Upload
jmgn
View
227
Download
0
Embed Size (px)
Citation preview
8/12/2019 05475595
http://slidepdf.com/reader/full/05475595 1/4
Influence of Earthing Resistance on the Performance
of Distribution Line Lightning Arrester N.A. Abd. Rahman
#1, N. Abdullah
*2, M.F. Ariffin
#3
# TNB Research Sdn. Bhd.
No. 1, Lorong Air Itam
Kawasan Institusi Penyelidikan, Kajang
43000 Selangor, [email protected]
*Tenaga Nasional Berhad,
11th
Floor, Wisma TNB, No. 19
Jalan Timur, Petaling Jaya
46200 Selangor, [email protected]
Abstract —
The line lightning performance of the 33kV distribution line
Tanjung Batu - Rompin gives very bad performance during
lightning. The lines have bad performance although they were
equipped with the line lightning arrester to limit the overvoltages
on the phase conductors when lightning strikes the line. There
are several cases where the surge arresters were broken and
exploded. In this study, the effect of earthing resistance on the
surge arrester was studied and simulated using ATP-EMTP to
determine the performance of the line lightning arrester in
limiting the lightning voltages on the phase conductor.
I. I NTRODUCTION
Lightning is the major cause of the 33kV Tanjung Batu –
Rompin (TJBU – RMPN) breakdown occurrences. The line is
approximately 55km long running through the rural area of
Pahang, located at East Coast of Peninsular Malaysia. From
the record, the total number of breakdown from the year 2002
to 2006 is 64 breakdowns. The line breakdown due tolightning is 30 which is about 47% from the total number of
line breakdown.
Based on Lightning Detection System Lab (LDS), TNB
Research Sdn. Bhd. (TNBR) records from January 2004 toSeptember 2008 indicate that the average ground stroke
densities of the area on which the line route range from 13 –
15 strokes/km2/year.
Fig. 1 Ground strokes density for TJBU-RMPN line traverse
II. BRIEF DESCRIPTION OF 33KV TANJUNG BATU – R OMPIN
DISTRIBUTION LINE
The 33kV Tanjung Batu – Rompin line length is
approximately 55km. The line has 413 poles which theaverage span length of 150m. The measured soil resistivity
along the line is varies between 10 to 600 Ω.m. A total of 22MOV line surge arresters have been installed on the line. The
phase conductors are single conductor of 150mm2 Silmalec.
This line has no shield wires installed, thus no dedicated
earthing system installed at every pole. The Basic Insulation
Level (BIL) of the line is 170kV.
2010 Asia-Pacific International Symposium on Electromagnetic Compatibility, April 12 - 16, 2010, Beijing, China
978-1-4244-5623-9/10/$26.00 ©2010 IEEE 1538
8/12/2019 05475595
http://slidepdf.com/reader/full/05475595 2/4
Fig. 2 Surge Arresters Installed on the Pole
III. SIMULATION DATA
A total of seven poles which are located approximately in
the middle of the 33kV Tanjung Batu-Rompin line are
selected and modelled in the ATP-EMTP. The phase
conductors at both ends are terminated by a 450 ohm
resistance which represents the surge impedance of theconductors for the remaining part of the circuit.
In this simulation, we study the case in which lightning
strikes Phase A (outer phase) in the mid-span between Pole
No.4 and No.5, where lightning surge arresters are installed atthe phases of Pole No. 4. It is expected that Phases A and C
are more susceptible to lightning strikes, as compared to Phase
B (middle phase). For unshielded horizontal circuits, both
outer phase wires will be more exposed to direct lightning
strikes, which would provide the middle phase with some
degree of shielding from direct strikes. Protecting the outer phases of a flat horizontal circuit with surge arresters could be
an effective means for improving line overall lightning performance.
Fig. 3 Modelling of Seven Distribution Poles in ATP EMTP
The lightning surge modelled in this simulation is
characterised by 8/20µs, Heidler current waveform, with a
peak magnitude 21kA which is the mean value of lightning
current at the traverse of Tanjung Batu – Rompin line for the
year 2007.
The line surge arrester currently installed is a gapless metal
oxide varistor. The rated voltage is 29kV and the MCOV
(Maximum Continuous Operating Voltage) is 36kV.
0
5
10
15
20
25
30
35
40
45
104 112 120 132 156 202
Current (kA)
V o l t a g e ( k V )
Fig. 4 Voltage – Current Characteristics of MOV Surge Arrester
IV. R ESULTS AND DISCUSSIONS
Figure 2 shows the voltage on Phase A when lightning
strikes the conductor. The maximum overvoltages on the line
is about 4.8 MV which exceeds the line BIL of 170kV.
Fig. 5 Overvoltages on Phase A when 21kA lightning strikes the phaseconductor
For the purpose of determining the importance of pole
earthing, 10kA and 15kA lightning surge currents are used. Table 1 below shows the overvoltages on Phase A conductor
when a 10kA lightning strikes the conductor. The maximum
overvoltages for lightning surge current of 10kA and 15kA are
about 2.29MV and 3.43MV respectively, which exceed the
line BIL of 170kV. Surge arresters are recommended to be
installed to prevent the current surges from flowing to thenetwork by diverting them harmlessly to the ground. They
would also limit the overvoltages to the lowest possible level.
TABLE I
LINE OVERVOLTAGES WHEN 10K A AND 15K A LIGHTNING SURGE CURRENTS
STRIKE THE PHASE CONDUCTOR
Overvoltages (MV)
Lightning Surge
= 10kA
Lightning Surge
= 15kA
WithoutArrester
2.29 3.43
1539
8/12/2019 05475595
http://slidepdf.com/reader/full/05475595 3/4
However, to install the surge arresters, earthing resistance
must be maintained at low or recommended value to ensure anoptimized lightning surge operation. Table 2 below shows the
overvoltages on Phase A conductor when 10kA and 15kA
currents of lightning strike the conductor with different values
of pole earthing.
TABLE IILINE OVERVOLTAGES WHEN 10K A AND 15K A LIGHTNING SURGE CURRENTS
STRIKE PHASE CONDUCTOR
Pole Earth
Resistance ( )
Overvoltages (kV)
Lightning Surge =
10kA
Lightning Surge =
15kA
0 131 144
1 140 158
5 176 213
10 219 277
15 258 336
20 290 391
30 360 487
40 416 571
50 465 644100 661 935
200 875 1251
Table 2 shows the overvoltages on the phase conductor
when surge arresters are grounded with different earthing
resistance values. The overvoltage on the line exceeds the line
BIL even when the earthing resistance is only 5 Ω. Therefore,it is crucial to have low earthing resistance since it will affect
the surge arrester operation effectiveness in limiting the line
overvoltages.
Line Lightning Overvoltages
0
200
400
600
800
1000
1200
1400
0 1 5 10 15 20 30 40 50 100 200
Earth Resistance (ohm)
O v e r v o l t a g e s ( k V )
10kA
15 kA
Fig. 6 Earth Resistances vs Line Overvoltages
From the Figure 3, it shows that at low earth resistance
value, the overvoltages on the phase conductor at different
value of lightning current shows not much different. The
performance of the line surge arrester in limiting the
overvoltages will decrease to about 5 % of every 5 ohm
increase.
The overvoltages on the line were analyzed with different
value of lightning magnitude. Table 3 shows the overvoltages
at the phase conductor at various magnitude of lightning
magnitude when the line surge arrester has good grounding
system which near to 0Ω and 20Ω.
TABLE III
LINE OVERVOLTAGES WHEN ARRESTERS GROUNDED WITH DIRECT GROUND
AND 20 Ω EARTHING RESISTANCE
Lightning
current (kA)
Overvoltages
(kV)Direct Ground (0 ) 20
10 130 295
11 133 314
12 136 333
13 139 352
14 142 372
15 144 391
16 146 410
Line Lightning Overvoltages
0
100
200
300
400
500
600
10 11 12 13 14 15 16
Lightning Current
O v e r v o l t a g e s ( k V )
20 ohm
~ 0 ohm
Fig. 7 Lightning Current vs Line Overvoltages
The higher the magnitude of the lightning current that
strikes the phase conductor, the higher lightning overvoltageson the line would be occurred on the line. Also, the higher theearth resistance of the arrester, the higher the line lightning
overvoltages would be.
However, it can be seen in Figure 3 that, when line surge
arrester has very good earthing system which the earth
resistance value is 0Ω, the increment of the line overvoltages
value at different lightning current magnitude are negligible.
The performance of line surge arrester is the best when it isgrounded with a very low earth resistance.
V. CONCLUSIONS
When the surge arrester is installed on the line, it will limit
the lightning overvoltage magnitude to about 95%. However,
the effectiveness of the surge arrester will decrease when the
resistance of the surge arrester to the earth increases. With an
increase of every 5 ohm, the performance of surge arrester to
limit the lightning overvoltages decreases by about 5%. These
results show that the effectiveness of line surge arresters is
affected by the earth resistance. To ensure the line surge
arrester is operated at the best performance, regardless the
lightning magnitude that will hit the line, earth resistance must
1540
8/12/2019 05475595
http://slidepdf.com/reader/full/05475595 4/4
be kept very low since the performance of the line surge
arrester is dependable on its earthing system value.
ACKNOWLEDGMENT
An acknowledgement is made to all relevant people who
have contributed towards the success of this study. The author
also would like to thank the Management of TNBR and
TNBD for providing the support for this study. Thanks alsoTNBR research team members who have worked very hard to
complete this project.
R EFERENCES
[1] IEEE Std. 1243 – 1997, IEEE Guide for Improving the LightningPerformance of Transmission Lines
[2] A.P. Sakis Meliopoulus, John Kennedy, “Statistical Lightning
Performance Evaluation of Overhead Distribution Lines”, IEEE, 2000[3] F.P. Dwalibi, W. Ruan, S. Fortin And J. Ma, “Computation of Power
Line Structure Surge Impedances Using the Electromagnetic Field
Method”, IEEE 2001[4] F.P. Dwalibi & P. Hotte, “Distribution Line Safety Grounding:
Parametric Analysis”, IEEE1998[5] F.P. Dwalibi, W. Ruan, S. Fortin, J. Ma & W.K. Daily, “Computation
of Power Line Structure Surge Impedances Using the Electromagnetic
Field Method”, IEEE 2001
1541