Upload
jcarlos-ibarra
View
213
Download
0
Embed Size (px)
Citation preview
7/31/2019 298525_94737
1/6
Type: DILM50(230V50HZ,240V60HZ)Article No.:277830
Ordering information
Rated operational current AC3 400 V I e A 50Max. rating for threephase motors, 50 60 Hz AC3230 V P kW 15.5
Max. rating for threephase motors, 50 60 Hz AC3400 V P kW 22
Max. rating for threephase motors, 50 60 Hz AC3690 V P kW 30
Max. rating for threephase motors, 50 60 Hz AC4230 V P kW 6
Max. rating for threephase motors, 50 60 Hz AC4400 V P kW 10
Max. rating for threephase motors, 50 60 Hz AC4690 V P kW 14
Conventional thermal current I th = I e AC1 Open I th = I e A 60
For use with DILM150XHI(V)..DILM1000XHI(V)..
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operated Operations 106 10DC operated Operations 106 10
Operating frequency, mechanical
AC operated Operations/h 5000DC operated Operations/h 5000
Climatic proofing Damp heat, constant, to IEC 60068278Damp heat, cyclical, to IEC 60068230
Ambient temperature
1
7/31/2019 298525_94737
2/6
Open C 25/60Enclosed C 25/40Storage C 40/80
Mechanical shock resistance (IEC/EN 60068227)
Halfsinusoidal shock, 20 ms
Main contacts
Make contact g 10
Auxiliary contacts
Make contact g 7Break contact g 5Protection type IP00Protection against direct contact when actuated fromfront (IEC 536) Finger and backofhand proof
Weight
AC operated kg 0,9DC operated kg 1,1
Terminal capacity Main cable
Solid mm2 1 (2.5 16)2 (2.5 16)
Flexible with ferrule mm2 2 (2.5 25)1 (2.5 35)
Stranded mm2 1 (16 50)2 (16 35)Solid or stranded AWG 12 2
flat conductorNumber ofsegments
width thickness
mm 2 (6 9 0.8)
Anschlussschraube Hauptleiter M6Tightening torque Nm 3
Terminal capacity Control circuit cables
Solid mm2 1 (0.75 4)1 (0.75 4)
Flexible with ferrule mm2 1 (0.75 2.5)2 (0.75 2.5)Solid or stranded AWG 18 14Anschlussschraube Hilfsleiter M3.5Tightening torque Nm 1.2
Tool
Main cablePozidriv screwdriver Size 2
Standard screwdriver mm 0.8 5.51 6
Control circuit cables
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 5.51 6
Terminal capacity Control circuit cables
Solid mm2 0.75 2.5
2
7/31/2019 298525_94737
3/6
Flexible mm2 0.75 2.5Flexible with ferrule mm2 0.75 2.5Solid or stranded AWG 18 14
Tool
Stripping length mm 10Screwdriver blade width mm 3,5
Main conducting paths
Rated impulse withstand voltage U imp V AC 8000Overvoltage category/pollution degree III/3
Rated insulation voltage
AC U i V AC 690Rated operational voltage U e V AC 690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between coil and contacts V AC 440between the contacts V AC 440Making capacity (cos to IEC/EN 60947) up to 690V A 700
Breaking capacity220/230 V A 500380/400 V A 500500 V A 500660/690 V A 320
Component lifespan
AC3/AC4 Tripping characteristics
Maximum operating frequency
AC1; 400 V I e Ops/h 800AC3; 400 V I e Ops/h 800AC4; 400 V I e Ops/h 300
Shortcircuit rating
Shortcircuit protection Maximum fuse
Type 2 coordination
400 V gG/gL 500 V A 80690 V gG/gL 690 V A 63
Type 1 coordination
400 V gG/gL 500 V A 160690 V gG/gL 690 V A 80
AC
AC1 duty
conv. therm. current 3pole 50 60 Hz
open
at 40 C I th A 70at 50 C I th A 65at 55 C I th A 63at 60 C I th A 60Enclosed I th A 54
3
7/31/2019 298525_94737
4/6
Conventional free air thermal current, 1pole
open I th A 150Enclosed I th A 135
AC3 duty
Rated operational current AC3 open, 50 60 Hz,3pole220/230 V I e A 50
240 V I e A 50380/400 V I e A 50415 V I e A 50440V I e A 50500 V I e A 50660/690 V I e A 32
Motor rating
220/230 V P kW 15,5240V P kW 17380/400 V P kW 22
415 V P kW 30440 V P kW 32500 V P kW 36660/690 V P kW 30
AC4 duty
Rated operational current AC4 open, 50 60 Hz,3pole220/230 V I e A 21240 V I e A 21380/400 V I e A 21415 V I e A 21440 V I e A 21500 V I e A 21660/690 V I e A 17
Motor rating
220/230 V P kW 6240 V P kW 6,5380/400 V P kW 10415 V P kW 11440 V P kW 12500 V P kW 13660/690 V P kW 14
DC
of threephase capacitors open
DC1 operation
60 V I e A 60110 V I e A 50220 V I e A 45440 V I e A 2,9
DC3 operation
4
7/31/2019 298525_94737
5/6
60 V I e A 60110 V I e A 50220 V I e A 25440 V I e A 0,6
DC5 operation
60 V I e A 60110 V I e A 50
220 V I e A 25440 V I e A 0,6
Current heat loss (3pole)
Current heat loss at I th W 16,2Current heat loss at I e to AC3/400 V W 11,3Impedance per pole m& 1,5
Magnet systems
Voltage tolerance
AC operated
AC operated Pickup U c 0,8 1,1
Dropout voltage AC operated
Dropout voltage AC operated Abfall U c 0,3 0,6
DC operated
DC operated Pickup U c 0,7 1,2
DC operated
DC operated Abfall U c 0,150,6Power consumption of the coil in a cold state and 1.0 U c50 Hz Pickup VA 13050 Hz Pickup W 8050 Hz Sealing VA 1450 Hz Sealing W 4DC operated Pickup W 24 at 24 VDC operated Sealing W 0.5 at 24 VDuty factor % DF 100
Switching times at 100 %U c (approximate values)
Main contacts
AC operated
Closing delay ms 25
Opening delay ms 25DC operated
Closing delay ms 60Opening delay ms 20Arcing time ms 10
Electromagnetic compatibility (EMC)
Emitted interference to EN 609471Interference immunity to EN 609471
Mounting position, AC and DC operated
5
7/31/2019 298525_94737
6/6
Moeller GmbH, HeinMoellerStr. 711, D53115 BonnEMail: [email protected], Internet: www.moeller.net, http://catalog.moeller.netCopyright 2005 by Moeller GmbH. Subject to modifications. HPLC2005GBINT V3.0
6