Canopy2) integrated
IP31/IP55solid
IP31/IP55for flanges3) Split4)
Article no. Article no. Article no. Article no.
A mm mm 1 off each 1 off each 1 off each 1 off each
Sections for rear dropper bar position (connection and dropperbar / component mounting area position interchangeable)
F 3200 600 600 XAD0606283488
XSPTC0606284305
XSPTF0606284320
XSPBM0606284290
800 XAD0806283811
XSPTC0806284308
XSPTF0806284323
XSPBM0806284293
800 XAD0806283811
XSPTC0806284308
XSPTF0806284323
XSPBM0806284293
1000 XAD1006283814
XSPTC1006284311
XSPTF1006284326
XSPBM1006284296
4000 800 600 XAD0608283489
XSPTC0608284306
XSPTF0608284321
XSPBM0608284291
800 XAD0808283812
XSPTC0808284309
XSPTF0808284324
XSPBM0808284294
800 XAD0808283812
XSPTC0808284309
XSPTF0808284324
XSPBM0808284294
1000 XAD1008283815
XSPTC1008284312
XSPTF1008284327
XSPBM1008284297
Notes 1) Order alternative hinge for 180° with side-by-side mounting, see page 11/22) Total height = section height 2000 mm + canopy 60 mm3) Flange F3A, see page 11/6
number of flanges per top plate, see section 154) With rubber seal; with cable entries for larger cable cross-sections, the degree of protection may need to be assured by additional
measures.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 28/143
3/11
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
Internal partitioning to form 4b for outgoer sections with rear dropper bars
Features:• Internal partitioning of
forms 2b or 4b• Degree of protection IP20
TypePartitions form 2b – partitions form 4b1)
Section depth Module width Coupling areawidth
Coupling / dropperbar area
Componentmounting area/componentmounting areahorizontal
Component mount-ing area/couplingarea 2)sealing strips
Cable connectionarea / busbar area
Article no. Article no. Article no. Article no.
mm mm mm every 1 set (= 2 off) 1 off each every 1 set (= 3 off) 1 off each
Sections for rear dropper bar position up to form 2b3)
actuation behind component mounting area door– – 200 – – – XPFCB02
284745
– – 400 – – – XPFCB04284119
600 – – XPFCD2006284132
– – –
800 – – XPFCD2008284133
– – –
Sections for rear dropper bar position up to form 4b3) actuation external via cover plate or behind additional componentmounting area door
– – 200 – – – XPFCB02284745
– – 400 – – – XPFCB04
284119– – – – XPFMC
284146
– 425 – – XPFMM04284147
– –
– 600 – – XPFMM06284148
– –
600 – – XPFCD2006284132
– – –
800 – – XPFCD2008284133
– – –
Notes 1) For form 4b an additional front surround is necessary2) Plastic, covers complete section height.3) Additional section/section partition XPSS... required a page 11/1
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 29/143
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
3/12 Dropper bars up to 1600 A for outgoer sections, fitting kit
Features:• 800 – 1600 A• TN-C, TN-C-S, TN-S,IT,TT• I cw (1 s) up to 50 kA1)
I e Busbar cross-section TypeBusbar bracket
TypeBracket for conductor in coupling area2)
L1, L2, L3, full N PE, PEN Modulewidth
4 or 5 conductorsystemL1, L2, L3, NArticle no.
Lower end bracket
Article no.
PE or PEN
Article no.
N + PE
Article no.
A mm2 mm2 mm 1 off each 1 off each 1 off each 1 off each
Side dropper bar, distance between busbar centres 60 mm
800 2 x 20 x 10 1 x 20 x 10 – XDSF08283888
XDSF08E283889
XDSFP283895
XDSFN283894
1250 2 x 40 x 10 1 x 40 x 10 – XDSF12283890
XDSF12E283891
XDSFP283895
XDSFN283894
1600 2 x 60 x 10 1 x 60 x 10 – XDSF16283892
XDSF16E283893
XDSFP283895
XDSFN283894
Rear dropper bar, distance between busbar centres 60 mm
800 2 x 20 x 10 1 x 20 x 10 425 XDSF08283888
XDSF08E283889
XDSFP283895
XDSFN283894
1250 2 x 40 x 10 1 x 40 x 10 425 XDSF12283890
XDSF12E283891
XDSFP283895
XDSFN283894
1600 2 x 60 x 10 1 x 60 x 10 425 XDSF16283892
XDSF16E283893
XDSFP283895
XDSFN283894
Module width TypeCross supports for XDSF...busbar bracket forrear dropper barsArticle no.
I e Busbar cross-section
TypeDuplex copper section busbarLength = 1800 mmArticle no.
mm 1 off each A mm2 1 off each
425 not required 1250 1 x 40x 30 XDP40X30283886
600 XDB06283885
1600 1 x 60x 30 XDP60X30283887
Notes 1) See chapter 14 for the short-circuit rating2) Can also be used for mounting of cable ducts, auxiliary circuit busbars etc.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 30/143
4/1
Moeller FK4810-1143GB-INT
O u t g o e r s w i t h f u s e s u p t o 6 3 0 A
f o r S A S I L a n d S L
Outgoers up to 630 A for SASIL fuse-switch units and SL fuse-load switch units
Overview Page
1 Mounting kit for SASIL switch-fuseunits – strips, plug-in, horizontalinstallation
4/2
– Mounting kit for SASIL switch-fuseunits – strips, plug-in, vertical
installation
4/4
– Mounting kit for SL fuse-load switchunits – strips, vertical fixed mounted
4/8
2 Sections 4/2, 4/8
3 Doors 4/2, 4/8
4 Back plates 4/2, 4/8
5 Protective cover plates 4/2, 4/8
6 Top and bottom plates 4/2, 4/8
7 Side walls 11/1
8 Plinths 11/1
– Cable anchoring rails 11/1
– Eyebolts 11/2
– Section connection kits 11/2
– Circuit diagram pockets 11/29 Lock mechanisms 11/2
10 Internal partitioning 4/3, 4/8
11 Dropper bars 4/6, 10
12 Rear main busbar 6/2
7
9
5
6
4
2
6
3
8
12
11
10
10
1
• Frames: frame top and bottom incl. green design rail
• Doors: incl. lock system for 3 mm double-ward key• SASIL or SL mounting kits: profiles and partitions for Form 2b (with the
exception of dropper bar covers with plug openings) incl. all fixing sundries• Dropper bar mounting kits: busbar bracket incl. all fixing sundries
• Outgoers with SASIL switch-fuse units up to 630 A, removable, vertical orhorizontal mounting
• Outgoers with SL fuse-load switch units up to 630 A, fixed mounted, verticalinstallation
• External actuation or behind door (SASIL vertical external only)• 3-pole• Cable connection from top or bottom
• SASIL and SL strip switch-fuse units as well as accessories such as guide rails,
dropper bar covers with plug openings, empty section covers etc, are to beordered separately using the manufacturers catalogue.
• Dropper bar covers with plug openings for SASIL strip switch-fuse units are alsoadditionally required for Form 2b.
• Details concerning mounting and the engineering design with dropper barsshould be taken from the assembly manual BA4810-015
• Busbar system for 4000 A can only be installed in sections with 800 mm depth.• Current derating values for the defined rated currents are to be observed, see
chapter 14.
Basic features
Features
Notes for selection, engineering and construction
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 31/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 32/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 33/143
Moeller FK4810-1143GB-INT
f o r S A S I L a n d S L
4/6 Dropper bars up to 1600 A for SASIL outgoer sections
Features:• 800 – 1600 A• TN-C, TN-C-S, TN-S, IT
I e Busbar cross-section TypeFitting kit dropperbar, 3-conductorL1, L2, L3
TypeBracket for conductor in couplingarea3)
L1, L2, L3, full N PE, PENArticle no.
PE or PENArticle no.
NArticle no.
A mm2 mm2 for 1 kit 1 off each 1 off each
Vertical dropper bar for horizontally installed SASIL switch-fuse unit strips, interval between phase centres 185 mm
800 1x 40x 10 1x 20x 10 XDSSV08283902
XDSFP283895
XDSFN283894
1000 1x 60x 10 1x 40x 10 XDSSV10283903
XDSFP283895
XDSFN283894
1250 1x 80x 10 1x 40x 10 XDSSV12283904
XDSFP283895
XDSFN283894
1600 1x 100x 10 1x 60x 10 XDSSV16283905
XDSFP283895
XDSFN283894
Horizontal dropper bar for vertically installed SASIL switch-fuse unit strips, interval between phase centres 185 mm
800 1x 40x 10(N = 1x 40x 10)2)
1x 20x 102) XDSSH08283896
XBSP283872
1)
1000 1x 60x 10(N = 2x 40x 10)2)
1x 40x 102) XDSSH10283897
XBSP283872
1)
1250 1x 80x 10(N = 2x 40x 10)2)
1x 40x 102) XDSSH12283898
XBSP283872
1)
1600 1x 100x 10(N = 2x 60x 10)2)
1x 60x 102) XDSSH16283899
XBSP283872
1)
Notes See chapter 14 for short-circuit rating1) Use a separate neutral pole XBSN... of the main busbar, see page 6/2.2) If necessary rate to required cross-section for N or PE, PEN of the main busbar.3) Can also be used for mounting of cable ducts, auxiliary circuit busbars etc.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 34/143
4/7
Moeller FK4810-1143GB-INT
O u t g o e r s w i t h f u s e s u p t o 6 3 0 A
f o r S A S I L a n d S L
Notes
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 35/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 36/143
Moeller FK4810-1143GB-INT
f o r S A S I L a n d S L
4/10 Dropper bars up to 1600 A for SL outgoer sections
Features:• TN-C, TN-C-S, TN-S,
IT
I e Busbar cross-section TypeFitting kitdropper bar,3-conductorL1, L2, L3
TypeBracket for conductor in couplingarea
L1, L2, L3, full N PE, PENArticle no.
PE or PENArticle no.
NArticle no.
A mm2 mm2 1 set 1 off 1 off
Vertical dropper bar for horizontally installed SL switch-fuse unit strips, interval between phase centres 185 mm
800 1x 40x 10
(N = 1x
40x
10)1)
1x 20x 101) contained in the
XSML... fitting kit
XBSP
283872
2)
1000 1x 60x 10(N = 2x 40x 10)1)
1x 40x 101) contained in theXSML... fitting kit
XBSP283872
2)
1250 1x 80x 10(N = 2x 40x 10)1)
1x 40x 101) contained in theXSML... fitting kit
XBSP283872
2)
1600 1x 100x 10(N = 2x 60x 10)1)
1x 60x 101) contained in theXSML... fitting kit
XBSP283872
2)
Notes See chapter 14 for short-circuit rating1) If necessary rate to required cross-section for N or PE, PEN of the main busbar.2) Use a separate neutral pole XBSN... of the main busbar, see page 6/2.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 37/143
5/1
Moeller FK4810-1143GB-INT
G e n e r a l f i t t i n g s
General fittings for modular installation devices, power electronic components,compensation, etc.
Overview Page
1 Fitting kit for lower adjustablemounting plate
5/2
2 Fitting kit for section heightmounting plate
5/2
– Fitting kit for MR25 5/2
– Fitting kit rail-mountedservice installation devices
5/2
3 Sections 5/2
4 Doors 5/3
5 Back plates 5/3
6 Protective cover plates 5/3
7 Top and bottom plates 5/3
8 Side walls 11/1
9 Plinths 11/1
– Cable anchoring rails 11/1
– Eyebolts 11/2
– Section connection kits 11/2
– Circuit diagram pockets 11/2
10 Lock mechanisms 11/2
– Internal partitioning 11/1
11 Rear main busbar 6/2
Catalogue
X pole xStart
HPL0211,IndustrialSwitchgear maincatalogue
MR25 rapid mounting system HPL0214, PowerDistributionSystems maincatalogue
10
4
1
2
8
3
7
5
6
7
9
4
11
• Frames: frame top and bottom incl. green design rail• Doors: incl. lock system for 3 mm double-ward key• Fitting kit for lower adjustable mounting plate: multifunctional walls incl. all
fixing sundries• Fitting kit for mounting plates on a single level: mounting plate incl. all fixing
sundries• Fitting kit MR25 rapid mounting system: profiles incl. all fixing sundries• Fitting kit modular installation device: support and insulating surround incl. all
fixing sundries
• Installation outgoers with X pole
• Individual fixed mounting on mounting plate up to 630 A, e.g. soft starter,frequency inverter, reactive power compensation
• Automation engineering• xStart, control engineering, adapter systems
• Details for cable connection to the busbar and mounting should be taken fromthe BA 4810-015 assembly manual.
• Please order 2x L section with b' = 1850 mm for MR 25 installation using theHPL0214 catalogue.
• Busbar system for 4000 A can only be installed in sections with 800 mm depth.• Permissible heat dissipation must be observed, see chapter 14
Basic features
Features
Notes for selection, engineering and construction
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 38/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 39/143
Moeller FK4810-1143GB-INT
G e n e r a l f i t t i n g s
5/4 Mounting plate for fitting kits XSMIB20 in sections for general fittings
Features:• Fittings up to 630 A• Fixed mounted• Depth can be adjusted• For top or bottom busbar position
TypeMounting plate
Width Height
Article no.
mm mm 1 off each
425 100 XME0404M283929
150 XME0604M284727
200 XME0804M283941
300 XME1204M285684
400 XME1604M283949
600 XME2404M285685
600 100 XME0406M283933
150 XME0606M284728
200 XME0806M283945
300 XME1206M
285686400 XME1606M
283951
600 XME2406M285687
800 100 XME0408M285689
150 XME0608M285690
200 XME0808M285691
300 XME1208M285692
400 XME1608M285693
600 XME2408M285694
1000 100 XME0410M285695
150 XME0610M285696
200 XME0810M285697
300 XME1210M285698
400 XME1610M285699
600 XME2410M285700
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 40/143
5/5
Moeller FK4810-1143GB-INT
G e n e r a l f i t t i n g s
Power factor correction
The supplier for power factor correction modules, regulator and fans isFRAKO. The expansion of the xEnergy sections is implemented on the basisof the range of offers and assembly instructions from FRAKO.
Address:FRAKO GmbH, Tscheulinstr. 21 A, D-79331 Teningen, GermanyTel. +49 (0)7641-453-0, Fax. +49 (0)7641-453-535
Reactive power compensation engineering notes:• Installation of 500 kvar is only possible with direct connection to the main
busbar.• The cable connection of the reactive power compensation section can have a
max. of 400 kvar installed.• If a disconnector or an upstream fuse is installed, the reactive compensation
power must be limited to 300 kvar (applies for sections with and without mainbusbars).
Engineering notes concerning section design:– XSFH20 vertical profiles and XSFB08... frames, e.g. select from the sections for
general fittings; accessories as required.– For sections without busbar or with top busbar a profile fitting kit is not required.
Reactive power in kvar Section
Degree of protection IP31 Degree of protection IP54/55
with canopy with closed top plate and topmounted fan with door mounted fan Version Dimensions
non-choked choked1)
5.67 %; 7 %; 8 %non-choked choked1)
5.67 %; 7 %; 8 %non-choked Height x width x depth
kvar kvar kvar kvar kvar mm
400 400 – 400 200 – 400 without main busbar 2000 x 600 x 600 / 8002000 x 800 x 600 / 800
400 500 500 400 200 – 400 with rear main busbar 2000 x 8002) x 600 / 800
400 400 – 300 200 – 300 with top main busbar 2000 x 600 x 6002000 x 800 x 600
1) Choked, 13.5 % on request.2) If a busbar transport split is necessary on the right hand side, a 75 mm wide side-by-side mount frame type XSAF2001... must be used,
to guarantee access.
FRAKOversion
Resonancefrequency
Choke degree For power networkswith electricity supplycompany audiofrequency3)
-P8 177 Hz p = 8 % f 217 Hz
-P7 189 Hz p = 7 % f 228 Hz
-P5 210 Hz p = 5.67 % f 270 Hz3) Divergent electricity supply company stipulations must be observed.
Mounting kits Part no.
Article no.
1 off each
Profile for reactive power compensationinstallation
• only necessary with rear busbars• 2 off required per section
XSMPB20288997
Busbar area partition rear/component mountingarea
• only for sections with rear busbars• for internal partitioning to form 2b
XPBM2008288998
• Required for degree of protection IP31:– Door, ventilated XSDML(R)V20...– Back plate, ventilated XSWV20...
– Top plate without apertures XSPTC... with top mounted fans– Canopy XAD... with 400 kvar non-choked without fan– Bottom plate without apertures XSPBM...– Partition section/section XPSS..., required on both ends to the neighbouring
sections with reactive power compensation sections with fans on both ends (notrequired if enclosure side plate or partition section/section is already available inthe neighbouring section).
– Enclosure side plate XAW.. if required.
• Required for degree of protection IP55– Door without apertures XSDMC20...– Back plate without apertures XSWC20...
– Top plate without apertures XSPTC...– Bottom plate without apertures XSPBM...– Partition section/section XPSS..., required on both ends to the neighbouring
sections (not required if enclosure side plate or partition section/section is alreadyavailable in the neighbouring section).
– Enclosure side plate XAW.. if required.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 41/143
Moeller FK4810-1143GB-INT
G e n e r a l f i t t i n g s
5/6 Corner sections for rear busbars
Features:• Section height 2000 mm• Degree of protection IP55• Protection class I• incl. back plate and top plate
TypeCorner section1)
TypePlinths
TypeBottom plate
Cornersection forsectiondepth
Busbar I e
Section depth Section width 100 mm high 200 mm high IP55
Article no. Article no. Article no. Article no.
mm A mm mm 1 off each 1 off each 1 off each 1 off each
600 F 3200 650 650 XSC200606286388
XAP010606C288868
XAP020606C288890
XSPBC0606C288995
800 4000 850 850 XSC200808288867 XAP010808C288869 XAP020808C288892 XSPBC0808C288996
Notes Four cross profiles XSFS06 or XSFS08 (instead of XBBB...) per section and at least 4 busbar supports XBSB... are required.Corner sections are not available as flatpack kits, they are always supplied fully assembled.1) The corner section for 600 mm section depth can also be used as a top busbar.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 42/143
5/7
Moeller FK4810-1143GB-INT
G e n e r a l f i t t i n g s
Side-by-side mount frame for rear busbars
Features:• Section height 2000 mm• Degree of protection IP55• Protection class I• incl. back plate, bottom plate and
top plate
TypeSide-by-sidemount frame
TypePlinths
TypeSide plate forside-by-sidemount frame
Frame for sectiondepth
Busbar I e
Section depth Frame width
Article no.
100 mm high
Article no.
200 mm high
Article no. Article no.
mm A mm mm 1 off each 1 off each 1 off each 1 off each
For access to the busbar transport split
600 F 3200 600 75 XSAF200106289908
XAP0101AF289950
XAP0201AF289951
XAW2006AF292908
800 4000 800 75 XSAF200108289909
XAP0101AF289950
XAP0201AF289951
XAW2008AF292909
Notes With a transport split between the following sections, use of a side-by-side mount frameis absolutely necessary:– XP sections in 425 mm width with installation of circuit-breaker IZM frame size 1– XG sections with complete expansion with reactive power compensation modules
– With all other sections where device installation limits access,e.g. if mounting plates of the empty modules in the XP sections in the transport split areaare fully occupied.
The side-by-side mount frame is fitted to the right section side,the section width and length of the busbars to be fitted are thus extended by 75 mm.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 43/143
Moeller FK4810-1143GB-INT
G e n e r a l f i t t i n g s
5/8 Notes
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 44/143
6/1
Moeller FK4810-1143GB-INT
R e a r m a i n b u s b a
r u p t o 4 0 0 0 A
Rear main busbar up to 4000 A
Overview Page
1 Busbar bracket 6/2
2 PE or PEN bracket 6/2
3 Cross support 6/2
1
2
3
• Busbar bracket: busbar bracket incl. all fixing sundries• PE or PEN bracket: retaining bracket incl. all fixing sundries• Cross support: support profile incl. all fixing sundries
• Rated current I e up to 4000 A• Rated short-time withstand current I cw (1s) up to 100 kA• Rated peak withstand current I pk up to 220 kA• 2 busbar system per section can be installed
• Details concerning the engineering design of the busbar system and thetransport split should be taken from the assembly manual BA4810-015
• Busbar system up to 3200 A installable in 600 mm deep sections, installable for4000 A only in 800 mm deep sections.
• Current derating values for the defined rated currents are to be observed, seechapter 14.
• Maximum clearance of the busbar supports should be determined conform tothe required short-circuit rating, see chapter 14.
Basic features
Features
Notes for selection, engineering and construction
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 45/143
Moeller FK4810-1143GB-INT
R e a r m a i n b u s b a
r u p t o 4 0 0 0 A
6/2 Rear main busbar up to 4000 AMounting kits
Features:• 1600 – 4000 A• TN-C, TN-C-S, TN-S, IT• I cw (1 s) up to 100 kA
I e Busbar cross-section min. sectiondepth
TypeBusbar bracket
TypeBracket1)
L1, L2, L3, full N PE, PEN 3-conductorL1, L2, L3Article no.
4-conductorL1, L2, L3, NArticle no.
PE or PENArticle no.
N
Article no.
A mm2 mm2 mm 1 off each 1 off each 1 off each 1 off each
1600 2x 40x 10 1x 40x 10 600 XBSB163283864
XBSB164283865
XBSP283872
XBSN16284747
2000 2x 60x 10 1x 60x 10 600 XBSB203283866
XBSB204283867
XBSP283872
XBSN20284748
2500 2x 80x 10 1x 80x 10 600 XBSB253285515
XBSB254285516
XBSP283872
XBSN40284750
3200 3 x 80x 10 1x 100x 10 600 XBSB323283868
XBSB324283869
XBSP283872
XBSN32284749
4000 3x 80x 10 2x 80x 10 800 XBSB403283870
XBSB404283871
XBSP283872
XBSN40284750
Notes 1) 2 off required per section
Sectionwidth
TypeCross support1) forbusbar bracket
Article no.
mm 1 off each
425 XBBB04283859
600 XBBB06283860
800 XBBB08283861
1000 XBBB10283862
1200 XBBB12283863
Notes 1) Per busbar and section 2off required.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 46/143
7/1
Moeller FK4810-1143GB-INT
I n c o m i n g s u p p l i e s a n d o u t g o e r s
u p t o 3 2 0 0 A
Incoming supplies and outgoers 800 to 3200 A for IZM/NZM4
Overview Page
1 Circuit-breaker fitting kits 7/6
2 Sections 7/2
3 Doors 7/3
4 Back plates 7/3
5 Protective cover plates 7/36 Top and bottom plates 7/3
7 Side walls 11/1
8 Plinths 11/1
– Cable anchoring rails 11/1
– Eyebolts 11/2
– Section connection kits 11/2
– Circuit diagram pockets 11/2
9 Lock mechanisms 11/2
– Supports 11/2
10 Internal partitioning 11/1
11 Main busbars top 10/2
CatalogueIZM circuit-breakersNZM4 circuit-breakers
HPL0211,IndustrialSwitchgear maincatalogue
7
3
1
6
8
9
10
10
5
6
2
4
2
10
11
1
• Frames: frame top and bottom incl. green design rail• Doors: incl. lock system for 3 mm double-ward key• Mounting kits: predrilled mounting plate for the circuit-breaker and cover plates
with cut-out for circuit-breakers IZM or enclosed for NZM4, incl. all fixingsundries
• Incoming supplies or outgoers, 3 or 4-pole, fixed mounted or drawer units• External operation, IP31 or IP55 degree of protection• IZM circuit-breaker up to I e = 3200 A and I cc = 100 kA (400 V AC)• NZM4 circuit-breaker up to I e = 1600 A and I cc = 100 kA (400 V AC)• Connection for cable or busbar trunking system from below
• See HPL0211 for IZM circuit-breaker and accessories, please order IZM chapterseparately. Order of the IZM-XRT door sealing frame and with IP55 IZM-XDTprotective cover always necessary.
• Details concerning the connection system and connections to the busbar systemfor circuit-breakers can be found in the BA4180-015.
• Busbar system for 2000 to 3200 A can only be installed in sections with 600 mmdepth.
• Current derating values for the defined rated currents are to be observed, seechapter 14.
• On all switchgear the use of additional fittings must be checked in accordancewith the catalogue or should be clarified with product support. Example: IZM1with mechanical interlock can only be fitted in a 600 mm wide section (insteadof 425 mm).
Basic features
Features
Notes for selection, engineering and construction
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 47/143
Moeller FK4810-1143GB-INT
u p t o 3 2 0 0 A
7/2 Sections for incoming supplies/outgoers 800 – 1600 Aup to form 2b
Features:• Section height 2000 mm• Degree of protection IP31 or IP55• Protection class I• Opening angle
– 180° with separate mounting– 170° with side-by-side installation1)
• Exchangeable door hinges
• Actuation behind the door2)
TypeFrames
TypeVerticalprofiles
TypeSectionmountingkits for
TypeSection door
I cc to(400 V AC)
I e up to Installationtype
Poles
Busbar I e
Sectiondepth
Sectionwidth
Top/bottom NZM3) IP55
Article no. Article no. Article no. Article no.
kA A A mm mm for 1 kit for 1 kit for 1 kit 1 off each
Circuit-breakers
NZM4-.. 100 1000 – 1600 Fixed,drawer unit
3 F 1600 400 425 XSFB0404284231
XSFH20284245
XSMNB20-1285513
XSDMC2004284198
Fixed 4 F 1600 400 425 XSFB0404284231
XSFH20284245
XSMNB20-1285513
XSDMC2004284198
Drawer unit 4 F 1600 400 600 XSFB0604284234
XSFH20284245
XSMNB20-1285513
XSDMC2006284199
NZM4-.. 100 1000 – 1600 Fixed,drawer unit
3 1250 – 3200 600 425 XSFB0406284232
XSFH20284245
XSMNT20285512
XSDMC2004284198
Fixed 4 1250 – 3200 600 425 XSFB0406284232
XSFH20284245
XSMNT20285512
XSDMC2004284198
Drawer unit 4 1250 – 3200 600 600 XSFB0606284235
XSFH20284245
XSMNT20285512
XSDMC2006284199
Notes 1) Order alternative hinge for 180° with side-by-side mounting, see page 11/22) Additional door coupling handles and shaft extensions should be ordered for NZM4 for external actuation.3) For installation of circuit-breakers NZM4 the mounting plate XMN4...24...M... on page 8/7 must be used.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 48/143
7/3
Moeller FK4810-1143GB-INT
I n c o m i n g s u p p l i e s a n d o u t g o e r s
u p t o 3 2 0 0 A
Sections for incoming supplies/outgoers 800 – 1600 Aup to form 2b
TypeSection door, IP31 ventilated
TypeBack plate
TypeTop plate
Bottom plate type5)
Hinge left Hinge right IP31 ventilated IP55 IP31/55Without apertures
IP31 integrated canopy4)
Split
Article no. Article no. Article no. Article no. Article no. Article no. Article no.
1 off each 1 off each 1 off each 1 off each 1 off each 1 off each 1 off each
XSDMLV2004284209
XSDMRV2004284218
XSWV2004284360
XSWC2004284355
XSPTC0404284301
XAD0404283484
XSPBM0404284286
XSDMLV2004284209
XSDMRV2004284218
XSWV2004284360
XSWC2004284355
XSPTC0404284301
XAD0404283484
XSPBM0404284286
XSDMLV2006284210
XSDMRV2006284219
XSWV2006284361
XSWC2006284356
XSPTC0604284304
XAD0604283487
XSPBM0604284289
XSDMLV2004284209
XSDMRV2004284218
XSWV2004284360
XSWC2004284355
XSPTC0406284302
XAD0406283485
XSPBM0406284287
XSDMLV2004284209
XSDMRV2004284218
XSWV2004284360
XSWC2004284355
XSPTC0406284302
XAD0406283485
XSPBM0406284287
XSDMLV2006284210
XSDMRV2006284219
XSWV2006284361
XSWC2006284356
XSPTC0606284305
XAD0606283488
XSPBM0606284290
4) Total height = section height 2000 mm plus canopy 60 mm5) With multiple part top and bottom plates with cable entries for larger cable cross-sections, the degree of protection may need to be assured by additional measures.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 49/143
Moeller FK4810-1143GB-INT
u p t o 3 2 0 0 A
7/4 Internal partitioning up to form 2b for incoming supplies and outgoers 800 – 1600 ATop busbars
Features:• Internal partitioning of
forms 2b• Degree of protection IP20
TypePartitionsform 2b
TypeForm 2b partitioning (busbar BBT to NZM4 included)
TypeShroud
Section width Section depth Busbar area / Componentmounting sec-tions
Componentmounting/bus-bar areas
Busbar area / Componentmountingsections1)
Busbar area /cable connectionarea
Coupling area
Article no. Article no. Article no. Article no. Article no.
mm mm 1 off each 1 off each 1 off each 1 off each 1 off each
Circuit-breakers
NZM 4 425 400 XPBMT0404284702
XPMMT0402284704
– XPNBCT0402285501
XPC0604284115
600 400 XPBMT0604284703
XPMMT0602284705
– XPNBCT0602285503
XPC0606284116
425 600 XPBMT0406284111
XPMMT0404284167
– XPNBCT0404285502
XPC0604284115
600 600 XPBMT0606
284112
XPMMT0604
284168
– XPNBCT0604
285504
XPC0606
284116
Notes 1) Partition with circuit-breaker NZM4 already included as a fitting kit in the mounting plate.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 50/143
7/5
Moeller FK4810-1143GB-INT
I n c o m i n g s u p p l i e s a n d o u t g o e r s
u p t o 3 2 0 0 A
Fitting kits for incoming supplies and outgoers 800 – 3200 Aup to form 4b
Features:• Rated current 800 – 3200 A• I cc (400 V AC) up to 100 kA• Fixed mounted or drawer units• 3 or 4-pole• External actuation• Module height 650 mm
I cc to(400 V AC)
I e up to Installation type Poles Section width TypeAssembly unitArticle no.
kA A mm 1 off each
Circuit-breakers
IZMB(N)1-.. 65 1000 – 1600 Fixed, drawerunit1)
3 425 XMI1304283955
4 600 XMI1406283964
IZMB(N,H)2-.. 100 1600 – 2500 Fixed, drawerunit1)
3 600 XMI2306283973
4 800 XMI2408
283975
IZMB(N,H)2-.. 100 3200 Fixed, drawerunit1)
3 600 XMI2306283973
4 800 XMI2408283975
Notes 1) IZM circuit-breaker in drawer unit can only be installed in 600 mm deep sections.
Features:• Rated current 800 – 1600 A• I cc (400 V AC) up to 100 kA• Fixed mounted or drawer units• 3 or 4-pole• External actuation• Module height 650 mm
I cc to(400 V AC)
I e up to Installation type Poles Sectionwidth
TypeAssembly unitArticle no.
kA A mm 1 off each
Circuit-breakers
NZM4-.. 100 1000 – 1600 Fixed 3 425 XMN4304284068
Drawer unit 3 425 XMN4304-1284853
Fixed 4 425 XMN4404284077
Drawer unit 4 600 XMN4406284078
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 51/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 52/143
Moeller FK4810-1143GB-INT
3 2 0 0 A
7/8 Internal partitioning up to form 4b for incoming supplies and outgoers 800 – 3200 A
Features:• Internal partitioning of
forms 2b or 4b• Degree of protection
IP20
TypePartitions form2b
TypePartitions form 4b
TypeShroud
Sectionwidth
Sectiondepth
Busbar area / Componentmountingsections
Componentmounting area /componentmounting area
Busbar area /cableconnectionarea
Busbar area / Componentmountingsections
Componentmounting area/ coupling area
Coupling area
Article no. Article no. Article no. Article no. Article no. Article no.
mm mm 1 off each 1 off each 1 off each 1 off each 1 off each 1 off each
Circuit-breakers
In order to achieve Form 4b, the partitions of Form2b must be extended.
IZM.. 425 600 XPBMT0406284111
XPMMT0404284167
XPBCB0402284099
XPIBMCB0604284151
– XPC0604284115
600 600 XPBMT0606284112
XPMMT0604284168
XPBCB0602284101
XPIBMCB0606284152
– XPC0606284116
800 600 XPBMT0806
284113
XPMMT0804
284169
XPBCB0802
284103
XPIBMCB0608
284153
– XPC0608
284117XPNBCBNZM4 425 600 XPBMT0406
284111XPMMT0404284167
XPNBCB0402289174
– XPNMCB04284174
XPC0604284115
600 600 XPBMT0606284112
XPMMT0604284168
XPNBCB0602289175
– XPNMCB06284175
XPC0606284116
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 53/143
8/1
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
a n d i n c o m e r s u p
t o 1 6 0 0 A f o r N Z M 4
Outgoers up to 630 A for NZM1 – 3 and combined incomers up to 1600 A for NZM4
Overview Page
1 Mounting plate for c ircuit-breaker up to 630 A
8/3
– Mounting plate for c ircuit-breaker up to 1600 A
8/7
– Mounting plate for empty
sections etc.
8/6
2 Front cover for circuit-breakersup to 630 A
8/2
– Front cover for circuit-breakersup to 1600 A
8/7
3 Front surround for emptysections, meter installation,etc.
8/6
4 Sections 8/8
5 Doors 8/9
6 Back plates 8/9
7 Protective cover plates 8/9
8 Top and bottom plates 8/9
9 Side walls 11/1
10 Plinths 11/1– Cable anchoring rails 11/1
– Eyebolts 11/2
– Section connection kits 11/2
– Circuit diagram pockets 11/2
11 Lock mechanisms 11/2
12 Internal partitioning 8/11, 12
13 Dropper bars 8/13
14 Main busbars top 10/2
Catalogue
PKZ circuit-breakers HPL0211,Industrial
Switchgearmain catalogue
NZM1, NZM2, NZM3 circuit-
breakersNZM4 circuit-breakers
9
11
5
2
5
7
124
6
13
8
10
8
12
3
12
4
1
14
• Mounting plates for circuit-breakers: pre-drilled mounting plates with cut-outfor cable entries incl. all fixing sundries
• Front surrounds for circuit-breaker: front surrounds with cut-out for circuit-breakers incl. all fixing sundries and hinges
• Frames: frame top and bottom incl. green design rail• Doors: incl. lock system for 3 mm double-ward key
• Outgoers with PKZ, NZM1 – 3, 3-pole or 4-pole, fixed mounted, connectors for
NZM2 or drawer units for NZM3• Incoming supply with IZM or NZM4, 3 or 4-pole, fixed mounted or drawer units• External actuation, degree of protection IP31 or IP55 (only with door)• External actuation for the IZM and behind the door for NZM4 (external
actuation possible), degree of protection IP31 or IP55• Circuit-breaker PKZ, NZM1 – 3 to I e = 630 A and I cc = 100 kA (400 V AC) and
NZM4 to I e = 1600 A and I cc = 100 kA (400 V AC)• Cable connection from below
• Details concerning wiring, the connection system and connections to the busbarsystem for circuit-breakers can be found in the BA4810-015 assembly manual.
• Busbar system for 2000 to 3200 A can only be installed in sections with 600 mmdepth.
• Current derating values for the defined rated currents are to be observed, seechapter 14.
• Engineer additional terminals if required for implementation of form 4b.• Cover plates can only be used in combination with fitting kit type XSMFD... .• Mounting plates for NZM and PKZ devices are rated for mounting the basic
units. Fittings (e.g. auxiliary contacts) should be tested with regard to theirinstallation suitability using the dimensional drawings in chapter 15.
Basic features
Features
Notes for selection, engineering and construction
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 54/143
Moeller FK4810-1143GB-INT
a n d i n c o m e r s u p
t o 1 6 0 0 A f o r N Z M 4
8/2 Outgoer sections: installable circuit-breakers and accessories
Side mounted accessories are not considered and must be separately tested for installation suitability.Installation of the drawer units is always relevant to the connected position, i.e. not disconnected.
Busbar position Top
Form fitting kit 2b 4b 4bon the rear
Section depth mm 600 600 600
max. mounting depth in section mm 237 191 191
max. mounting depth up to cover plate mm – 122 122
Basic unit mounting depth + accessories mm
PKZM0 76 X X X
+ current limiter 127 X X X
PKZ2 134 X X X
PKZ4 160 – 171 X X X
NZM1 85 X X X
+ rotary drive 148 X X X
NZM2 149 X X X
+ rotary drive 191 X X X+ remote operator 236 X – –
+ plug-in technology 236 X X X
+ plug-in technology + rotary drive 279 – – –
+ plug-in technology + remote operator 326 – – –
NZM3 166 X X X
+ rotary drive 229 X X1) X1)
+ remote operator 271 – – –
+ drawer units 271 – – –
+ drawer units + rotary drive 334 – – –
+ drawer units + remote operator 379 – – –
NZM4 207 X X X
+ rotary drive 264 – – –
Notes 1) Can only be installed without front door.
X device can be fitted– device cannot be fitted
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 55/143
8/3
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
a n d i n c o m e r s u p
t o 1 6 0 0 A f o r N Z M 4
Mounting kits for horizontal installed compact circuit-breaker NZM1 – 3up to 630 A and PKZ... up to 63 A for outgoers
Features:• Rated current up to 630 A• I cc (400 V AC) up to 100 kA• Fixed mounted (plug-in or withdrawable unit)• 3 or 4-pole• External actuation or behind component area door• Horizontal installation
I e up to Installation type Poles Number ofswitches permodule
Moduleheight
Modulewidth
TypeMounting plate
Article no.
TypeFront surround1)
Article no.
A A mm mm 1 off each 1 off each
Circuit-breakers
Mounting kit for 3-pole circuit-breaker (installation of a switch insulating surround not possible.)
PKZM0 32 Fixed 3 1 50 425 XMP030204M284088
XMP030204C284087
600 XMP030206M284090
XMP030206C284089
PKZ2, PKZM4 63 100 4252) 6) XMP430404M284096
XMP430404C284095
6002) 6) XMP430406M284098
XMP430406C284097
NZM1 125 4254) XMN130404M283996
XMN130404C283995
600 XMN130406M283998
XMN130406C283997
NZM2, GSTA007) 250 Fixed 150 4254) XMN230604M284012
XMN230604C284011
600 XMN230606M284014
XMN230606C284013
Plug-in 150 600 XMN230606MP284724
XMN230606C284013
Fixed+remoteoperator
600 XMN230606MP284724
XMN230606CR292907
NZM3, GSTA17)
630 Fixed8)
200 600 XMN330806M284038 XMN330806C284036
Fitting kit for 4-pole circuit-breaker (switch insulating surround NZM-XBR required for degree of protection and must be ordered separately.Installation of 3-pole circuit-breaker is possible.)
PKZ24 40 Fixed 4 1 100 4255) XMP430404M284096
XMP430404C284095
6005) XMP430406M284098
XMP430406C284097
NZM1 125 150 4254) XMN140604M284004
XMN140604C284003
600 XMN140606M284006
XMN140606C284005
NZM2 250 Fixed 200 4254) 3) XMN240804M284025
XMN240804C284024
600 XMN240806M284027
XMN240806C284026
Plug-in 200 600 XMN240806MP284726
XMN240806C284026
Fixed andfault-current trip4-poleNZM2-4-XFI...
200 600 XMN240806M284027
XMN240806CF284659
NZM3, GSTA27) 630 Fixed8) 250 600 XMN341006M284054
XMN341006C284052
Notes 1) Front surround can be attached with or without hinge.2) PKZ2 installation with R...-PKZ2 remote operator not possible.3) Installation of NZM2-4-XFI... fault current release not possible.4) Installation of covers for NZM...-...-XKSA connections not possible.
5) PKZ24 installation with side mounted accessories not possible.6) PKZM4 installation with front standard auxiliary contact NHI-E-... not possible;
please use side mounted auxiliary contacts.7) Installation possible without front surround only.8) Drawer unit only possible with vertical installation.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 56/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 57/143
Moeller FK4810-1143GB-INT
a n d i n c o m e r s u p
t o 1 6 0 0 A f o r N Z M 4
8/6 Accessories for fitting kits for outgoers
Covers1) for empty or reserved sections and installation of control circuit devices
TypeMounting platewithout apertures
TypeFront surroundwithout cut-out
TypeVentilated frontsurround2)
TypeFront surround for control circuit deviceinstallation
Module height Module widthArticle no. Article no. Article no.
8x RMQ-TitanArticle no.
12x RMQ-TitanArticle no.
mm mm 1 off each 1 off each 1 off each 1 off each 1 off each
50 425 XME0204M283923
XME0204C283922
– – –
100 XME0404M283929
XME0404C283926
XME0404CV283928
XME0404CI283927
–
150 XME0604M284727
XME0604C283936
– – –
200 XME0804M283941
XME0804C283939
– – –
400 XME1604M283949
XME1604C283948
– – –
50 600 XME0206M283925
XME0206C283924
– – –
100 XME0406M283933
XME0406C283930
XME0406CV283932
– XME0406CI283931
150 XME0606M284728
XME0606C283936
– – –
200 XME0806M283945
XME0806C283942
– – –
400 XME1606M283951
XME1606C283950
– – –
Notes 1) Covers can only be combined in conjunction with fitting kit XSMFDB... .2) Surround in lowest installation position always required for sections with IP30/IP31 degree of protection
Covers1) for installation of meters
TypeFront surround for meter installation
Module height Module width 4 x 72 x 72 mm+ 1 changeoverArticle no.
2 x 72 x 72 mm+ 2 changeoversArticle no.
4 x 72 x 72 mm+ 1 changeoverArticle no.
2 x 72 x 72 mm+ 2 changeoversArticle no.
4 x 96 x 96 mm+ 1 changeoverArticle no.
2 x 96 x 96 mm+ 2 changeoverArticle no.
mm mm 1 off each 1 off each 1 off each 1 off each 1 off each 1 off each
150 425 – XME0604CM283935
– – – –
200 XME0804CM283940
– – – – –
150 600 – – XME0606CM4283938
– – –
– – – XME0606CM2238937
– –
200 600 – – – – XME0806CM4283944
–
– – – – – XME0806CM2283943
Notes 1) Covers can only be combined in conjunction with fitting kit XSMFDB... .
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 58/143
8/7
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
a n d i n c o m e r s u p
t o 1 6 0 0 A f o r N Z M 4
Mounting kits for NZM4 up to 1600 A for incomersin outgoer sections
Features:• Rated current up to 1600 A• I cc (400 V AC) up to 100 kA• Fixed installation or withdrawable unit• 3-pole and 4-pole• External actuation or behind component area door• Incoming supply on dropper bar• Vertical installation
I cc up to I e up to Installationtype
Pole2) Number ofswitches permodule andsection
Moduleheight
Modulewidth
TypeMounting plateArticle no.
TypeFront surroundArticle no.
kA A mm mm 1 off each 1 off each
Circuit-breakers (installation only possible in sections with 600 mm depth)
NZM4 100 1600 Fixed 3 1 600 425 XMN442404MVF284081
XMN432404CVF284069
600 XMN442406MVF284085
XMN432406CVF284073
Drawer unit1) 3 1 600 425 XMN432404MVW
284072
XMN432404CVW
284070600 XMN432406MVW
284076XMN432406CVW284074
Fixed 4 1 600 425 XMN442404MVF284081
XMN442404CVF284079
600 XMN442406MVF284085
XMN442406CVF284083
Drawer unit1) 4 1 600 600 XMN442406MVW284086
XMN442406CVW284084
Notes 1) No dropper bars behind the mounting plate with 600 mm deep sections possible.2) With fitting kits for 3-pole NZM4 circuit-breakers installation of an insulating surround is not
possible.An insulating surround for the fitting kit for 4-pole NZM4 circuit-breakers is alwaysrequired for degree of protection and should be ordered separately, this also applies when
3-pole circuit-breakers are to be installed. Installation of 3-pole circuit-breaker is possible.
TypeCircuit-breaker cut-out cover (vertical installation) for empty compartment in the cover plate
NZM1 NZM2 NZM3
3-pole 4-pole 3-pole 4-pole 3-pole 4-pole
Article no. Article no. Article no. Article no. Article no. Article no.
1 off each 1 off each 1 off each 1 off each 1 off each 1 off each
XAS1-4284740
XAS1-4284740
XAS2-3284741
XAS2-4284742
XAS3-3284743
XAS3-4284744
TypeCable duct support for FAZ mounting kit, 425 mm wide
TypeCable duct support for FAZ mounting kit, 600 mm wide
Article no. Article no.
1 off each 1 off each
XADB04284710
XADB06284711
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 59/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 60/143
Moeller FK4810-1143GB-INT
a n d i n c o m e r s u p
t o 1 6 0 0 A f o r N Z M 4
8/10 Outgoer sections for rear dropper bars
Features:• Section height 2000 mm• Degree of protection IP30, IP31 or
IP55• Protection class I• Door opening angle 170°• Exchangeable door hinges
TypeTop plate
TypeTop or bottom plate
Section depth Section width IP31Canopy1) integrated
IP55Without apertures
IP55Split2)
Article no. Article no. Article no.
mm mm 1 off each 1 off each 1 off each
Sections for rear dropper bar position
600 400 XAD0406283485
XSPTC0406284302
XSPBM0406284287
600 XAD0606283488
XSPTC0606284305
XSPBM0606284290
800 XAD0806283811
XSPTC0806284308
XSPBM0806284293
1000 XAD1006283814
XSPTC1006284311
XSPBM1006284296
Notes 1) Total height = section height 2000 mm plus canopy 60 mm2) With rubber seal; with cable entries for larger cable cross-sections, the degree of protection may need to be assured
by additional measures.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 61/143
8/11
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
a n d i n c o m e r s u p
t o 1 6 0 0 A f o r N Z M 4
Features:• Internal partitioning of forms
2b or 4b• Degree of protection IP20
TypePartitions form 2b –partitions form 4b1)
Section depth Module width Connectionarea width
Coupling / dropperbar area
Componentmounting area /componentmounting areahorizontal
Componentmounting area/coupling areasealing strips
Busbar area / Component mountingsections top
Busbar area / cableconnection area top
Article no. Article no. Article no. Article no. Article no.
mm mm mm every 1 set (= 2 off) 1 off each 1 off each 1 off each 1 off each
Sections for rear dropper bar position up to form 2b,actuation behind component mounting area door
600 425 – – – – XPF2BMT0406289906
–
600 – – – – XPF2BMT0606289907
–
– – XPFCD2006284132
– – – –
– 200 – – – – XPFBCT0206284771
– 400 – – – – XPFBCT0406284770
Sections for rear dropper bar position up to form 4b,actuation external or behind component mounting
area door
600 425 – – – – XPFBMT0406284759
–
600 600 – – – – XPFBMT0606284758
–
– – – – – XPFMC284146
– –
– 425 – – XPFMM04284147
– – –
– 600 – – XPFMM06284148
–
–
–
600 – – XPFCD2006284132
– – – –
– 200 – – – – XPFBCT0206284771
– 400 – – – – XPFBCT0406284770
Notes 1) For form 4b an additional front surround is necessary
Internal partitioning to form 4b for outgoer sections with rear dropper bars
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 62/143
Moeller FK4810-1143GB-INT
a n d i n c o m e r s u p
t o 1 6 0 0 A f o r N Z M 4
8/12
Features:• Internal partitioning of
forms 2b or 4b• Degree of protection IP20
TypePartitions form 2b
TypePartitions form 4b(supplement 2b partitions)
Sectiondepth
Sectionwidth
Modulewidth
Moduleheight
Coupling / dropperbar area
Componentmounting area/componentmounting areahorizontal1)
Busbar area top Connection area/cableconnection area
Article no. Article no. Article no. Article no.
mm mm mm mm 1 off each 1 off each 1 off each 1 off each
Sections with rear cable connection area for rear dropperbar position up to form 4b, actuation external via coverplate or behind additional component mounting area door
600 425 – – – – XPFBMT0406284759
–
600 600 – – – – XPFBMT0606284758
–
– – 425 – – XPFMMR04284149
– –
– – 600 – – XPFMMR06284150
– –
– – 425 50 XPFCDR0204284134
– – XPFCCR0204284120
– – 425 100 XPFCDR0404284136
– – XPFCCR0404284122
– – 425 150 XPFCDR0604284138
– – XPFCCR0604284124
– – 425 200 XPFCDR0804284140
– – XPFCCR0804284126
– – 425 250 XPFCDR1004284142
– – XPFCCR1004284128
– – 425 300 XPFCDR1204284144
– – XPFCCR1204284130
– – 600 50 XPFCDR0206284135
– – XPFCCR0206284121
– – 600 100 XPFCDR0406284137
– – XPFCCR0406284123
– – 600 150 XPFCDR0606284139
– – XPFCCR0606284125
– – 600 200 XPFCDR0806284141
– – XPFCCR0806284127
– – 600 250 XPFCDR1006284143
– – XPFCCR1006284129
– – 600 300 XPFCDR1206284145
– – XPFCCR1206284131
Notes 1) Partition only required if the mounting plate with depth offset is fitted.
Internal partitioning to form 4b for outgoer sections with rear dropper bars
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 63/143
8/13
Moeller FK4810-1143GB-INT
O u t g o e r s u p t o 6 3 0 A f o r N Z M 1 – 3
a n d i n c o m e r s u p
t o 1 6 0 0 A f o r N Z M 4
Dropper bars up to 1600 A for outgoer sections, fitting kit
Features:• 800 – 1600 A• TN-C, TN-C-S, TN-S,
IT• I cw (1 s) up to 50 kA
I e Busbarcross-section
TypeBusbar bracket
TypeBracket for conductor in coupling area1)
L1, L2, L3, full N PE, PEN 3-conductor L1, L2, L3 or4-conductor L1, L2, L3, NArticle no.
Lower end bracket
Article no.
PE or PEN
Article no.
N
Article no.
A mm2 mm2 1 off each 1 off each 1 off each 1 off each
Side dropper bar, distance between busbar centres 60 mm
800 2x 20x 10 1x 20x 10 XDSF08283888
XDSF08E283889
XDSFP283895
XDSFN283894
1250 2x 40x 10 1x 40x 10 XDSF12283890
XDSF12E283891
XDSFP283895
XDSFN283894
1600 2x 60x 10 1x 60x 10 XDSF16283892 XDSF16E283893 XDSFP283895 XDSFN283894
Module width TypeCross supports for XDSF...busbar bracket forrear dropper bars
Article no.
I e Busbar cross-section
TypeDuplex copper section busbarLength = 1800 mm
Article no.
mm 1 off each A mm2 1 off each
600 XDB06283885
1250 1x 40x 30 XDP40X30283886
1600 1x 60x 30 XDP60X30283887
Notes: See chapter 14 for the short-circuit rating1) Can also be used for mounting of cable ducts, auxiliary circuit busbars etc.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 64/143
Moeller FK4810-1143GB-INT
a n d i n c o m e r s u p
t o 1 6 0 0 A f o r N Z M 4
8/14 Notes
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 65/143
9/1
Moeller FK4810-1143GB-INT
G e n e r a l f i t t i n g s
General fittings for modular installation devices, power electronic components,compensation, etc.
Overview Page
1 Fitting kit for height adjustablemounting plates
9/2
2 Fitting kit for section heightmounting plate
9/2
– Fitting kit for MR25 9/2
– Modular installation devicefitting kit
9/2
3 Sections 9/2
4 Doors 9/3
5 Back plates 9/3
6 Protective cover plates 9/3
7 Top and bottom plates 9/3
8 Side walls 11/1
9 Plinths 11/1
– Cable anchoring rails 11/1
– Eyebolts 11/2
– Section connection kits 11/2
– Circuit diagram pockets 11/2
10 Lock mechanisms 11/2
– Internal partitioning 11/1
11 Main busbars top 10/2
Catalogue
X pole xStart
HPL0211,IndustrialSwitchgearmain catalogue
MR25 rapid mounting system HPL0214,PowerDistributionSystemsmain catalogue
8
2
1
4
10
6
7
3
4
7
9
5
11
• Frames: frame top and bottom incl. green design rail• Doors: incl. lock system for 3 mm double-ward key• Fitting kit for lower adjustable mounting plate: multifunctional walls incl. all
fixing sundries• Fitting kit for mounting plates on a single level: mounting plate incl. all fixing
sundries• Fitting kit MR25 rapid mounting system: profiles incl. all fixing sundries• Fitting kit modular installation device: support and insulating surround incl. all
fixing sundries
• Installation outgoers with X pole • Individual fixed mounting on mounting plate up to 630 A, e.g. soft starter,
frequency inverter, reactive power compensation• Automation engineering• xStart, control engineering, adapter systems
• Details for cable connection to the busbar and mounting should be taken fromthe BA 4810-015 assembly manual.
• Please order 2x L section with b' = 1850 mm for MR 25 installation from theHPL0214 catalogue.
• Busbar system for 2000 to 3200 A can only be installed in sections with 600 mmdepth.
• Permissible heat dissipation must be observed, see chapter 14.• Reactive power compensation selection, see page 5/5• Corner sections for 600 mm deep sections, see page 5/6
Basic features
Features
Notes for selection, engineering and construction
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 66/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 67/143
Moeller FK4810-1143GB-INT
G e n e r a l f i t t i n g s
9/4 Mounting plate for fitting kits XSMIT20 in sections for general fittings
Features:• Fittings up to 630 A• Fixed mounted• Depth can be adjusted• For top or bottom busbar position
TypeMounting plate
Width Height
Article no.
mm mm 1 off each
425 100 XME0404M283929
150 XME0604M284727
200 XME0804M283941
300 XME1204M285684
400 XME1604M283949
600 XME2404M285685
600 100 XME0406M283933
150 XME0606M284728
200 XME0806M283945
300 XME1206M
285686400 XME1606M
283951
600 XME2406M285687
800 100 XME0408M285689
150 XME0608M285690
200 XME0808M285691
300 XME1208M285692
400 XME1608M285693
600 XME2408M285694
1000 100 XME0410M285695
150 XME0610M285696
200 XME0810M285697
300 XME1210M285698
400 XME1610M285699
600 XME2410M285700
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 68/143
10/1
Moeller FK4810-1143GB-INT
T o p m a i n b u s b a r s u p t o 3 2 0 0 A
Top main busbars up to 3200 A
Overview Page
1 Busbar bracket 10/2
2 PE or PEN bracket 10/2
– Cross support 10/2
– Transport split 10/2
1
2
• Busbar bracket: busbar bracket incl. all fixing sundries• PE or PEN bracket: retaining bracket incl. all fixing sundries• Cross support: support profile incl. all fixing sundries
• Rated current I e up to 3200 A• Rated short-time withstand current I cw (1s) up to 65 kA• Rated peak withstand current I pk up to 143 kA
• 1 busbar system per section can be installed
• Details concerning the engineering design of the busbar system and thetransport split should be taken from the assembly manual BA4810-015
• Busbar systems with 60 mm interval between phase centres up to 1600 A canbe installed in 400 mm and 600 mm deep sections, with 125 mm intervalbetween phase centres up to 3200 A they can only be installed in 600 mm deepsections.
• Current derating values for the defined rated currents are to be observed, seechapter 14.
• Maximum clearance of the busbar supports should be determined conform tothe required short-circuit rating, see chapter 14.
Basic features
Features
Notes for selection, engineering and construction
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 69/143
Moeller FK4810-1143GB-INT
T o p m a i n b u s b a r s u p t o 3 2 0 0 A
10/2 Top main busbars up to 3200 AMounting kits
Features:• 800 – 3200 A• TN-C, TN-C-S, TN-S, IT• I cw (1 s) up to 65 kA
I e Busbar cross-section min.sectiondepth
TypeBusbar bracket
TypeBracket
TypeBusbartransport split
3-conductor L1, L2, L3or 4-conductor L1, L2,L3, N
PE or PEN N(separate)
3-conductorL1, L2, L3
4-conductorL1, L2, L3, N
L1, L2, L3, full N PE, PEN Article no. Article no. Article no. Article no. Article no.
A mm2 mm2 mm 1 off each 1 off each 1 off each for 1 kit for 1 kit
Interval between phase centres 60 mm
800 2x 20x 101) 1x 20x 10 400 XBST08-1283873
XBSP283872
XBSN16284747
XBTT12-3289080
XBTT12284778
1250 2x 40x 10 1x 40x 10 400 XBST12-1283875
XBSP283872
XBSN16284747
XBTT12-3289080
XBTT12284778
1600 2x 60x 10 1x 60x 10 400 XBST16-1283877
XBSP283872
XBSN20284748
XBTT20-3289081
XBTT20284779
Interval between phase centres 125 mm
1250 2x 40x 10 1x 40x 10 600 XBST12283874
XBSP283872
XBSN16284747
XBTT12-3289080
XBTT12284778
1600 2x 60x 10 1x 60x 10 600 XBST16283876
XBSP283872
XBSN20284748
XBTT20-3289081
XBTT20284779
2000 2x 80x 10 1x 80x 10 600 XBST20283878
XBSP283872
XBSN40284750
XBTT20-3289081
XBTT20284779
2500 2x 100x 10 1x 100x 10 600 XBST25283879
XBSP283872
XBSN32284749
XBTT32-3289082
XBTT32284780
3200 2x 120x 102) 1x 120x 10 600 XBST32
283880
XBSP
283872
XBSN40
284750
XBTT32-3
289082
XBTT32
284780
Notes 1) N-conductor separate with 1 x 40 x 10 mm2) N-conductor separate with 3 x 80 x 10 mm
Section width TypeCross support 3) for XBST....-1 busbar support in 600 mmdeep or XBST... in 800 mm deep sections
Article no.
mm 1 off each
425 XBBB04283859
600 XBBB06283860
800 XBBB08283861
1000 XBBB10283862
1200 XBBB12283863
Notes 3) 1 off required per section
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 70/143
11/1
Moeller FK4810-1143GB-INT
G e n e r a l a c c e s s o
r i e s
Enclosure individual parts
Busbar Section depth Section width TypeSide plate1)
TypePlinths
TypeCable anchoringrails2)
TypePartitionsection/section3)
IP55Article no.
100 mmArticle no.
200 mmArticle no. Article no. Article no.
Position, I e in A mm mm every 1 set (= 2 off) 1 off each 1 off each 1 off each 1 off each
Top, F 1600 400 425 XAW2004283856
XAP010404283822
XAP020404283836
XAR04283850
XPSS2004284781
600 XAW2004283856
XAP010604283825
XAP020604283839
XAR06283851
XPSS2004284781
800 XAW2004283856
XAP010804283828
XAP020804283842
XAR08283852
XPSS2004284781
1000 XAW2004283856
XAP011004283831
XAP021004283845
XAR10283853
XPSS2004284781
Top, F 3200 600 425 XAW2006283857
XAP010406283823
XAP020406283837
XAR04283850
XPSS2006284178
Rear,F 3200 600 XAW2006283857
XAP010606283826
XAP020606283840
XAR06283851
XPSS2006284178
800 XAW2006283857
XAP010806283829
XAP020806283843
XAR08283852
XPSS2006284178
1000 XAW2006283857
XAP011006283832
XAP021006283846
XAR10283853
XPSS2006284178
1200 XAW2006283857
XAP011206283834
XAP021206283848
XAR12283854
XPSS2006284178
Rear, 4000 800 425 XAW2008283858 XAP010408283824 XAP020408283838 XAR04283850 XPSS2008284179
600 XAW2008283858
XAP010608283827
XAP020608283841
XAR06283851
XPSS2008284179
800 XAW2008283858
XAP010808283830
XAP020808283844
XAR08283852
XPSS2008284179
1000 XAW2008283858
XAP011008283833
XAP021008283847
XAR10283853
XPSS2008284179
1200 XAW2008283858
XAP011208283835
XAP021208283849
XAR12283854
XPSS2008284179
Notes 1) Enclosure side plate cannot be combined with partition section/section.2) Cable anchoring rail for 400, 600, 800 mm wide sections can also be side mounted with respective section depths. With outgoer sections
with side cable connection area and rear busbar, the cable anchoring rail can be installed in combination with the profile:(1 off per section) XSMPB20 (page 5/5):Section width 600 mm XAR04
800 mm XAR063) Required for all sections with rear busbar from internal partitioning form 2b. Exception:
sections for three-part front for IZM, NZM4, SASIL vertical and SL vertical installation do not requiresection/section partition with side-by-side mounting of the same sections.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 71/143
Moeller FK4810-1143GB-INT
G e n e r a l a c c e s s o
r i e s
11/2 Enclosure individual parts
TypeEyebolts
TypeAssembly kitsection/section
TypeAssembly kit section/IP55 section
TypeDIN A4 circuitdiagram pocket
TypeLock mechanism1) roller lever withpushbutton
TypeAdapter kit for profile halfcylinder installation inXALP
Article no. Article no. Article no. Article no. Article no. Article no.
1 set (= 4 off) 1 set (= 8 off) 1 set (= 8 off) 1 off each 1 off each 1 off each
XAT283855
XAC283483
XAC 55284793
XAB4283482
XALP283821
XALA283819
Notes 1) Lock mechanism with 3 mm double-ward key is included as standard in doors.
TypeProfile half cylinderE012 incl. key
TypeEdge protection forcable entries
Type1 set of cover strips45 mm standard frontdimension formounting plates, 12 SU
TypeHinge2) for door openingangle 180°, right
TypeHinge2) for dooropening angle 180°,left
TypeSpecialscoloursto RAL
Article no. Article no. Article no. Article no. Article no. Article no.
1 off each 1 set (2 m) 10 off each 2 off each 2 off each per order
XALE012283820
XAK283818
XAS12284708
XAH180284713
XAH180L284792
XARAL285005
Notes 2) For section height doors 3 hinges are required; the hinge cannot be used for cover plate.
Cross-sectionmm2
Lengthmm
TypeGrounding cableArticle no.per 20 pieces
4 180 XAE4-18293897
4 420 XAE4-42293898
10 180 XAE10-18293896
10 420 XAE-10284712
Supports for cable connection systems for circuit-breakers 800 – 4000 A
Support selection according to assembly manual BA4810-015
TypeSupport cable connection system1)
I e up to Poles Section widthArticle no.
A mm 1 set each (per busbar)
Circuit-breakers
IZM..2-.. 3200 3 600 XCSIY308283882
4 800 XCSIY412283884
IZM..3-.. 4000 3 800 XCSIY308283882
4 1200 XCSIY412283884
Notes 1) For connection bar 3 x 60 mm x 10 mm
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 72/143
11/3
Moeller FK4810-1143GB-INT
G e n e r a l a c c e s s o
r i e s
Individual parts and material conform to assembly manual BA4810-0015
Note: Necessary number and exact use of the following listed articles should be taken from the BA 4810-0015 assembly manual.The details listed below are only intended as ordering help.
Rated size Standard Quality Length Description Part no.Article no.
Std. pack
mmSelf-tapping screws
M4 DIN 7500 – 16 M4X16, LINSENKOPF,FORM C, VZN
XNGFS-M4X16288963
1 set of 100 off
M5 10 M5X10, LINSENKOPF,FORM C, VZN
XNGFS-M5X10288964
M6 12 M6X12, LINSENKOPF,FORM C, VZN
XNGFS-M6X12288965
20 M6X20, LINSENKOPF,FORM C, VZN
XNGFS-M6X20288966
Hexagon-head screw
M8 DIN EN 24017 – 16 M8X16, VZN XNSKS-M8X16288978
1 set of 50 off
45 M8X45, VZN XNSKS-M8X45
288979M10 DIN EN 24014 8.8 60 M10X60-8.8 XNSKS-M10X60-8
288980
70 M10X70-8.8 XNSKS-M10X70-8288981
80 M10X80-8.8 XNSKS-M10X80-8288982
100 M10X100-8.8 XNSKS-M10X100-8288983
1 set of 30 off
120 M10X120-8.8 XNSKS-M10X120-8288984
140 M10X140-8.8 XNSKS-M10X140-8288985
160 M10X160-8.8 XNSKS-M10X160-8288986
180 M10X180-8.8 XNSKS-M10X180-8288987
190 M10X190-8.8 XNSKS-M10X190-8288988
M12 55 M12X55-8.8 XNSKS-M12X55-8288989
70 M12X70-8.8 XNSKS-M12X70-8288990
80 M12X80-8.8 XNSKS-M12X80-8288991
90 M12X90-8.8 XNSKS-M12X90-8288992
T-head boltswith lug
M10 DIN 188 8.8 30 M10X30, VERZ XNHKS-M10X30288967
1 set of 50 off
50 M10X50, VERZ XNHKS-M10X50288968
Saucer-head screwwith square neck
M12 DIN 603 8.8 50 M12X50-8.8 XNFRS-M12X50-8293899
1 set of 30 off
70 M12X70-8.8 XNFRS-M12X70-8293970
Hexagon nut
M5 DIN EN 24032 – – VZN XNSKM-M5288972
1 set of 50 off
M6 DIN 6923 VZN, FLANSCH/VERZAHNG. XNSKM-M6
288973M8 DIN EN 24032 VZN XNSKM-M8
288974
M10 XNSKM-M10288970
M12 XNSKM-M12288971
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 73/143
Moeller FK4810-1143GB-INT
G e n e r a l a c c e s s o
r i e s
11/4 Individual parts and material conform to assembly manual BA4810-0015
Rated size Standard Quality Length Description Part no.Article no.
Std. pack
mm
Lock washer
M6 – – – GR. 6, GEZ., DACROMET 320 XNKS-M6
288969
1 set of
50 off Insert nut
M12 – – – – XNEM-M12292378
1 set of30 off
Washers
M6 DIN 125 – – U-SCHEIBE, 6,4 VZN XNUS-6288976
1 set of 100 off
M8 U-SCHEIBE, 8,4 VZN XNUS-8288977
M10 U-SCHEIBE, 10,5 VZN XNUS-10288975
Split washers
M6 DIN 127 FST – B6, VZN XNFR-M6288961
1 set of 100 off
M8 B8, VZN XNFR-M8288962
Insulating coverfor hexagon-head screw
M10 – – – – XNIK-M10285667
1 set of 50 off
M12 XNIK-M12285668
Washers
M8 DIN 6796 FST – washer, FST, 8,4 XNSS-8-FST285676
1 set of 50 off
M10 washer, FST, 11 XNSS-10-FST285678
M12 washer, FST, 13 XNSS-12-FST
285679
Rated size Description Part no.Article no.
Std. pack
Copper clipfor cable and busbar connection to parallel busbars
M10 Contact area for cable lug 30 mm wide XNCB285839
1 set of 50 off
Steel clip
M10 XNSB293895
1 set of 50 off
Copper spacerfor busbar connection to parallel busbars, height 10 mm
M10 Contact area 30 mm wide XNCD285840
1 set of 10 off
Contact area 50 mm wide XNCD50293890
Contact area 60 mm wide XNCD60293891
Contact area 80 mm wide XNCD80293892
Contact area 100 mm wide XNCD100293893
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 74/143
11/5
Moeller FK4810-1143GB-INT
G e n e r a l a c c e s s o
r i e s
Individual parts and material conform to assembly manual BA4810-0015
Rear cable connection positionto cable connection
Sectiondepth
Description TypeArticle no.
Std. pack
mm
Fixing bracket for insulated dividerfor busbars on the busbar or connection system
600 – XNBW-G06289171 1 set of 10 off
800 – XNBW-G08289172
600 – XNBW-E06285670
800 – XNBW-E08285671
For busbar or cable connection systems directly on the clips
– – – XNBW-G285669
1 set of 10 off
Fixing bracket for cable anchoring railsfor IZM busbar connection to the busbars
top/top orbottom/bottom
– – XNBW-R289173
1 set of 10 off
Fixing bracket for mounting rails
– – XNBW-M290215
1 set of 2 off
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 75/143
Moeller FK4810-1143GB-INT
G e n e r a l a c c e s s o
r i e s
11/6 Individual parts and material conform to assembly manual BA4810-0015Flange F3A, diaphragm grommet
DimensionsHeightx widthx length
Description Part no. Article no.
Std. pack
mm
Material for insulated dividerfor IZM/NZM4 busbar connection to the busbars
for cable connection systems50x 10x 1150 – XNS-50X10
2856731 set of 5 off
25x 25x 1150 – XNS-25X25285674
30x 30x 1150 – XNS-30X30285675
Flange for top plate XSPTF... and cable grommet for mounting plate XMN...M... are ordered using the HPL0214 Power Distribution Systems maincatalogue, steel sheet enclosure chapter.
Cable entry Type
Article no. Std. pack
Flange
Insulating material
Blank plate F3A-0074182
10 off
Insulating material with metric knockouts
6x M25/168x M32/20, 4x M16
F3A-4081301
2x M168x M25/164x M32/201x M50/32
F3A-8091468
12x M20, 2x M162x M40/25
2x M50/32
F3A-12076555
24x M1613x M20
F3A-34078928
With cable grommets
2 cables up to 70 mm o F3A-KTD083674
5 off
Sponge rubber
Sponge-rubber flange40 cables, 10 – 13 mmo2 cables, 17 – 21 mmo2 cables, 27 – 30 mmo
F3A-D010145
10 off
Sheet steel
blank plate 2 mm,galvanized
F3A-XM088420
10 off
Cable entry Drill holediameter
Externaldiameter ofcable
Cableusage NYM/NYY, 4-core
TypeArticle no.
Std. pack
mm mm mm2
Metric diaphragm grommet
• IP65• With integrated push-through diaphragm• PE and thermoplastic rubber, halogen free
M16 16,5 1 – 10 H03VV-F3x 0.75 mm2,NYM 1x 16/3x 1.5 mm2
KT-M16216983
100 off
M20 20,5 1 – 13 H03VV-F3x 0.75 mm2,NYM 5x 1./5x 2.5 mm2
KT-M20207602
M25 25,5 1 – 18 H03VV-F 3x 0.75 mm2,NYM 4x 10 mm2
KT-M25207603
M32 32,5 1 – 24 H03VV-F 3x 0.75 mm2,NYM 4x 16/5x 10 mm2
KT-M32207604
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 76/143
12/1
Moeller FK4810-1143GB-INT
O r d e r i n g i n f o r m
a t i o n
Type key
X xEnergy (System) M Fitting kits (function group)
Assemblies
I IZM 1
2
3
IZM..1..IZM..2..IZM..3..
3
4
3-pole4-pole
04.. Section width x 100 in mm
I IZM 1 IZM..1.. 3
4
3-pole4-pole
24.. Module height in HUof 25 mm each
04.. Module widthx 100 in mm
M
C
Mounting plateModule panel
VF
VW
vertical, fixedvertical, AF
N NZM 4 NZM4 3
4
3-pole4-pole
04.. Section width x 100 in mm
N NZM 4 NZM4 3
4
3-pole4-pole
24.. Module height in HUof 25 mm each
04.. Module widthx 100 in mm
M
C
Mounting plateModule panel
VF
VW
vertical, fixedvertical, AF
N NZM 1
2
3
4
NZM1NZM2NZM3NZM4
3
4
3-pole4-pole
01.. Module height in HUof 25 mm each
04.. Module widthx 100 in mm
M
C
CR
CF
Mounting plateModule panelModule panel for remote operatorModule panel for residual-currentrelease
V vertical
P PKZ 0
2
PKZM0PKZ2
3
4
–
3-pole4-pole
01.. Module height in HUof 25 mm each
04.. Module widthx 100 in mm
M
C
Mounting plateModule panel
V vertical
M FAZ etc. C MCB 01.. Module height in HU of 25 mm each 04.. Module width x 100 in mm M
C
Mounting plateModule panel
V vertical
E Empty
compartment
01
...
Module height in
HU of 25 mmeach
04
06
Module width x
100 in mm
M
C
Mounting plate
Module panel
V
IM
Ventilated
RMQ flush mountingMeasurementdevices
–
–2 Number of measurement devices
B Bracket D Foundation stirrups
X xEnergy (System) S Sections (function group)
Assemblies
F Housing frame B Frame 04.. Section width x 100 in mm 06.. Section depth x 100 in mm
F Housing frame H Vertical profiles 20 Section height x 100 in mm
M Assembly unit IF
S
L
M
LS IZM u.NZM4Outgoer LSSASILSLEmpty sections
H
V
MV
MF
horizontalverticalMounting plate deepMounting plate fixed
I
D
Actuation behindthe doorExternalactuation
B
T
Main busbarrearMain busbartop
06.. Height (width)x 100 in mm
04.. Width (depth) x100 in mm
D Doors F
S
Outgoer LSSASIL
C
M
Cable connection areaComponent mounting area
L
R
Hinge leftHinge right
C
V
D
Without aperturesVentilated
Transparent
06.. Height x 100in mm
04.. Width x 100in mm
W Back plate C
V
solidVentilated
20.. Height x 100 in mm 04.. Width x 100 in mm
P Top/bottom plate T
B
topBottom
C
F
V
M
solidfor flangesVentilatedSplit
04.. Width x 100 in mm 06.. Depth x 100inmm
X xEnergy (System) P Internal partitioning (function group)
Assemblies
I
N
F
S
C
IZMNZM4Outgoer LSSASILCable connectionarea cover
S
B
D
C
M
SectionBusbar areaDropper bar areaCable connection areaComponent mounting area
S
B
D
C
M
SectionBusbar areaDropper bar areaCable connection areaComponent mounting area
V
H
S
B
T
R
Mounting positionVerticalHorizontal on sideMain busbar rearMain busbar topCable connection area rear
06.. Height (width)x 100 in mm
04.. Width (depth)x 100 in mm
XxEnergy
(System) DDropper bar
(function group)
Assemblies
S Busbar bracket F
SH
SV
LH
Outgoer LSSASIL horizontalSASIL verticalSL horizontal
P
N
PE or PEN conductorN conductor
16.. I e x 100 in A E End bracket
B Cross support 06 Length x 100 in mm
X xEnergy (System) B Busbar (function group)
Assemblies
S
T
Busbar bracketTransport split
B
T
P
Busbar position rearBusbar position topPE or PEN conductor
16.. I e x 100 in A 3
4 3-pole 4-pole
P Copper section busbar 60 Profile height mm X 30 Profile width in mm
B Cross support B Busbar position rear 06 Section width (depth) x 100 in mm
X xEnergy (System) A Accessories (function group)
Assemblies
D Protective cover plate 04.. Section width x 100 in mm 06.. Section depth x 100 in mm
P Plinths 01.. Height x 100 in mm 04.. Section width x 100 in mm 06.. Section depth x 100 in mm
W Side plate 06.. Section height x 100 in mm 04.. Section width x 100 in mm
R Cable anchoring rails 06.. Length x 100 in mm
L Lock mechanisms ...
T Eyebolts
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 77/143
Moeller FK4810-1143GB-INT
O r d e r i n g i n f o r m
a t i o n
12/2 Ordering examples
Function Incoming supply 3-pole, 1000 kVA transformer, operating current1450 A
Degree of protection IP55
Main busbars Operating current 1450 A, TN-S, rear mounting position
Internal partitioning Form 4b
Type Article no. Description Quantity
XMI1304 283955 Fitting kit IZM, 3-pole, frame size 1 1
XSFB0406 284232 Frames top/bottom 1
XAP010406 283823 Plinth 100 mm 1
XSFH20 284245 Vertical profiles 1
XSMIB20 284257 Section mounting kits for IZM/NZM 1
XSDMC0604 284194 Component mounting area door IP55 top and bottom 2
XSWC2004 284355 Back plate, IP55 1
XSPTC0406 284302 Top plate, without apertures 1
XSPBM0406 284287 Bottom plate, split 1
XPBMB0604 284107 Partition GR/SR 1
XPBCB0402 284099 Partition AR/SR 1
XPIBMCB0604 284151 Partition GR/AR/SR 1
XPMMB0404 284163 Partition GR/GR 1
XPC0604 284155 Cover AR (transparent) 1
XBSB164 283865 Busbar support L1-3,N 2
XBSP 283872 Halter PE or PEN 2
XAW2006 283857 Side plate 1
Function Section with outgoers for fuse-load switch units SL
Degree of protection IP31
Main busbars Operating current 1600 A, TN-S, rear mounting position
Internal partitioning Form 3b
Outgoers 1 x fuse-load switch units 630 A, 3-pole
2 x fuse-load switch units 250 A, 3-pole
4 x fuse-load switch units 160 A, 3-pole
Type Article no. Description QuantityXSFB0606 284235 Frames top/bottom 1
XAP010606 283826 Plinth 100 mm 1
XSFH20 284245 Vertical profiles 1
XSML0608 284260 Section mounting kits for SL 1
XPL06 284161 Partitions form 3b 1
XPSS2006 284178 Partition section/section 1
XSDMLV0606 284206 Component mounting area door, ventilated, bottom 1
XSDMC0606 284195 Component mounting area door IP55 top 1
XSWV2006 284361 Back plate, ventilated 1
XAD0606 283488 Top plate with canopy, ventilated 1
XSPBM0606 284290 Bottom plate, split 1
XBSB164 283865 Busbar support L1-3,N 2
XBBB06 283860 Cross support for busbar bracket 2XBSP 283872 Halter PE or PEN 2
XBSN16 284747 Bracket for N conductor in coupling area 2
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 78/143
12/3
Moeller FK4810-1143GB-INT
O r d e r i n g i n f o r m
a t i o n
Ordering examples
Function Section with outgoers for c ircuit-breaker, actuation behind door (transparent),connection area width 400 mm
Degree of protection IP31
Main busbars Operating current 1600 A, TN-S, rear mounting position
Dropper bars Operating current 1600 A, TN-S for 3-pole c ircuit-breaker
Internal partitioning Form 4bOutgoers 1 x circuit-breaker 630 A, 3-pole with withdrawable unit
3 x circuit-breaker 200 A, 3-pole
6 x circuit-breaker 80 A, 3-pole
Modular installation device 48 SU
3-phase current measurement, voltage, changeover contact
Type Article no. Description Quantity
XME0206M 283925 Mounting plate 50 mm, without apertures 1
XME0206C 283924 Cover plate without apertures, 50 mm 1
XME0606M 284728 Mounting plate 150 mm, without apertures 1
XME0606CM4 283938 Front surround for meter installation 1
XMMC0806C 283985 Cover plate for REG, 24SU 2XADB06 284711 Cable duct support for FAZ fitting kit 2
XMN130406M 283998 Mounting plate, NZM1 horiz. 6
XMN130406C 283997 Cover plate for NZM1 horiz. 6
XMN230606M 284014 Mounting plate, NZM2, horiz. 3
XMN230606C 284013 Cover plate for NZM2, horiz. 3
XMN330806M 284038 Mounting plate, NZM3 horiz. 1
XMN330806C 284036 Cover plate NZM3 horiz. 1
XSFB1006 284241 Frames top/bottom 1
XSFH20 284245 Vertical profiles 1
XAP011006 283832 Plinth 100 mm 1
XSMFDB0606 284248 Fitting kit for outgoers with circuit-breakers 1
XSDFMD2006 284187 Component mounting area door, transparent 1
XSDFCC2004 284183 Coupling area door, without apertures 1XSWC2010 284358 Back plate 1
XSPTC1006 284311 Top plate, without apertures IP55 1
XSPBM1006 284296 Bottom plate, split 1
XPFCD2006 284132 Partition AR/VS 1
XPFMM06 284148 Partition horiz. GR/GR 11
XPFMC 284146 Partition GR/AR 1
XPFCB04 284119 Partition AR/SR 1
XDSF16 283892 Busbar support L1-L3, N 3
XDSF16E 283893 Busbar support L1-L3, N, end bracket, bottom 1
XDSFP 283895 Bracket for PE conductor in AR 3
XDSFN 283894 Bracket for N conductor in AR 3
XDB06 283885 Cross profile for dropper bar rear 4
XBSB164 283865 Busbar support L1-3,N 3
XBBB10 283862 Cross support for busbar bracket 2
XBSP 283872 Halter PE or PEN 2
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 79/143
Moeller FK4810-1143GB-INT
O r d e r i n g i n f o r m
a t i o n
12/4 Ordering examples
Function Section with outgoers for switch-fuse units, cable connection area 600 mm
Degree of protection IP31
Main busbars Operating current 2500 A, TN-S, rear mounting position
Dropper bars Operating current 1600 A, TN-S
Internal partitioning Form 3b
Outgoers 2 x switch-fuse unit 630 A, 3-pole
6 x switch-fuse unit 250 A, 3-pole
12 x switch-fuse unit 160 A, 3-pole
Type Article no. Description Quantity
XSFB1206 284243 Frames top/bottom 1
XAP011206 283834 Plinth 100 mm 1
XSFH20 284245 Vertical profiles 1
XSMSHD06 284274 Section mounting kits for SASIL 1
XPFCB06 284746 Busbar area partition form 2b 1
XPSS2006 284178 Partition section/section 1XSDSCRV2006 284229 Cable coupling area door, ventilated 1
XSWV2012 284364 Back plate, ventilated 1
XAD1206 283816 Top plate with canopy, ventilated 1
XDSSV16 283905 Fitting kit for dropper bar L1-3 1
XDSFP 283895 Bracket for PE conductor in AR 3
XDSFN 283894 Bracket for N conductor in AR 3
XBSB254 283871 Busbar support L1-3,N 2
XBBB12 283863 Cross support for busbar bracket 2
XBSP 283872 Halter PE or PEN 2
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 80/143
12/5
Moeller FK4810-1143GB-INT
O r d e r i n g i n f o r m
a t i o n
Ordering aid for switch-fuse units SASIL andfuse-load switch units SL from Jean Müller
Switch fuse units SASIL
Types which can be usedfor xEnergy
Description
SSA-185 Busbar shroud section IP20, module height 150 mm,12 x per section for horizontally installed SASIL switch-fuse unit strips are necessary
KA/SSA-185 Cable connection area cover, module height 150 mm,12 x per section for horizontally installed SASIL switch-fuse unit strips are necessary
BS1/SST Kit attachment rail (2 off) for busbar shroud sections, 1 x per section required
BL/SASIL00-3 Socket terminal strip 16-pole
AW/SASIL00-3 Retractable tool
LF01/SASIL 00-50 (1,2-3) Strip guide, kit for installation of a SASIL switch-fuse unit strips
KSH/SASIL00-50(1,2-3) Cable barrier, kit for sealing cable connection area/cabinet
LFA-D3/SASIL00-50(1,2-3) Empty section cover, transparent
LFALH-D3/SASIL1(2-3) Empty section covers, transparent, with IP30 ventilation points
LFA050(075,150,300)/25 Empty section covers sheet steel
LFA050(075,150,300)L/25 Empty section covers sheet steel, ventilation slots IP30
Fuse-load switch units SLSH100/185 Busbar support (2 off each already contained in the XSML...)
Notes Date: 25.06.04
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 81/143
Moeller FK4810-1143GB-INT
O r d e r i n g i n f o r m
a t i o n
12/6 Ordering help for reactive power compensation from FRAKO
The supplier for power factor correction modules, regulator and fans is FRAKO. The expansion of the xEnergy sections is implemented on the basis of therange of offers and assembly instructions from FRAKO.Address: FRAKO GmbH, Tscheulinstr. 21 A, D-79331 Teningen, Germany Tel. +49 (0)7641-453-0, Fax. +49 (0)7641-453-535
Total power Power ranges Operating sequence Type Weight
Article no. approx. (kg)
kvar kvar
Non-choked module for 600 mm section width and 600/800 mm section depth for all versionsDimensions (W x H x D) 500 x 300 x 350 mm
50 12.5 1:1:2 C64C-50-12,5-21-400/440-64
50 25 1:1 C64C-50-25-2-400/440-64
50 50 1 C64C-50-50-1-400/440-64
100 12.5 1:1:2:4 C64C-100-12,5-211-400/440-64
100 25 1:1:2 C64C-100-25-21-400/440-64
100 50 1:1 C64C-100-50-2-400/440-64
Accessories: support rail kit complete for C modules in xEnergy 600 mm deep
for busbars rear 34-80173
without busbars or for busbar top 34-80174
Choked modules for 600 mm section width and 600/800 mm section depth without busbarsor for busbars topDimensions (W x H x D) 500 x 300 x 350 mm for C64D... , 500 x 300 x 550 mm for C66D...
50 12.5 1:1:2 C64D-50-12,5-21-400/440-64-P...1)
50 25 1:1 C64D-50-25-2-400/440-64-P...1)
50 50 1 C64D-50-50-1-400/440-64-P...1)
100 25 1:1:2 C66D-100-25-21-400/440-66-P...1)
100 50 1:1 C66D-100-50-2-400/440-66-P...1)
Accessories: support rail kit complete for C modules in xEnergy 600 mm deep
without busbars or for busbar top 34-80174
Non-choked module for 800 mm section width and 600/800 mm section depth for all versionsDimensions (W x H x D) 700 x 300 x 350 mm
50 12.5 1:1:2 C84C-50-12,5-21-400/440-8450 25 1:1 C84C-50-25-2-400/440-84
50 50 1 C84C-50-50-1-400/440-84
100 12.5 1:1:2:4 C84C-100-12,5-211-400/440-84
100 25 1:1:2 C84C-100-25-21-400/440-84
100 50 1:1 C84C-100-50-2-400/440-84
tAccessories: support rail kit complete for C modules in xEnergy 600 mm deep
for busbars rear 34-80173
without busbars or for busbar top 34-80174
Notes Date: 18.11.20041) Choked 5.67 % = P5; 7 % = P7; 8 % = P8
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 82/143
12/7
Moeller FK4810-1143GB-INT
O r d e r i n g i n f o r m
a t i o n
Ordering help for reactive power compensation from FRAKO
Total power Power ranges Operating sequence Type Weight
Article no. approx. (kg)
kvar kvar
Choked module for 800 mm section width and 600/800 mm section depth for all versionsDimensions (W x H x D) 700 x 300 x 350 mm
50 12.5 1:1:2 C84D-50-12,5-21-400/440-84-P...1)
50 25 1:1 C84D-50-25-2-400/440-84-P...1)
50 50 1 C84D-50-50-1-400/440-84-P...1)
100 25 1:1:2 C84D-100-25-21-400/440-84-P...1)
100 50 1:1 C84D-100-50-2-400/440-84-P...1)
Accessories: support rail kit complete for C modules in xEnergy 600 mm deep
for busbars rear 34-80173
without busbars or for busbar top 34-80174
Notes 1) Choked 5.67 % = P5; 7 % = P7; 8 % = P8Other versions on request
Type
Article no.
Regulator, controller, fans
6-stage regulator packagewith regulator terminal strip on the top-hat rail
STR-RM 9606-150034-72016
12-stage regulator packagewith regulator terminal strip on the top-hat rail
STR-EMR 1100S-150034-72024
Connection from the rear CU-AW 134-80006
Complete IP31 fan package
Top mounted fan with thermostat
LP-LSFC
34-80096Complete IP54 fan packageDoor fan with thermostat
LP-LSFC IP54-3426/134-80169
Control mounting panelFor fitting the regulator terminal strip, thermostat, control transformer, core-balance transformer, etc.
for 600 mm section width SB-C634-80069
for 800 mm section width SB-C834-80053
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 83/143
Moeller FK4810-1143GB-INT
O r d e r i n g i n f o r m
a t i o n
12/8 Notes
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 84/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/1Contents
Page
System description
Product features 13/2
Main busbars and section depths 13/4
Power sections
For circuit-breakers up to 1600 A 13/5For circuit-breakers up to 4000 A 13/6
Device installation and section width 13/7
Outgoer sections
For fixed installation modules up to 630 A, form 2b 13/8
For fixed installation modules up to 630 A, form 4b 13/9
For fixed installation modules up to 630 A, form 4b,cable connection on rear
13/10
For fixed installation modules up to 630 A, functional areas 13/11
Outgoer sections without dropper bars
For fixed installation modules up to 630 A 13/12
Outgoer section module heights and component installation
Horizontal switch installation 13/13
Vertical switch installation 13/14
Module panels for rail-mounted service installation devices,measuring devices and control circuit devices
13/16
Outgoer sections
For switch-fuse units 13/17
For fuse-load switch units 13/18
Empty sections
For universal application 13/19
ARCON® arc fault protection system 13/20
ARC-Detection arc fault detection system 13/20
Planing tools 13/21
Planning notes
Heat dissipation 13/22
Heat dissipation, weights 13/23
Further information
Project checklist 13/24
Tender text 13/25
TTA conform to IEC/EN 60439-1 13/26
Test list for low-voltage switchgear assemblies 13/27
Rated/short-ci rcuit current of standard transformers 13/30
Internal partitioning 13/31
xEnergy installation instructions 13/33
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 85/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
13/2 System descriptionProduct features
• Incoming supplies, outgoers or couplings• With circuit-breakers NZM4 up to 1600 A• With circuit-breakers IZM up to 4000 A• With withdrawable or fixed mounted units
• In 3-pole or 4-pole version• Clear separation into functional areas from Form 1 up to Form 4b• Cable connection from top or bottom
• For outgoers with circuit-breaker NZM up to 630 A, in 3-pole or4-pole version
• For fuse switch-disconnector GSTA• For motor-protective circuit-breaker PKZ with contact module up to
34 kW/400 V• For miniature circuit-breaker FAZ
• For control circuit devices RMQ Titan• For measurement device installation• Cable connection from above or below, with separate cable connection
area in the right or left hand section of the distribution section• Clear separation into functional areas from Form 1 up to Form 4b
Power sectionsfor circuit-breakers up to 4000 A
Outgoer sectionsfor fixed installation modules up to 630 A
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 86/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/3System descriptionProduct features
• Outgoers with switch-fuse units SASIL up to 630 A• With plug-in or fixed mounted units• Vertical or horizontal installation• In 3-pole version
• Cable connection from top or bottom
• Outgoers with fuse-load switch units SL up to 630 A• Fixed mounted• Vertical installation• External operation or behind the door actuation• In 3-pole version• Cable connection from top or bottom
• Service distribution system• Control engineering• xStart adapter system• Frequency inverters, soft starters• Automation engineering• Power factor correction
Outgoer sections for switch-fuse unitsand fuse-load switch units
Empty sectionsfor universal use
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 87/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
13/4 System descriptionMain busbars and section depths
Busbarrated current I e
(Cu cross-sections)
1600 A (2 x 40 x 10 mm2)2000 A (2 x 60 x 10 mm2)2500 A (2 x 80 x 10 mm2)3200 A (3 x 80 x 10 mm2) 4000 A (3 x 80 x 10 mm2)
Installation positionrear
(side view)
Busbarrated current I e
(Cu cross-sections)
800 A (2 x 20 x 10 mm2)1250 A (2 x 40 x 10 mm2)1600 A (2 x 60 x 10 mm2)
1250 A (2 x 40 x 10 mm2)1600 A (2 x 60 x 10 mm2)2000 A (2 x 80 x 10 mm2)2500 A (2 x 100 x 10 mm2)3200 A (2 x 120 x 10 mm2)
Installation positiontop
(side view)
Busbar area Component mounting area
600
2 0 0 0
800
2 0 0 0
400
2 0 0 0
600
2 0 0 0
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 88/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/5Power sectionsFor circuit-breakers up to 1600 A
For NZM4 compact circuit-breakers: • With drawer units or fixed mounted units• In 3-pole or 4-pole version• As incomer, outgoer or coupling switch or with busbar position top only
as an incomer or outgoer switch• The current transformer can be installed between the connection and
switch for measurement purposes.Dimensions • Section width 425 or 600 mm• Section height 2000 mm, optional with plinth 100 or 200 mm• Section depth 600 or 800 mm; section depth 800 mm only with busbar
position rear
Cable connection area• Incomers from above or below; with busbar position top only incomers
from below are possible• Connection directly on the cable lugs
With internal partitioning form 1 to form 2b:• With a front door in panel height• Door ventilated, without apertures or transparent
• With door hinges on right or left• Operation of a switch behind the door or with an extension shaft and
external door coupling rotary handle
With internal partitioning form 4b:• 2 component mounting area doors each above and below the switch,
as well as a surround with quick-release fasteners centrally before theswitch
• External operation of a switch• Door ventilated or without apertures• With door hinges on right or left• Areas not used for cable connection can be used for additional fittings,
e.g. for controls or overvoltage protection.
Section width 425 mm and 600 mm,internal partitioning to form 2b
Section width 425 mm and 600 mm,internal partitioning to form 4b
425
425(600)
425
425(600)
425
425(600)
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 89/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
13/6 Power sectionsfor circuit-breakers up to 4000 A
For air circuit-breaker IZM • With drawer units or fixed mounted units• In 3-pole or 4-pole version• As incomer, outgoer or coupling switch or with busbar position top only
as an incomer or outgoer switch• The current transformer can be installed between the connection and
switch for measurement purposes.Dimensions• Section width 425, 600, 800 or 1200 mm• Section height 2000 mm, optional with plinth 100 or 200 mm• Section depth 600 or 800 mm; section depth 800 mm only with busbar
position rear
Cable connection area• Incomers from above or below; with busbar position top only incomers
from below are possible• Connection directly on the cable lugs
or• Connection to cable connection systems without drilling requirement
across the entire section width with contact from the front
Internal partitioning from form 1 to form 4 b • Ready to fit partition sheets for section expansion up to form 4• 2 component mounting area doors each above and below the switch,
as well as a surround with quick-release fasteners centrally before theswitch
• External operation of a switch• Door ventilated or without apertures• With door hinges on right or left• Areas not used for cable connection can be used for additional fittings,
e.g. for controls for overvoltage protection.
Section width 600 to 1200 mm,internal partitioning to form 4b
Cable direct connection
Cable connection system: connection without drilling requirement acrossthe entire section width with contact from the front
Basic Internal partitioningup to form 4b
425 800
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 90/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/7Power sectionsDevice installation and section width
Section width,3-pole
Section width,4-pole
Compact circuit-breakertype NZM4,
up to 1600 A
Air circuit-breakertype NZM4,up to 1600 A
Air circuit-breakertype IZM,up to 3200 A
Air circuit-breaker
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 91/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
13/8 Outgoer sectionsFor fixed installation modules up to 630 A, form 2b
• For circuit-breakers, motor starters, miniature circuit-breakers andfuse switch-disconnectors
• In horizontal and vertical mounting position• Installation of the switchgear in a mounting plate on mounting plate
in a width of 425 or 600 mm• Internal partitioning to form 2b
• On the input side the connection to the connection to verticallyorientated dropper bar system is protected against accidental contact(by mounting plate).
• The cable connection is implemented on the side in the right or left partof the distribution section.
• With a front door in panel height, ventilated, without apertures ortransparent, with door hinges on right or left
• Operation of a switchgear behind the door or with an extension shaftand external door coupling rotary handle
Horizontal fixed installation
Vertical fixed installation
Information about the packing density from page 3/3.
Section width 600, 800 or 1000 mm,door without apertures or transparent
The cable connection area in various installation positions in the 200 and400 mm widths.
Installation of the switchgear on predrilled mounting plate, with all fixingand connection openings, preprepared for installation.
Circuit-breakers Module height (HU/mm)
3-pole 4-pole
25 A 2/50 –
40 A 4/100 4/10063 A 4/100 –
125 A 4/100 6/150
250 A 6/150 8/200
630 A 8/2001) 10/2501)
1) Horizontal installation NZM3 (up to 630 A) only for 600 mm width modules
Circuit-breaker Module height1)
(HU/mm)
Number of circuit-breakers per module
425 mm 600 mm
125 A 12/300 2 3
250 A 16/400 2/12) 3/22)
630 A 24/600 1 2/12)
1) Vertical installation of the devices preferably at the top and/or bottom of the sec-tion, depending on the cable entry. With vertical installation in the section middleor provided if necessary with more height units for cable entry.
2) 4-pole
425
600
6 4 H U
=
1 6 0 0 m m ( b
u s b a r t o p )
7 6 H U
=
1 9 0 0 m m ( b
u s b a r r e a r )
425
800
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 92/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/9Outgoer sectionsFor fixed installation modules up to 630 A, form 4b
• For circuit-breakers, motor starters and miniature circuit-breakers• In horizontal and vertical mounting position• The switchgear is installed behind module panels and is situated in
an operator level.• The module panels are provided with hinges, can be swivelled and
allow access to each individual module.
• Mounting plate in widths 425 or 600 mm• Installation of internal partitioning to form 4b1) • On the input side the connection to the connection to vertically
orientated dropper bar system is protected against accidental contact.• The cable connection is implemented on the side in the right or left part
of the distribution section.• The cable connection area is accessible via a separate cable connection
area door and can be sealed off from the busbar and componentmounting area.
• External operation of the switchgear via cut-outs in the module panels• Can be optionally equipped with a front door in panel height,
ventilated, without apertures or transparent, with door hinges on rightor left
Information about the packing density see page 13/8.
1) consider additional terminals if necessary.
Section width 600, 800 or 1000 mm,door without apertures or transparent component mounting area door
Installation of the switchgear on predrilled mounting plate, with allfixing and connection openings, preprepared for installation. Swivellingcover plate with cut-out for the actuating lever for external operation.
The cable connection area in various installation positions in the 200 and400 mm widths.
425
600
6 4 H U =
1 6 0 0 m m ( b
u s b a r t o p )
7 6 H U =
1 9 0 0 m m ( b
u s b a r r e a r )
425
800
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 93/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
13/10 Outgoer sectionsFor fixed installation modules up to 630 A, form 4b
• For circuit-breakers, motor starters and miniature circuit-breakers• In horizontal and vertical mounting position• The switchgear is installed behind module panels and is situated in
an operator level.
• The module panels are provided with hinges, can be swivelled andallow access to each individual module.
• Mounting plate in widths 425 or 600 mm• On the input side the connection to the connection to vertically
orientated dropper bar system is protected against accidental contact.• The cable connection area is located at the rear left, the cable is
connected from the rear.• Installation of internal partitioning to form 4b• External operation of the switchgear via cut-outs in the module panels• Can be optionally equipped with a front door in panel height,
ventilated, without apertures or transparent, with door hinges on rightor left
• Can only be used with busbar position top
Section width 425 or 600 mm,door without apertures or transparent
Minimal section width due to cable connection from the rear.The distribution system must be accessible from the rear.
For cable connection from the rear
425
6 4 H U =
1 6 0 0 m m ( b
u s b a r t o p )
600
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 94/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/11Outgoer sectionsfor fixed installation modules up to 630 A
Busbars rear
Busbars top
1 component mounting area
2 cable connection area
3 dropper bar
4 main busbars
Functional areas
a
c
b
d
b
d
a
c
a
d
b
c
b
d
a
c
a
d
b
c
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 95/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
13/12 Outgoer sections without dropper barsfor fixed installation modules up to 630 A
• For circuit-breakers and miniature circuit-breaker• In vertical mounting position• The switchgear is fitted vertically on mounting plates and can be offset
at the required depth for installation.• Mounting plate width 425, 600, 800 or 1000 mm• On the input side the connection is made directly from the main busbar.
• The main busbars can be covered and protected against accidentalcontact (internal partitioning to form 2).• The cable connection is established from below either directly on the
switchgear or on the terminals in the lower section.• With a front door in panel height, ventilated, without apertures or
transparent, with door hinges on right or left• Alternatively with doors on the front and rear for device installation on
both sides• Operation of switchgear behind the door or with an extension shaft and
external door coupling rotary handle• Can only be used with busbar position top
Section width 425, 600, 800 and 1000 mm
Double sided installation
425
6 4 H U
=
1 6 0 0 m m ( b
u s b a r t o p )
600
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 96/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/13Outgoer sectionsModule heights and component installation: horizontal switch installation
Module width
Motor-starter combination up to 32 A PKZM0 type, 2 HU = 50 mm
Motor-starter combination up to 40 APKZ2 type, 4 HU = 100 mm
Motor-protective circuit-breaker up to 63 APKZM4 type, 4 HU = 100 mm
Circuit-breaker up to 160 A, 3-poleNZM1 type, 4 HU = 100 mm
Circuit-breaker up to 160 A, 4-poleNZM1 type, 6 HU = 150 mm
Circuit-breaker up to 250 A, 3-poleNZM2 type, 6 HU = 150 mm
Circuit-breaker up to 250 A, 4-poleNZM2 type, 8 HU = 200 mm
Circuit-breaker up to 630 A, 3-poleNZM3 type, 8 HU = 200 mm
Circuit-breaker up to 630 A, 4-poleNZM3 type, 10 HU = 250 mm
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 97/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
13/14 Outgoer sectionsModule heights and component installation: vertical switch installation
Module width
Circuit-breaker up to 160 A, 3-poleNZM1 type, 12 HU = 300 mm
Circuit-breaker up to 160 A, 4-poleNZM1 type, 12 HU = 300 mm
Circuit-breaker up to 250 A, 3-poleNZM2 type, 16 HU = 400 mm
Circuit-breaker up to 250 A, 4-poleNZM2 type, 16 HU = 400 mm
Circuit-breaker up to 250
A, with plug-in module, 3-poleNZM2 type, 24 HU = 600 mm
Circuit-breaker up to 250A, with plug-in module, 4-poleNZM2 type, 24 HU = 600 mm
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 98/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/15Outgoer sectionsModule heights and component installation: vertical switch installation
Module width
Circuit-breaker up to 630A, fixed installation, 3-pole
NZM3 type, 24 HU = 600 mm
Circuit-breaker up to 630A, with withdrawable unit, 3-poleNZM3 type, 24 HU = 600 mm
Circuit-breaker up to 630A, fixed or with withdrawable unit, 4-poleNZM3 type, 24 HU = 600 mm
Fuse base or switch-disconnector up to 160 A, 3-poleType GS00/GSTA00, 12 HU = 300 mm
Fuse base or switch-disconnector up to 250 A, 3-poleType GS1/GSTA1, 16 HU = 400 mm
Fuse base or switch-disconnector up to 400 A, 3-poleType GS2/GSTA2, 16 HU = 400 mm
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 99/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
13/16 Outgoer sectionsModule height, component installation: module panels, measuring and control circuit devices
Module width
Modular installation devices/PKZ...1 x 12 SU/1 x 24 SU, 6 HU = 150 mm
1 x 12 SU/1 x 24 SU, 8 HU = 200 mm
2 x 12 SU/2 x 24 SU, 12 HU = 300 mm
2 x 12 SU/2 x 24 SU, 16 HU = 400 mm
Modules for terminals6 HU = 150 mm
12 HU = 300 mm
Cover platesFor control circuit and signalling device installation9 x RMQ-Titan/12 x RMQ-Titan, 4 HU = 100 mm
For measurement device installation4 x 72 x 72 mm + 1 changeover contact8 HU = 200 mm/6 HU = 150 mm
2 x 72 x 72 mm + 2 changeover contacts6 HU = 150 mm
4 x 96 x 96 mm + 1 changeover contact8 HU = 200 mm
2 x 96 x 96 mm + 2 changeover contacts8 HU = 200 mm
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 100/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/17Outgoer sectionsFor switch-fuse units
• For switch-fuse units of the SASIL type, Jean Müller• With double break feature• In vertical or horizontal mounting position
Component mounting area:• Operation of the switchgear externally or from behind the door
• Connection of the switch unit input side to a vertically orientated drop-per bar system, optionally available with plug-in technology and pro-tected against accidental contact
• The dropper bar available across the entire section width with contactfrom the front.
Dropper bars:• Interval between phase centres 185 mm• Rated current up to 1600 A• Rated short-time withstand current I cw up to 65 kA
Cable connection area :• The cable connection is implemented in the right section of the distri-
bution section, the outgoer cables can be introduced from above orbelow.
• The connections of the switch-fuse units can be optionally covered withcable barriers for protection against accidental contact.• Cable anchoring rails assure secure guidance of the outgoer cable.• The cable connection area is accessible via a separate cable connection
area door and can be sealed off from the busbar and componentmounting area.
• Vertical PE, N or PEN busbars are installed in the cable connection areaand can be equipped with terminations for every outgoer cable.
Vertical installation:• Connection of the switch unit input side to a horizontally orientated
dropper bar system• The cable connection is implemented from the top or bottom• The cable connection area is accessible via a separate cable connection
area door.• Areas not used for cable entry can be used for additional fittings, e.g.
for controls.• External actuation of the switchgear
Section width 1000 and 1200 mm (horizontal installation)Section width 600, 800 and 1000 mm (vertical installation),Internal partitioning to form 4
Switch-fuse units can only be used with busbar position rear.Please observe the max. current carrying capacity of the switch-fuse unitsin dependance on the ambient temperature, degree of protection andnumber of switch-fuse units per section in accordance with the xEnergytechnical data.
1000
1000/1200
Type I e up to Size Number per sec-tion
A mm
SASIL00 160 50 30
SASIL1 250 75 20
SASIL2 400 150 10
SASIL3 630 150 10
Type I e up to Size
A mm
SASIL00 160 50
SASIL1 250 75SASIL2 400 150
SASIL3 630 150
Section width Max. installation space
mm mm
600 500
800 700
1000 900
800
600/800/1000
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 101/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
13/18 Outgoer sectionsFor fuse-load switch units
• For fuse-load switch units SL, Jean Müller• With single break• In vertical mounting position
Component mounting area:• Operation of the switch-fuse units externally or from behind the
door• Connection of the switch unit input side to a horizontally orientated
dropper bar system• The dropper bar available across the entire height with contact from the
front.
Dropper bars:• Interval between phase centres 185 mm• Rated current up to 1600 A• Rated short-time withstand current I cw up to 65 kA
Cable connection area :• The cable connection is implemented from the top or bottom.• The connections of the switch-fuse units can be individually covered for
protection against accidental contact.
• Cable anchoring rails assure secure guidance of the outgoer cable• The cable connection area is accessible via a separate cable connectionarea door and can be sealed off from the busbar and componentmounting area.
• Areas not used for cable entry can be used for additional fittings, e.g.for controls.
Section width 600, 800 and 1000 mm,internal partitioning to form 4
Switch-fuse units can only be used with busbar position rear.Please observe the max. current carrying capacity of the switch-fuse unitsin dependance on the ambient temperature, degree of protection andnumber of switch-fuse units per section in accordance with the xEnergytechnical data.
800
600/800/1000
Type I e up to Size
A mm
SL00 160 50
SL1 250 100
SL2 400 100
SL3 630 100
Section width Max. installation space
mm mm
600 500
800 700
1000 900
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 102/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/19Empty sectionsfor universal application
Universal empty sections for the following installation possibilities:
Control engineering e.g. with the Moeller fast mounting and wiringsystem MR25
Main catalogue HPL0214,Power Distribution Systems orElectronic Catalogue
Service distribution system e.g. with Moeller IVS Main catalogue HPL0214,Power Distribution Systems orElectronic Catalogue
Component adapter e.g. with Moeller xStart Main Catalogue HPL0211,Industrial Switchgear orElectronic Catalogue
Frequency inverters e.g. Moeller DF5/6 and DV5/6 Main Catalogue HPL0213, Automation Systemsand Drives orElectronic Catalogue
Soft starters e.g. Moeller DS4 and DM4 Main Catalogue HPL0213, Automation Systemsand Drives orElectronic Catalogue
Automation engineering e.g. with Moeller PS4 Main Catalogue HPL0213, Automation Systemsand Drives orElectronic Catalogue
Large motor starters e.g. with Moeller contactors up to450 kW/400 V
Main Catalogue HPL0211,Industrial Switchgear orElectronic Catalogue
Reactive power compensation e.g. with FRAKO Chapter 5
With a front door in panel height, ventilated, without apertures or transparent, with door hinges on right or left
425
600
800
1000
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 103/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/20 ARCON® arc fault protection systemARC-Detection arc fault detection system
On low-voltage switchgear systems with a high requirement for operatingcontinuity, ARCON offers maximum protection during an arc-fault andguarantees a high level of security for operating personnel and switchgearsystems. ARCON also offers personnel protection with opened control
panel doors.
By parallel detection of an arc-fault with light and current sensors: theoptical sensors monitor and signal the characteristic frequency range of thearc-fault. If a current transformer simultaneously detects and overcurrent(2 x I n), the electronics sends a signal to the quenching device and to theincoming circuit-breakers.The ARC-AT quenching device generates a three-pole metallic short-circuitand thus dissipates and limits the energy from the arcto a max. arc time of 2 ms.As a result, the pressure and temperature parameters which can destroythe system are limited at a very early stage. The effects of an arc remainlimited to the foot points of the arc.
Causes which can lead to the occurrence of an arc include• Operating and handling faults (e.g. a tool forgotten after maintenance)• Connection faults (e.g. with transport split)• Foreign bodies in the system (e.g. rodents)• Overvoltages (e.g. by switching processes)
What happens after an arc-fault?• After an arc-fault the cause must be found and eliminated.• The quenching device is exchanged.• After an insulation test has been performed, the system is ready for
renewed operation.
ARC-AT quenching device
The ARC-Detection arc fault detection system consists of ARCON sensorsand the ARCON evaluation (master unit and slave modules). The arc isdetected by the detection system, evaluated and shutdown via the
incoming circuit-breaker.Point sensors (ARC-SP) are used for optical monitoring of the system.These point sensors are based on electro-optical phototransistors and canbe quickly and easily positioned in the switchgear system.
Parallel to the detection of the light emission, monitoring of the arc-fault
current is the second criteria for shutdown of an arc-fault. The currentdetection is implemented via a measurement transformer which isinstalled before every incoming circuit-breaker.
The total shutdown time of the arc-fault detection system is primarilydetermined by the break time of the circuit-breaker, and is between 25 and70 ms. In addition to the improved personnel protection, the sensors alsooffer improved system protection. The effects of the arc fault remainlimited to the arc-fault relevant section.
Use of ARCON1)
The ARCON arc-fault protection system for the xEnergy system is availableto the local panel builder. The functional installation is performed inaccordance with the stipulations and technical documents from Moeller.
The installation of the ARCON arc-fault protection system in xEnergy isperformed under the following prerequisites:All ARCON system components are used exclusively for the installation inthe xEnergy switchgear system.
The panel builder completes an ARCON system training with the followingcontent:• System/functions• Selection/engineering• Installation/commissioning
Moeller awards a certificate after the ARCON training has been completedwhich certifies the qualification for the application of ARCON in xEnergyswitchgear systems.
Moeller service for ARCONFurthermore, Moeller offers onsite service. The costs result on the basis ofa project related offer.
1) available upon request
When should ARCON® be used?
How does ARCON® function?
ARCON® operational conditions in xEnergy
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 104/143
13/21
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Planning tools
Moeller Engineering Tools support you in• Network planning and calculation• Preparation of offers• Engineering distribution systems
• Generation of parts lists and ordering
Proven functions for network planning and calculation• Load flow and short-circuit calculation• Dimensioning of the devices• Selectivity calculation• Conformity to the DIN VDE 0102 (IEC 909) and DIN VDE 0289 standards• Automatic verification of data completeness
Competence and experience• NetPlan simplifies and speeds up the work by relieving you from time-
consuming routine work.• NetPlan guarantees against planning faults in low-voltage networks.
Functional and flexible• Type database with the device data of the equipment• Modular programming structure allows adaptation to changing
demands.
With Moeller NetPlan you plan low voltage networks (meshed systems and
radial networks) safely and without problems.
Simple operation with the selection of xEnergy• Windows based dialogs• Functional, self-explanatory design• Short familiarisation times with look and feel
Flexible applications• Project administration and system structure• The most suitable distribution system is automatically generated via the
function guided system selection.
• Generation of a materials part list for devices, fitting kits and power dis-tribution
• Inclusion of devices from other manufacturers simplify fast order gener-ation
• Generation of a front view for orders, individual matching with drag anddrop
Moeller ConFix is the fastest selection tool for xEnergy.
The engineering tool for creation of plan types:• Device assignment plans
• Parts list• Circuit diagrams, terminal assignments• Cable plans and lots more
The fastest way to a circuit diagram• Intelligent assistant• Drag and drop from the symbol library or from the material database
MatSelect• Standard conform circuit diagram to DIN 61082
Full overview• One and multiple screen solutions can be freely selected• Unrestricted nesting levels of the system, location and project structure• Localisation of equipment at the touch of a button as required
Simple application friendliness• Windows based dialog guidance and self-explanatory design structure
• Short familiarisation times with look and feel
Comfortable distribution engineering including design drawings andcircuit diagram with Moeller ProPlan
The right tool for every phase of the project
Moeller NetPlan
Moeller ConFix
Moeller ProPlan
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 105/143
13/22
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
Planning notesHeat dissipation
Calculation of effective heatdissipation
Note:The installed losses per section are requiredonly where the overall heat dissipation of
the switchgear assembly must bedetermined, such as for the rating of air-conditioning or ventilated systems in switchrooms.
Effective heat dissipation:
P = P w1 + P w2 + P w3 + P w...
Heat dissipation at rated current of thecircuit:
P e = P n x
Effective heat dissipation taking intoaccount the rated diversity !:
P w1 = P n x !2
Characters used in the formulae:
P = Overall heat dissipation
P n = Heat dissipation at rated currentof circuit device
P e = Heat dissipation at rated currentof circuit
P w1...n = Effective heat dissipation of thegroup of services
I n = Rated current of the device
I e = Rated current of the current circuit
! = Rated diversity factor
Heat Dissipation
Incomers / outgoers / couplers, 630 – 6300 A with IZM circuit-breakers
Outgoers with fuse-load switch units SL with h.b.c. fuses up to 630 A
Incomers/outgoers with circuit-breakers up to 630 A
Outgoers with switch-fuse units SASIL with h.b.c. fuses up to 630 A
I e
I ----
" #$ %& '
2
Rated current of circuit-breakersA
Heat dissipation in WFixed mounted
Heat dissipation in Wwithdrawable
630 100 195
800 100 195
1000 100 195
1250 105 205
1600 170 350
2000 180 320
2500 270 520
3200 410 710
4000 520 810
Fuse size / rated currentA
Heat DissipationW
00/160 54
1/250 119
2/400 184
3/630 254
Rated current of circuit-breakersA
Heat Dissipation
W
125 38
160 43
250 57
400 52
630 120
Rated currentA/ size NH
Heat dissipation in W double-break
00/160 80
1/250 150
2/400 230
3/630 410
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 106/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/23Planning notesHeat dissipation, weights
Motor starters
Power factor correction
Empty sections for general fittings
Main busbar, heat dissipation
Dropper bar, interval between phase centres 60 mm, heat dissipation
Weight for distribution section with max. equipment fittedAll weight details are based on weights of representative sample sections.
AC-3 motor rating at 400 V kW Heat dissipationW
11 10
18.5 20
30 2045 40
75 60
110 70
160 80
200 130
Heat dissipationW
with choke 8/kvar
non-choked 2/kvar
Section width / degree of protection Heat dissipationW
425 mm/IP30/31 max. 800
425 mm/IP55 max. 260
600 mm/IP30/31 max. 1000
600 mm/IP55 max. 340
800 mm/IP30/31 max. 1200
800 mm/IP55 max. 420
1000 mm/IP30/31 max. 1400
1000 mm/IP55 max. 500
Rated current
A
Installation position rear
Power dissipationW/m
Mounting position topInterval between phase centres 60 mmHeat dissipationW/m
125 mm
W/m
800 – – –
1250 – – –
1600 – – –
2000 – – –
2500 – – –
3200 – – –
4000 – – –
Rated current A Heat dissipationW
800 –
1250 –
1600 –
Feeder section/outgoer section with circuit-breaker IZM
1600 A2500 A3200 A
4000 A
280 kg360 kg550 kg
–Outgoer sections for fixed installation modules
630 A 280 kg
Sections with fuse-load switch units SL
630 A 250 kg
Sections with switch-fuse units , SASIL
630 A 500 kg
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 107/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
13/24 Further informationProject checklist
Project:
Project number:
Name of the switchgear system:
Date:
Customer:
Planner:
Telephone:
e-mail:
Place of installation:
Company type:
Ambient temperature: 35 °C
Standards: IEC/EN 60439-1
Rated operational voltage: 400 V V
Frequency: 50 Hz Hz
Transformer power: kVA
Rated incoming current: A
Rated short-time withstand currentof the main busbars I cw (1 s) kA
Degree of protection: IP31 IP55
Internal partitioning Form
With bottom plate yes no
System configuration: TN-C TN-S TN-C-S TT IT
PEN or N conductor cross-section half full
Control voltage AC: V
external internal kVA
Control voltage DC: V
external internal kVA
Control wiring mm2
Wiring designation
Space reserves %
Maximum permitteddistribution system dimensions W x H x D mm
Room height mm
Max. transport dimensions W x H x D mm
Arc fault protection conventional
ARCON® arc-fault protection system
ARC-Detection arc fault detection system
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 108/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/25Further informationTender text
• Ready to connect, steel-encapsulated low-voltage switchgear system inmultiple control panel design with type-tested mounting system to ICE/EN 60439-1 (VDE 0660 part 500).
• The following descriptions are components of the calculation and
contract. They are to be considered with the descriptions of theindividual systems and the equipment, even when they are not to bementioned in detail.
• A cabinet system consisting of modular individual sections of the sametype in torsionally-rigid steel profile design, made of electrolyticallygalvanized 2 mm thick steel sections, with internal pre-drilled holes at25 mm intervals to DIN 43660, structured powder spray paint RAL 7035light grey, open on the side, can be grouped.
• Removable external panelling, made of 1.5 mm electrolyticallygalvanized sheet steel, structured powder spray paint RAL 7035 l ightgrey.
• All construction parts for internal expansion are hot-galvanized andfeature pre-drilled holes at 25 mm intervals to DIN 43660.
• Plinth 100/200 mm high, electrolytic galvanisation, powder-coatedpaint-finish in RAL 7035 light grey, with removable front, side and rearpanels. The plinth must be suitable for direct transport with therespective tools.
• Control panels accessible from the front by supported doors withexternal hinges. Door opening angle 180°. Door interlock withespagnolette lock, 4 point locking and double-ward lock, actuation viaroller lever for half cylinder safety lock.
Fully assembled switchgear system described above ready to connect andprewired, subject to 100% test ex-factory to IEC/EN 60439 part 1. The testprotocol is part of the documentation.
• Degree of protection IP31 to DIN EN 60529IP55 with sealed door
• Protective measure: with protective conductor,protection class I
• Rate insulation voltage 690 V
• Overvoltage category: III
• Pollution degree 3
• Rated operational voltage V
• Frequency Hz
• Control voltage AC/DC V
• Busbar rated current A
• Rated short-time withstand current I cw kA/s
• Network system
• Busbar (number),conductor marking
• Largest permissible dimensions
Width
Height
Depth
• Largest permissible transport unit
Width
Height
Depth
• All transport units feature removable eyebolts.
• Equipment of the switchgear system with the following described,fixed installed equipment:
• Make Moeller
• Type xEnergy
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 109/143
13/26
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Further informationTTA conform to IEC/EN 60439-1
The safety standard for low-voltageswitchgear combinations1)
The requirement placed on low-voltageswitchgear in respect of heat dissipation,higher packing densities, control of high
short-circuits and insulation capacity haveincreased considerably over the last fewyears.
Rated currents of up to 6000 A and highshort-circuit ratings with rated short-timewithstand currents up to 100 kA are nolonger unusual.
The compact design, not to mention theintegration of electronic components intosupply networks subject to powerfulharmonics, requires precise rating andtesting of the switchgear assembly.
Safe operation of a low-voltage switchgearassembly is only ensured where the
manufacturer complies with theappropriate standard for the assembly inquestion and also verifies the fact.
Only switchgear assemblies which complywith current standards fulfil today's safetyregulations
1) The information contained on this pagereflects the information supplied in abrochure by the ZVEI (German electricaland electronic manufacturers')concerning this topic.
Current standards are:
IEC/EN 60439-1, VDE 0660 part 500;
Low-voltage switchgear combinations
Type-tested and partially type-tested
assemblies
These three standards are identical interms of content. They show twooptions for the manufacturing ofswitchgear assemblies:
– Type-tested assembly (TTA)– Partially type-tested assemblies (PTTA)
Type-tested assembly (TTA)
In assemblies of this sort, all componentsare type-tested separately and in theirfunctional state, including all electrical andmechanical connections.
Where other devices are used for switchingand protection, it is a requirement that thetechnical data are at least the same orbetter (argument by analogy).
Partially type-tested assemblies(PTTA)
Both type-tested and non type-testedcomponents are comprised in this type ofassembly. Non-type-tested componentsmust be based on type-tested ones.
Proof required of adherence to standards
Requirements Proof of TTA produced by Proof of PTTA produced by
1. temperature-rise limit Test Test or extrapolation
2. insulation resistance Test Test
3. short-circuit rating Test Test or extrapolation
4. effectiveness of the protective conductor Test Test
5. clearance and creepage distances Test Test
6. mechanical function Test Test
7. degree of protection IP Test Test
For type-tested assemblies, all proof isproduced by testing.With partially-type-tested assemblies, thereare two exceptions:
a) Proof of compliance with temperature-rise limits. For switchgear with amaximum input current of 3150 A, thisproof can also be provided by means ofextrapolation where calculation isperformed in accordance with DIN VDE0660 Part 507.
b) Proof of the short-circuit rating is notrequired for switchgear assemblies
which are protected by a current-limitingprotective device and where the let-through current 15 kA
Where an extrapolation or calculation toDIN VDE 0660 Part 509 is necessary, this isalways based on values derived from type-tested busbar systems.
Only where all information has been clearlyproduced can the terms type-tested low-voltage switchgear and controlgearassembly (TTA) and partially type-testedassembly (PTTA) be used. This combinationthus corresponds to the valid safetyregulations.
xEnergy is a tested and type-tested l.v. switchgear and controlgearassembly (TTA)
The type-testing is carried out in Moeller'sindependent, accredited test laboratory.
Quality assurance is undertaken inaccordance with a certified qualityassurancesystem (ISO 9001/EN 29001).xEnergy provides tested and verifiablesafety with consistently high quality.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 110/143
13/27
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Further informationTest list for low-voltage switchgear assemblies
Check list for TTA
for a low-voltage switchgear assembly toIEC/EN 60439-1, IEC/EN 60439-2 and IEC/EN 60439-3
DIN VDE 0660, Part 500, 502 and 504
Special application conditions ..................................................
Routine tests
Explanation of terms:
S = Visual inspection for compliance with requirementsP = Manual testing using mechanical or electrical measuring equipmentV = Comparison with production specifications
Customer:
Unit:
Order No.:
No. Type of test Tests VDE 0660Part 500Section
Resulttested by
Tester
1 – Type test 8.2.1 –
8.2.7
Test passed
2 P Mechanical function test(actuators, interlocks, etc.)
R o u
t i n e
t e s t s
8.3.1
3 S Component mounting to standard
4 S Correct cable routine
5 S/P Degree of protection of the enclosure
6 S/P Clearances, creepage distances and spacing
7 P Connection between components, between conductors and betweenconductors and their devices(random testing of tightening torque's)
8.1 P/V Conformance of the wiring with the circuit documentation
8.2 V Conformance with:designations, markings, completeness of instruction leaflets etc., withthe circuit diagrams and other documentation
9 P Insulation test 8.3.2
10 S/P Protective measures and earth continuity 8.3.3
11 P Electrical function test(when expressly specified)
8.3.1
Date Signature (Head of the construction organizational unit)
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 111/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/28 Further informationTest list for low-voltage switchgear assemblies
Test list for PTTA
for a low-voltage switchgear assembly toIEC/EN 60439-1, IEC/EN 60439-2 and IEC/EN 60890 (HD528 S1)
DIN VDE 0660, Part 500, 502 and 507
Special application conditions ..................................................
Verification / tests
Customer:
Unit:
Order No.:
No. Requirements VDE 0660Part 500Section
Tests Result Tester
1 Temperature-rise limit 8.2.1
T e s t s
Verification of conformance to temperaturerise-limit by means of testing, extrapolationfrom TTA or by determining toVDE 0660 Part 507
2 Insulation resistance 8.2.2 See No.10/
3 Short-circuit rating 8.2.3 Verification of short-circuit rating by testingor extrapolation of similar type-testedlayouts
4 Effectiveness of the protectiveconductor circuit
8.2.4 Verification of correct connection betweencomponents in the switchgear assembly andthe protective conductor by means ofinspection or resistance testsCorrect connection between exposed
conductive parts of the switchgearcombination and protective conductorcircuit
8.2.4.1
Short-circuit rating of theprotective conductor circuit
8.2.4.2 Verification of short-circuit rating ofprotective conductor by testing orappropriate implementation and layout ofthe protective conductor (see section7.4.3.1.1 of VDE 0660 Part 500)
5 Clearance and creepage distances 8.2.5 Verification of clearances and creepagedistances
6 Mechanical function 8.2.6 Verification of mechanical function
7 Degree of protection IP 8.2.7 Verification of IP Degree of protection
8 EMC 8.2.8 Verification of the EMC conformityand adherence to the demands of7.10.2. a) and b)
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 112/143
13/29
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Further informationTest list for low-voltage switchgear assemblies
Explanation of terms:
S = Visual inspection for compliance with requirementsP = Manual testing using mechanical or electrical measuring equipmentV = Comparison with production specifications
No. Type oftest
Tests VDE 0660 Part500 Section
Result testedby
Tester
9.1 P Mechanical function test(actuators, interlocks, etc.)
T e s t s
8.3.1
9.2 S Component mounting to standard
9.3 S Correct cable routine
9.4 S/P Degree of protection of the enclosure
9.5 S/P Clearances, creepage distances and spacing
9.6 P Connection between components, between conductors andbetween conductors and their devices (random testing oftightening torque's)
9.7 P/V Conformance of the wiring with the circuit documentation
9.8 V Conformance with:designations, markings, completeness of instruction leaflets etc.,
with the circuit diagrams and other documentation
9.9 P Electrical function testing (if prescribed,agreement user/manufacturer, FO322)
10 P Insulation testorVerification of the isolation resistance of the isolation resistance
8.3.2
8.3.4
11 S/P Protective measures and earth continuity 8.3.3
Date Signature (Head of the construction organizational unit)
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 113/143
13/30
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Moeller FK4810-1143GB-INT
Further informationRated/short-circuit current of standard transformers
Approximation formulaTransformer rated current
I N [A] = k × SNT [kVA]
400 V: k = 1.45500 V: k = 1.1690 V: k = 0.84
Transformer short-circuit current
Dimensioning of low-voltageswitchgear assemblies
In the main, when rating switchgear
assemblies with regard to short-circuitwithstand strength, the rated short-circuitvalues must be compared with the short-circuit currents of the incoming powersupply. The switchgear assembly must berated merely for the short-circuit load whichcan occur. The busbars must resist thethermal and dynamic load of the short-circuit current which may flow in them(such as via a circuit-breaker on theincoming side, and for a limited time). Tofacilitate rating, only the rated values of theswitchgear assembly according to thefollowing scheme are used.
The let-through characteristics of the short-circuit protective device and the dampingeffect of the connection between thetransformer and the switchgear assemblyare thus disregarded.
Rated short-time withstand currentIcw transformer short-circuit currentI"k
and
Rated peak withstand current I pk peak short-circuit current i p
Where a short-circuit protective deviceleads to a restriction in the duration of theshort-circuit, a rated short-time withstandcurrent can be applied for a correspondinglength of time. Example: incoming circuit-breaker disconnects short-circuit after 40ms; an established rated short-timewithstand current value for 100 ms iscompared with transformer short-circuitcurrent for rating purposes. The ratedoperational voltage U e must be the same or
greater than the transformer voltage.
Transformer rated current I N: I N = k × SNT
Transformer short-circuit current I ''k: I ''k = I N × 100/uk %
Peak short-circuit current i p: i p = n × I ''k
n = 2.2 with I > 50 kAn = 2.1 with 20 kA < I 50 kA
The procedure described above for ratingthe switchgear assembly refers primarily tothe rating of main busbar systems. Rating ofthe distribution busbar systems and/or of allconnections from the main busbar to theincoming side of function units, need onlybe rated for the reduced short-circuit loadwhich may occur on the outgoing side ofthe short circuit protective device for thefunction units. It is a prerequisite that,under normal operating conditions, a short-circuit is not expected to occur on thesedistribution busbars or connections.
Example:The transformer short-circuit current I ''k =90 kA, the selected main busbars have a
rated short-time-withstand current I cw of100 kA, however the distribution busbarshave a rated short-time withstand current I cw of only 65 kA (because the circuit-breaker for the outgoer from thedistribution busbar, thanks to its current-limiting effect, has reduced the short-circuitload).
Rated voltage UN 400/230 V 525 V 690/400 V
Short-circuit voltageuk
4 %1) 6 %2) 4 %1) 6 %2) 4 %1) 6 %2)
Motor rating
kVA
Rated current
A
Short-circuit current3)
I ''k
A
Rated current
A
Short-circuit current3)
I ''k
A
Rated current
A
Short-circuit current3)
I ''k
A
400 578 14450 9630 440 11000 7333 336 8336 5568
500 722 18050 12030 550 13750 9166 420 10440 7120
630 909 22750 15166 693 17320 11550 526 13300 8760
800 1156 28900 19260 880 22000 14666 672 16672 11136
1000 1444 36100 24060 1100 27500 18333 840 20840 13920
1250 1805 45125 30080 1375 34375 22916 1050 26060 17480
1600 2312 57800 38530 1760 44000 29333 1330 33300 22300
2000 2888 72200 48120 2200 55000 36666 1680 41680 27840
2500 3612 90300 60200 2752 68800 45866 2094 52350 34900
1) uk = 4 % standardised to
DIN 42500 for SNT = 50...630 kVA
2) uk = 6 % standardised to
DIN 42500 for SNT = 100...1600 kVA
3) I ''k = Initial symmetrical short-circuit current of transformer
for connection to a supply network with unlimited short-circuit capacity
I"k =IN
× 100uk
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 114/143
13/31
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Further informationInternal partitioning
Forms of internal separationto IEC/EN 60439-1
Low-voltage switchgear assembliescan be divided by means of partitions orbarriers into separate compartments or
enclosed protected spaces. The aim offorming separate compartments orenclosed protected spaces which containthe functional units is:
– Protection against direct contact withhazardous parts belonging to thefunctional unit (degree of protection mustbe at least IP XXB).
– Limitation of possibility of fault arcoccurrence.
– To protect against the passage of solidforeign bodies from one functional unitinto the adjacent unit (degree ofprotection should be at least IP2X)
Typical forms of internal separation aredifferentiated depending on how thecompartment or subsection is constructed:
Form 1
– No internal separation
Form 2a
– Separation of busbars from thefunctional units
– The terminals of external conductorsdo not need to be separated from oneanother.
Form 2b
– Separation of busbars from thefunctional units
– The terminals for external conductorsdo not need to be separated from thebusbars
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 115/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/32 Further informationInternal partitioning
Form 3a
– Internal partitioning between busbarsand functional units as well as separationof functional units from one another
– The terminals of external conductors donot need to be separated from oneanother.
Form 3b
– Separation of the terminals for externalconductors from functional units, but notfrom one another
– The terminals for external conductors donot need to be separated from thebusbars
Form 4a
– Internal separation between busbars andfunctional units as well as functional unitsamong one another, including theterminals for external conductors whichare an integral part of the functional unit
– Terminals for external conductors whichare an integral part of the functional unit
Form 4b
– Internal separation between busbars andfunctional units as well as functional unitsamong one another, including theterminals for external conductors whichare an integral part of the functional unit
– Terminals for external conductors whichare not an integral part of the functionalunit, which however are in an individual,separate, enclosed protected space orcompartment
The form of separation and higher degreesof protection (where greater than IP2X orIPXX B) shall be agreed between themanufacturer and the end user. Internalseparation is used for the protection ofpersonnel and of the system where work isbeing carried out on the switchgearassembly, and where for operationalreasons, switching cannot be carried out
unless the installation is live. Depending onoperational requirements, the distributionsections can optimally be designed withvarious Forms of separation. Distributionsections designed to facilitate the removalof functional units (e.g. withdrawabledistribution boards) are equipped asstandard with a
higher form of internal partitioninge.g. form 3b. Separation in accordance withForm 2b, i.e. separation between busbarsand functional units, is recommended inevery case.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 116/143
13/33
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
Further informationxEnergy installation instructions
Operation and maintenance gangways within the switchgear combinations
The minimum width for operation andmaintenance of switchgear combinations is700 mm, the minimum headroom under the
panelling is 2000 mm. If a crane is used forexchanging circuit-breakers, the gangwaydimensions must be considered during the
design phase.
The doors of the switchgear combinationshould be arranged so that they closeproperly. With a different assignment, a
free access clearance of 500 mm mustremain. If switchgear combinations areinstalled opposite each other, it is not
necessary to consider that doors on bothsides are opened simultaneously.
a Drawer unit in disconnected position
2 0 0 0
600
700
600
700700700
a Direction of escape
7 0 0
( 6 0
0 )
5 0 0
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 117/143
Moeller FK4810-1143GB-INT
x E n e r g y p l a n n i n
g i n f o r m a t i o n
13/34 Further informationxEnergy installation instructions
Distribution section floor view Bottom view of plinth
Installation (plan view)
a-162
b - 5 2
o11
a-110
b -
5 6
Dimension a [in mm] 425 600 800 1000 1200
Dimension b [in mm] 375 575 775Section depth with front door 400 600 800
f 150
f
5 0
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 118/143
14/1
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
Short-circuit rating for circuit-breaker/devices
Circuit-breaker
Installation type I e up to Categoryswitching capacity/accessories
Short-circuit ratingat 400 V AC
I cc I cw I cu
A kA kA (1 s) kA (only for device)
IZM...1-.. Fixed, drawer unit 1600 B 50 42 50N 65 50 65
IZM..2-.. Fixed, drawer unit 3200 B 55 55 55
N 80 65 80
H 80 80 100
IZM..3-.. Fixed, drawer unit 4000 H 80 80 100
NZM 4 Fixed, drawer unit 1600 N 50 – 50
H 100 – 100
PKZM0 Fixed 10 – 100 – 100
32 – 50 – 50
CL-PKZ0 100 – 100
PKZ2 Fixed 16 – 100 – 100
40 – 30 – 30
CL-PKZ2 100 – 100
PKZM4 Fixed 25 – 100 – 100
63 – 50 – 50
NZM1 Fixed 125 B 25 – 25
N 50 – 50
H 100 – 100
NZM2 Fixed, 250 B 30 – 30
Plug-in N 85 – 85
H 100 – 100
NZM3 Fixed, drawer unit 630 N 85 – 85
H 100 – 100
Devices Installation type Frame size/ I e up to
Maximum rated current of low-voltage h.b.c. fuse bases, utilization class gL, gG(VDE 0636/IEC/EN 60269-1) in A
Rated conditional short-circuit current I cf at 500 V AC
Rated conditional short-circuit current I cf at 690 V AC
A 50 kA 65 kA 80 kA 100 kA 50 kA 65 kA 80 kA 100 kA
GS(TA) Fixed 00/100 100 – – – – – – –
1/250 250 – – – – – – –
2/400 400 – – – – – – –
SASIL Fixed 00/160 160 125 100 80 100 100 100 80
1/250 250 224 200 160 200 160 125 100
2/400 400 400 400 355 315 315 315 250
3 /630 630 500 500 425 500 500 500 400
SL Fixed 00/160 160 – – – 100 – – –
1/250 – – 250 – – – 200 –
2/400 – – 400 – – – 315 –
3/630 – – 630 – – – 500 –
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 119/143
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
14/2 Short-circuit rating for busbars
Busbar Busbar cross-section Max. distance between centres for the busbar bracket in mm for I cw (1s)
I e
L1, L2, L3 and full N 35 kA 45 kA 50 kA 65 kA 80 kA 100 kA
A mm2 mm mm mm mm mm mm
Dropper bars
Flat copper for fixed installation modules with circuit-breakers, on the rear or side with busbar supports XDSF...,interval between phase centres 60 mm
800 2 x 20 x 10 325 – – – – –
1250 2 x 40 x 10 325 325 – – – –
1600 2 x 60 x 10 600 325 325 – – –
Duplex profile for fixed installation modules with circuit-breakers, on the rear or side with busbar supports XDSF...,interval between phase centres 60 mm
1250 40 x 30 300 300 * – – –1600 60 x 30 300 300 * – – –
Flat copper for horizontally installed SASIL switch-fuse with busbar support XDSSV...,interval between phase centres 185 mm
800 1 x 40 x 10 – 600 600 – – –
1000 1 x 60 x 10 – 600 600 600 – –
1250 1 x 80 x 10 – 750 750 600 – –
1600 1 x 100 x 10 – 750 750 750 – –
If necessary further busbar supports from Jean-Müller should be complemented according to the required short-circuit rating.
Flat copper for vertically installed SASIL switch-fuse with busbar support XDSSH...,interval between phase centres 185 mm
800 1 x 40 x 10 – 600 600 – – –
1000 1 x 60 x 10 – 600 600 600 – –
1250 1 x 80 x 10 – 750 750 600 – –
1600 1 x 100 x 10 – 750 750 750 – –
If necessary further busbar supports from Jean-Müller should be complemented according to the required short-circuit rating.
Flat copper for vertically installed SL switch-fuse with fitting kit XSML...,
interval between phase centres 185 mm800 1 x 40 x 10 – 400 400 – – –
1000 1 x 60 x 10 – 400 400 – – –
1250 1 x 80 x 10 – 400 400 – – –
1600 1 x 100 x 10 – 400 400 – – –
Notes *on request
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 120/143
14/3
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
Short-circuit rating for busbars
Busbar Busbar cross-section Max. distance between centres for the busbar bracket in mm for I cw (1s)
I e
L1, L2, L3 and full N 35 kA 45 kA 50 kA 65 kA 80 kA 100 kA
A mm2 mm mm mm mm mm mm
Main busbar systems
Flat copper rear with busbar support XBSB...,interval between phase centres 180 mm
1600 2 x 40 x 10 – * 350 350 – –
2000 2 x 60 x 10 – * 350 350 – –
2500 2 x 80 x 10 – * 350 350 350 –
3200 3 x 80 x 10 – * * 350 350 –
4000 3 x 80 x 10 – * * 350 350 350*
Flat copper top with busbar support XBST...-1,interval between phase centres 60 mm
800 2 x 20 x 10 * * * – – –1250 2 x 40 x 10 300 300 * – – –
1600 2 x 60 x 10 300 300 * – – –
Flat copper top with busbar support XBST...,interval between phase centres 125 mm
1250 2 x 40 x 10 450 350 – – – –
1600 2 x 60 x 10 450 350 350 – – –
2000 2 x 80 x 10 – 450 350 350 – –
2500 2 x 100 x 10 – 450 350 350 – –
3200 2 x 120 x 10 – * * 350 – –
Notes *on request
Note!With incomer, outgoer and coupling sections with circuit-breaker IZM or NZM4 up to the maximumshort-circuit rating of the busbar• Position rear, of I cw (1 s) = 80 kA from cross-section of the busbar 2 x 80 x 10 mm, XBSB...• Position top, of I cw (1 s) = 65 kA from cross-section of the busbar 2 x 80 x 10 mm, XBST...the installation of 2 busbar supports per section is sufficient.
Exception:With circuit-breaker NZM4 in a 600 mm width section a maximum short-circuit rating of I cw (1 s) = 45 kA with the installation of 2 busbarsupports XBSB... or XBST... per section is achieved.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 121/143
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
14/4 Current loading for circuit-breakers up to 4000 A
Configuration Circuit-breaker
Installation type I e up to Degree of protection Permissible continuous current I inrelation to the ambient temperatureand degree of protection of thedistribution sections
25 °C 35 °C 45 °C
A A A A
Busbar area rear,up to 3200 Aat section depth 600 mm,4000 A at section depth 800 mm
IZM..1-.. Fixed, drawer unit 1600 IP31 with canopy XAD... 1600 1520 1430
IP31 with top plate without apertures XSPTC... 1550 1450 1360
IP55 1450 1370 1270
IZM..2-.. Fixed, drawer unit 2000 IP31 with canopy XAD... 2000 1900 1790
IP31 with top plate without apertures XSPTC... 1950 1820 1710
IP55 1850 1750 1620
2500 IP31 with canopy XAD... 2350 2225 2100
IP31 with top plate without apertures XSPTC... 2225 2075 1950
IP55 1825 1725 16003200 IP31 with canopy XAD... 3000 2800 2620
IP31 with top plate without apertures XSPTC... 2800 2600 2400
IP55 2200 2100 1980
IZM..3-.. Fixed, drawer unit 4000 IP31 with canopy XAD... 4000 4000 3700
IP31 with top plate without apertures XSPTC... 3950 3680 3400
IP55 3830 3500 3150
NZM41) Fixed 1600 IP31 with canopy XAD... 1600 1550 1440
IP31 with top plate without apertures XSPTC... 1600 1550 1440
IP55 1600 1550 1440
Drawer unit 1600 IP31 with canopy XAD... 1355 1305 1220
IP31 with top plate without apertures XSPTC... 1355 1305 1220
IP55 1220 1175 1120
IZM..1-.. Fixed, drawer unit 1600 IP31 with canopy XAD... 1600 1520 1430
IP31 with top plate without apertures XSPTC... 1550 1450 1360
IP55 1450 1370 1270
IZM..2-.. Fixed, drawer unit 2000 IP31 with canopy XAD... 2000 1900 1790
IP31 with top plate without apertures XSPTC... 1950 1820 1710
IP55 1850 1750 1620
2500 IP31 with canopy XAD... 2350 2225 2100
IP31 with top plate without apertures XSPTC... 2225 2075 1950
IP55 1825 1725 1600
3200 IP31 with canopy XAD... 3000 2800 2620
IP31 with top plate without apertures XSPTC... 2800 2600 2400
IP55 2200 2100 1980
IZM..3-.. Fixed, drawer unit 4000 IP31 with canopy XAD... 4000 4000 3700IP31 with top plate without apertures XSPTC... 3950 3680 3400
IP55 3830 3500 3150
NZM41) Fixed 1600 IP31 with canopy XAD... 1600 1550 1440
IP31 with top plate without apertures XSPTC... 1600 1550 1440
IP55 1600 1550 1440
Drawer unit 1600 IP31 with canopy XAD... 1355 1305 1220
IP31 with top plate without apertures XSPTC... 1355 1305 1220
IP55 1220 1175 1120
Notes 1) For sections with internal partitioning to form 4b an additional current derating of 10 % must be considered.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 122/143
14/5
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
Current loading for circuit-breakers up to 4000 A
Configuration Circuit-breaker
Installation type I e up to Degree of protection Permissible continuous current I inrelation to the ambient temperatureand degree of protection of thedistribution sections
25 °C 35 °C 45 °C
A A A A
Busbar area top,up to 1600 Aa section depth 400 mm,up to 3200 Aa section depth 600 mm,
IZM..1-.. Fixed, drawer unit 1600 IP31 with canopy XAD... 1600 1520 1430
IP31 with top plate without apertures XSPTC... 1550 1450 1360
IP55 1450 1370 1270
IZM..2-.. Fixed, drawer unit 2000 IP31 with canopy XAD... 2000 1900 1790
IP31 with top plate without apertures XSPTC... 1950 1820 1710
IP55 1850 1750 1620
2500 IP31 with canopy XAD... 2350 2225 2100
IP31 with top plate without apertures XSPTC... 2225 2075 1950
IP55 1825 1725 16003200 IP31 with canopy XAD... 2950 2790 2620
IP31 with top plate without apertures XSPTC... 2780 2600 2430
IP55 2280 2130 1980
NZM41) Fixed 1600 IP31 with canopy XAD... 1600 1550 1440
IP31 with top plate without apertures XSPTC... 1600 1550 1440
IP55 1600 1550 1440
Drawer unit 1600 IP31 with canopy XAD... 1355 1305 1220
IP31 with top plate without apertures XSPTC... 1355 1305 1220
IP55 1220 1175 1120
Notes 1) For sections with internal partitioning to form 4b an additional current derating of 10 % must be considered.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 123/143
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
14/6 Current loading for circuit-breakers up to 630 A
Configuration Circuit-breaker/device
Installation type I e up to Degree of protection Permissible continuous current I inrelation to the ambient temperatureand degree of protection of thedistribution sections
25 °C 35 °C 45 °C
A A A A
Device installation horizontal, form 2b
PKZM0 Fixed 32 IP31 with canopy XAD... 25 25 18
IP31 with top plate without apertures XSPTC... 23 23 17
IP55 21 20 14
PKZ2 Fixed 40 IP31 with canopy XAD... 40 40 32
IP31 with top plate without apertures XSPTC... 37 37 30
IP55 37 35 27
PKZM4 Fixed 63 IP31 with canopy XAD... 63 63 53
IP31 with top plate without apertures XSPTC... 63 61 51
IP55 62 58 49
NZM1 Fixed 125 IP31 with canopy XAD... 125 125 111IP31 with top plate without apertures XSPTC... 116 116 103
IP55 110 100 88
NZM2 Fixed 250 IP31 with canopy XAD... 250 250 226
IP31 with top plate without apertures XSPTC... 232 232 210
IP55 224 210 189
Plug-in 250 IP31 with canopy XAD... * * *
IP31 with top plate without apertures XSPTC... * * *
IP55 * * *
NZM3 Fixed 630 IP31 with canopy XAD... 630 630 578
IP31 with top plate without apertures XSPTC... 585 585 537
IP55 481 450 412
Drawer unit 630 IP31 with canopy XAD... * * *
IP31 with top plate without apertures XSPTC... * * *
IP55 * * *
Device installation horizontal, form 4b
PKZM0 Fixed 32 IP31 with canopy XAD... 25 24 17
IP31 with top plate without apertures XSPTC... 23 22 16
IP55 21 20 14
37 35 28PKZ2 Fixed 40 IP31 with canopy XAD... 40 38 30
IP31 with top plate without apertures XSPTC... 37 35 28
IP55 34 32 25
61 61 51PKZM4 Fixed 63 IP31 with canopy XAD... 63 63 53
IP31 with top plate without apertures XSPTC... 61 61 51
IP55 59 55 46
NZM1 Fixed 125 IP31 with canopy XAD... 123 115 101
IP31 with top plate without apertures XSPTC... 114 107 94
IP55 107 100 88
NZM2 Fixed 250 IP31 with canopy XAD... 250 250 226
IP31 with top plate without apertures XSPTC... 232 232 210
IP55 224 210 189
Plug-in 250 IP31 with canopy XAD... * * *
IP31 with top plate without apertures XSPTC... * * *
IP55 * * *
NZM3 Fixed 630 IP31 with canopy XAD... 620 580 532
IP31 with top plate without apertures XSPTC... 615 575 527
IP55 609 570 523
Drawer unit 630 IP31 with canopy XAD... * * *
IP31 with top plate without apertures XSPTC... * * *
IP55 * * *
Notes * Values on request
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 124/143
14/7
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
Current loading for circuit-breakers up to 630 A
Configuration Circuit-breaker/device
Installation type I e up to Degree of protection Permissible continuous current I inrelation to the ambient temperatureand degree of protection of thedistribution sections
25 °C 35 °C 45 °C
A A A A
Device installation vertical, form 2b
PKZM0 Fixed 32 IP31 with canopy XAD... 25 25 18
IP31 with top plate without apertures XSPTC... 23 23 17
IP55 21 20 14
PKZ2 Fixed 40 IP31 with canopy XAD... 40 40 32
IP31 with top plate without apertures XSPTC... 37 37 30
IP55 37 35 27
PKZM4 Fixed 63 IP31 with canopy XAD... 63 63 53
IP31 with top plate without apertures XSPTC... 63 61 51
IP55 62 58 49
NZM1 Fixed 125 IP31 with canopy XAD... 125 125 111IP31 with top plate without apertures XSPTC... 116 116 103
IP55 110 100 88
NZM2 Fixed 250 IP31 with canopy XAD... 250 250 226
IP31 with top plate without apertures XSPTC... 232 232 210
IP55 224 210 189
Plug-in 250 IP31 with canopy XAD... * * *
IP31 with top plate without apertures XSPTC... * * *
IP55 * * *
NZM3 Fixed 630 IP31 with canopy XAD... 630 630 578
IP31 with top plate without apertures XSPTC... 585 585 537
IP55 481 450 412
Drawer unit 630 IP31 with canopy XAD... * * *
IP31 with top plate without apertures XSPTC... * * *
IP55 * * *
GS(TA) 00 Fixed 160 IP31 with canopy XAD... * * *
IP31 with top plate without apertures XSPTC... * * *
IP55 * * *
GS(TA) 1 Fixed 250 IP31 with canopy XAD... * * *
IP31 with top plate without apertures XSPTC... * * *
IP55 * * *
GS(TA) 2 Fixed 400 IP31 with canopy XAD... * * *
IP31 with top plate without apertures XSPTC... * * *
IP55 * * *
Notes * Values on request
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 125/143
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
14/8 Current loading for switch-fuse units SASIL up to 630 A
Device I e up to Numberper section
Degree of protection Permissible continuous current I in relation to the ambient temperature anddegree of protection of the distribution sections
25 °C 35 °C 45 °C
A A A ADevice installation horizontal
SASIL00 160 1 IP31 with canopy XAD... 145 135 125
IP31 with top plate without apertures XSPTC... 130 121 112
3 IP31 with canopy XAD... 120 110 105
IP31 with top plate without apertures XSPTC... 108 99 95
5 IP31 with canopy XAD... 115 110 100
IP31 with top plate without apertures XSPTC... 104 99 90
7 IP31 with canopy XAD... 115 110 100
IP31 with top plate without apertures XSPTC... 104 99 90
10 IP31 with canopy XAD... 110 105 100
IP31 with top plate without apertures XSPTC... 99 94 90
30 IP31 with canopy XAD... 65 65 60
IP31 with top plate without apertures XSPTC... 58 58 54
SASIL1 250 1 IP31 with canopy XAD... 230 220 205
IP31 with top plate without apertures XSPTC... 207 198 184
3 IP31 with canopy XAD... 190 180 170
IP31 with top plate without apertures XSPTC... 171 162 153
5 IP31 with canopy XAD... 190 180 165
IP31 with top plate without apertures XSPTC... 171 162 148
7 IP31 with canopy XAD... 175 175 165
IP31 with top plate without apertures XSPTC... 157 157 148
10 IP31 with canopy XAD... 125 125 125
IP31 with top plate without apertures XSPTC... 112 112 112
20 IP31 with canopy XAD... 65 65 65
IP31 with top plate without apertures XSPTC... 58 58 58
SASIL2 400 1 IP31 with canopy XAD... 400 400 400
IP31 with top plate without apertures XSPTC... 360 360 360
3 IP31 with canopy XAD... 360 345 330
IP31 with top plate without apertures XSPTC... 324 310 297
5 IP31 with canopy XAD... 345 330 320
IP31 with top plate without apertures XSPTC... 310 297 288
7 IP31 with canopy XAD... 280 265 245
IP31 with top plate without apertures XSPTC... 252 238 220
10 IP31 with canopy XAD... 213 242 185
IP31 with top plate without apertures XSPTC... 191 217 166
SASIL3 630 1 IP31 with canopy XAD... 550 530 510
IP31 with top plate without apertures XSPTC... 495 477 459
3 IP31 with canopy XAD... 435 420 395IP31 with top plate without apertures XSPTC... 391 378 355
5 IP31 with canopy XAD... 370 350 310
IP31 with top plate without apertures XSPTC... 333 315 279
7 IP31 with canopy XAD... 295 275 250
IP31 with top plate without apertures XSPTC... 265 247 225
10 IP31 with canopy XAD... 190 178 175
IP31 with top plate without apertures XSPTC... 171 160 157
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 126/143
14/9
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
Current loading for switch-fuse units SASIL up to 630 A
Device I e up to Numberper section
Degree of protection Permissible continuous current I in relation to the ambient temperature anddegree of protection of the distribution sections
25 °C 35 °C 45 °C
A A A ADevice installation vertical
SASIL00 160 1 IP31 with canopy XAD... 94 87 81
IP31 with top plate without apertures XSPTC... 84 78 73
3 IP31 with canopy XAD... 78 71 68
IP31 with top plate without apertures XSPTC... 70 64 61
5 IP31 with canopy XAD... 74 71 65
IP31 with top plate without apertures XSPTC... 67 64 58
7 IP31 with canopy XAD... 74 71 65
IP31 with top plate without apertures XSPTC... 67 64 58
10 IP31 with canopy XAD... 71 68 62
IP31 with top plate without apertures XSPTC... 64 61 55
14 IP31 with canopy XAD... 61 58 55
IP31 with top plate without apertures XSPTC... 55 52 48
SASIL1 250 1 IP31 with canopy XAD... 149 143 133
IP31 with top plate without apertures XSPTC... 134 128 119
3 IP31 with canopy XAD... 123 117 110
IP31 with top plate without apertures XSPTC... 111 105 99
5 IP31 with canopy XAD... 123 117 107
IP31 with top plate without apertures XSPTC... 111 105 96
7 IP31 with canopy XAD... 113 113 107
IP31 with top plate without apertures XSPTC... 102 102 96
9 IP31 with canopy XAD... 81 81 81
IP31 with top plate without apertures XSPTC... 72 72 72
SASIL2 400 1 IP31 with canopy XAD... 260 260 260
IP31 with top plate without apertures XSPTC... 234 234 2343 IP31 with canopy XAD... 234 224 214
IP31 with top plate without apertures XSPTC... 210 201 193
4 IP31 with canopy XAD... 224 214 208
IP31 with top plate without apertures XSPTC... 201 193 187
SASIL3 630 1 IP31 with canopy XAD... 357 344 331
IP31 with top plate without apertures XSPTC... 321 310 298
3 IP31 with canopy XAD... 282 273 256
IP31 with top plate without apertures XSPTC... 254 245 230
4 IP31 with canopy XAD... 240 227 201
IP31 with top plate without apertures XSPTC... 216 204 181
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 127/143
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
14/10 Current loading for fuse-load switch units SL up to 630 A
Device I e up to Numberper section
Degree of protection Permissible continuous current I in relation to the ambient temperature anddegree of protection of the distribution sections
25 °C 35 °C 45 °C
A A A ADevice installation vertical
SL00 160 1 IP31 with canopy XAD... 155 145 135
IP31 with top plate without apertures XSPTC... 155 145 135
IP55 150 145 130
3 IP31 with canopy XAD... 140 125 110
IP31 with top plate without apertures XSPTC... 140 125 110
IP55 135 125 105
5 IP31 with canopy XAD... 130 115 100
IP31 with top plate without apertures XSPTC... 125 110 95
IP55 120 110 90
9 IP31 with canopy XAD... 115 105 90
IP31 with top plate without apertures XSPTC... 110 100 85
IP55 105 100 80
14 IP31 with canopy XAD... 110 100 85
IP31 with top plate without apertures XSPTC... 105 95 80
IP55 95 90 70
SL1 250 1 IP31 with canopy XAD... 250 250 250
IP31 with top plate without apertures XSPTC... 250 250 250
IP55 250 250 250
3 IP31 with canopy XAD... 250 250 250
IP31 with top plate without apertures XSPTC... 250 250 250
IP55 250 250 245
5 IP31 with canopy XAD... 250 250 245
IP31 with top plate without apertures XSPTC... 250 240 235
IP55 240 230 220
7 IP31 with canopy XAD... 250 250 240
IP31 with top plate without apertures XSPTC... 245 240 230
IP55 235 230 210
SL2 400 1 IP31 with canopy XAD... 400 400 380
IP31 with top plate without apertures XSPTC... 400 395 360
IP55 400 390 340
3 IP31 with canopy XAD... 390 365 320
IP31 with top plate without apertures XSPTC... 365 350 305
IP55 360 330 290
5 IP31 with canopy XAD... 360 330 310
IP31 with top plate without apertures XSPTC... 340 310 280
IP55 320 290 250
7 IP31 with canopy XAD... 345 320 295IP31 with top plate without apertures XSPTC... 325 300 265
IP55 310 280 240
SL3 630 1 IP31 with canopy XAD... 610 580 530
IP31 with top plate without apertures XSPTC... 605 575 520
IP55 600 570 510
3 IP31 with canopy XAD... 540 510 460
IP31 with top plate without apertures XSPTC... 515 490 440
IP55 490 470 420
5 IP31 with canopy XAD... 480 450 405
IP31 with top plate without apertures XSPTC... 445 420 375
IP55 410 390 350
7 IP31 with canopy XAD... 420 400 360
IP31 with top plate without apertures XSPTC... 385 365 330
IP55 350 330 300
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 128/143
14/11
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
Current loading for busbarsDropper bars
I e up to Busbar cross-sectionL1, L2, L3 andfull N
Degree of protection Permissible continuous current I inrelation to the ambient temperature anddegree of protection of the distributionsections
25 °C 35 °C 45 °C
A mm2 A A A
Dropper bars
Flat copper for fixed installation modules with circuit-breakers, on the rear or side with busbar supports XDSF...,interval between phase centres 60 mm
800 2 x 20 x 10 IP31 with canopy XAD... 1400 1300 1200
IP31 with top plate without apertures XSPTC... 1220 1150 1080
IP55 1080 940 840
1250 2 x 40 x 10 IP31 with canopy XAD... 2060 1920 1770
IP31 with top plate without apertures XSPTC... 1880 1730 1580
IP55 1700 1550 1400
1600 2 x 60 x 10 IP31 with canopy XAD... 2250 2120 1970
IP31 with top plate without apertures XSPTC... 2050 1900 1760
IP55 1900 1760 1620
Duplex profile for fixed installation modules with circuit-breakers, on the rear or side with busbar supports XDSF..., intervalbetween phase centres 60 mm
1250 40 x 30 IP31 with canopy XAD... 1310 1250 1130
IP31 with top plate without apertures XSPTC... 1050 1000 910
IP55 840 800 720
1600 60 x 30 IP31 with canopy XAD... 1680 1600 1450
IP31 with top plate without apertures XSPTC... 1470 1400 1270
IP55 1150 1100 1000
Flat copper for horizontally installed SASIL switch-fuse with busbar support XDSSV...,interval between phase centres 185 mm
800 1 x 40 x 10 IP31 with canopy XAD... 890 850 790
IP31 with top plate without apertures XSPTC... 730 700 650IP55 570 550 510
1000 1 x 60 x 10 IP31 with canopy XAD... 1260 1200 1120
IP31 with top plate without apertures XSPTC... 1050 1000 940
IP55 840 800 750
1250 1 x 80 x 10 IP31 with canopy XAD... 1680 1600 1500
IP31 with top plate without apertures XSPTC... 1360 1300 1220
IP55 1100 1050 980
1600 1 x 100 x 10 IP31 with canopy XAD... 1890 1800 1690
IP31 with top plate without apertures XSPTC... 1520 1450 1360
IP55 1260 1200 1120
Flat copper for vertically installed SASIL switch-fuse with busbar support XDSSH...,interval between phase centres 185 mm
800 1 x 40 x 10 IP31 with canopy XAD... 890 850 790
IP31 with top plate without apertures XSPTC... 730 700 650
IP55 570 550 510
1000 1 x 60 x 10 IP31 with canopy XAD... 1260 1200 1120
IP31 with top plate without apertures XSPTC... 1050 1000 940
IP55 840 800 750
1250 1 x 80 x 10 IP31 with canopy XAD... 1680 1600 1500
IP31 with top plate without apertures XSPTC... 1360 1300 1220
IP55 1100 1050 980
1600 1 x 100 x 10 IP31 with canopy XAD... 1890 1800 1690
IP31 with top plate without apertures XSPTC... 1520 1450 1360
IP55 1260 1200 1120
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 129/143
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
14/12 Current loading for busbarsDropper bars
I e up to Busbar cross-sectionL1, L2, L3 andfull N
Degree of protection Permissible continuous current I inrelation to the ambient temperature anddegree of protection of the distributionsections
25 °C 35 °C 45 °C
A mm2 A A A
Flat copper for vertically installed SL switch-fuse with fitting kit XSML...,interval between phase centres 185 mm
800 1 x 40 x 10 IP31 with canopy XAD... 1350 1220 1100
IP31 with top plate without apertures XSPTC... 1250 1130 1010
IP55 1150 1030 910
1000 1 x 60 x 10 IP31 with canopy XAD... 1770 1620 1480
IP31 with top plate without apertures XSPTC... 1580 1460 1330
IP55 1380 1270 1150
1250 1 x 80 x 10 IP31 with canopy XAD... 1960 1820 1670
IP31 with top plate without apertures XSPTC... 1770 1640 1500
IP55 1540 1420 1290
1600 1 x 100 x 10 IP31 with canopy XAD... 2110 1960 1800
IP31 with top plate without apertures XSPTC... 1910 1770 1620
IP55 1660 1530 1390
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 130/143
14/13
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
Current loading for busbarsMain busbar systems
I e up to Busbar cross-sectionL1, L2, L3 and full N
Degree of protection Permissible continuous current I inrelation to the ambient temperature anddegree of protection of the distributionsections
25 °C 35 °C 45 °C
A mm2 A A A
Main busbar systems
Flat copper rear with busbar support XBSB...,interval between phase centres 180 mm
1600 2 x 40 x 10 IP31 with canopy XAD... 2140 2000 1860
IP31 with top plate without apertures XSPTC... 1980 1830 1700
IP55 1780 1600 1440
2000 2 x 60 x 10 IP31 with canopy XAD... 2700 2520 2340
IP31 with top plate without apertures XSPTC... 2600 2400 2200
IP55 2150 2000 1820
2500 2 x 80 x 10 IP31 with canopy XAD... 3200 2940 2700
IP31 with top plate without apertures XSPTC... 3030 2750 2500
IP55 2460 2270 2060
3200 3 x 80 x 10 IP31 with canopy XAD... 3900 3600 3400
IP31 with top plate without apertures XSPTC... 3530 3250 3000
IP55 2950 2730 2500
4000 3 x 80 x 10 IP31 with canopy XAD... 4060 3750 3430
IP31 with top plate without apertures XSPTC... 3730 3470 3200
IP55 3070 2850 2620
Flat copper top with busbar support XBST...-1,interval between phase centres 60 mm
800 2 x 20 x 10 IP31 with canopy XAD... 1030 950 860
IP31 with top plate without apertures XSPTC... 880 800 720
IP55 690 630 560
1250 2 x 40 x 10 IP31 with canopy XAD... 1625 1500 1360IP31 with top plate without apertures XSPTC... 1375 1250 1125
IP55 1100 1000 880
1600 2 x 60 x 10 IP31 with canopy XAD... 1950 1800 1640
IP31 with top plate without apertures XSPTC... 1650 1500 1350
IP55 1380 1250 1110
Flat copper top with busbar support XBST...,interval between phase centres 125 mm
1250 2 x 40 x 10 IP31 with canopy XAD... 1950 1800 1600
IP31 with top plate without apertures XSPTC... 1650 1500 1350
IP55 1470 1300 1120
1600 2 x 60 x 10 IP31 with canopy XAD... 2500 2300 2100
IP31 with top plate without apertures XSPTC... 2200 2000 1800
IP55 1880 1700 1520
2000 2 x 80 x 10 IP31 with canopy XAD... 2930 2720 2500
IP31 with top plate without apertures XSPTC... 2430 2230 2030
IP55 2180 1980 1780
2500 2 x 100 x 10 IP31 with canopy XAD... 3350 3080 2820
IP31 with top plate without apertures XSPTC... 2750 2590 2420
IP55 2360 2200 2030
3200 2 x 120 x 10 IP31 with canopy XAD... 3600 3350 3120
IP31 with top plate without apertures XSPTC... 3320 3060 2800
IP55 2560 2350 2140
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 131/143
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
14/14 Total permissible power dissipation in sections
Degree of protection Installable power dissipation Pv1) in W in dependance on the section width with an
ambient temperature of 35 °C
425 600 800 1000 1200
mm mm mm mm mm
IP31 with canopy XAD... 800 1000 1200 1400 1600
IP31 with top plate without apertures XSPTC... 720 900 1080 1260 1440
IP55 260 340 420 500 580
Conversion factors for otherambient temperatures
Ambient temperature 25 °C 45 °C
Factor 1,4 0,6
Notes 1) The power dissipation from the main busbar is already included and therefore does not require addi-tional consideration when determining the installable power dissipation.
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 132/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 133/143
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
14/16 Overview of circuit-types for incomers and outgoers 800 to 3200 A,busbar top
TN-S TN-S TN-C TN-C-S
Main busbar: 4-conductor L1, L2, L3, N
Device: 4-pole L1, L2, L3, N
Connection: 5-conductor L1, L2, L3, N,
Main busbar: 4-conductor L1, L2, L3, N
Device: 3-pole L1, L2, L3
Connection: 5-conductor L1, L2, L3, N,
Main busbar: 3-conductor L1, L2, L3
Device: 3-pole L1, L2, L3
Connection: 4-conductor L1, L2, L3,
Main busbar: 4-conductor L1, L2, L3, N
Device: 3-pole L1, L2, L3
Connection: 4-conductor L1, L2, L3,
E13-45 E13-35N E13-34 E13-34N
a Connection system: KSY or KSD
b TN-C-S: connection PEN to main busbar N = main conductor cross-section
cMain busbar-N: runs through all system sections individual N bracketsposition as with main busbar-N of the rear busbar
N L3 L2 L1
L1
L2
L3
PE
N
L3 L2 L1
L1
L2
L3
PE
NN
3
L3 L2 L1
L1
L2
L3
PEN
L3 L2 L1
L1
L2
L3
PEN
N2, 3 1
Overview of circuit types for sections with switch-fuse units SASIL or fuse-load switch units SL,
vertical, outgoers up to 630 A,
busbar rear
Overview of circuit type/xEnergy grid types XF-busbar rear + SSL (SL)
TN-S
A13-35 or A13-35N A11-35
TN-C
A13-34 A11-34
TN-C-S
A13-34/35N A11-34/35
A31-35 or A31-35N A33-35 A31-34 A33-34 A31-34/35N A33-34/35
PE
N
N
L1
L2
L3
L1
L2
L3
PE
NN
L1
L2
L3
L1
L2
L3
PE
NN
L1
L2
L3
L1
L2
L3
PEN
L1
L2
L3
L1
L2
L3
PEN
L1
L2
L3
L1
L2
L3
PEN/PE
N
L1
L2
L3
L1
L2
L3
PEN/PE
N
L1
L2
L3
L1
L2
L3
PE
N
N
L3
L2
L1
L1
L2
L3
PE
NN
L3
L2
L1
L1
L2
L3
PE
NN
L3
L2
L1
L1
L2
L3
PEN
L3
L2
L1
L1
L2
L3
PEN
L3
L2
L1
L1
L2
L3
PEN/PE
N
L3
L2
L1
L1
L2
L3
PEN/PE
N
L3
L2
L1
L1
L2
L3
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 134/143
14/17
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
Example for design of the busbar rear for section combinations with two incomersand a coupling for TN-S electrical power networks, 3-pole switched
L1
L2
L3
L1
L2L3
PE
N
XBSN... XBSB...4 XBSP
XBSB...3
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 135/143
Moeller FK4810-1143GB-INT
T e c h n i c a l d a t a
14/18 Notes
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 136/143
15/1
Moeller FK4810-1143GB-INT
D i m e n s i o n s
Dimensions
XP section with installation of circuit-breaker
XSMIB20, XMI2306
XP section with installation of circuit-breaker
XSMIB20, XMN4...
Fixed mounted Withdrawable components
2 0 0 0
b2
b1
5 5
6 5 0
6 5 0
6 5 0
2 5
2 0 3 0
a
b 1
a
b1 b2
600 575800 775
a4256008001200
121.5
73
279
230.5
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 137/143
Moeller FK4810-1143GB-INT
D i m e n s i o n s
15/2 Dimensions
XF -section with installation of circuit-breaker NZM1 – 3, form 2b Fitting kit form 2b
XSMFIB06... XSMFIB06...
Fitting kit form 4bXSMFDB...
XF -section with installation of circuit-breaker NZM1 – 3, form 4b with rear cable connection areaXSMFRDT...06
2 0 0 0
b2
52 273
b1
2 0 3 0
a2a1
a
5 0
8 0
1 9 0 0
405/580
2 7 5
335/510
2 7 5
b1 b2
600 575800 775
a a1 a2
600 314 149800 314 349800 489 1741000 489 374
2 0 0 0
575
230.5212.5
600
2 0 3 0
1 5 0
a1
a
3 8 0
1 5 0 0
a a1
425 284600 459
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 138/143
15/3
Moeller FK4810-1143GB-INT
D i m e n s i o n s
Dimensions
XF section, mounting plate
XMN...M...
Version I
Version II
XF section in form 4b, installation positions for mounting plates and cover plates
XSMFDB..., XMN...M... and XMN...C...
XF section with rear installation dropper bars for circuit-breaker NZM1 – 3
XDSF... Possible installation positions XDSF...
b3
b2
b1
h 3
h 2
h 1
Article no. H1 B1 H2 B2 H3 B3
XNM140604M 147 314 100 300 140 283XNM140606M 147 489 100 475 140 458XNM240804M 197 314 150 300 190 283XNM240806M 197 489 150 475 190 458XNM240806MP 197 489 150 475 190 458XNM341006M 247 489 200 475 240 458XNM141204MV 297 314 250 300 290 283XNM141206MV 297 489 250 475 290 458XNM241604MV 397 314 350 300 390 283XNM241606MV 397 489 350 475 390 458XNM242404MV 597 314 550 300 590 283XNM242406MV 597 489 550 475 590 458XNM342404MV 597 314 550 300 590 283XNM342406MV 597 489 550 475 590 458
b3
b2
b1
h 1
h 3
h 2
Article no. H1 B1 H2 B2 H3 B3
XNM130404M 97 314 50 300 90 247
XNM130406M 97 489 50 475 90 422XNM230604M 147 314 100 300 140 247XNM230606M 147 489 100 475 140 422XNM230606MP 147 489 100 475 140 422XNM330806M 197 489 150 475 190 422XNM131204MV 297 314 250 300 290 247XNM131206MV 297 489 250 475 290 422XNM231604MV 397 314 350 300 390 247XNM231606MV 397 489 350 475 390 422XNM232404MV 597 314 550 300 590 247XNM232406MV 597 489 550 475 590 422XNM332404MV 597 314 550 300 590 247XNM332406MV 597 489 550 475 590 422
1
19 b
a
c
4
294
a max. 193b max. 264c 64
600
2 7 5
4 4 .
5
6 2
7 9 .
5
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 139/143
Moeller FK4810-1143GB-INT
D i m e n s i o n s
15/4 Dimensions
XF section with fitted switch-fuse units SASIL, horizontal
XSMSHD...
XF section with fitted dropper bars for switch-fuse units SASIL, vertical
XDSSV...
2 0 0 0
b2
b1
2 0 3 0
a2a1
25
a
2 2 0
3 0
5 5
2 2 0
1 5 0 5
b 1
5 3a
b1 b2
600 575800 775
a a1 a21000 590 3691200 590 569
1 8 0
1 8 0
4 1 5
7 6 2 .
5
7 6 2 .
5
2 3 7 .
5
2 2 0
1 5 0 5
2 2 0
3 0
5
2 0 0 0
238 108
600600
500
185
SSA-185
185
550
2 0 0
2 2 9
5 7 5
1000
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 140/143
15/5
Moeller FK4810-1143GB-INT
D i m e n s i o n s
Dimensions
XF section with fitted switch-fuse units SASIL, vertical
XSMSV...08
XF section with fitted fuse-load switch units SASIL, vertical
XSML...08
2 0 0 0
b2
b1
5 5
6 5 0
6 5 0
6 5 0
2 5
2 0 3 0
c
a
b 1
5 3
a
b1 b2
600 575800 775
a c
600 500800 7001000 900
2 0 0 0
b2
b1
7 2 5
6 6 2 . 5
6 6 2 . 5
215.8
250.8
8 5 4
1 8 5
1 8 5
b 1
1 5a
b1 b2
600 575
800 775
a
6008001000
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 141/143
Moeller FK4810-1143GB-INT
D i m e n s i o n s
15/6 Dimensions
Empty section XG with fitting kit for height adjustable mounting Section door 1200 mm wide
XSMIB20 XSDMLV2012
Fitting kit for section height mounting plate Section floor clear opening width
XSMMFB20... XSFB...
Base fixing plinthXAP...
2 0 0 0
5 0
b2
b1
17.5
35 125.5
8 0
1 9 0 0
5 0
2 0 3 0
a1
a
b1 b2
600 575800 775
a a1
425 314600 489800 689
1000 889
9 0 0
9 0 0
1 0 0
1 0 0
2 0 0 0
1 9 0 8
4 6
4 6
409 9142191 188
1200
472 6060 537 71
2 4 g 1
1 8 7 9
2 0 .
5
18g1
a
a
3224976978971097
b
–
1 4 1
b
a – 141
a
7 0 . 5
7 0
. 5
2 5
b –
6 7 . 4
7 5
1 0 0
44
69
100
b
a – 67.4
55
5 5
33.7
3 3 . 7
a
o 11
b1 b2
600 575800 775
a
4256008001000
1200
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 142/143
7/22/2019 fk1143en
http://slidepdf.com/reader/full/fk1143en 143/143
Moeller FK4810-1143GB-INT
D i m e n s i o n s
15/8 Dimensions
Top plate split, section depth 800 mm
XSPBM...08
1 9 0
9 6
6 8 2
150
332
300
507
580
707
3 1 0
1 8 6
173.521070 153.5300
907
3 0 0
1 9 1
2 1 0
2 3 6
45721070 70300
1107
Rear busbar
XBSB..., XBSN... and XBSP
2
3 5 1
5 0
1 8 0