QIS 33Y06H52-31E1st Edition: Sep. 2005 (YK)

Models YNT522S, YNT522DOptical Bus Repeater (For Max. 15km)

This inspection standard applies to the Models YNT522S and YNT522D Optical Bus Repeater.

1. INSPECTION AREAS

1.1 Hardware Configuration Inspection• Checking of Hardware Specifications• Configuration Equipment Inspection

1.2 Standard Function Inspection• Communication Inspection (Vnet)

2. INSPECTION METHODS, CONDITIONS AND STANDARDS2.1 Hardware Configuration Inspection

Check the hardware specifications and system components as follows:

2.1.1 Checking Hardware Specifications

(1) ComponentsCheck the model and quantities of the system by referring to the drawings for approval (hereinaftercalled manufacturing specification sheets).

(2) Standard accessoriesCheck the quantities of the standard accessories by referring to the manufacturing specification sheets.

QualityInspectionStandards

Page 2: QIS33Y06H52_31E_001

8/13/2019 QIS33Y06H52_31E_001

http://slidepdf.com/reader/full/qis33y06h5231e001 2/2

QIS 33Y06H52-31E

2/22.1.2 System Component Inspection

(1) Visual Inspection of Constructiona. Checking External Dimensions

Measure the major outside dimensions and check that they are as shown in the general specifications(publication number GS 33Y06H52-31E). Dimension-tolerances are in accordance with the followingtable:Normal tolerance of outside dimensions for system products (Unit: mm)

Range of Basis Dimensions

Min. Max.

0.5 120 0.8 1.5

120 400 2 3

400 1000 2 4 4

1000 2000 3 6 6

2000 4000 4 8 8

4000 8000 10

CombinedTolerance (*1)

Panel WidthToleranceTolerance

(*1) Indicates the measurements and combined tolerance of front door and rear door or each surface.

Remarks The tolerance in this table for measurements are over 120 mm and up to 8000 mm refer to JEM1459“Power Distribution Panels, Control Panels, Construction and Dimensions”.

b. Visual InspectionCheck paint color. Also check for external defects such as deformation, flaws and stains. Check thecomponent, domain and station numbers to see that they agree with those described on the manufactur-ing specification sheets.

* (2) Insulation Resistance and Dielectric Strength Tests

Test point Insulation resistance Dielectric strength

Between power terminal and ground At least 20 M at 500V DC 1500V AC for 1 minute

(Caution1) When a 24 VDC power supply is specified for the unit, test the dielectric strength with a 500 VAC

withstand voltage tester.

(Caution2) Perform the dielectric strength test with the card units that represent the secondary circuit load removed.

Note) Since the inspection items marked with asterisks (*) have already been inspected at the factory duringthe manufacturing process, the test certificate shall substitute for an actual test.

2.2 Standard Function Inspection

2.2.1 Communication Inspection (Vnet)

Check that Vnet performs communication function normaly. In case of dual-redundant type, check respectivebuses.