TURBINETURBINE
STRESSSTRESS
EVALUATOREVALUATOR
[T S E][T S E]
S. Mundle. DGM. CW
T S E (cont’d)T S E (cont’d)• IMPORTANT FOR TURBINE OPERATION
o To GUIDE THE OPERATOR during
o START UP & SHUTDOWN OPERATION
WITHOUT STRESSING THE TURBINE
PREVENTING FATIGUE
T S E (cont’d)T S E (cont’d)• INPUTS TO T S E:-
‡ WALL TEMPERATURE MEASUREMENT
(TSE THERMOCOUPLES – Ti / T100 )
‡ MEAN TEMPERATURE MEASUREMENT
(TEMPERTAURE – Tm / T50)
‡ TURBINE SPEED
‡ ACTUAL MW LOAD
T S E (cont’d)T S E (cont’d)
• COMPUTING CHANNELS:
• HP STOP VALVE
• HP TURBINE SHAFT
• IP TURBINE SHAFT
T S E (cont’d)T S E (cont’d)• INDICATING AND RECORDING VALUES:
• BARGRAPH INDICATOR(back
up panel)
• MMI + TG DCS
MINIMUM TEMP MARGINS
ACTUAL LOAD, LOAD MARGINS, SPEED,
TEMP MARGINS, TEMPERTAURES.
T S E (cont’d)T S E (cont’d)• IMPORTANCE OF MARGINS
• THERMAL STRESS CAN OCCUR:
DURING STARTUP
• MARGIN INDICATES THE THERMAL STRESS IN TURBINE
STRESS OCCURS WHEN MARGIN IS CONSUMED
LOADING OF TURBINE
! ZERO MARGIN IS AVAILABLE
T S E (cont’d)T S E (cont’d)
• How to Re-gain MARGINS ?
Bring Changes in:
Steam Temperature
Steam Flow
Steam Pressure
T S E (cont’d)T S E (cont’d)
• SYSTEM DESCRIPTIONS:
– It is a µP (Procontrol ‘P’ ) Based System
– Two Separate DC Supply
– Analog & Binary Signals are exchanged with
other system.
T S E (cont’d)T S E (cont’d)
• FUNCTIONS
TT100
T50
+
TpermU
TpermL
Upper Temperature Margin [dTu]
Lower Temperature Margin [dTl]
Load
MW
Function Generator
Upper Load Margin
Lpper Load Margin
T S E (cont’d)
T100FUNCTION GENERATOR
T50
• SHAFT TEMPERATURE SIMULATION [for HP / IP Turbine Shaft]
SHAFT TEMPERTAURE DIRECT MEASUREMENT NOT POSSIBLE
T S E (cont’d)T S E (cont’d)
Upper
Temp
Margin
HP Computing Channels
Lower
Temp
Margin
IP Computing Channels
Upper
Temp
Margin
Lower
Temp Margin
MIN SELECTION MIN SELECTION
Upper Temp
Margin
Lower Temp
Margin
HP Stop Valve Body
Upper
Temp
Margin
Lower
Temp
Margin
ADMISSION
TURBINE
T S E (cont’d)T S E (cont’d)SIGNAL EXCHANGE:
SIGNALS RECEIVED
Turbine Speed
GENERATION MW
SIGNALS SENT
Upper Temp
Margin
Lower Temp
Margin
Turbine Controller
T S E (cont’d)T S E (cont’d)SIGNAL EXCHANGE (Cont’d..)
Shaft Temperature ( Simulated) Upper & Lower Tem Margins
Actual Load / Speed
Upper & Lower Load Margins
RECORDER
T S E (cont’d)T S E (cont’d)
SELF MONITORING OF THE SYSTEM
DYNAMIC MONITORING OF THE SYSTEM
T
t>
Pre-determined gradient
[T= Temperature & t = Time]
T S E (cont’d)T S E (cont’d)
FAULTS & ALARMS:
• Failure of Thermocouples• Dynamic Alarm
• ATRS & Turbine Controller
THANK YOU !