8/18/2019 17.1-16 Pwr Dist System
1/16
15P o w e r
D i s t r i b u t i o n
S y s t e m s
Low Voltage Produc ts &Systems 17ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0
Switchboard MaxSBLow Volta ge P rod ucts a nd S ystems
New / ExperiencedBuilding on years of experience in supplying
low voltage distribution equipment all over the
world ABB o pens a new a pproach to what a
swi tchboard can b e and how i t can b et ter serve
the user, the des ign engineer and the co ntractor.
Fresh / FamiliarABB builds on the familiar look of a s witchboa rd
with group mounted molded c as e circuit breakers
and fi xed or draw out ma in breakers. Fresh
ideas a re incorporated w ith features such as a
slotted vertica l bus de sign, a full hinged doo r
that incorporates the breaker cover plates, and a
modular frame e nclosure system.
Unique / ReliableUnique design features such as the slotted bus,
and hinged door make this switchboard new.Pla ted copper bus , b ol ted b us connect ions , a
frame enclosure structure, a nd ABB’s proven
breaker technology ma ke this ABB sw itchbo ard
highly reliab le. Qua lity is a sta nda rd fea ture in
ABB sw itchbo ards. A l ist of expens ive optionsis not needed to ensure the highest qua lity
s tanda rds are met.
Features
• Hinged door and large wire ways save t ime a
money in field wiring.
• Unique bus layout delivers the freedom to
locate feeder breakers independent of any hopattern.
• Plated copper bus used in al l three phases an
neutral.
• Cop per ground bus extends full width of
switchboard.
• Horizontal bus up to 5000 Amps
• Vertica l bus up to 3000 Amps
• G roup mounted feeder breakers ranging from
15 amps to 1200 Amps
• Main breakers up to 5000 Amps
• Strong frame construction isolates bus andbreaker ass emblies from enclosure “s kin”. Du
rable dry paint finish. Four inch b as e and liftin
eyes are standa rd.
8/18/2019 17.1-16 Pwr Dist System
2/16
7
15 P o w e
r
D i s t r i b u
t i o n
S y s t e
m s
17.2 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com
Switchboard MaxSBGeneral information
5000 amp Mains and 3000
amp vertical bus designs
enable this switchboard to
distribute power in the largest
low voltag e applica tions. A
multi-layered b us d esign a ndmodular enclosure system
provide the flexibility to
provide a n 800 amp free-s tanding sw itchboard tha t
has an extremely small foot
print.
Precise / FlexibleABB ’s switchboa rd uses a frame-bas ed enclosure system. Unlike self-
supporting enclosures the frame supports the bus ba r and breaker as semb lies.
Front panels, s idewalls, and rear panels a re also supported by the frame
structure. This design offers a number of adva ntage s over self-supporting
enclosure systems . Dama ged wa lls and panels can be eas ily replac ed
without the need to disa ss emble interior bus or breaker ass emblies. The
modular nature of ABB’s frame e nclosure system ma kes i t easy to expand
the sw itchbo ard by adding sections as system requirements change. Simply
remove a side wa ll and b utt the new se ction aga inst the old. Overlappinghorizontal bus de sign makes for a simple and ac curate splice c onnection.
Custom / StandardWouldn’t it be nice to have the freedom to layout a sw itchbo ard in such a wa y
that i t compliments the a pplica tion a nd s i te requirements? Would you benefit
from the freedo m to loca te breakers as you cho ose ? Wouldn’t you l ike to ad dcustom fea tures l ike a d ust-proof enclosure, or a full glass doo r for add ed
sec urity and an enha nced appe aranc e in high visibil ity si tes?
ABB’s standard switchboard design makes these and other custom like
features affordab le.
1 15-30A are 65kA at 480VAC
Industrial / CommercialThe Operations Mana ger wa nts reliab ili ty, the s pecifying e ngineer wants a
product he c an b elieve in, the service depa rtment demand s ma intainab ili ty,
the CFO wants value and the contractor wa nts a supplier and prod uct that is
eas y to work with and o n time delivery. One compa ny can ma tch al l of these
requirements; ABB .
The Operations Manag er and s pecifying engineer appreciate features s uch
as plated copper bus and bolted bus connections. A frame-based enclosure
system delivers strength, expa nda bili ty and simplifies repairs. The c ompletesystem is designed a nd tested to meet or exceed UL req uirements.
The maintenance d epartment enjoys a hinged d oor that ma kes i t easy for
qua lified perso nnel to acc ess the c ab inet to maintain and s ervice ABB’s
sw itchbo ards . Connec tions are located so that you can ac tually get to them. A
framed enclosure construction and bus design make this switchboard easy toexpand as requirements change.
Contrac tors save on instal lation time with easy to acc ess terminals, increas ed
cab le area a nd a d esign tha t makes i t easy to add breakers and a ccess or ies inthe field.
Unique hole-less bus b ar
arrangement a l lows you to instal l
feeder breakers in any loca tion
vertica lly. Less t ime less has sle.
Easy a cc ess to incoming terminals.
Less t ime less has sle
8/18/2019 17.1-16 Pwr Dist System
3/16
15P o w e r
D i s t r i b u t i o n
S y s t e m s
Low Voltage Produc ts &Systems 17ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0
Switchboard MaxSBLow Volta ge P rod ucts a nd S ystems
Feeder BreakersKAIC Trip Frame Ra ting Amps
Fra me P olesS p a c e
Inches277 240 480 15 20 25 30 35 40 50 60
T1B 1 1.0 182
T1N 3 3.0 50 223T2S 2/3 3.54 65 35
T2H 2/3 3.54 100 65
T3N 2/3 4.13 50 25T3S 2/3 4.13 65 35
S 3N 2/3 4.13 65 25S 3H 2/3 4.13 100 50
S 3L 2/3 4.13 150 851
70 80 90 100
T1B 1 1.0 18T1N 3 3.0 50 22
T2S 2/3 3.54 65 35
T2H 2/3 3.54 100 65T3N 2/3 4.13 50 25
T3S 2/3 4.13 65 35
S 3N 2/3 4.13 65 25
S 3H 2/3 4.13 100 50
S 3L 2/3 4.13 150 85
125 150 175 200 225
T3N 2/3 4.13 50 25
T3S 2/3 4.13 65 35
S 3N 2/3 4.13 65 25
S 3H 2/3 4.13 100 50
S 3L 2/3 4.13 150 85
250 Electronic - ad justa ble 40 - 250
S 4N 2/3 4.13 65 25
S 4H 2/3 4.13 150 65
S 4L 2/3 4.13 200 100
400 Electronic - ad justa ble 160 - 400
S 5N 2/3 5.51 65 35
S 5H 2/3 5.51 150 65
S 5L 2/3 5.51 200 100
600 Electronic - ad justa ble 240 - 600
S 6N 2/3 8.27 65 50
S 6H 2/3 8.27 150 65
S 6L 2/3 8.27 200 100
800 Electronic - adjustable 320 - 800
S 6N 2/3 8.27 65 50
S 6H 2/3 8.27 150 65
S 6L 2/3 8.27 200 100
1200 Electronic - ad justa ble 480 - 1200
S 7H 2/3 8.27 100 65
1 S 3L 15-30A 65kA@480V
2 T1B 15A 10kA@277V
3
T1N 15A35kA@240V
14kA@480V
Maximum switchboard rating = 100kA
T4 = 4.14
T5 = 5.51
T4 &T5 = 5.61 D B L M
8/18/2019 17.1-16 Pwr Dist System
4/16
7
15 P o w e
r
D i s t r i b u
t i o n
S y s t e
m s
17.4 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com
Molded case circuit breakersTma xT1 100 A - T2 100A - T3 225 A
UL 489 CSA 22.2C irc uit b rea kers Tma x T1 1p Tma x T1 Tma x T2 Tma x T3
Ma ximum fra me c o ntinuous c urrent 40° C lu [A] 100 100 100 225Numb er of po les [Nr] 1 3/4 2/3/4 2/3/4
Ra ted opera tiona l vo lta g e (AC ) 50-80Hz Ue [V] 277 480 480 480
S ho rt c irc uit interrupting c a pa c ity, Ic u B N S H N S
AC 240V [kA] 50 65 100 50 65
277V [kA] 181
480V [kA] 222 35 65 25 35
DC 250V 2 poles in s eries [kA] 25 25 35
500V 3 po les in s erie s [kA] 25 25 35
Rela ys TM – – – –
P R22 1DS –
MA – –
Vers io ns MC C B – – – –
MC S – –
MC P – –
IEC 60047-2C irc uit b rea kers Tma x T1 1p Tma x T1 Tma x T2 Tma x T3
Ra ted uninterrupted c urrent lu [A] 160 160 160 250
Numb er of po les [Nr] 1 3/4 3/4 3/4
Ra ted s ervic e vo lta g e, Ue AC 50-60Hz [V] 240 690 690 690DC [V] 125 500 500 500
Ra ted ultima te s hort c irc uit b rea king c a pa c ity , lc u B B C N N S H L N S
AC 220/230V [kA] 25 25 40 50 65 85 100 120 50 85
380/415 [kA] 16 25 36 36 50 70 85 36 50
440V [kA] 10 15 22 30 45 55 75 25 40
500V [kA] 8 10 15 25 30 36 50 20 30
690V [kA] 3 4 6 6 7 8 10 5 8
DC 250V 2 poles in s eries [kA] 16 25 36 35 50 70 85 36 50 250V 2 po les in s eries [kA] 20 3 0 40 40 55 85 100 40 55
500V 2 po les in s eries [kA] 16 25 36 36 50 70 85 36 50
Trip units Fixed therma l ma g netic –Fixed therma l ma g netic – – –
P R221/DS –
Fixed ma g netic –
Ad jus ta b le ma g netic – –
Dimens ions H [in/mm] 5.12/130 5.12/130 5.12/130 5.9/150
W 1p o r 3p [in/mm] 1/25.4 3/76 3.54/90 4.13/105
W 4p [in/mm] 4/102 4.72/122 5.5/140
D [in/mm] 2.76/70 2.76/70 2.76/70 2.76/70
Me c ha nic a l life [No opera tio ns ] 25000 25000 25000 25000
[No ho urly opera tio ns ] 240 240 240 120
Elec tric a l life [No opera tio ns ] 8000 8000 8000 8000
[No ho urly opera tio ns ] 120 120 120 120
Tma x T2 ca n be fit ted w ith the late st g enera tion in electronic trip units.
This is the first time that a c ircuit-breaker of this size ca n bene fit fromelectronic protection, and the setting flexibility it provides.
1 15A : 10kA@277Va c2 15A : 35kA@240Vac ; 14kA@480Vac
T1 100A T2 100A T3 225A
8/18/2019 17.1-16 Pwr Dist System
5/16
15P o w e r
D i s t r i b u t i o n
S y s t e m s
Low Voltage Produc ts &Systems 17ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0
Molded case circuit breakersIsomaxS 3B - S 3 - S 4
Circuit breaker type S 3B S 3 S 4
Ma ximum fra me c o ntinuous ra ted c urrent 40° C A 225 150 225 250
Ra ted o pera tiona l vo lta g e 50/60Hz V 240 600 480 600
Tes t volta g e 1 min. 50/60 Hz V 3000 3000 3000 3000
Ra ted impuls e w iths ta nd vo lta g e kV 6 6 6 8
P o les No. 2/3 2/3/4 2/3/4 2/3/4
P erforma nc e level B N H L N H L N H L 240VAC 150 65 100 150 65 100 150 65 100 150
UL/C S A s hort-c irc uit 480VAC – 25 50 852 25 5 0 65 65 150 200
Interrupting c a pa c ity 600VAC kA RMS – 14 14 25 – – – 18 32 35UL 489, File #E93565 500VDC 1 50 35 50 65 25 35 50 – – –
CS A, File #LR90467 600VDC 1 – 20 35 50 – – – – – –
202/230VAC 150 65 100 170 65 100 170 65 100 200
IEC -947 ra ted ultima te 380/400/415VAC – 35 65 85 35 65 85 35 65 100
S ho rt-c irc uit Ic u 440VAC kA RMS – 30 50 65 30 50 65 30 50 80B rea king c a pa c ity 500VAC – 25 40 50 25 40 50 25 40 65
660/690VAC – 14 18 20 14 18 20 18 22 30
Overc urrent trip unit/relay
Therma l-ma g netic • • • –
Mic ro pro c es s o r-ba s ed – – – •Dia lo g ue unit – – – •
Interc ha ng ea b ility – – – •
Vers ion — Term ina ls
Fixed — fro nt o r rea r • • • •P lug -in — fro nt o r rea r • • • •Withd ra w a b le — front o r rea r • • • •
Dimensions (fixed circuit-breaker)
2P &3 P (H x W x D ) in 6 .7 0 x 4 .13 x 4 . 07 6 .7 0 x 4.13 x 4 . 07 6 .70 x 4.13 x 4 . 07 10 .0 x 4 .13 x 4 . 04P (H x W x D) in 6.70 x 5.51 x 4 .07 6.70 x 5.51 x 4 .07 6.70 x 5.51 x 4 .07 10.0 x 5.51 x 4 .0
Mechanica l duration o pera tio ns No. 25,000 25,000 25,000 25,000
freq uenc y ops . /ho ur 240 120 120 120
Weig hts (fixed 3P ) lbs . 6.75 6.75 6.75 8.8
Isolation of control
accessor ies and
power poles al lows
for the sa fe add ition /
replac ement of s hunttrips, auxiliaries, bellalarm and under
voltag e relays.
S 3B S 3 S 4
1 For use w ith thermal - magnetic trip only:
500 VDC, 2 po les in series
600 VDC, 3 poles in series2 15-30A units a re 65kA at 480VAC
8/18/2019 17.1-16 Pwr Dist System
6/16
7
15 P o w e
r
D i s t r i b u
t i o n
S y s t e
m s
17.6 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com
Molded case circuit breakersIsomaxS 3B - S 3 - S 4
Circuit breaker type S 5 S 6 S 7 S 8
Ma ximum fra me c o ntinuous ra te d c urre nt 40° C A 400 600 800 1200 1600 /200 0/2500
Ra ted o pera tiona l vo lta g e 50/60Hz V 600 600 600 600 600
Tes t volta g e 1 min. 50/60 Hz V 3000 3000 3000 3000 3000
Ra ted impuls e w iths ta nd volta g e kV 8 8 8 8 8
P o les No. 2/3/4 2/3/4 2/3/4 2/3/4 3
P erforma nc e level N H L N H L N H L H V
240VAC 65 150 200 65 150 200 65 150 200 100 120UL/C S A s ho rt-c irc uit 480VAC 35 65 100 50 65 100 50 65 100 65 100
Interrupting c a pa c ity 600VAC kA RMS 22 22 35 25 35 42 25 35 42 50 85
UL 489, File #E93565 500VDC 1 35 50 65 35 50 65 35 50 65 – –
CS A, File #LR90467 600VDC 1 20 35 50 20 35 50 20 35 50 – –
202/230VAC 65 100 200 65 100 200 65 100 200 100 120
IEC -947 ra ted ultima te 380/400/415VAC 35 65 100 35 65 100 35 65 100 65 120S ho rt-c irc uit Ic u 440VAC kA RMS 30 50 80 30 50 680 30 50 80 55 100
B rea king c a pa c ity 500VAC 25 40 65 25 40 65 25 40 65 45 70
660/690VAC 20 25 30 20 25 35 20 25 35 25 50
Overc urrent trip unit/re la y
Therma l-ma g netic • • • – –
Mic ro pro c es s o r-ba s ed • • • • •Dia lo g ue unit • • • • •
Interc ha ng ea b ility • • • • •
Vers ion — Term ina lsFixed — fro nt o r rea r • • • • •
P lug -in — fro nt o r rea r • • • – –Withd ra w a b le — front o r rea r • • • • –
Dimensions (fixed circuit-breaker)2P &3P (H x W x D) in 10.0 x 5.51 x 4 .07 10.55 x 8.27 x 4 .07 14.25 x 8.27 x 4.07 15.98 x 8.27 x 5.45 15.75 x 15.98 x 9.25
4P (H x W x D) in 10.0 x 7.24 x 4 .07 10.55 x 11.0 x 4 .07 14.25 x 11.0 x 4.07 15.98 x 11.0 x 5.45
Mechanica l duration o pera tio ns No. 20,000 20,000 20,000 10,000 10,00
freq uenc y ops . /ho ur 120 120 120 120 20
Weig hts (fixed 3P ) lb s . 11.0 21.0 22.0 37.5 135
S5 S 6 S 6 S7 S8 K4TB
Standard cable lug kits
Fo r b rea ke rs Amps Wire ra ng eC a t a l og
number
S 3 60 14AWG - 2AWG K3TAS 3 - S 4 100 14AWG - 1/0 K4TB
S 3 - S 4 150 14AWG - 4/0 K4TCS 3 - S 4 - S 5 225 4AWG - 300kc mil K4TD
S 4 250 6AWG - 350kc mil K4TE
S 5 300 250kc mil - 500kc mil K5TF
S 5 400 (2) 3/0 - 250kc mil K5TGS 6 600 (2) 250kc mil - 250Kc mil K5TH
S 6 800 (3) 2/0 - 400kc mil K6TJS 7 1200 (4) 4/0 - 400kc mil K7TK
S 8 1600 (4) 1/0 - 750kc mil K8TL
S 8 2500 (6) 1/0 - 750kc mil K8TM
Standard cable lugs, for use on load side of circuit breaker. Suitable for use with Cu or AI.
Special versions available with taps and screw for control wire connection. Note: S6 and
S7 lugs a re Al9Cu (90° ); all others AL7Cu (75°C ). Must use wire bas ed on 75°C amp ac ity.
8/18/2019 17.1-16 Pwr Dist System
7/16
15P o w e r
D i s t r i b u t i o n
S y s t e m s
Low Voltage Produc ts &Systems 17ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0
Air circuit breakersEmaxE1 - E2 - E3 - E4 - E6
Circuit breaker type E1 E2 E3 E4 E6
P erforma nc e level B -A B -A N-A N-A S -A H-A V-A S -A H-A V-A H-A V-
Ra ted c ontinuo us c urrent A 800 1600 1200 2000 1200 1200 1200 3200 3200 3200 4000 400
File # E194191 A 1200 – 1600 2500 1600 1600 1600 3600 3600 3600 5000 500
A – – – – 2000 2000 2000 – – – – A – – – – 2500 2500 2500 – – – –
Ra ted s hort c irc uit c urrent 240VAC kA 42 42 65 65 85 85 100 85 100 100 125 12
480VAC kA 42 42 50 50 65 85 100 65 85 100 85 12
600VAC kA 35 42 50 50 65 65 85 65 85 85 85 8
Ra ted s ho rt time c urrent kA 35 42 50 50 65 65 65 65 85 85 100 10
Trip units
P R111/P -A • • • • • • • • • • • P R112/P -A • • • • • • • • • • •
P R113/P -A • • • • • • • • • • •
Operation timesMa ke time (ma x) ms 80 80 80 80 80 80 80 80 80 80 80 8
B rea k time (IS Tc urrent)(ma x) ms 30 30 30 30 30 30 30 30 30 30 30 3
Overall dimensions, 3 pole
Fixed : H= 418mm /16.46in D= 302mm /11.89in
W (3 po les ) mm /in 296/11.65 296/11.65 404/15.91 566/22.28 782/30.7
Draw out: H= 461mm /18.15in
D= 396.5mm /15.61 in W (3 po les )
mm /in 324/12.76 324/12.76 432/17.01 594/23.39 810/31.8
Weights (CB w ith releas es, RH terminals a nd CTs, a cc ess ories excluded )
Fixed 3 po les Kg /lb s 452/93 46/101 68/150 95/209 140/30
Dra w out 3 po les Kg /lb s 65/143 72/159 100/220 147/324 210/46
Overall dimensions, 4 poleFixed : H= 418mm /16.46in
D= 302mm /11.89in
W (4 poles ) mm /in 386/15.20 386/15.20 530/20.87 656/25.83 908/35.7Draw out: H= 461mm /18.15in
D= 396.5mm /15.61in
W (4 poles ) mm /in 414/16.30 414/16.30 558/21.97 684/26.93 936/36.8
Weights (CB w ith releas es, RH terminals a nd CTs, a cc ess ories excluded )
Fixed 4 po les Kg /lb s 50/110 55/121 80/176 115/253 170/374Dra w o ut 4 po les Kg /lbs 80/176 89/196 125/275 190/418 260/57
Spe cifica tions c ommon to the entire rang e
Ra ted ma x volta g e 635 VAC
Ra ted voltag e 600VACTe st vo lta ge (1 min 50/60Hz ) 2. 2kFreq uenc y 50/60Hz
Numb er of po les 3/4
Vers io ns Fixed /Dra w o ut
E1 E2 E3 E4 E6
Lugs: Main Breakers and Main Lugs Only
Fra me s Lug s ize Wire s izeC a t a l og
number
E1 (4) #2-600kc mil KE1C LK 4600
E2 (4) #2-600kc mil KE2C LK 4600
E3 (6) # 2-600kc mil KE3C LK 6600E4 (10) # 2-600kc mil KE4C LK 10600
E5 (12) #2-600kc mil KE6C LK 12600
ABB's Emax a ir circuit breaker is a vailab le with three trip units models. From the P R111 that o ffer
only the bas ic protection functions to the P R113 that offers protec tion, multi-meter ca pab ility, and
co mmunication ca pa bility there is a trip unit for every ap plica tion.
8/18/2019 17.1-16 Pwr Dist System
8/16
7
15 P o w e
r
D i s t r i b u
t i o n
S y s t e
m s
17.8 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com
Air circuit breakersEmaxE1 - E2 - E3 - E4 - E6
Mains
4000 - 5000 Amps
W/D/H: 45" /33"/88"
2500 - 5000 Amps
W/D/H: 29.5" /25"/88"
800- 1600 Amps
37.3" /14.25"/88"
2000 - 2500 Amps
37.3" /25"/88"
3000Amps
37.3" /33"/88"
2000 - 2500 Amps
29.5" /33"/88"
800- 1200 Amps*
37.3" /14.25"/88"
43.7 in
feeder
breaker
section
52in52 in
Mains Lugs Only and Feeder BreakerSec t ions
*2 5 " deep enc losure
required as a
minimum for multiple
sections with
horizontalbus.
Typical layouts
8/18/2019 17.1-16 Pwr Dist System
9/16
15P o w e r
D i s t r i b u t i o n
S y s t e m s
Low Voltage Produc ts &Systems 17ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0
ATLV MaxSGLow Volta ge Meta l Enclos edSwitchgear
MaxSG can acc ommodate four Emax P ower Ci rcu
Breaker frame types :
E2 1200-1600A: B -A N-AE3 1200 -2500A: N-A, S -A, H-A, V-A
E4 3200-36 00A: S -A, H-A, V-AE6 400 0-5000A : H-A, V-A
ABB MaxSG switchgear and the use of these
breakers will allow a full range of selectivity,
coo rdination, and short circuit withstand ca pab ili
MaxSG vertica l sections are offered in 23.6”
(600mm), 31.5” (800mm), a nd 39.4” (1000mm) width
and will allow four 2000A circuit breakers to be placin one vertical section maximizing power supply
ca pab ility and minimizing floor spa ce. In ad dition
MaxSG offers depths of 65”(1650mm) and 75”
(1900mm) to provide maximum available cable area
ABB Ma xSG sw itchge ar and Ema x circuit breakers
have been designed and conformance tested to
meet a nd exce ed the industry requirements of ANSI
C37.13, C37.16, C37.17 and UL 1066 for the breakerelements and ANSI C37.20.1, C37.51 a nd U L1558 fo
the switchgear assembly.
MaxSG and ABB w ill fill the customer’s need s
from general application through a full range ofspec ial applications including electrica l protection,
trans fer/co ordination, an d extreme environmenta l
applications.
MaxSG SwitchgearABB MaxSG sw itchge ar is a further continuation in
the development of innovative produc ts from ABB,
a w orld-wide leade r in development and production
of low voltage sw itchge ar. MaxSG is industrial duty
eq uipment buil t to ANSI sta nda rds. MaxSG isdes igned to use 100% rated Ema x circuit breakers
and follows the vision of ABB products in providing
custome rs with ad vance d solutions to meet the
needs associated with the mechanical , electrical
and thermal stress of today’s ma nufacturing
environment.
The MaxS G Metal-Enclosed Low Voltage
Sw i tchgear of fers many ad vantages tha t include :
Modular frame a rrang ements
Optional b arriers for increase d personnel protection
Efficient and flexible designs
Sta nda rd connections to a full range of ABB p roducts
MaxSG is availab le with the following nominalratings:
• 600Vac ma x
• 5000Aac ma x
• 50/60 Hz
• 2200Vac R MS Dielectric
• 125kA Sy mmetrica l S hort Circuit
Withstand Rating
• Seismic Qualifica tion Zones 1 -4
Standard Line-Up of MaxSG Metal Enclosed
Low Voltage sw itchge ar w ith instrumentation
and Emax Po wer Circuit Breakers.
8/18/2019 17.1-16 Pwr Dist System
10/16
7
15 P o w e
r
D i s t r i b u
t i o n
S y s t e
m s
17.10 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com
True Close d Doo r Draw
out Ca pab ility
Emax b reaker
rejection feature.
Safety shutters
sta nda rd in every
Breaker cub icle.
Closed-Door Draw out Capability (standard)MaxS G o ffers the ab ility to rac k the breaker from the “C ONNECT” po sition
through the “TEST” pos ition an d to the “DISC ONNECT” pos ition while the
breaker compartment doo r remains sta tiona ry and close d providing maximum
convenience and personnel safety.
Draw out Padlock ProvisionAllow s the Ema x brea ker to be pa dloc ked in the “C ONNECT”, “TEST” or
“DISCONNECT” po sition providing an a dde d de gree of sa fety.
Breaker Rejection Feature (standard)P revents brea kers with lowe r sho rt circuit/co ntinuous current rating s from
being inserted into the breaker compa rtment.
Safety Shutters (standard)Sa fety shutters to prevent acc idental contac t with live bus a re a stand ard on a l l
breakers. In addition a pad lock feature is availab le to lock the shutters in the
closed position for an added degree of safety.
Breaker Insertion / Withdrawal Interlock (standard)Interlocks prevent racking of the breaker while the ma in contac ts a re closed.
Kirk Key InterlocksAllow s the breaker to be locked ope n when in the conne cted p os ition. Typica l
mecha nical breaker interlocking can b e ac hieved w ith this feature. Single and
double ba rrel locks a re availab le in the brea ker compa rtment.
Overhead Lift DeviceA rail mounted hoist is installed on top of the equipment for lifting the breakers
into a nd out of the breaker cubicles.
MaxSG overhead lift
device.
ATLV MaxSGFeatures
8/18/2019 17.1-16 Pwr Dist System
11/16
15P o w e r
D i s t r i b u t i o n
S y s t e m s
Low Voltage Produc ts &Systems 17.ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0
Bus DesignAll horizonta l and vertica l bus a re rate d for ANSI an d UL sta nda rd temperature
rise req uirements of ma ximum 65°C rise o ver an amb ient temperature of 40°C.
Bus Insulation SystemsBa re bus is provided as s tanda rd in al l MaxSG sw itchg ear. The config urationprovides horizontal isolation ba rriers at al l t iebreakers for a dde d protection inthe event of a fault . An insulated bus s ystem that c ompletely insulates the bus
with thermo-contrac tile flame resistant tubing is also a vailab le. At connec tion
joints an ad hesive coated low voltag e tape o r optional flexible boots are
supplied for customer inspection and ma intenanc e.
Bus BracingSteel supported polyester type fingerplates provide bus brac ing. Bus brac ingis ava ilab le from 50kA to 125kA symm etrical ratings .
Rear BarriersSteel main bus ba rriers a re availab le to completely isolate the rear ca ble
compa rtment area from the main bus for ad ded pe rsonnel safety. Steel inter-
compa rtment barriers are a lso available to isolate ea ch vertica l section.
Silver Plated Bus (Standard)All bus is co ppe r with a silver plated s urfac e. Tin plated b us is offered as a noption.
Ground BusA ground b us is supplied over the entire length of the s witchgea r and is
conveniently located for customer connec tions.
MaxSG main bus designed w ith the end user in mind.
ATLV MaxSGBus d esign
Optional rear main bus barriers, providing a completely
isolated cable compartment.
8/18/2019 17.1-16 Pwr Dist System
12/16
7
15 P o w e
r
D i s t r i b u
t i o n
S y s t e
m s
17.12 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com
Rear cable area.
Basic StructureThe ba sic structure of the switchg ea r is a rigid platform co nstructe d of 12gA
stee l. Lifting is ava ilab le through floo r jac ks.
HingesDoors are atta ched w ith semi-concea led hinges a l lowing rugged s upport forequipment mounting and providing protection ag ainst non-a uthorized removalof doors w ith the use of tamper resistant hardwa re.
Sta nda rd bolted rear cover and optional hinged rea r door.
Rear Covers/ DoorsRear bolted covers w ith tap type s crews p rovide ea sy removal and instal lation
in the field. Optional full height hinged d oors a re also ava ilab le on req uest.
Rear Cable SpaceCond uit entries meet and exce ed a l l app lica ble NEC requirements. Extended
rear compartment spa ce is available as a n option to al low extra s pac e i f
desired.
Paint and FinishMaxSG uses an electro-static powder coat finish that meets and exceeds IEEE
C37.20.1 coa ting qua lific ation requirements . ANSI 61 light gray is offered as a
s tandard.
ATLV MaxSGS tructura l des ig n
8/18/2019 17.1-16 Pwr Dist System
13/16
15P o w e r
D i s t r i b u t i o n
S y s t e m s
Low Voltage Produc ts &Systems 17.ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0
Secondary TerminationsCustome r second ary terminations a re loca ted a bove the circuit breaker
providing a mple room for cus tomer connec tion routing and termination.
Spa re terminal points c an b e loca ted in the front of the gea r in an instrument
compartment.
Instrument compartmentsWhen a dditional devices are required s epa rate instrument compa rtments
are supplied. Voltage transformers, when spe cified, a re also mounted in the
instrument compa rtments with their primary and s eco nda ry fuse protection.
Intercubicle WiringIntercubicle wiring is done on terminal strips located in a wire way on top of the
equipment. This al lows for quick and ea sy ac ces s w hen instal l ing or expandingthe MaxSG swi tchgear.
Wire DesignationHeat s hrink permanent marking origin destination w ire tag s a re offered a s a
standard on al l MaxSG switchgear.
Control Wiring#14 gA SIS wiring is standard. Wiring is offered with the standard insulated
locking fork and optional ring type terminals.
Customer secondary
terminal locations.
Instrument compa rtment
ATLV MaxSGWiring /Instrumenta tion
8/18/2019 17.1-16 Pwr Dist System
14/16
7
15 P o w e
r
D i s t r i b u
t i o n
S y s t e
m s
17.14 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com
Section sizingThe ba sic Ma xSG sw itchge ar is 87” (2200mm) in height, 90.2” (2290mm) to the
top of the w iring and 98.9” (2511mm) over the top of the overhea d lifting d evice,and 65” (1650mm) de ep. The width of the vertica l se ction is determined b y the
breaker type and frame s ize.
Tab le: Se ction Sizing
Brea ker Brea ker Min. Minimum Optional
Frame Cubicle Se ction Equipment Equipment
Size Height Width Depth Depth
1200-2000A 20.7" 23.6" 65" 75"
525 mm 600mm 1650mm 1900mm
2500A-3600A 20.7" 31.5" 65" 75"
525 mm 800mm 1650mm 1900mm
4000A-5000A 20.7" 39.4" 65" 75"
525 mm 1000mm 1650mm 1900mm
MaxSG weightsThe proces s for determining the c umulative weight for MaxS G sw itchge ar is to
ad d the weights for each vertica l sec tion of eq uipment and a dd the total weight
of the breakers to b e instal led.
Tab le: MaxS G Sw itchgea r Se ction Weights S ec tion Width Weight (lbs .)
23.6” 971
31.5” 1155
39.4” 1381
* 257lbs to be a dde d for end pa nels
Tab le: Emax B reaker Weights
Brea ker type Weight (lbs.)
E2 159
E3 220
E4 324
E6 463
MaxSG rules for layouts and sizing• Main and tie breakers must be plac ed in the “C” compa rtment.
• One breaker ca n be plac ed below a ma in breaker.
• One breaker ca n be placed b elow a t ie breaker.
• Instrument co mpa rtments are 20.7” (525mm) or 41.4" (1050mm) in height.
• Miniature c ontrol switches, miniature volt/ammeters, and indica ting l ights ca n
be mounted on breaker compa rtment doo rs.
• Liquid co oled transformers require a 15” trans ition section.
• A maximum of four breakers ca n be plac ed in a vertical section.
• The factory s hould be co nsulted to d etermine i f cabling a rrang ements w ill
al low UL service e ntrance.
• The factory should be c onsulted for special applica tions such a s fire pump
breakers.
ATLV MaxSGDimens iona l da ta
8/18/2019 17.1-16 Pwr Dist System
15/16
15P o w e r
D i s t r i b u t i o n
S y s t e m s
Low Voltage Produc ts &Systems 17.ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0
ATLV MaxSGDimens iona l da ta
MaxSG elevation and section view
MaxSG base plan drawings
FRONT VIEWSIDE SECTION
E2 TYPE
FEEDER BREAKER
E3 TYPE
MAIN BREAKER
E3 TYPE
FEEDER BREAKER
MAIN BUS
E3 TYPE
FEEDER BREAKERNEUTRAL BUS
FLOOR PLAN
OOR PLAN
FLOOR PLAN
8/18/2019 17.1-16 Pwr Dist System
16/16
7
15 P o w e
r
D i s t r i b u
t i o n
S y s t e
m s
ABB 's Ema x air circuit breaker is ava ilab le with three trip units mo dels . From the P R111 that o ffers
only the basic protection functions to the PR113 that offers protection, multi-meter capability, and
communication capability there is a trip unit for every application.
Circuit breaker type E2 E3 E4 E6
P erforma nc e level B -A N-A N-A S -A H-A V-A S -A H-A V-A H-A V-A
Ra ted c ontinuo us c urrent A 1600 1200 2000 1200 1200 1200 3200 3200 3200 4000 4000
File # E194191 A – 1600 2500 1600 1600 1600 3600 3600 3600 5000 5000 A – – – 2000 2000 2000 – – – – –
A – – – 2500 2500 2500 – – – – –
Ra ted s hort c irc uit c urrent 240VAC kA 42 65 65 85 85 100 85 100 100 125 125
480VAC kA 42 50 50 65 8 5 100 65 85 100 85 125
600VAC kA 42 50 50 65 65 85 65 85 85 85 85
Ra ted s hort time c urrent kA 42 50 50 65 65 65 85 85 85 100 100
Trip units
P R111/P -A • • • • • • • • • • •
P R112/P -A • • • • • • • • • • •P R113/P -A • • • • • • • • • • •
Operation times
Ma ke time (ma x) ms 80 80 80 80 80 80 80 80 80 80 80Brea k time (IST
current)(ma x)
ms 30 30 30 30 30 30 30 30 30 30 30
Overall dimensions, 3 pole
W (3 po les ) mm /in 296/11.65 404/15.91 566/22.28 782/30.79
Draw out: H= 461mm /18.15in
D= 396.5mm /15.61in W (3 po les )
mm /in 324/12.76 432/17.01 594/23.39 810/31.89Weights (CB w ith releas es, RH terminals a nd CTs, a cc ess ories excluded )
Dra w out 3 po les Kg /lb s 72/159 100/220 147/324 210/463
Spe cifica tions c ommon to the entire rang eRa ted ma x volta g e 635 VAC
Ra ted voltag e 600VAC
Te st vo lta ge (1 min 50/60Hz ) 2. 2kVFreq uenc y 50/60Hz
Numb er of po les 3
Vers io ns Dra w o ut
ATLV MaxSGAir circuit breakers
E2 E3 E4 E6
* For add itiona l information on Emax circuit brea kers and
related products see catalogs listed below:
* Emax Catalog :
1SDC200003D0201
* MaxSB C ata log: AC1800