    Low Voltage Produc ts &Systems 17ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0

    Switchboard MaxSBLow Volta ge P rod ucts a nd S ystems

    New / ExperiencedBuilding on years of experience in supplying

    low voltage distribution equipment all over the

    world ABB o pens a new a pproach to what a

    swi tchboard can b e and how i t can b et ter serve

    the user, the des ign engineer and the co ntractor.

    Fresh / FamiliarABB builds on the familiar look of a s witchboa rd

    with group mounted molded c as e circuit breakers

    and fi xed or draw out ma in breakers. Fresh

    ideas a re incorporated w ith features such as a

    slotted vertica l bus de sign, a full hinged doo r

    that incorporates the breaker cover plates, and a

    modular frame e nclosure system.

    Unique / ReliableUnique design features such as the slotted bus,

    and hinged door make this switchboard new.Pla ted copper bus , b ol ted b us connect ions , a

    frame enclosure structure, a nd ABB’s proven

    breaker technology ma ke this ABB sw itchbo ard

    highly reliab le. Qua lity is a sta nda rd fea ture in

    ABB sw itchbo ards. A l ist of expens ive optionsis not needed to ensure the highest qua lity

    s tanda rds are met.

    Features

    • Hinged door and large wire ways save t ime a

    money in field wiring.

    • Unique bus layout delivers the freedom to

    locate feeder breakers independent of any hopattern.

    • Plated copper bus used in al l three phases an

    neutral.

    • Cop per ground bus extends full width of

    switchboard.

    • Horizontal bus up to 5000 Amps

    • Vertica l bus up to 3000 Amps

    • G roup mounted feeder breakers ranging from

    15 amps to 1200 Amps

    • Main breakers up to 5000 Amps

    • Strong frame construction isolates bus andbreaker ass emblies from enclosure “s kin”. Du

    rable dry paint finish. Four inch b as e and liftin

    eyes are standa rd.

  • 8/18/2019 17.1-16 Pwr Dist System

    2/16

    7

    15  P o w e

     r

      D  i s  t r  i  b u

      t  i o n 

     S  y s  t e

     m s

    17.2 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com

    Switchboard MaxSBGeneral information

    5000 amp Mains and 3000

    amp vertical bus designs

    enable this switchboard to

    distribute power in the largest

    low voltag e applica tions. A

    multi-layered b us d esign a ndmodular enclosure system

    provide the flexibility to

    provide a n 800 amp free-s tanding sw itchboard tha t

    has an extremely small foot

    print.

    Precise / FlexibleABB ’s switchboa rd uses a frame-bas ed enclosure system. Unlike self-

    supporting enclosures the frame supports the bus ba r and breaker as semb lies.

    Front panels, s idewalls, and rear panels a re also supported by the frame

    structure. This design offers a number of adva ntage s over self-supporting

    enclosure systems . Dama ged wa lls and panels can be eas ily replac ed

    without the need to disa ss emble interior bus or breaker ass emblies. The

    modular nature of ABB’s frame e nclosure system ma kes i t easy to expand

    the sw itchbo ard by adding sections as system requirements change. Simply

    remove a side wa ll and b utt the new se ction aga inst the old. Overlappinghorizontal bus de sign makes for a simple and ac curate splice c onnection.

    Custom / StandardWouldn’t it be nice to have the freedom to layout a sw itchbo ard in such a wa y

    that i t compliments the a pplica tion a nd s i te requirements? Would you benefit

    from the freedo m to loca te breakers as you cho ose ? Wouldn’t you l ike to ad dcustom fea tures l ike a d ust-proof enclosure, or a full glass doo r for add ed

    sec urity and an enha nced appe aranc e in high visibil ity si tes?

    ABB’s standard switchboard design makes these and other custom like

    features affordab le.

    1 15-30A are 65kA at 480VAC

    Industrial / CommercialThe Operations Mana ger wa nts reliab ili ty, the s pecifying e ngineer wants a

    product he c an b elieve in, the service depa rtment demand s ma intainab ili ty,

    the CFO wants value and the contractor wa nts a supplier and prod uct that is

    eas y to work with and o n time delivery. One compa ny can ma tch al l of these

    requirements; ABB .

    The Operations Manag er and s pecifying engineer appreciate features s uch

    as plated copper bus and bolted bus connections. A frame-based enclosure

    system delivers strength, expa nda bili ty and simplifies repairs. The c ompletesystem is designed a nd tested to meet or exceed UL req uirements.

    The maintenance d epartment enjoys a hinged d oor that ma kes i t easy for

    qua lified perso nnel to acc ess the c ab inet to maintain and s ervice ABB’s

    sw itchbo ards . Connec tions are located so that you can ac tually get to them. A

    framed enclosure construction and bus design make this switchboard easy toexpand as requirements change.

    Contrac tors save on instal lation time with easy to acc ess terminals, increas ed

    cab le area a nd a d esign tha t makes i t easy to add breakers and a ccess or ies inthe field.

    Unique hole-less bus b ar

    arrangement a l lows you to instal l

    feeder breakers in any loca tion

    vertica lly. Less t ime less has sle.

    Easy a cc ess to incoming terminals.

    Less t ime less has sle

  • 8/18/2019 17.1-16 Pwr Dist System

    3/16

    15P  o w  e r  

    D i  s t  r  i  b u t  i  o n  

    S   y  s t  e m s 

    Low Voltage Produc ts &Systems 17ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0

    Switchboard MaxSBLow Volta ge P rod ucts a nd S ystems

    Feeder BreakersKAIC Trip Frame Ra ting Amps

    Fra me P olesS p a c e

    Inches277 240 480 15 20 25 30 35 40 50 60

    T1B 1 1.0   182

    T1N 3 3.0 50 223T2S 2/3 3.54 65 35

    T2H 2/3 3.54 100 65

    T3N 2/3 4.13 50 25T3S 2/3 4.13 65 35

    S 3N 2/3 4.13 65 25S 3H 2/3 4.13 100 50

    S 3L 2/3 4.13 150   851

    70 80 90 100

    T1B 1 1.0 18T1N 3 3.0 50 22

    T2S 2/3 3.54 65 35

    T2H 2/3 3.54 100 65T3N 2/3 4.13 50 25

    T3S 2/3 4.13 65 35

    S 3N 2/3 4.13 65 25

    S 3H 2/3 4.13 100 50

    S 3L 2/3 4.13 150 85

    125 150 175 200 225

    T3N 2/3 4.13 50 25

    T3S 2/3 4.13 65 35

    S 3N 2/3 4.13 65 25

    S 3H 2/3 4.13 100 50

    S 3L 2/3 4.13 150 85

      250 Electronic - ad justa ble 40 - 250

    S 4N 2/3 4.13 65 25

    S 4H 2/3 4.13 150 65

    S 4L 2/3 4.13 200 100

      400 Electronic - ad justa ble 160 - 400

    S 5N 2/3 5.51 65 35

    S 5H 2/3 5.51 150 65

    S 5L 2/3 5.51 200 100

      600 Electronic - ad justa ble 240 - 600

    S 6N 2/3 8.27 65 50

    S 6H 2/3 8.27 150 65

    S 6L 2/3 8.27 200 100

    800 Electronic - adjustable 320 - 800

    S 6N 2/3 8.27 65 50

    S 6H 2/3 8.27 150 65

    S 6L 2/3 8.27 200 100

      1200 Electronic - ad justa ble 480 - 1200

    S 7H 2/3 8.27 100 65

    1 S 3L 15-30A 65kA@480V

    2 T1B 15A 10kA@277V

    T1N 15A35kA@240V

    14kA@480V

    Maximum switchboard rating = 100kA

    T4 = 4.14

    T5 = 5.51

    T4 &T5 = 5.61 D B L M

          

                  

                          

              

  • 8/18/2019 17.1-16 Pwr Dist System

    4/16

    7

    15  P o w e

     r

      D  i s  t r  i  b u

      t  i o n 

     S  y s  t e

     m s

    17.4 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com

    Molded case circuit breakersTma xT1 100 A - T2 100A - T3 225 A

    UL 489 CSA 22.2C irc uit b rea kers Tma x T1 1p Tma x T1 Tma x T2 Tma x T3

    Ma ximum fra me c o ntinuous c urrent 40° C lu [A] 100 100 100 225Numb er of po les [Nr] 1 3/4 2/3/4 2/3/4

    Ra ted opera tiona l vo lta g e (AC ) 50-80Hz Ue [V] 277 480 480 480

    S ho rt c irc uit interrupting c a pa c ity, Ic u B N S H N S

    AC 240V [kA] 50 65 100 50 65

     277V [kA] 181

     480V [kA] 222   35 65 25 35

    DC 250V 2 poles in s eries [kA] 25 25 35

     500V 3 po les in s erie s [kA] 25 25 35

    Rela ys TM   – –    –   – 

      P R22 1DS –

      MA –   – 

    Vers io ns MC C B – –    –   – 

      MC S   – – 

      MC P –   – 

    IEC 60047-2C irc uit b rea kers Tma x T1 1p Tma x T1 Tma x T2 Tma x T3

    Ra ted uninterrupted c urrent lu [A] 160 160 160 250

    Numb er of po les [Nr] 1 3/4 3/4 3/4

    Ra ted s ervic e vo lta g e, Ue AC 50-60Hz [V] 240 690 690 690DC [V] 125 500 500 500

    Ra ted ultima te s hort c irc uit b rea king c a pa c ity , lc u B B C N N S H L N S

    AC 220/230V [kA] 25 25 40 50 65 85 100 120 50 85

      380/415 [kA] 16 25 36 36 50 70 85 36 50

      440V [kA] 10 15 22 30 45 55 75 25 40

      500V [kA] 8 10 15 25 30 36 50 20 30

      690V [kA] 3 4 6 6 7 8 10 5 8

    DC 250V 2 poles in s eries [kA] 16 25 36 35 50 70 85 36 50  250V 2 po les in s eries [kA] 20 3 0 40 40 55 85 100 40 55

      500V 2 po les in s eries [kA] 16 25 36 36 50 70 85 36 50

    Trip units Fixed therma l ma g netic –Fixed therma l ma g netic – – –

      P R221/DS –

      Fixed ma g netic –

      Ad jus ta b le ma g netic – –

    Dimens ions H [in/mm] 5.12/130 5.12/130 5.12/130 5.9/150

      W 1p o r 3p [in/mm] 1/25.4 3/76 3.54/90 4.13/105

      W 4p [in/mm] 4/102 4.72/122 5.5/140

      D [in/mm] 2.76/70 2.76/70 2.76/70 2.76/70

    Me c ha nic a l life [No opera tio ns ] 25000 25000 25000 25000

      [No ho urly opera tio ns ] 240 240 240 120

    Elec tric a l life [No opera tio ns ] 8000 8000 8000 8000

      [No ho urly opera tio ns ] 120 120 120 120

    Tma x T2 ca n be fit ted w ith the late st g enera tion in electronic trip units.

    This is the first time that a c ircuit-breaker of this size ca n bene fit fromelectronic protection, and the setting flexibility it provides.

    1 15A : 10kA@277Va c2 15A : 35kA@240Vac ; 14kA@480Vac

    T1 100A T2 100A T3 225A

  • 8/18/2019 17.1-16 Pwr Dist System

    5/16

    15P  o w  e r  

    D i  s t  r  i  b u t  i  o n  

    S   y  s t  e m s 

    Low Voltage Produc ts &Systems 17ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0

    Molded case circuit breakersIsomaxS 3B - S 3 - S 4

    Circuit breaker type S 3B S 3 S 4

    Ma ximum fra me c o ntinuous ra ted c urrent 40° C A 225 150 225 250

    Ra ted o pera tiona l vo lta g e 50/60Hz V 240 600 480 600

    Tes t volta g e 1 min. 50/60 Hz V 3000 3000 3000 3000

    Ra ted impuls e w iths ta nd vo lta g e kV 6 6 6 8

    P o les No. 2/3 2/3/4 2/3/4 2/3/4

    P erforma nc e level B N H L N H L N H L  240VAC 150 65 100 150 65 100 150 65 100 150

    UL/C S A s hort-c irc uit 480VAC – 25 50 852 25 5 0 65 65 150 200

    Interrupting c a pa c ity 600VAC kA RMS – 14 14 25 – – – 18 32 35UL 489, File #E93565   500VDC 1 50 35 50 65 25 35 50 – – –

    CS A, File #LR90467   600VDC 1 – 20 35 50 – – – – – –

      202/230VAC 150 65 100 170 65 100 170 65 100 200

    IEC -947 ra ted ultima te 380/400/415VAC – 35 65 85 35 65 85 35 65 100

    S ho rt-c irc uit Ic u 440VAC kA RMS – 30 50 65 30 50 65 30 50 80B rea king c a pa c ity 500VAC – 25 40 50 25 40 50 25 40 65

      660/690VAC – 14 18 20 14 18 20 18 22 30

    Overc urrent trip unit/relay

    Therma l-ma g netic • • • –

    Mic ro pro c es s o r-ba s ed – – – •Dia lo g ue unit – – – •

    Interc ha ng ea b ility – – – •

    Vers ion — Term ina ls

    Fixed — fro nt o r rea r • • • •P lug -in — fro nt o r rea r • • • •Withd ra w a b le — front o r rea r • • • •

    Dimensions (fixed circuit-breaker)

    2P &3 P (H x W x D ) in 6 .7 0 x 4 .13 x 4 . 07 6 .7 0 x 4.13 x 4 . 07 6 .70 x 4.13 x 4 . 07 10 .0 x 4 .13 x 4 . 04P (H x W x D) in 6.70 x 5.51 x 4 .07 6.70 x 5.51 x 4 .07 6.70 x 5.51 x 4 .07 10.0 x 5.51 x 4 .0

    Mechanica l duration  o pera tio ns No. 25,000 25,000 25,000 25,000

      freq uenc y ops . /ho ur 240 120 120 120

    Weig hts (fixed 3P ) lbs . 6.75 6.75 6.75 8.8

    Isolation of control

    accessor ies and

    power poles al lows

    for the sa fe add ition /

    replac ement of s hunttrips, auxiliaries, bellalarm and under

    voltag e relays.

    S 3B S 3 S 4

    1 For use w ith thermal - magnetic trip only:

    500 VDC, 2 po les in series

    600 VDC, 3 poles in series2 15-30A units a re 65kA at 480VAC

  • 8/18/2019 17.1-16 Pwr Dist System

    6/16

    7

    15  P o w e

     r

      D  i s  t r  i  b u

      t  i o n 

     S  y s  t e

     m s

    17.6 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com

    Molded case circuit breakersIsomaxS 3B - S 3 - S 4

    Circuit breaker type S 5 S 6 S 7 S 8

    Ma ximum fra me c o ntinuous ra te d c urre nt 40° C A 400 600 800 1200 1600 /200 0/2500

    Ra ted o pera tiona l vo lta g e 50/60Hz V 600 600 600 600 600

    Tes t volta g e 1 min. 50/60 Hz V 3000 3000 3000 3000 3000

    Ra ted impuls e w iths ta nd volta g e kV 8 8 8 8 8

    P o les No. 2/3/4 2/3/4 2/3/4 2/3/4 3

    P erforma nc e level N H L N H L N H L H V

      240VAC 65 150 200 65 150 200 65 150 200 100 120UL/C S A s ho rt-c irc uit 480VAC 35 65 100 50 65 100 50 65 100 65 100

    Interrupting c a pa c ity 600VAC kA RMS 22 22 35 25 35 42 25 35 42 50 85

    UL 489, File #E93565   500VDC 1 35 50 65 35 50 65 35 50 65 – –

    CS A, File #LR90467   600VDC 1 20 35 50 20 35 50 20 35 50 – –

      202/230VAC 65 100 200 65 100 200 65 100 200 100 120

    IEC -947 ra ted ultima te 380/400/415VAC 35 65 100 35 65 100 35 65 100 65 120S ho rt-c irc uit Ic u 440VAC kA RMS 30 50 80 30 50 680 30 50 80 55 100

    B rea king c a pa c ity 500VAC 25 40 65 25 40 65 25 40 65 45 70

      660/690VAC 20 25 30 20 25 35 20 25 35 25 50

    Overc urrent trip unit/re la y

    Therma l-ma g netic • • • – –

    Mic ro pro c es s o r-ba s ed • • • • •Dia lo g ue unit • • • • •

    Interc ha ng ea b ility • • • • •

    Vers ion — Term ina lsFixed — fro nt o r rea r • • • • •

    P lug -in — fro nt o r rea r • • • – –Withd ra w a b le — front o r rea r • • • • –

    Dimensions (fixed circuit-breaker)2P &3P (H x W x D) in 10.0 x 5.51 x 4 .07 10.55 x 8.27 x 4 .07 14.25 x 8.27 x 4.07 15.98 x 8.27 x 5.45 15.75 x 15.98 x 9.25

    4P (H x W x D) in 10.0 x 7.24 x 4 .07 10.55 x 11.0 x 4 .07 14.25 x 11.0 x 4.07 15.98 x 11.0 x 5.45

    Mechanica l duration  o pera tio ns No. 20,000 20,000 20,000 10,000 10,00

      freq uenc y ops . /ho ur 120 120 120 120 20

    Weig hts (fixed 3P ) lb s . 11.0 21.0 22.0 37.5 135

    S5 S 6 S 6 S7 S8 K4TB

     Standard cable lug kits

    Fo r b rea ke rs Amps Wire ra ng eC a t a l og

    number

    S 3 60 14AWG - 2AWG K3TAS 3 - S 4 100 14AWG - 1/0 K4TB

    S 3 - S 4 150 14AWG - 4/0 K4TCS 3 - S 4 - S 5 225 4AWG - 300kc mil K4TD

    S 4 250 6AWG - 350kc mil K4TE

    S 5 300 250kc mil - 500kc mil K5TF

    S 5 400 (2) 3/0 - 250kc mil K5TGS 6 600 (2) 250kc mil - 250Kc mil K5TH

    S 6 800 (3) 2/0 - 400kc mil K6TJS 7 1200 (4) 4/0 - 400kc mil K7TK

    S 8 1600 (4) 1/0 - 750kc mil K8TL

    S 8 2500 (6) 1/0 - 750kc mil K8TM

    Standard cable lugs, for use on load side of circuit breaker. Suitable for use with Cu or AI.

    Special versions available with taps and screw for control wire connection. Note: S6 and

    S7 lugs a re Al9Cu (90° ); all others AL7Cu (75°C ). Must use wire bas ed on 75°C amp ac ity.

  • 8/18/2019 17.1-16 Pwr Dist System

    7/16

    15P  o w  e r  

    D i  s t  r  i  b u t  i  o n  

    S   y  s t  e m s 

    Low Voltage Produc ts &Systems 17ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0

    Air circuit breakersEmaxE1 - E2 - E3 - E4 - E6

    Circuit breaker type E1 E2 E3 E4 E6

    P erforma nc e level B -A B -A N-A N-A S -A H-A V-A S -A H-A V-A   H-A V-

    Ra ted c ontinuo us c urrent A 800 1600 1200 2000 1200 1200 1200 3200 3200 3200 4000 400

      File # E194191 A 1200 – 1600 2500 1600 1600 1600 3600 3600 3600 5000 500

      A – – – – 2000 2000 2000 – – – –   A – – – – 2500 2500 2500 – – – –

    Ra ted s hort c irc uit c urrent 240VAC kA 42 42 65 65 85 85 100 85 100 100 125 12

      480VAC kA 42 42 50 50 65 85 100 65 85 100 85 12

      600VAC kA 35 42 50 50 65 65 85 65 85 85 85 8

    Ra ted s ho rt time c urrent kA 35 42 50 50 65 65 65 65 85 85 100 10

    Trip units

    P R111/P -A • • • • • • • • • • • P R112/P -A • • • • • • • • • • •

    P R113/P -A • • • • • • • • • • •

    Operation timesMa ke time (ma x) ms 80 80 80 80 80 80 80 80 80 80 80 8

    B rea k time (IS Tc urrent)(ma x) ms 30 30 30 30 30 30 30 30 30 30 30 3

    Overall dimensions, 3 pole

    Fixed : H= 418mm /16.46in  D= 302mm /11.89in

      W (3 po les ) mm /in 296/11.65 296/11.65 404/15.91 566/22.28 782/30.7

    Draw out: H= 461mm /18.15in

      D= 396.5mm /15.61 in  W (3 po les ) 

    mm /in 324/12.76 324/12.76 432/17.01 594/23.39 810/31.8

    Weights (CB w ith releas es, RH terminals a nd CTs, a cc ess ories excluded )

    Fixed 3 po les Kg /lb s 452/93 46/101 68/150 95/209 140/30

    Dra w out 3 po les Kg /lb s 65/143 72/159 100/220 147/324 210/46

    Overall dimensions, 4 poleFixed : H= 418mm /16.46in

      D= 302mm /11.89in

      W (4 poles ) mm /in 386/15.20 386/15.20 530/20.87 656/25.83 908/35.7Draw out: H= 461mm /18.15in

      D= 396.5mm /15.61in

      W (4 poles ) mm /in 414/16.30 414/16.30 558/21.97 684/26.93 936/36.8

    Weights (CB w ith releas es, RH terminals a nd CTs, a cc ess ories excluded )

    Fixed 4 po les Kg /lb s 50/110 55/121 80/176 115/253 170/374Dra w o ut 4 po les Kg /lbs 80/176 89/196 125/275 190/418 260/57

    Spe cifica tions c ommon to the entire rang e

    Ra ted ma x volta g e 635 VAC

    Ra ted voltag e 600VACTe st vo lta ge (1 min 50/60Hz ) 2. 2kFreq uenc y 50/60Hz

    Numb er of po les 3/4

    Vers io ns Fixed /Dra w o ut

    E1 E2 E3 E4 E6

    Lugs: Main Breakers and Main Lugs Only

    Fra me s Lug s ize Wire s izeC a t a l og

    number

    E1 (4) #2-600kc mil KE1C LK 4600

    E2 (4) #2-600kc mil KE2C LK 4600

    E3 (6) # 2-600kc mil KE3C LK 6600E4 (10) # 2-600kc mil KE4C LK 10600

    E5 (12) #2-600kc mil KE6C LK 12600

    ABB's Emax a ir circuit breaker is a vailab le with three trip units models. From the P R111 that o ffer

    only the bas ic protection functions to the P R113 that offers protec tion, multi-meter ca pab ility, and

    co mmunication ca pa bility there is a trip unit for every ap plica tion.

  • 8/18/2019 17.1-16 Pwr Dist System

    8/16

    7

    15  P o w e

     r

      D  i s  t r  i  b u

      t  i o n 

     S  y s  t e

     m s

    17.8 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com

    Air circuit breakersEmaxE1 - E2 - E3 - E4 - E6

    Mains

    4000 - 5000 Amps

    W/D/H: 45" /33"/88"

    2500 - 5000 Amps

    W/D/H: 29.5" /25"/88"

    800- 1600 Amps

    37.3" /14.25"/88"

    2000 - 2500 Amps

    37.3" /25"/88"

    3000Amps

    37.3" /33"/88"

    2000 - 2500 Amps

    29.5" /33"/88"

    800- 1200 Amps*

    37.3" /14.25"/88"

    43.7 in

    feeder

    breaker

    section

    52in52 in

    Mains Lugs Only and Feeder BreakerSec t ions

    *2 5 " deep enc losure

    required as a

    minimum for multiple

    sections with

    horizontalbus.

    Typical layouts

  • 8/18/2019 17.1-16 Pwr Dist System

    9/16

    15P  o w  e r  

    D i  s t  r  i  b u t  i  o n  

    S   y  s t  e m s 

    Low Voltage Produc ts &Systems 17ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0

    ATLV MaxSGLow Volta ge Meta l Enclos edSwitchgear

    MaxSG can acc ommodate four Emax P ower Ci rcu

    Breaker frame types :

    E2 1200-1600A: B -A N-AE3 1200 -2500A: N-A, S -A, H-A, V-A

    E4 3200-36 00A: S -A, H-A, V-AE6 400 0-5000A : H-A, V-A

    ABB MaxSG switchgear and the use of these

    breakers will allow a full range of selectivity,

    coo rdination, and short circuit withstand ca pab ili

    MaxSG vertica l sections are offered in 23.6”

    (600mm), 31.5” (800mm), a nd 39.4” (1000mm) width

    and will allow four 2000A circuit breakers to be placin one vertical section maximizing power supply

    ca pab ility and minimizing floor spa ce. In ad dition

    MaxSG offers depths of 65”(1650mm) and 75”

    (1900mm) to provide maximum available cable area

    ABB Ma xSG sw itchge ar and Ema x circuit breakers

    have been designed and conformance tested to

    meet a nd exce ed the industry requirements of ANSI

    C37.13, C37.16, C37.17 and UL 1066 for the breakerelements and ANSI C37.20.1, C37.51 a nd U L1558 fo

    the switchgear assembly.

    MaxSG and ABB w ill fill the customer’s need s

    from general application through a full range ofspec ial applications including electrica l protection,

    trans fer/co ordination, an d extreme environmenta l

    applications.

    MaxSG SwitchgearABB MaxSG sw itchge ar is a further continuation in

    the development of innovative produc ts from ABB,

    a w orld-wide leade r in development and production

    of low voltage sw itchge ar. MaxSG is industrial duty

    eq uipment buil t to ANSI sta nda rds. MaxSG isdes igned to use 100% rated Ema x circuit breakers

    and follows the vision of ABB products in providing

    custome rs with ad vance d solutions to meet the

    needs associated with the mechanical , electrical

    and thermal stress of today’s ma nufacturing

    environment.

    The MaxS G Metal-Enclosed Low Voltage

    Sw i tchgear of fers many ad vantages tha t include :

    Modular frame a rrang ements

    Optional b arriers for increase d personnel protection

    Efficient and flexible designs

    Sta nda rd connections to a full range of ABB p roducts

    MaxSG is availab le with the following nominalratings:

    • 600Vac ma x

    • 5000Aac ma x

    • 50/60 Hz

    • 2200Vac R MS Dielectric

    • 125kA Sy mmetrica l S hort Circuit

    Withstand Rating

    • Seismic Qualifica tion Zones 1 -4

     

    Standard Line-Up of MaxSG Metal Enclosed

    Low Voltage sw itchge ar w ith instrumentation

    and Emax Po wer Circuit Breakers.

  • 8/18/2019 17.1-16 Pwr Dist System

    10/16

    7

    15  P o w e

     r

      D  i s  t r  i  b u

      t  i o n 

     S  y s  t e

     m s

    17.10 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com

    True Close d Doo r Draw

    out Ca pab ility

    Emax b reaker

    rejection feature.

    Safety shutters

    sta nda rd in every

    Breaker cub icle.

    Closed-Door Draw out Capability (standard)MaxS G o ffers the ab ility to rac k the breaker from the “C ONNECT” po sition

    through the “TEST” pos ition an d to the “DISC ONNECT” pos ition while the

    breaker compartment doo r remains sta tiona ry and close d providing maximum

    convenience and personnel safety.

    Draw out Padlock ProvisionAllow s the Ema x brea ker to be pa dloc ked in the “C ONNECT”, “TEST” or

    “DISCONNECT” po sition providing an a dde d de gree of sa fety.

    Breaker Rejection Feature (standard)P revents brea kers with lowe r sho rt circuit/co ntinuous current rating s from

    being inserted into the breaker compa rtment.

    Safety Shutters (standard)Sa fety shutters to prevent acc idental contac t with live bus a re a stand ard on a l l

    breakers. In addition a pad lock feature is availab le to lock the shutters in the

    closed position for an added degree of safety.

    Breaker Insertion / Withdrawal Interlock (standard)Interlocks prevent racking of the breaker while the ma in contac ts a re closed.

    Kirk Key InterlocksAllow s the breaker to be locked ope n when in the conne cted p os ition. Typica l

    mecha nical breaker interlocking can b e ac hieved w ith this feature. Single and

    double ba rrel locks a re availab le in the brea ker compa rtment.

    Overhead Lift DeviceA rail mounted hoist is installed on top of the equipment for lifting the breakers

    into a nd out of the breaker cubicles.

    MaxSG overhead lift

    device.

    ATLV MaxSGFeatures

  • 8/18/2019 17.1-16 Pwr Dist System

    11/16

    15P  o w  e r  

    D i  s t  r  i  b u t  i  o n  

    S   y  s t  e m s 

    Low Voltage Produc ts &Systems 17.ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0

    Bus DesignAll horizonta l and vertica l bus a re rate d for ANSI an d UL sta nda rd temperature

    rise req uirements of ma ximum 65°C rise o ver an amb ient temperature of 40°C.

    Bus Insulation SystemsBa re bus is provided as s tanda rd in al l MaxSG sw itchg ear. The config urationprovides horizontal isolation ba rriers at al l t iebreakers for a dde d protection inthe event of a fault . An insulated bus s ystem that c ompletely insulates the bus

    with thermo-contrac tile flame resistant tubing is also a vailab le. At connec tion

    joints an ad hesive coated low voltag e tape o r optional flexible boots are

    supplied for customer inspection and ma intenanc e.

    Bus BracingSteel supported polyester type fingerplates provide bus brac ing. Bus brac ingis ava ilab le from 50kA to 125kA symm etrical ratings .

    Rear BarriersSteel main bus ba rriers a re availab le to completely isolate the rear ca ble

    compa rtment area from the main bus for ad ded pe rsonnel safety. Steel inter-

    compa rtment barriers are a lso available to isolate ea ch vertica l section.

    Silver Plated Bus (Standard)All bus is co ppe r with a silver plated s urfac e. Tin plated b us is offered as a noption.

    Ground BusA ground b us is supplied over the entire length of the s witchgea r and is

    conveniently located for customer connec tions.

    MaxSG main bus designed w ith the end user in mind.

    ATLV MaxSGBus d esign

    Optional rear main bus barriers, providing a completely

    isolated cable compartment.

  • 8/18/2019 17.1-16 Pwr Dist System

    12/16

    7

    15  P o w e

     r

      D  i s  t r  i  b u

      t  i o n 

     S  y s  t e

     m s

    17.12 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com

    Rear cable area.

    Basic StructureThe ba sic structure of the switchg ea r is a rigid platform co nstructe d of 12gA

    stee l. Lifting is ava ilab le through floo r jac ks.

    HingesDoors are atta ched w ith semi-concea led hinges a l lowing rugged s upport forequipment mounting and providing protection ag ainst non-a uthorized removalof doors w ith the use of tamper resistant hardwa re.

    Sta nda rd bolted rear cover and optional hinged rea r door.

    Rear Covers/ DoorsRear bolted covers w ith tap type s crews p rovide ea sy removal and instal lation

    in the field. Optional full height hinged d oors a re also ava ilab le on req uest.

    Rear Cable SpaceCond uit entries meet and exce ed a l l app lica ble NEC requirements. Extended

    rear compartment spa ce is available as a n option to al low extra s pac e i f

    desired.

    Paint and FinishMaxSG uses an electro-static powder coat finish that meets and exceeds IEEE

    C37.20.1 coa ting qua lific ation requirements . ANSI 61 light gray is offered as a

    s tandard.

    ATLV MaxSGS tructura l des ig n

  • 8/18/2019 17.1-16 Pwr Dist System

    13/16

    15P  o w  e r  

    D i  s t  r  i  b u t  i  o n  

    S   y  s t  e m s 

    Low Voltage Produc ts &Systems 17.ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0

    Secondary TerminationsCustome r second ary terminations a re loca ted a bove the circuit breaker

    providing a mple room for cus tomer connec tion routing and termination.

    Spa re terminal points c an b e loca ted in the front of the gea r in an instrument

    compartment.

    Instrument compartmentsWhen a dditional devices are required s epa rate instrument compa rtments

    are supplied. Voltage transformers, when spe cified, a re also mounted in the

    instrument compa rtments with their primary and s eco nda ry fuse protection.

    Intercubicle WiringIntercubicle wiring is done on terminal strips located in a wire way on top of the

    equipment. This al lows for quick and ea sy ac ces s w hen instal l ing or expandingthe MaxSG swi tchgear.

    Wire DesignationHeat s hrink permanent marking origin destination w ire tag s a re offered a s a

    standard on al l MaxSG switchgear.

    Control Wiring#14 gA SIS wiring is standard. Wiring is offered with the standard insulated

    locking fork and optional ring type terminals.

    Customer secondary

    terminal locations.

    Instrument compa rtment

    ATLV MaxSGWiring /Instrumenta tion

  • 8/18/2019 17.1-16 Pwr Dist System

    14/16

    7

    15  P o w e

     r

      D  i s  t r  i  b u

      t  i o n 

     S  y s  t e

     m s

    17.14 Low Voltage P roducts &Systems1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • ww w.ab b-control.com

    Section sizingThe ba sic Ma xSG sw itchge ar is 87” (2200mm) in height, 90.2” (2290mm) to the

    top of the w iring and 98.9” (2511mm) over the top of the overhea d lifting d evice,and 65” (1650mm) de ep. The width of the vertica l se ction is determined b y the

    breaker type and frame s ize.

    Tab le: Se ction Sizing

      Brea ker Brea ker Min. Minimum Optional

    Frame Cubicle Se ction Equipment Equipment

      Size Height Width Depth Depth  

    1200-2000A  20.7" 23.6" 65" 75"

      525 mm   600mm   1650mm   1900mm

      2500A-3600A  20.7" 31.5" 65" 75"

      525 mm   800mm   1650mm   1900mm  

    4000A-5000A  20.7" 39.4" 65" 75"

      525 mm   1000mm   1650mm   1900mm  

    MaxSG weightsThe proces s for determining the c umulative weight for MaxS G sw itchge ar is to

    ad d the weights for each vertica l sec tion of eq uipment and a dd the total weight

    of the breakers to b e instal led.

    Tab le: MaxS G Sw itchgea r Se ction Weights  S ec tion Width Weight (lbs .)

      23.6” 971

    31.5” 1155

    39.4” 1381

    * 257lbs to be a dde d for end pa nels

    Tab le: Emax B reaker Weights

      Brea ker type Weight (lbs.)

      E2 159

      E3 220

      E4 324

      E6 463

    MaxSG rules for layouts and sizing• Main and tie breakers must be plac ed in the “C” compa rtment.

    • One breaker ca n be plac ed below a ma in breaker.

    • One breaker ca n be placed b elow a t ie breaker.

    • Instrument co mpa rtments are 20.7” (525mm) or 41.4" (1050mm) in height.

    • Miniature c ontrol switches, miniature volt/ammeters, and indica ting l ights ca n

      be mounted on breaker compa rtment doo rs.

    • Liquid co oled transformers require a 15” trans ition section.

    • A maximum of four breakers ca n be plac ed in a vertical section.

    • The factory s hould be co nsulted to d etermine i f cabling a rrang ements w ill

    al low UL service e ntrance.

    • The factory should be c onsulted for special applica tions such a s fire pump

    breakers.

    ATLV MaxSGDimens iona l da ta

  • 8/18/2019 17.1-16 Pwr Dist System

    15/16

    15P  o w  e r  

    D i  s t  r  i  b u t  i  o n  

    S   y  s t  e m s 

    Low Voltage Produc ts &Systems 17.ABB Inc. • 888-385-1221 • ww w.abb -control.com 1SXU 000 023 C0

    ATLV MaxSGDimens iona l da ta

    MaxSG elevation and section view

    MaxSG base plan drawings

    FRONT VIEWSIDE SECTION

      E2 TYPE

    FEEDER BREAKER

    E3 TYPE

    MAIN BREAKER

    E3 TYPE

    FEEDER BREAKER

    MAIN BUS

      E3 TYPE

    FEEDER BREAKERNEUTRAL BUS

    FLOOR PLAN

      OOR PLAN

    FLOOR PLAN

  • 8/18/2019 17.1-16 Pwr Dist System

    16/16

    7

    15  P o w e

     r

      D  i s  t r  i  b u

      t  i o n 

     S  y s  t e

     m s

    ABB 's Ema x air circuit breaker is ava ilab le with three trip units mo dels . From the P R111 that o ffers

    only the basic protection functions to the PR113 that offers protection, multi-meter capability, and

    communication capability there is a trip unit for every application.

    Circuit breaker type E2 E3 E4 E6

    P erforma nc e level B -A N-A N-A S -A H-A V-A S -A H-A V-A   H-A V-A

    Ra ted c ontinuo us c urrent A 1600 1200 2000 1200 1200 1200 3200 3200 3200 4000 4000

      File # E194191 A – 1600 2500 1600 1600 1600 3600 3600 3600 5000 5000  A – – – 2000 2000 2000 – – – – –

      A – – – 2500 2500 2500 – – – – –

    Ra ted s hort c irc uit c urrent 240VAC kA 42 65 65 85 85 100 85 100 100 125 125

      480VAC kA 42 50 50 65 8 5 100 65 85 100 85 125

      600VAC kA 42 50 50 65 65 85 65 85 85 85 85

    Ra ted s hort time c urrent kA 42 50 50 65 65 65 85 85 85 100 100

    Trip units

    P R111/P -A • • • • • • • • • • •

    P R112/P -A • • • • • • • • • • •P R113/P -A • • • • • • • • • • •

    Operation times

    Ma ke time (ma x) ms 80 80 80 80 80 80 80 80 80 80 80Brea k time (IST

    current)(ma x)

      ms 30 30 30 30 30 30 30 30 30 30 30

    Overall dimensions, 3 pole

      W (3 po les ) mm /in 296/11.65 404/15.91 566/22.28 782/30.79

    Draw out: H= 461mm /18.15in

      D= 396.5mm /15.61in  W (3 po les ) 

    mm /in 324/12.76 432/17.01 594/23.39 810/31.89Weights (CB w ith releas es, RH terminals a nd CTs, a cc ess ories excluded )

    Dra w out 3 po les Kg /lb s 72/159 100/220 147/324 210/463

    Spe cifica tions c ommon to the entire rang eRa ted ma x volta g e 635 VAC

    Ra ted voltag e 600VAC

    Te st vo lta ge (1 min 50/60Hz ) 2. 2kVFreq uenc y 50/60Hz

    Numb er of po les 3

    Vers io ns Dra w o ut

    ATLV MaxSGAir circuit breakers

    E2 E3 E4 E6

    * For add itiona l information on Emax circuit brea kers and

    related products see catalogs listed below:

    * Emax Catalog :

    1SDC200003D0201

    * MaxSB C ata log: AC1800